Long Line Application CARRIER-R22

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

Air Conditioners and

Heat Pumps Using


R-22 Refrigerant
Visit www.carrier.com

Application Guide
and Service Manual
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................2
INTRODUCTION ..........................................................................2
INSTALLATION GUIDELINE ....................................................2
Residential New Construction ..................................................2
Add-On Replacement (Retrofit) ...............................................2
Seacoast (For Air Conditioners Only) .....................................2
ACCESSORY DESCRIPTIONS ...................................................2
Compressor Crankcase Heater..................................................2
Evaporator Freeze Thermostat..................................................2
Winter Start Control .................................................................2
Compressor Start AssistPTC ................................................2
Compressor Start AssistCapacitor/Relay..............................2
Low-Ambient Controller ..........................................................2
MotorMaster Control ............................................................2
Low-Ambient Pressure Switch.................................................2
Wind Baffle...............................................................................3
Coastal Filter.............................................................................3
Support Feet ..............................................................................3
Liquid-Line Solenoid Valve .....................................................3
Thermostatic-Expansion Valve.................................................3
Isolation Relay ..........................................................................3

Defrost Thermostats................................................................18
Defrost-Control Board ............................................................18
Fan Motors ..............................................................................22
Service Alarm Control Board.................................................23
Outdoor Thermostat(s)............................................................24
Compressor Plug.....................................................................24
Low-Voltage Terminals ..........................................................24
RECIPROCATING COMPRESSOR ..........................................25
Mechanical Failures ................................................................25
Electrical Failures ...................................................................26
System Cleanup After Burnout ..............................................27
Compressor Removal And Replacement ...............................28
COPELAND SCROLL COMPRESSOR ....................................28
Features ...................................................................................28
Troubleshooting ......................................................................28
Discharge Thermostat .............................................................28
Discharge Solenoid Valve ......................................................29
MILLENNIUM SCROLL COMPRESSOR ................................29
Features ...................................................................................29
Compressor Protection............................................................29
Troubleshooting ......................................................................29
Scroll-Compressor, 3Phase Monitor.....................................29

LOW-AMBIENT GUIDELINE.....................................................3

OLYMPIA SERIES HORIZONTAL UNITS .............................29


General ....................................................................................29
Remove Fan Motor.................................................................31
Cleaning Coil ..........................................................................31

LONG-LINE GUIDELINE............................................................3
Approved Systems ....................................................................3
Interconnecting Tubing Sizing .................................................3
Metering Device Sizing ............................................................5
Liquid-Line Solenoid And Tubing Configuration ...................5
Charging Information................................................................6
2Speed Applications ...............................................................7

TWO-SPEED SYSTEM ..............................................................31


Cautions and Warnings...........................................................31
System Functions ....................................................................31
Factory Defaults......................................................................34
Major Components..................................................................34
LED Function/Malfunction Lights .........................................36
Troubleshooting ......................................................................36

UNIT IDENTIFICATION .............................................................9


Product Number Stamped on Unit-Rating Plate......................9
Serial Number Identification ..................................................10

REFRIGERATION SYSTEM .....................................................38


Refrigeration Cycle.................................................................38
Leak Detection ........................................................................38
Brazing ....................................................................................39
Service Valves ........................................................................39
AccuRater (Bypass-Type) Heat Pumps Only ....................40
Reversing Valve......................................................................41
Thermostatic-Expansion Valves (TXV).................................42
Thermostatic-Expansion Valve (Bi-Flow TXV)....................43
Coil Removal ..........................................................................43
Liquid-Line Strainer (Heat Pumps Only) ..............................43
Accumulator ............................................................................43
Contaminant Removal ............................................................45
System Charging.....................................................................45
Checking Charge.....................................................................45

CABINET.....................................................................................10
Remove Top Cover-WeatherMaker ...................................10
Remove Fan-Motor Assembly-WeatherMaker ..................10
Information PlateWeatherMaker.....................................11
Control-Box CoverCube Products......................................11
Remove Top CoverCube Products.....................................11
Remove Fan-Motor AssemblyCube Products....................11
ELECTRICAL..............................................................................12
Aluminum Wire ......................................................................12
Contactors................................................................................13
Capacitors................................................................................14
Cycle Protector........................................................................16
Crankcase Heater ....................................................................16
Time-Delay Relay...................................................................17
Pressure Switches....................................................................18

CARE AND MAINTENANCE...................................................46

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
PC 101
Catalog No. 563-732
Printed in U.S.A.
Form 38-10SM
Pg 1
11-00
Replaces: 38-1SM, 38-16XA
Tab 3a 5a 2a 5a

SAFETY CONSIDERATIONS
Service and repair of these units should be attempted only by
trained service technicians familiar with Carrier standard service
instructions and training manual.

liquid-line filter driers. Be sure to purge system with dry


nitrogen and evacuate when replacing filter driers. Continue to
monitor pressure drop across suction-line filter drier. After 10
hr of run time, remove suction-line filter drier and replace
liquid-line filter drier. Never leave suction-line filter drier in
system longer than 72 hr (actual time).

All equipment should be installed in accordance with accepted


practices and unit Installation Instructions, and in compliance with
all national and local codes.

7. Charge system. (See unit information plate.)


Step 3Seacoast (For Air Conditioners Only)

Power should be turned off when servicing or repairing electrical


components. Extreme caution should be observed when troubleshooting electrical components with power on. Observe all warning notices posted on equipment.

Installation of these units in seacoast locations requires the use of


a coastal filter. (See section on care and maintenance.)

Refrigeration system contains refrigerant under pressure. Extreme


caution should be observed when handling refrigerants. Wear
safety glasses and gloves to prevent personal injury. During
normal system operation, some components are hot and can cause
burns. Rotating fan blades can cause personal injury. Appropriate
safety considerations are posted throughout this manual where
potentially dangerous techniques are addressed.

ACCESSORY DESCRIPTIONS
Refer to Table 1 for an Accessory Usage Guide for Air Conditioners and Heat Pumps. See Model-specific product literature for
any kit part number. Refer to the appropriate section below for a
description of each accessory and its use.
Step 1Compressor Crankcase Heater
An electric heater which mounts to base of compressor to keep
lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes chance of refrigerant slugging and oil
pumpout. The crankcase heater may or may not include a
thermostat control. For units equipped with crankcase heaters,
apply power for 24 hr before starting compressor.

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or
other conditions which may cause personal injury, death, or
property damage. Consult a qualified installer, service
agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product.

Step 2Evaporator Freeze Thermostat


An SPST temperature-activated switch stops unit operation when
evaporator reaches freeze-up conditions.
Step 3Winter Start Control

INTRODUCTION
This service manual enables a service technician to service, repair,
and maintain a family of similar air conditioners and heat pumps.
It covers standard single-speed products and 2speed products
only. For variable-speed products, refer to the respective service
manuals.

An SPST delay relay which bypasses the low-pressure switch for


approximately 3 minutes to permit startup for cooling operation
under low-load conditions.
Step 4Compressor Start AssistPTC
Solid-state electrical device which gives a soft boost to the
compressor at each start.

INSTALLATION GUIDELINE
Step 1Residential New Construction

Step 5Compressor Start AssistCapacitor/Relay

Specifications for this unit in the residential, new-construction


market require the outdoor unit, indoor unit, refrigerant-tubing
sets, metering device, and filter drier listed in Product Data Digest
(PDD). DO NOT DEVIATE FROM PDD. Consult unit Installation Instructions for detailed information.

Start capacitor and start relay gives hard boost to compressor


motor at each start. Required with liquid-line solenoid or hardshutoff TXV for all equipment.

Step 2Add-On Replacement (Retrofit)

Low-ambient controller is a cycle-control device activated by a


temperature sensor mounted on a header tube of the outdoor coil.
It is designed to cycle the outdoor fan motor in order to maintain
condensing temperature within normal operating limits (approximately 100F high, and 60F low). The control will maintain
working head pressure at low-ambient temperatures down to 0F
when properly installed.

Step 6Low-Ambient Controller

Specifications for this unit in the add-on replacement/retrofit


market require change-out of outdoor unit, metering device, and all
capillary-tube coils. Change-out of indoor coil is recommended.
There can be no deviation.
1. If system is being replaced due to compressor electrical
failure, assume acid is in system. If system is being replaced
for any other reason, use approved acid test kit to determine
acid level. If even low levels of acid are detected, install
factory-approved, suction-line filter drier in addition to the
factory-supplied, liquid-line filter drier. Remove the suctionline filter drier as soon as possible, with a maximum of 72 hr.

