Implementation of A Transformer Monitoring c57.92 PDF
Implementation of A Transformer Monitoring c57.92 PDF
Implementation of A Transformer Monitoring c57.92 PDF
I. INTRODUCTION
CenterPoint Energy in Texas has distribution substations
that deliver power to about 5 million customers. CenterPoint
Energy is experiencing steady load growth, similar to other
electric utilities across the United States. As the demand for
electric power increases, the load on each distribution
transformer also increases. Increased loads on distribution
transformers can lead to additional mechanical wear and
insulation deterioration of the transformer. Prolonged
exposure to abnormal operating scenarios can also lead to
transformer failures and distribution outages. Such failures
may be prevented by using an effective real-time transformer
monitoring solution for all distribution power transformers.
This paper outlines the need to monitor power transformers
and discusses the methods used to monitor them. The paper
presents the design and algorithm involved in implementing a
transformer monitoring system using an automation controller.
Laboratory tests were conducted for multiple operating
scenarios, and the test results obtained are also presented.
II. NEED FOR POWER TRANSFORMER MONITORING
Large oil-immersed power transformers are the most
expensive components of a transmission and distribution
system and are considered the most valuable assets of an
electric power utility system. System abnormalities, excessive
loading, switching, and ambient conditions contribute to
accelerated aging and can lead to the sudden failure of
transformers [1]. Some of these failures can cause irreversible
442
ProRelay 2012
Control Center
Control
Building
IRIG-B Connection
Serial DNP3 Outstation
Data Service
Unit Modem
Substation
Remote
Terminal
Unit (RTU)
NEMA Enclosure
in Yard
Status
Substation
Computer
Fan Motor
NEMA Enclosure
in Yard
Status
Control
Control
DAQ
Module
Ambient
Temperature
Top-Oil
Temperature
Automation
Controller
DAQ
Module
Top-Oil
Temperature
Global
Positioning
System
(GPS) Clock
Ambient
Temperature
Substation
12 kV Bus
Cooling Bank
Cooling Bank
Distribution Transformer 1
Fig. 1.
Distribution Transformer 2
443
Fig. 2.
444
TH
TA 'TTO 'TH
where:
H is the hottest-spot temperature.
A is the ambient temperature.
H is the hottest-spot rise over top-oil temperature.
TO is the top-oil rise over ambient temperature.
(1)
't
'TTO
'TTO,U
K 2 RATL 1
RATL 1
(2)
EXPn
'TTO,R
(3)
where:
TO,U is the ultimate top-oil rise over ambient
temperature in degrees Celsius.
TO,R is the top-oil rise over ambient temperature at rated
load in degrees Celsius.
TO,i is the initial top-oil rise over ambient temperature
in degrees Celsius.
RATL is the ratio of load loss at rated load to no-load
loss.
K is the ratio of present load to the rated load.
EXPn is an empirically derived exponent used to
calculate the variation of TO,U with changes in load.
TO is the oil time constant of the transformer for any load
and for any specific temperature differential between the
ultimate top-oil rise and the initial top-oil rise temperature
in hours.
t is the duration of load in hours.
Equation (2) is the solution for the first order differential
equation shown by (4).
WTO
d'TTO
dt
'TTO,i
(4)
15000 15000
368 TH 273
(5)
445
(6)
where:
i is the iterative variable.
The algorithm starts the convergence process by setting the
load multiplier to 1 and determining the present MVA on the
transformer. The base MVA is set based on the active
transformer cooling stage. The active cooling stage is
determined by predefined activation rules, such as those
shown in Table I. The cooling stage selection is validated by
current detection of cooling bank loads by the DAQ modules.
Top-Oil Temperature
Hottest-Spot
Temperature
Load Current
Value
Capacity
High-Voltage Winding
67 kV
Low-Voltage Winding
12.47 kV
Impedance
7.79%
TABLE III
HEAT-RUN DATA
Parameter
Value
Transformer Life
TABLE I
COOLING STAGE ACTIVATION RULES
Criteria
Parameter
180,000 hours
Cooling Stage
OA(1)
FA(2)
FOA(3)
47.6
39.3
39.6
Threshold
Cooling
75C
85C
17.4
25.7
25.4
100C
0.8
0.8
0.9
120C
0.8
0.8
1.0
1.00 pu
1.20 pu
9.322
8.133
6.715
(2)
(3)
0.1
The test setup consisted of a secondary injection of threephase currents and voltages with a test set. This test set output
was varied to simulate actual distribution transformer loading
patterns. The inputs from an RTD simulator were used to
represent the inputs obtained from an ambient temperature
probe. These laboratory tests used the calculated top-oil
temperature to determine the hottest-spot temperature. In field
implementation, the top-oil temperature is a measured value
obtained from an RTD probe placed in a thermal well inside
the transformer core. In the laboratory, the analog inputs from
the test set and the RTD simulator were connected to the DAQ
modules.
446
Temperature (C)
447
[6]
[7]
IEEE Standard C57.91-1995, IEEE Guide for Loading Mineral-OilImmersed Transformers, 1996.
B. C. Lesieutre, W. H. Hagman, and J. L. Kirtley Jr., An Improved
Transformer Top Oil Temperature Model for Use in an On-Line
Monitoring and Diagnostic System, IEEE Transactions on Power
Delivery, Vol. 12, No. 1, January 1997, pp. 249256.
IX. BIOGRAPHIES
Walter A. Castillo received his B.S. in 2006 from Louisiana State University.
He worked at PPG Aerospace in Huntsville, Alabama, as a process engineer
for less than a year. In 2006, he joined CenterPoint Energy and is presently a
lead engineer in the substation protection and automation group. He is a
registered professional engineer in the state of Texas.
Rekha T. Jagaduri received her B.S. in 2003 from Madras University in
India and her M.S. (magna cum laude) in power systems from Tennessee
Technological University. She worked as a power system engineer in the
protection and control division for the EPC Company in Knoxville,
Tennessee. Rekha has utility company and research experience. She was
involved in electric power engineering protection and control design, solution
development, and detailed engineering design. In 2008, Rekha joined
Schweitzer Engineering Laboratories, Inc. She has led large industrial
projects, is a member of IEEE, and has authored various technical papers. She
is a registered professional engineer in the state of Texas.
Prasanna K. Muralimanohar received his B.S. in 2008 from Anna
University in India and his M.S. in electric power systems from Rensselaer
Polytechnic Institute in 2009. His research encompassed power system
modeling and analysis. Prasanna worked as a junior protection engineer at
United Electric Systems in Allentown, Pennsylvania, where he was involved
in performing protection settings analysis for industrial protection schemes. In
2010, he joined Schweitzer Engineering Laboratories, Inc. as a protection
engineer.
VIII. REFERENCES
[1]
[2]
[3]
[4]
[5]
448
20120217 TP6551