Step 7MotorMaster Control


A fan speed-control device activated by a temperature sensor. It is
designed to control condenser fan-motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperature down to -20F, it maintains
condensing temperature at 100F 10F. Requires a ball-bearing
fan motor.

2. Drain oil from low points or traps in suction-line and


evaporator if they were not replaced.

Step 8Low-Ambient Pressure Switch

3. Change out indoor coil or verify existing coil is listed in the


Product Data Digest.

A long-life pressure switch which is mounted to outdoor unit


service valve. It is designed to cycle the outdoor fan motor in
response to condenser pressure in cooling mode in order to
maintain head pressure within normal operating limits (approximately 100 psig to 225 psig). The control will maintain working
head pressure at low-ambient temperatures down to 0F when
properly installed.

4. Replace outdoor unit.


5. Install liquid-line filter drier.
6. If suction-line filter drier was installed for system clean up,
operate system for 10 hr. Monitor pressure drop across drier.
If pressure drop exceeds 3 psig, replace suction-line and

Table 1Required Field-Installed Accessories for Air Conditioners and Heat Pumps
ACCESSORY
Crankcase Heater
Evaporator Freeze Thermostat
Winter Start Control
Accumulator
Compressor Start Assist
Capacitor and Relay
Low Ambient Controller,
MotorMaster Control,
or
Low-Ambient Pressure Switch
Wind Baffle
Coastal Filter
Support Feet
Liquid-Line Solenoid Valve
or
Hard-Shutoff TXV
Ball-Bearing Fan Motor
Isolation Relay

REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(BELOW 55F)
Yes
Yes
Yes
No

REQUIRED FOR
LONG-LINE
APPLICATIONS*
(OVER 50 FT)
Yes
No
No
No

REQUIRED FOR
SEA COAST
APPLICATIONS
(WITHIN 2 MILES)
No
No
No
No

Yes

Yes

No

Yes

No

No

See Low-Ambient Instructions


No
Recommended

No
No
No
See Long-Line
Application
Guideline
No
No

No
Yes
Recommended

No
Yes
Yes**

No
No
No

*For tubing line sets between 50 and 175 ft, refer to Residential Split-System Long-Line Application Guideline.
Only when low-pressure switch is used.
Required for Low-Ambient Controller (full modulation feature) and MotorMaster control only.
** Required on Heat Pumps only.

Step 9Wind Baffle

Four adhesive plastic feet which raise unit 4 in. above mounting
pad. This allows sand, dirt, and other debris to be flushed from unit
base; minimizes corrosion.

LONG-LINE GUIDELINE
This Long-Line Application Guideline applies to all Carrier
residential air conditioner and heat pump split systems that have a
nominal capacity of 18,000 to 60,000 Btuh. This guideline
provides required system changes and accessories necessary for
any residential product having piping requirements greater than 50
ft or installations where indoor unit is located above outdoor unit.
This guideline is intended to cover applications outside the
standard Installation Instructions. This guideline is for standard,
single-speed products. For applications involving 2-speed products, refer to Step 6 first.
NOTE: The presale literature for outdoor unit must be referred to
in conjunction with this guideline.

Step 12Liquid-Line Solenoid Valve

Step 1Approved Systems

An electrically operated shutoff valve to be installed at outdoor or


indoor unit (depending on tubing configuration) which stops and
starts refrigerant liquid flow in response to compressor operation.
Maintains a column of refrigerant liquid ready for action at next
compressor-operation cycle and prevents liquid migration during
the off cycle.

Any residential indoor/outdoor unit combination listed in the


outdoor unit presale literature is an approved system, EXCEPT the
following:

A field-fabricated sheet-metal cover used to stop prevailing winds


or where outdoor ambient temperature is less than 55F during unit
operation of cooling mode.
Step 10Coastal Filter
A mesh screen inserted under top cover and inside base pan to
protect condenser coil from salt damage without restricting airflow.
Step 11Support Feet

Indoor coils with capillary-metering devices


All equipment less than nominal 18,000 Btuh
All 1/4-in. and 3/16in. liquid-line applications
Any indoor furnace coil/fan coil not listed in outdoor unit
presale literature
Any application which has interconnecting tubing with an
equivalent length greater than 175 ft
Step 2Interconnecting Tubing Sizing

Step 13Thermostatic-Expansion Valve


A modulating flow-control device which meters refrigerant flow
rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator. Only use factory-specified
TXVs.
Step 14Isolation Relay

Table 5 lists recommended interconnecting vapor-line diameters


for equivalent total-line lengths. All residential split systems
installed in long-line applications must use only 3/8-in. liquid
lines. Equivalent line length equals the linear length (measured) of
interconnecting vapor tubing plus losses due to elbows. (See Table
6 and Fig. 3.) Liquid lines larger than 3/8-in. OD greatly increase
charge quantity of the system. Excessive charge increases risk of
migration and compressor damage. Table 5 provides the estimated
percentage of nominal cooling-capacity losses based on the standard, required vapor line size versus what is selected for the
long-line application. Since the vapor line is the discharge line in
heating mode, losses are minimal.

A DPDT relay which switches the low-ambient controller out of


the outdoor fan-motor circuit when the heat pump switches to
heating mode.
LOW-AMBIENT GUIDELINE
The minimum operating temperature for these units in cooling
mode is 55F outdoor ambient without additional accessories. This
equipment may be operated in cooling mode at ambient temperatures below 55F when the accessories listed in Table 1 are
installed. Wind baffles are required when operating in cooling
mode at ambients below 55F. Refer to Fig. 1 or 2 and Table 2, 3,
or 4 for wind baffle construction details.

7/ x 3/ (5.56
32
8

x 9.53) SLOT

4 REQ'D
9/ (3.45) DIA HOLE
64
2 REQ'D

H
3/
8

6 1/16
(154.0)

(9.6)
TYP

1/
2

SUPPORT

(12.7)
TYP

7/

MAT'L: 18 GA STEEL

16

(11.6)
TYP

1
/2
(12.7)
TYP

9/ (3.45) DIA HOLE


64
1 REQ'D

K
B

16

7/

(11.6)
TYP

7/ (5.56) DIA HOLE


32
3 REQ'D

1/
4

1/
4

(6.3)
TYP

(6.3)
TYP

BAFFLE
SCREW
10 REQ'D

7/ x 2
32
(5.56 x 50.8) SLOT

MAT'L: 20 GA STEEL

SUPPORT
4 REQ'D

OUTDOOR
UNIT

BAFFLE
2 REQ'D

AA

BAFFLE ASSEMBLY
A95444

Fig. 1WeatherMaker Units


For minimal capacity loss in long-line application, 1/2-in. insulation should be specified.

Calculate the linear length of vapor tube required, adding any


losses for the total number of elbows for application. (See Table
6.) Using this equivalent length, select desired vapor-line size from
Table 5. Subtract the nominal percentage loss from outdoor-unit
presale-literature Detailed Cooling Capacities data for the given
indoor/outdoor combination. Reference all notes of Table 5.

For reference only, the close cell insulation material specified for
accessory tubing kits is a compound of vinyl, neoprene, or nitrile
blends of these polymers. Performance requirements include
thermal range of 0 F to 200F (-17.8 C to 93 C) and a maximum
thermal conductivity of 0.28.
NOTE: Special consideration must be given to isolating interconnecting tubing from building structure. Isolate tubing so that
vibration or noise is not transmitted into structure.

NOTE: When specifying vapor-line insulation, be aware of the


following standard practice:
All standard accessory-tubing kits are supplied with 3/8-in. insulation on vapor line.

Table 2Wind Baffle Dimensions for WeatherMaker Units with Star-Burst Top (In.)
UNIT SIZE
Small

Medium

Large

AA

UNIT HEIGHT
A
B
C
D
21-7/8
17
25-1/4 10-3/8 19-3/4
27-1/2
25-7/8
17
25-1/4 10-3/8 23-3/4
31-7/8
17
25-1/4 10-3/8 29-3/4
25-7/8
21
32
11-3/16 23-3/4
34-15/16
31-7/8
21
32
11-3/16 29-3/4
37-7/8
21
32
11-3/16 35-3/4
31-7/8
25-3/16
42
12-15/16 29-3/4
45
37-7/8
25-3/16
42
15-15/16 35-3/4

E
F
G
20-1/2
34
19-11/16
24-1/2
34
23-11/16
30-1/2
34
29-11/16
24-1/2
42
23-11/16
30-1/2
42
29-11/16
36-1/2
42
35-11/16
30-1/2 50-7/16 29-11/16
36-1/2 50-7/16 35-11/16

H
20-7/16
24-7/16
30-7/16
24-7/16
30-7/16
36-7/16
30-7/16
36-7/16

J
19-5/8
23-5/8
29-5/8
23-5/8
29-5/8
35-5/8
29-5/8
35-5/8

K
0
0
0
19-11/16
19-11/16
19-11/16
22-11/16
22-11/16

L
M
0
6-1/8
11-7/8 6-1/8
14-7/8 6-1/8
11-7/8 6-11/16
14-7/8 6-11/16
17-7/8 6-11/16
14-7/8 7-1/16
17-7/8 7-1/16

Table 3Wind Baffle Dimensions for WeatherMaker Units with Silencer System Top (In.)
UNIT SIZE
Small

Medium

Large

AA

UNIT HEIGHT
A
B
C
D
23-13/16
17
25-1/4 10-3/8 19-3/4
27-1/2
27-13/16
17
25-1/4 10-3/8 23-3/4
33-13/16
17
25-1/4 10-3/8 29-3/4
27-13/16
21
32
11-3/16 23-3/4
34-15/16
33-13/16
21
32
11-3/16 29-3/4
39-13/16
21
32
11-3/16 35-3/4
33-13/16
25-3/16
42
12-15/16 29-3/4
45
39-13/16
25-3/16
42
15-15/16 35-3/4

Step 3Metering Device Sizing


The metering device for a long-line application must be flexible
enough to compensate for frictional losses due to long refrigerant
lines and installed system design (indoor coil above or below
outdoor unit.) The piston or TXV provides such flexibility.
The piston should be changed for both indoor coil and outdoor heat
pump unit, depending on system configuration and line length.
Tables 7 and 8 provide necessary changes for a given application.
Use Tables 7 and 8 when selecting correct piston size. Outdoorunit presale literature must be consulted to determine metering
devices specified for standard applications. After determining
standard application piston size(s), refer to Tables 7 and 8 as they
relate to system design (outdoor unit above or below indoor unit)
per equivalent length of tubing.
NOTE: If total equivalent horizontal length is 100 ft or longer,
both indoor and outdoor pistons must be increased 1 full piston
size, in addition to changes required by Tables 7 and 8.
After finding appropriate change in piston size, add or subtract the
change from original piston number. If piston size is decreased,
round new piston number down to nearest common piston number
found in Table 9. If piston size is increased, round new piston
number up to nearest common piston number found in Table 9.

E
F
G.
20-1/2
34
19-11/16
24-1/2
34
23-11/16
30-1/2
34
29-11/16
24-1/2
42
23-11/16
30-1/2
42
29-11/16
36-1/2
42
35-11/16
30-1/2 50-7/16 29-11/16
36-1/2 50-7/16 35-11/16

H.
20-7/16
24-7/16
30-7/16
24-7/16
30-7/16
36-7/16
30-7/16
36-7/16

J
19-5/8
23-5/8
29-5/8
23-5/8
29-5/8
35-5/8
29-5/8
35-5/8

K
0
0
0
19-11/16
19-11/16
19-11/16
22-11/16
22-11/16

L
M
0
6-1/8
11-7/8 6-1/8
14-7/8 6-1/8
11-7/8 6-11/16
14-7/8 6-11/16
17-7/8 6-11/16
14-7/8 7-1/16
17-7/8 7-1/16

EXAMPLE:
An 042 size heat pump is 75 ft above an 042 size fan coil.
The 042 size heat-pump presale literature specifies a size
80 indoor piston and size 63 outdoor piston.
To establish correct indoor piston size for a 75 ft vertical
separation, refer to Table 7. For a 75 ft equivalent line
length, the piston change is -5. Therefore subtract 5 from
the original indoor piston size of 80:
80 5 = 75
Table 9 provides common piston sizes. In this instance, 75
is not listed, therefore round DOWN to next piston size,
which would be 74.
To establish correct outdoor piston size for a 75 ft vertical
separation, refer to Table 8. For a 75 ft equivalent line
length, the piston change is +4. Therefore add 4 to the
original outdoor piston size of 63:
63 + 4 = 67
Since 67 is listed in Table 9, that is the piston which should
be used. If a 67 size piston were not listed, it would be
necessary to round UP to next piston size.
TXVs may be used instead of pistons for indoor-metering devices.
Some fan coils are equipped with a hard-shutoff, bi-flow TXV
standard, and no change is required. When sizing an accessory
TXV for long-line applications, TXV should be the same nominal
tonnage as outdoor unit. Refer to presale literature for kit part
numbers.
Step 4Liquid-Line Solenoid And Tubing Configuration
There are 2 types of liquid-line solenoids: 1 for single-flow
applications and the other for bi-flow applications. The purpose of
having 2 solenoids is to minimize the valve internal-pressure drop
in accordance with refrigerant flow direction and liquid migration
to the compressor. The bi-flow solenoid is designed to have
minimal refrigerant-pressure drop in either flow direction, which
makes it suitable for heat pump usage. Refer to Table 10 for
liquid-line solenoid kit part numbers.
NOTE: When installing a liquid-line solenoid, the system may
require a minimum 60-va low-voltage transformer.

7 7/8
(200.0)

3/
16

1/ (3.45) DIA
8
2 REQ'D

(4.6)

5 3/64
(128.0)

E
C

1/
1/
4

(12.7)

(6.4)
5 3/64
(128.0)

13/
64

7 8
(199.9)
7/

25/

64 (10.0)

(5.4)
TYP
1 21/32 (42.1)

BAFFLE - LEFT
MAT'L: 20 GA STEEL

1/

7 29/32 (200.8)

(12.7)
TYP

BAFFLE - RIGHT
MAT'L: 20 GA STEEL

1/

(5.56) DIA
2 REQ'D

2 1/2
(63.5)

A
2 1/2
(63.5)

1/ x 3/ (5.56 x 9.53) SLOT


4
8
6 REQ'D
1/ (5.56) DIA
4
4 REQ'D

1 21/32 (42.1)
4

1/

x 3/8 (5.56 x 9.53) SLOT

25
64

6 REQ'D

(10.0)

AA

4 9/64 (105.2)
45
TYP

64

23/

(9.2)

LEFT
SIDE

2 5/64
(52.6)

8 5/64 (205.3)
TYP

1/
4

(6.4)

1/ (12.7)
2
TYP
23/ (9.2)
64

SCREW
14 REQ'D

1/ (5.56) DIA
4
2 REQ'D

4 5764
(124.2) TYP

RIGHT
SIDE

OUTDOOR
UNIT

SUPPORT
3 REQ'D

SUPPORT
MAT'L: 18 GA STEEL

1/ (3.45) DIA.
8
4 REQ'D

BAFFLE ASSEMBLY

JH

A95446

Fig. 2Cube Units


correct charge. The standard charging methods can be found on
outdoor unit-information plate, in unit Installation Instructions, or
in the Service Manual. Since total system charge is increased for
long-line applications, it may be necessary to calculate the
additional refrigerant charge. Since long-line applications only
involve 3/8-in. liquid lines, the additional refrigerant charge
required is 0.6 oz of Refrigerant 22 (R-22) per ft of 3/8-in. liquid
line over 15 ft.

Each type of solenoid has an indicator flow arrow stamped on the


valve body. When solenoid is closed (not energized) and pressure
is applied in direction of flow arrow, complete shutoff occurs. If
pressure is applied against direction of flow arrow, leakage
through valve occurs. When determining proper installation of
valve within liquid line, 2 considerations must be made:
1. Direction of flow arrow
2. Where solenoid is installed in system.
TXVs can only be substituted for liquid-line solenoids in singleflow air conditioning systems. Bi-flow TXVs allow liquid migration to coldest point during off cycles, which could allow liquid
into compressor.

EXAMPLE:
To calculate additional charge required for a 25ft line set:
25 ft 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

Fig. 4 through 7 detail proper installation of liquid-line solenoid


and provide applications where TXVs may be substituted. Reference all notes of the appropriate figures.

The rating-plate charge of a given outdoor unit is for a standard


application of 15 ft of interconnecting tubing. The rating-plate
charge can be found on outdoor unit-rating plate or in outdoor
unit-presale literature. Long-line applications do not require additional oil charge.

Step 5Charging Information


Weigh in appropriate refrigerant charge, then use the standard
practices of superheat-charging method for piston applications and
subcooling-charging method for TXV applications to confirm

Table 4Wind Baffle Dimensions for Cube Units (In.)


UNIT SIZE

AA

Small

18

Medium

22-1/2

Large

30

UNIT HEIGHT
21-15/16
23-15/16
25-15/16
27-15/16
29-15/16
31-15/16
33-15/16
21-15/16
23-15/16
25-15/16
27-15/16
29-15/16
31-15/16
33-15/16
35-15/16
37-15/16
25-15/16
27-15/16
29-15/16
31-15/16
33-15/16
35-15/16
37-15/16
39-15/16

A
19-7/8
21-7/8
23-7/8
25-7/8
27-7/8
29-7/8
31-7/8
19-7/8
21-7/8
23-7/8
25-7/8
27-7/8
29-7/8
31-7/8
33-7/8
35-7/8
23-7/8
25-7/8
27-7/8
29-7/8
31-7/8
33-7/8
35-7/8
37-7/8

B
13-3/4
13-3/4
13-3/4
13-3/4
13-3/4
13-3/4
13-3/4
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4

C
28-1/8
28-1/8
28-1/8
28-1/8
28-1/8
28-1/8
28-1/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8

D
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16

E
20-1/4
20-1/4
20-1/4
20-1/4
20-1/4
20-1/4
20-1/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4

F
11-11/16
11-11/16
11-11/16
11-11/16
11-11/16
11-11/16
11-11/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16

G.
3-13/16
3-13/16
3-13/16
3-13/16
3-13/16
3-13/16
3-13/16
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16

H.
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
35-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
35-13/16
37-13/16

J
17-13/16
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
17-13/16
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
35-13/16

Table 5Estimated Percentage of Nominal Cooling-Capacity Losses*


UNIT
NOMINAL
SIZE
(BTUH)
18,000
24,000
30,000
36,000

42,000

48,000

60,000

LONG-LINE
VAPOR-LINE
DIAMETER
(IN.)
5/8
3/4
5/8
3/4
5/8
3/4
3/4
7/8
3/4
7/8
1-1/8
3/4
7/8
1-1/8
7/8
1-1/8

EQUIVALENT LINE LENGTH (FT)


50

75

100

125

150

175

5
1
6
0
6
2
7
2
7
3
0
10
4
0
7
1

7
3
9
1
8
3
10
4
10
4
0
14
6
0
9
2

9
4
13
1
10
4
14
6
13
6
1
18
7
1
11
2

12
5
16
2
13
5
17
8
17
7
1
22
9
1
14
3

12
5
19
3
15
6
21
10
20
8
2
NR
11
2
16
3

14
7
22
4
17
7
NR
11
23
10
2
NR
13
2
19
4

*The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling Capacities data specified in outdoor unit-presale literature for any given
indoor/outdoor combination.
Vapor-line diameter that may be selected for a long-line application. If smaller vapor lines are selected but not specified within the table, large capacity losses will occur
and defrost capabilities will be reduced. If larger vapor lines are selected but not specified within the table, refrigerant oil return will be impaired due to velocity losses.
N/RNot recommended due to excessive loss of capacity.

Step 62Speed Applications

Vapor tube diameter for the 036 and 048 is 7/8 in.; 060 is
11/8
Vapor refrigerant connection diameter for all sizes is 7/8 in.
DO NOT INSTALL EQUIVALENT INTERCONNECTING
TUBING LENGTHS GREATER THAN 100 FT.
2. Do not increase or decrease tubing sizes.
For other applications see the previous sections under Long-Line
Guidelines.

Outdoor units may be connected to indoor section using accessory


tubing package or field-supplied refrigerant grade tubing or correct
size and condition. In long-line applications, 2speed units are
handled basically the same way as the single-speed units. There are
2 major differences:
1. For tubing up to 100 ft:
Liquid tube diameters and refrigerant connection diameters for
all sizes are 3/8 in.

Table 7Calculation of Indoor Piston No.


OUTDOOR UNIT ABOVE INDOOR
FT
PISTON CHANGE
0-25
0
26-50
-3
51-75
-5
76-100
-7
101-125
-9
126-150
-10
OUTDOOR UNIT BELOW INDOOR
FT
PISTON CHANGE
0-25
0
26-50
+4

Table 8Calculation of Outdoor Piston No.


OUTDOOR UNIT ABOVE INDOOR
FT
PISTON CHANGE
0-50
0
51-75
+4
76-100
+6
101-125
+8
126-150
+10
OUTDOOR UNIT BELOW INDOOR
FT
PISTON CHANGE
0-50
0

90 STD

Table 9Common Piston Sizes


ACCURATER

35

38

40

42

46

49
51
52

55
57
59
61

63

90 LONG RAD

45 STD
A92498

CHATLEFF
32
33
35
36
37
38
39
40
41
42
43
45

47
49
51
52
53
55
57
59
61
62
63

ACCURATER
65
67

70

73

76
78
80

82
84
86
88

90

93
96
98
101
104
109

CHATLEFF
65
67
68
70
71
73
74
76
78
80
81
82
84
86
88
89
90
92
93
96
98
101
104

Table 6Fitting Losses in Equivalent Ft


TUBE SIZE OD
(IN.)
5/8
3/4
7/8
1-1/8

Table 10Liquid-Line Solenoid Kit Part Numbers

REFERENCE DIAGRAM IN FIG. 1


A
B
C
1.6
1.0
0.8
1.8
1.2
0.9
2.0
1.4
1.0
2.6
1.7
1.3

TYPE OF VALVE
Single Flow
Bi-Flow

Fig. 3Tube Bend Losses

PART NO.
KAALS0101LLS
KHALS0101LLS

175' MAX.

GROUND LEVEL

BASEMENT

A90074

Fig. 4Application with Air Conditioner Installed in a Horizontal Configuration

175' MAX.

GROUND LEVEL

BASEMENT

A90075

Fig. 5Application with Heat Pump Installed in a Horizontal Configuration


UNIT IDENTIFICATION
Step 1Product Number Stamped on Unit-Rating Plate

Positions 6, 7, and 8Nominal Cooling Capacity (in thousands


Btuh)
Example: 036 = 36,000 Btuh or 3ton capacity.
Position 9Not Used
Ths position will contain a dash ().
Position 10Description
CCanada
LLimited Edition
Position 11Not Used
Ths position will contain a dash ().
Position 12Electrical Characteristics

The unit product number has 16 positions containing groups of


numbers and letters that indicate specific information about the
unit. Listed below is the breakdown of the 16 positions.
Positions 1, and 2Model Number
Example:
A 38 indicates the unit is either an air conditioner or a heat pump.
Positions 3, 4, and 5Model Letters
Identifies a specific product model.

TRAP

50' MAX.

HEAT PUMP ONLY

GROUND LEVEL

A90076

Fig. 6Application with Air Conditioner or Heat Pump Installed with Indoor Unit Above Outdoor Unit
AIndianapolis
ECollierville
Positions 6 through 10Serial Number

Example:
3230 or 208230 or 208/230, 1 Phase, 60 Hertz
5230 or 208230 or 208/230, 3 Phase, 60 Hertz
6460, 3 Phase, 60 Hertz
7220/240, 1 Phase, 50 Hertz
8220, 3 Phase, 50 Hertz
9380/415, 3 Phase, 50 Hertz
Position 13Series
New units have a 0. As major component variations occur,
including compressor changes, fan motors, coil circuitry size, etc.,
the change is identified by increasing this digit in increments of 1.
Position 14Packaging
On split-system products, this digit will be 0.
Positions 15 and 16Not Used
These positions will contain dashes ( ).
Step 2Serial Number Identification
The unit serial number has 10 positions containing groups of
numbers and a letter that indicate specific information about the
unit. Listed below is the breakdown of the 10 positions.
Positions 1 and 2Week of Manufacture
Example:
01First week of a year
52Last week of a year
Positions 3 and 4Year of Manufacture
Example:
941994
Position 5Manufacturing Site
Example:

CABINET
Certain maintenance routines and repairs require removal of
cabinet panels. There are 4 basic cabinet designs for air conditioners and heat pumps. (See Fig. 8.) The horizontal discharge unit will
be discussed in a separate section of this manual.
Step 1Remove Top Cover-WeatherMaker
1. Turn off all power to outdoor and indoor units.
2. Remove screws holding top cover to coil grille and corner
posts.
3. Remove access panel.
4. Remove information plate.
5. Disconnect fan motor wires, cut wire ties, and remove wire
ties from control box. Refer to unit-wiring label.
6. Lift top cover from unit.
7. Reverse sequence for reassembly.
Step 2Remove Fan-Motor Assembly-WeatherMaker
1. Perform items 1 through 6 above.
2. Remove nuts holding fan-motor top cover.
3. Remove motor and fan blade assembly.
4. Reverse sequence for reassembly.
5. Prior to applying power, check that fan rotates freely.

10

HEAT PUMP ONLY

150' MAX.

A90077

Fig. 7Application with Air Conditioner or Heat Pump Installed Above Indoor Unit
Step 3Information PlateWeatherMaker

5. Disconnect fan motor wires, cut any wire ties, and move wires
out of control box and through tube clamp on back of control
box.
6. Lift top cover from unit.
7. Reverse sequence for reassembly.
Step 6Remove Fan-Motor AssemblyCube Products
1. Perform items 1, 3, 4, and 5 above. (Note item 2 is not
required.)
2. Remove 4 screws holding wire basket to top cover.
3. Lift wire basket from unit.
4. Remove nuts holding fan motor to wire basket.
5. Remove motor and fan blade assembly.
6. Pull wires through wire raceway to change motor.
7. Reverse sequence for reassembly.
8. Prior to applying power, check that fan rotates freely.

The information plate is secured to the front of the control box and
provides a cover for it. (See Fig. 9.) This plate also provides a
surface to attach the wiring schematic, superheat-charging tables
with instructions, and warning labels. The plate has 2 tabs on the
top edge that are bent down at slightly more than 90. When the
information plate is removed, these tabs can be inserted into 2
mating slots in the bottom-front edge of the control box, and the
plate will hang down, forming a lower front panel. (See Fig. 10.)
This is convenient where access to the controls is required while
the unit is operating. The information plate on the small size casing
completely covers the opening below the control box. On larger
models, the information plate may not cover the entire opening. In
this instance, the top cover can be removed and placed on its side
to cover the additional space.
Step 4Control-Box CoverCube Products
This panel contains much of the same information as the information plate mentioned previously, but is designed only to cover the
control box.
Step 5Remove Top CoverCube Products
1. Turn off all power to outdoor and indoor units.
2. Remove 5 screws holding top cover to coil grille and coil tube
sheet.
3. Remove 2 screws holding control-box cover.
4. Remove 2 screws holding information plate.

11

A00009

Fig. 8Basic Cabinet Designs


ELECTRICAL

SEFL JOSD
J SEFL
JOSDJ
SEFL JOSD
J SEFL
JOSDJ
SEFL JOSD
J SEFL
JOSDJ

Exercise extreme caution when working on any electrical


components. Shut off all power to system prior to troubleshooting. Some troubleshooting techniques require power to
remain on. In these instances, exercise extreme caution to
avoid danger of electrical shock. ONLY TRAINED SERVICE PERSONNEL SHOULD PERFORM ELECTRICAL
TROUBLESHOOTING.

SEFL JOSDJ
SEFL JOSDJ SEFL JOSDJ
SEFL JOSDJ SEFL JOSDJ PAASFLDLKREW
ATC
SEFL JOSDJ SEFL JOSDJ
UTUHD
SEFL JOSDJ SEFL JOSDJC
SEFL JOSDJ SEFL JOSDJH MD
SEFL JOSDJ R ITYALK

Troubleshooting charts for air conditioning and heat pump units


are provided in the back of this manual. They enable the service
technician to use a systematic approach to locating the cause of a
problem and correcting system malfunctions.
Step 1Aluminum Wire

Aluminum wire may be used in the branch circuit (such as the


circuit between the main and unit disconnect), but only
copper wire may be used between the unit disconnect and the
unit on Carrier systems.

A88411

Whenever aluminum wire is used in the branch-circuit wiring with


this unit, adhere to the following recommendations.

Fig. 9Information Plate

Connections must be made in accordance with the National


Electrical Code (NEC), using connectors approved for aluminum
wire. The connectors must be UL-approved (marked Al/Cu with
the UL symbol) for the application and wire size. The wire size
selected must have a current capacity not less than that of the
copper wire specified, and must not create a voltage drop between
the service panel and the unit in excess of 2 percent of the
unit-rated voltage.
To prepare the wire before installing the connector, all aluminum
wire must be brush-scratched and coated with a corrosion
inhibiter such as Pentrox A. When it is suspected that the

12

SEFL
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SDJ

SEFL
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SDJ

SEFL
JOSDJ
SEFL
JOSDJ SEFL JOS
SEFL
JOSDJ SEFL JOSDJ PAASFLD
SEFL
LKREW
JOSDJ SEFL JOSDJ ATC
SEFL
JOSDJ SEFL JOSDJ UTUHD
SEFL
JOSDJ SEFL JOSDJC MD
DJH
SEFL
JOSDJ R ITYALK

SEFL
JOSDJ
SEFL
JOSDJ SEFL JOS
SEFL
JOSDJ SEFL JOSDJ PAASFL
SEFL
DLKREW
JOSDJ SEFL JOSDJ ATC
SEFL
JOSDJ SEFL JOSDJ UTUHD
SEFL
JOSDJ SEFL JOSDJC MD
DJH
SEFL
JOSDJ R ITYALK

A88412

Fig. 10Information Plate Removed/Installed Below Control Box

A88413

The contactor provides a means of applying power to unit using


low voltage (24v) from transformer in order to power the contactor
coil. (See Fig. 11.) Depending on unit model, you may encounter
single-, double-, or triple-pole contactors to break power. One side
of the line may be electrically energized, so exercise extreme
caution when troubleshooting.
The contactor coil for residential air-conditioning units and heat
pumps is powered by 24vac. If contactor does not operate:
1. With power off, check whether contacts are free to move.
Check for severe burning or arcing on contact points.
2. With power off, use ohmmeter to check for continuity of coil.
Disconnect leads before checking. A low-resistance reading is
normal. Do not look for a specific value, as different part
numbers have different resistance values.
3. Reconnect leads and apply low-voltage power to contactor
coil. This may be done by leaving high-voltage power to
outdoor unit off, and turning thermostat to heat or cool. Check
voltage at coil with voltmeter. Reading should be between 20v
and 30v. Contactor should pull in if voltage is correct and coil
is good. If contactor does not pull in, change contactor.
4. With high-voltage power off and contacts pulled in, check for
continuity across contacts with ohmmeter. A very low or zero
resistance should be read. Higher readings could indicate
burned or pitted contacts which may cause future failures.

A88350

Fig. 11Contactor
connection will be exposed to moisture, it is very important to
cover the entire connection completely to prevent an electrochemical action that will cause the connection to fail very quickly. Do
not reduce the effective size of wire, such as cutting off strands so
that the wire will fit a connector. Proper size connectors should be
used. Check all factory and field electrical connections for
tightness. This should also be done after the unit has reached
operating temperatures, especially if aluminum conductors are
used.
Step 2Contactors
NOTE: The section applies to single-speed models only.

13

Step 3Capacitors

3. Remove any capacitor that shows signs of bulging, dents, or


leaking. Do not apply power to a defective capacitor as it may
explode.
START CAPACITORS AND PTC DEVICES

Capacitors can store electrical energy when power is off.


Electrical shock can result if you touch the capacitor terminals and discharge the stored energy. Exercise extreme
caution when working near capacitors. With power off,
discharge stored energy by shorting across the capacitor
terminals with a 15,000-ohm, 2-watt resistor.

Sometimes under adverse conditions, a standard run capacitor in a


system is inadequate to start compressor. In these instances, a
start-assist device is used to provide an extra starting boost to
compressor motor. The first device is called a positive-temperature
coefficient (PTC) or thermistor. (See Fig. 13.) It is a resistor wired
in parallel with the run capacitor. As current flows through the
PTC at start-up, it heats up. As it heats up, its resistance increases
greatly until it effectively lowers the current through it to an
extremely low value. This, in effect, removes it from the circuit.

NOTE: If bleed resistor is wired across start capacitor, it must be


disconnected to avoid erroneous readings when ohmmeter is
applied across capacitor. (See Fig. 12.)

12.5-22.5 OHMS

12.5 OHM
(BEIGE COLOR)

25-45 OHMS

20-36 OHMS

BLUE
20 OHM
(BLUE COLOR)

25 OHM
(BLUE COLOR)
A88414

Fig. 13PTC Devices

A91455

Fig. 12Capacitors

After system shutdown, resistor cools and resistance value returns


to normal until next time system starts. If indoor coil does not have
a bleed-type expansion device, it may be necessary to remove start
thermistor and replace with accessory start capacitor and relay.
Consult pre-sale literature for application of start kits. Thermistor
device is adequate for most conditions; however, in systems where
off-cycle is short, device cannot cool fully and becomes less
effective as a start device. It is an easy device to troubleshoot.

Always check capacitors with power off. Attempting to


troubleshoot a capacitor with power on can be dangerous.
Defective capacitors may explode when power is applied.
Insulating fluid inside is combustible and may ignite, causing
burns.

1. Shut off all power to system.

Capacitors are used as a phase-shifting device to aid in starting


certain single-phase motors. Check capacitors as follows.

2. Check thermistor with ohmmeter as described below.

1. After power is off, discharge capacitors as outlined above.


Disconnect capacitor from circuit. Put ohmmeter on R X 10k
scale. Using ohmmeter, check each terminal to ground (use
capacitor case). Discard any capacitor which measures
1/2scale deflection or less. Place ohmmeter leads across
capacitor and place on R X 10k scale. Meter should jump to a
low-resistance value and slowly climb to higher value. Failure
of meter to do this indicates an open capacitor. If resistance
stays at zero or a low value, capacitor is internally shorted.

3. Shut off all power to unit.


4. Remove PTC from unit. Wait at least 10 minutes for PTC to
cool to ambient temperature.
5. Measure resistance of PTC with ohmmeter as shown in Fig.13.
The cold resistance (RT) of any PTC device should be approximately 100 180 percent of device ohm rating.
12.5ohm PTC = 12.522.5 ohm resistance beige color
25ohm PTC = 2545 ohm resistance blue color
20ohm PTC = 2036 ohm resistance blue color

2. Capacitance testers are available which read value of capacitor. If value is not within 10 percent value stated on
capacitor, it should be changed. If capacitor is not open or
shorted, the capacitance value is calculated by measuring
voltage across capacitor and current it draws.

If PTC resistance is appreciably less than rating or more than 200


percent higher than rating, device is defective.
If thermistor is good and compressor does not start:
1. Disconnect thermistor from starting circuit.
2. Give compressor a temporary capacitance boost (see next
section).

Exercise extreme caution when taking readings while power


is on. Electrical shock can cause personal injury or death.

3. Run compressor for 10 minutes, shut off, and allow system


pressure to equalize.

Use the following formula to calculate capacitance:


Capacitance (mfd) = (2650 X amps) divided by (volts)

4. Reconnect start thermistor.

14

5. Discharge start capacitor by using a pair of insulated, needlenose pliers and shorting a 15,000ohm, 2watt resistor across
terminals.
NOTE: Some start capacitors already have a bleed resistor
attached. If so, it will discharge itself over a short period of time.
6. Run compressor 10 minutes. Stop and allow unit to sit idle for
5 minutes.
7. Check system pressure equalization.
8. Attempt to restart without capacitance boost.
If PTC thermistor device is inadequate as start device, a start
capacitor and relay may be added to system to ensure positive start.
Capacitor is wired in parallel with run capacitor through normally
closed set of contacts on a device called start relay. The relay coil
is wired across start and common terminals of compressor. The
added capacitance gets the compressor started. As compressor
comes up to speed, voltage across start and common terminals
increases to a value high enough to cause start relay to energize.
This opens normally closed contacts and removes start capacitor
from circuit. In actual practice, this occurs in a fraction of a
second.
NOTE: If bleed resistor is wired across start capacitor, it must be
disconnected to avoid erroneous readings when ohmmeter is
applied across capacitor.
To check start relay and capacitor:
1. Turn off all power to unit.
2. Discharge start and run capacitors as outlined earlier.
3. Most start capacitors will have a 15,000-ohm, 2-watt bleed
resistor. Disconnect these devices from system.
Start capacitor can be inspected visually. It is designed for short
duration or intermittent duty. If left in circuit for prolonged period,
start capacitor blows through a specially designed bleed hole. If it
appears blown, check for welded contacts in start relay. Start
capacitor can be checked by ohmmeter method discussed earlier.
Start relay is checked with ohmmeter. Check for continuity across
coil of relay. You should encounter a high resistance. Since relay
contacts are normally closed, you should read low resistance

5. Try restarting compressor without boost capacitor. If after 2


attempts compressor does not start, remove thermistor. Add an
accessory start-capacitor relay package.
TEMPORARY CAPACITANCE BOOST

Do not under any circumstances attach a temporary boost


capacitor directly to the compressor terminals. Serious personal injury can result. Exercise extreme caution with this
procedure when high-voltage power is on.
There are times when a temporary capacitance boost is needed to
get compressor started. (See Fig. 14.) If compressor motor does not
start, it may be due to low-line voltage, improper pressure
equalization, weak run capacitor, or a seized compressor. Check
each possibility and attempt capacitance boost before adding
auxiliary start capacitor and relay.
1. Turn off all power to unit. There may be more than one power
source to condensing unit.
NOTE: If a PTC is already installed, remove it from the system
by pulling PTC wires from H. and C terminals on run capacitor.
2. Check compressor for ground or open windings. If windings
resistance is within manufacturers recommendations, proceed. (See Section on proper compressor-winding check.)

Do not check winding at compressor terminals with pressure


in the system. Check resistance by removing wires attached at
the compressor contactor and run capacitor.
3. Obtain a start capacitor in the range of 150180F volts rating.
Connect 8gauge wires with insulated clips or terminals to the
H. and C terminals of the run capacitor.
4. Turn power on to unit. If compressor starts, immediately
remove start-capacitor wires from H. and C terminals of run
capacitor, using a pair of insulated, needle-nose pliers. DO
NOT leave start capacitor attached to run capacitor for more
than 3 seconds, even if compressor doesnt start.

L2
FIELD POWER
SUPPLY
L1
R
C
C

COMP
S

Start capacitor
(SC)
temporarily
connected

SC

RC

Capacitance boosting
A00195

Fig. 14Capacitance Boosting


15

T2
T1
T3

T1

T3

T2

HN67ZA002
A91438

HN67ZA008
A94005
T3 BLK
T1 YEL

T2 VIO
T3 BLK

T2

T1

T3

HN67PA025

HN67ZA003

A91440

A91439

Fig. 15Cycle-Protector Device


Step 5Crankcase Heater

across them. Both PTC device and capacitor-relay start system are
standard equipment on some of these units. They are also available
as accessories and may be field-installed.
Step 4Cycle Protector
Solid-state cycle-protector device protects unit compressor by
preventing short cycling. After a system shutdown, cycle protector
provides for a 5 2-minute delay before compressor restarts. On
normal start-up, a 5-minute delay occurs before thermostat closes.
After thermostat closes, cycle protector device provides a 3-sec
delay on HN67PA025, HN67ZA003, and HN67ZA008. (See Fig.
15, 16, and 17.)
Cycle-protector device is simple to troubleshoot. Only a voltmeter
capable of reading 24v is needed. Device is in control circuit;
therefore, troubleshooting is safe with control power (24v) on and
high-voltage power off.
With high-voltage power off, attach voltmeter leads across T1 and
T3 and set thermostat so that Y terminal is energized. Make sure
all protective devices in series with Y terminal are closed.
Voltmeter should read 24v across T1 and T3. With 24v still
applied, move voltmeter lead from T1 terminal to T2 terminal
across T2 and T3. After 5 2 minutes, voltmeter should read 24v,
indicating control is functioning normally. If no time delay is
encountered or device never times out, change control.

Crankcase heater is a device for keeping compressor oil warm. By


keeping oil warm, refrigerant does not migrate to and condense in
compressor shell when the compressor is off. This prevents
flooded starts which can damage compressor.
Crankcase heaters come in 2 basic types: wraparound-(bellyband)
type that is wrapped externally around compressor shell, and
insertion-type that is inserted into compressor oil well in shell of
compressor. Both types are used in outdoor units.
On units that have a single-pole contactor, the crankcase heater is
wired parallel with the contactor contacts and in series with the
compressor. (See Fig. 18.) When the contacts are open, a circuit is
completed from the line side of the contactor, through the
crankcase heater, through the run windings of the compressor, and
to the other side of the line. When the contacts are closed, there is
no circuit through the crankcase heater because both leads are
connected to the same side of the line. This allows the heater to
operate when the system is not calling for heating/cooling. The
heater does not operate when the system is calling for
heating/cooling. On units with 2 or 3 pole contactors, the crankcase heater is connected to the line side of the contactor and is not
controlled by the contactor contacts.
The crankcase heater is powered by high-voltage power of unit.
Use extreme caution troubleshooting this device with power on.
The easiest method of troubleshooting is to apply voltmeter across
crankcase heater leads to see if heater has power. Do not touch

16

OPERATING
TIME

OPERATING
TIME

3
SEC

5 MIN

T1
_

T1
_

T2

T2

5 MIN

BLK DENOTES CLOSED CONTACTS

BLK DENOTES CLOSED CONTACTS

HN67PA025, HN67ZA003, HN67ZA008

HN67ZA002
A91436

A91437

Fig. 16Cycle-Protector Sequence


CUT YELLOW WIRE
BETWEEN CONTACTOR AND
LOW-PRESSURE SWITCH

YEL

SAFETY
CONTROL

TERMINAL
BOARD
CONNECTION

YEL

YEL

YEL

T1

BRN

TERMINAL
BOARD
CONNECTION

VIO

LOGIC

T3

BLK

T2

A88415

Fig. 17Cycle-Protector Wiring


heater. Carefully feel area around crankcase heater. If warm,
crankcase heater is probably functioning. Do not rely on this
method as absolute evidence heater is functioning. If compressor
has been running, the area will still be warm.
With power off and heater leads disconnected, check across leads
with ohmmeter. Do not look for a specific resistance reading.
Check for resistance or an open circuit. Change heater if an open
circuit is detected. Some crankcase heaters in this series of units
are equipped with a crankcase-heater switch. This energy-saving
device shuts off power to heater when temperatures are high
enough that heater is not needed. Be sure this switch is functioning
normally before condemning crankcase heater.
Step 6Time-Delay Relay
The time-delay relay (TDR) is a solid-state-controlled, recycledelay timer which keeps the indoor blower operating for 90 sec
after thermostat is satisfied. This delay enables the blower to
remove residual cooling in the coil after compression shutdown,
thereby improving the efficiency of the system. The sequence of
operation is that on closure of the wall thermostat and at the end of
a fixed on-delay of 1 sec, the fan relay is energized. When the
thermostat is satisfied, an off-delay is initiated. When the fixed
delay of 90 20 sec is completed, the fan relay is de-energized and
fan motor stops. If the wall thermostat closes during this delay, the

DSV

CH

11

21

A91426

Fig. 18Wiring for Single-Pole Contactor


TDR is reset, and the fan relay remains energized. The TDR is a
24v device that operates within a range of 15 to 30v and draws
about 0.5 amps.
If the blower runs continuously instead of cycling off when the fan
switch is set on AUTO, the TDR is probably defective and must be
replaced.

17

Step 7Pressure Switches

Step 9Defrost-Control Board

Pressure switches are protective devices wired into control circuit


(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. Depending on unit
model, you may find a low- and/or high-pressure switch in system.

Solid-state defrost boards used on heat pumps replace electromechanical timer and defrost relay found on older defrost systems.
The defrost-control board can be field-set to check need for defrost
every 30, 50, or 90 minutes of operating time by connecting the
jumper (labeled W1 on the circuit board) to the terminal for the
defrost time desired. The board is set at factory for 90 minutes. The
defrost period is field-selectable, depending upon geographic areas
and defrost demands. Two types of defrost boards are used. Their
functions are described in the sections to follow.

LOW-PRESSURE SWITCH
Located on suction line of condensing unit only, the low-pressure
switch protects against low-suction pressures caused by such
events as loss of charge, low airflow across indoor coil, dirty
filters, and so forth. It opens on a pressure drop at about 27 psi. If
system pressure is above this, switch should be closed. To check
switch, turn off all power to unit, disconnect leads on switch, and
apply ohmmeter leads across switch. You should have continuity
on a good switch. Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this
device for troubleshooting unless you are reasonably certain that a
problem exists. If switch must be removed, remove and recover all
system charge so that pressure gages read 0 psi.

Troubleshooting defrost control involves a series of simple steps


that indicate whether or not board is defective.
NOTE: This procedure allows the service technician to check
control board and defrost thermostat for defects. First troubleshoot
to make sure unit operates properly in heating and cooling modes.
This ensures operational problems are not attributed to the defrostcontrol board.
HK32FA003, 006 DEFROST CONTROL
This control board utilizes screw terminals for the low-voltage
field wiring. The board has a feature that allows the heat pump to
restart in defrost if room thermostat is satisfied during defrost. To
troubleshoot the board, perform the following items.

Wear safety glasses and gloves when working with refrigerants.

1. Turn thermostat to OFF. Shut off all power to outdoor unit.

Apply heat with torch to solder joint and remove switch. Wear
safety glasses when using torch. Have quenching cloth available.
Oil vapor in line may ignite when switch is removed. Braze in
1/4-in. flare fitting and screw on replacement pressure switch.

2. Remove control-box cover for access to electrical components


and defrost-control board.
3. Disconnect defrost-thermostat leads from control board and
connect to ohmmeter. Thermostat leads are the black, insulated wires connected to DFT and R terminals on control
board. Resistance reading may be zero (indicating closed
defrost thermostat) or infinity ( for open thermostat) depending on outdoor temperature.

HIGH-PRESSURE SWITCH
Located on discharge line, the high-pressure switch protects
against high-discharge pressures caused by such events as overcharge, condenser-fan motor failure, system restriction, and so
forth. It opens on pressure rise at about 435 psi. If system pressures
go above this setting during abnormal conditions, the switch
opens. Do not attempt to simulate these system abnormalities as
high pressures pose a serious safety hazard. High-pressure switch
is also checked with an ohmmeter similar to checking low-pressure
switch. If system pressure is below 435 psi, the switch shows
continuity. It is replaced in the same manner as low-pressure
switch. Observe all safety precautions.

4. Jumper between DFT and R terminals on control board as


shown in Fig. 19.
5. Disconnect outdoor fan motor lead from OF2. Tape lead to
prevent grounding.
6. Turn on power to outdoor unit.
7. Restart unit in heating, allowing frost to accumulate on
outdoor coil.
8. After a few minutes in heating, liquid-line temperature at
defrost thermostat should drop below closing set point of
defrost thermostat of approximately 30F. Using ohmmeter,
check resistance across defrost-thermostat leads. Resistance of
zero indicates defrost thermostat is closed and operating
properly.

LIQUID-LINE PRESSURE SWITCH


Located on liquid line of heat pump only, the liquid-line pressure
switch functions similar to conventional low-pressure switch.
Because heat pumps experience very low suction pressures during
normal system operation, a conventional low-pressure switch
cannot be installed on suction line. This switch is installed in liquid
line instead and acts as loss-of-charge protector. The liquid line is
the low side of the system in heating mode. It operates identically
to low-pressure switch except it opens at 7 psi when the heating
piston is in the liquid valve or 27 psi when the heating piston is in
the liquid line. Troubleshooting and removing this switch is
identical to procedures used on other switches. Observe same
safety precautions.

9. Remove protective cover from TP1 and TP2 speed-up terminals. Install jumper wire on speed-up terminals. This reduces
the timing sequence to 1/60 of original time. (See Fig. 20.)
Since Fig. 20 shows timing cycle set at 30 minutes, unit
initiates defrost within approximately 30 sec; if setting is at 50
minutes, within 50 sec; 90 minutes, within 90 sec. When you
hear the reversing valve change position, remove protective
cover/jumper. Otherwise, control will terminate normal 10minute defrost cycle in approximately 10 sec.

Step 8Defrost Thermostats


Defrost thermostat signals heat pump that conditions are right for
defrost or that conditions have changed to terminate defrost. It is
a thermally actuated switch clamped to outdoor coil to sense its
temperature. Normal temperature range is closed at 30 3F and
open at 80 5F.

Exercise extreme caution when shorting speed-up pins. If pins


are accidentally grounded, damage to the control board will
occur.

NOTE: The defrost thermostat must be located on the liquid side


of the outdoor coil on the bottom circuit and as close to the coil as
possible.

10. Unit is now operating in defrost mode. Using voltmeter, check


between C and W2 as shown in Fig. 21. Reading on voltmeter
should indicate 24v. This step ensures defrost relay contacts

18

OF2 OF1
OF2

OF1

E
W2

14

L
W3

DFT

T2

TI DFT

TEST 30 50 90

W1

O
R
W2
Y

30 50

W1

CES0110063,
CES0130024

HK32FA003/HK32FA006

A91442

A88402

Fig. 19Jumper DFT and R Terminals


7. Unit changes over to defrost within 90 sec (depending on
timing cycle setting). Liquid-line temperature rises to range
where defrost thermostat contacts open. Temperature range is
from 75F to 85F. Resistance goes from zero to when
contacts open.

have closed, energizing supplemental heat (W2) and reversing


valve solenoid (O).
11. Unit should remain in defrost no longer than 10 minutes.
Actual time in defrost depends on how quickly speed-up
jumper is removed. If it takes 3 sec to remove speed-up
jumper after unit has switched to defrost, only 7 minutes of
defrost cycle remains.

8. If either opening or closing temperature does not fall within


above ranges or thermostat sticks in 1 position, replace
thermostat to ensure proper defrost operation.

12. After a few minutes in defrost (cooling) operation, liquid line


should be warm enough to have caused defrost-thermostat
contacts to open. Check resistance across defrost thermostat.
Ohmmeter should read infinite resistance, indicating defrost
thermostat has opened at approximately 80F.

CES0110063 DEFROST CONTROL


Some heat pumps built in 1991 and later incorporate a new defrost
control. The screw terminals found on the previous control board
have been replaced by a connector plug with stripped-wire leads.
This control board also contains the feature that allows the heat
pump to restart in defrost if the room thermostat is satisfied during
defrost. The board also contains a 5-minute cycle protector that
prevents the unit from short cycling after it cycles off or after a
power interruption. To troubleshoot the board, perform the following items.

13. Shut off unit power and reconnect fan lead.


14. Remove jumper wire from speed-up terminal and reinsert
cover on speed-up terminals. Failure to remove jumper causes
unit to speed up operating cycles continuously.
15. Remove jumper between DFT and R terminals. Reconnect
defrost thermostat leads.

1. Turn thermostat to OFF. Shut off all power to outdoor unit.

16. Replace control-box cover. Restore power to unit.

2. Remove control-box cover for access to electrical components


and defrost-control board.

If defrost thermostat does not check out following above items or


incorrect calibration is suspected, check for a defective thermostat
as follows.

3. Disconnect defrost-thermostat leads from control board and


connect to ohmmeter. Thermostat leads are black, insulated
wires connected to DFT and R terminals on control board.
Resistance reading may be zero (indicating closed-defrost
thermostat), or infinity ( for open thermostat) depending on
outdoor temperature.

1. Follow items 1-5 above.


2. Using thermocouple temperature-measuring device, route sensor or probe underneath coil (or other convenient location).
Attach to liquid line near defrost thermostat. Insulate for more
accurate reading.

4. Jumper between DFT and R terminals on control board as


shown in Fig. 21.

3. Turn on power to outdoor unit.

5. Disconnect outdoor fan-motor lead from OF2. Tape lead to


prevent grounding.

4. Restart unit in heating mode.


5. Within a few minutes, liquid-line temperature drops within a
range causing defrost thermostat contacts to close. Temperature range is from 33F to 27F. Notice temperature at which
ohmmeter reading goes from to zero ohms. Thermostat
contacts close at this point.

6. Turn on power to outdoor unit.


7. Restart unit in heating mode, allowing frost to accumulate on
outdoor coil.
8. After a few minutes in heating mode, liquid-line temperature
at defrost thermostat should drop below closing set point of
defrost thermostat of approximately 30F. Check resistance

6. Remove protective cover from TP1 and TP2 speed-up terminals and install jumper wire on the speed-up terminals.

19

OF1 OF2
G

OF2
OF1

W2

14

L
G

W3

T2

TI DFT

TEST 30 50 90

W1

DFT

O
R

50 90

W2

W1

Y
C

HK32FA003/HK32FA006

CES0110063,
CES0130024

A88404

A91444

Fig. 20Inserting Jumper Wire

OF2
OF1

OF2 OF1

G
E
W2

14

L
W3

G C
C

DFT

T2

TI DFT

TEST 30 50 90

W1

30 50

R
W2

W1

Y
C

HK32FA003/HK32FA006

CES0110063,
CES0130024

A88403

Fig. 21Checking Between C and W2


across defrost thermostat leads using ohmmeter. Resistance of
zero indicates defrost thermostat is closed and operating
properly.
9. Short between the speed-up terminals using a thermostat
screwdriver. This reduces the timing sequence to 1/256 of
original time. (See Fig. 20 and Table 11.)
NOTE: Since Fig. 20 shows timing cycle set at 90 minutes, unit
initiates defrost within approximately 21 sec. When you hear the
reversing valve change position, remove screwdriver immediately.
Otherwise, control will terminate normal 10-minute defrost cycle
in approximately 2 sec.

A91443

Exercise extreme caution when shorting speed-up pins. If pins


are accidentally shorted to other terminals, damage to the
control board will occur.
10. Unit is now operating in defrost mode. Check between C and
W2 using voltmeter as shown in Fig. 21. Reading on voltmeter
should indicate 24v. This step ensures defrost-relay contacts
have closed, energizing supplemental heat (W2) and
reversing-valve solenoid (O).
11. Unit should remain in defrost no longer than 10 minutes.
Actual time in defrost depends on how quickly speed-up
jumper is removed. If it takes 2 sec. to remove speed-up
jumper after unit has switched to defrost, the unit will switch
back to heat mode.

20

Table 11Defrost Control Speed-Up Timing Sequence for CES0110063/CES0130024


PARAMETER

MINIMUM

MAXIMUM

30-minute cycle
50-minute cycle
90-minute cycle
10-minute cycle
5 minutes

27
45
81
9
4.5

33
55
99
11
5.5

SPEED-UP
(NOMINAL)
7 sec
12 sec
21 sec
2 sec
1 sec

new control, you must have replacement-defrost thermostat and


harness kit. See your replacement-component representative for kit
part number.

12. After a few minutes in defrost (cooling) operation, liquid line


should be warm enough to have caused defrost-thermostat
contacts to open. Check resistance across defrost thermostat.
Ohmmeter should read infinite resistance, indicating defrost
thermostat has opened at approximately 80F.
13. Shut off unit power and reconnect fan lead.
14. Remove jumper between DFT and R terminals. Reconnect
defrost-thermostat leads. Failure to remove jumper causes unit
to switch to defrost every 30, 50, or 90 minutes and remain in
defrost for full 10 minutes.
15. Replace control-box cover. Restore power to unit.
If defrost thermostat does not check out following above items or
incorrect calibration is suspected, check for a defective thermostat
as follows.
1. Follow items 1-5 above.
2. Route sensor or probe underneath coil (or other convenient
location) using thermocouple temperature-measuring device.
Attach to liquid line near defrost thermostat. Insulate for more
accurate reading.
3. Turn on power to outdoor unit.
4. Restart unit in heating.
5. Within a few minutes, liquid-line temperature drops within a
range causing defrost-thermostat contacts to close. Temperature range is from 33F to 27F. Notice temperature at which
ohmmeter reading goes from to zero ohms. Thermostat
contacts close at this point.
6. Short between the speed-up terminals using a small, slotted
screwdriver.
7. Unit changes over to defrost within 21 sec (depending on
timing-cycle setting). Liquid-line temperature rises to range
where defrost-thermostat contacts open. Temperature range is
from 75F to 85F. Resistance goes from zero to when
contacts open.
8. If either opening or closing temperature does not fall within
above ranges or thermostat sticks in 1 position, replace
thermostat to ensure proper defrost operation.
CES0130024 DEFROST CONTROL
Some heat pumps built in 1993 and later incorporated a new
defrost control similar to the CES0110063 except the 5-minute
cycle protector has been removed. This control is used on heat
pump units with reciprocating compressors where short-cycle
protection is not required.
Troubleshooting this control will be the same as the CES0110063
control except for the cycle-protector function. The CES0130024
control is identical to the CES0110063 except the T2 terminal and
cycle-protector logic have been removed.
CES0130076 DEFROST CONTROL
This defrost control is the same size as the CES0130063 control
but is not backwards-compatible. (See Fig. 22.) To upgrade to the

Defrost Settings
The defrost control is a time/temperature control which includes a
field-selectable time period (DIP switch 1 and 2 on board, see
Table 12) between defrost cycles of 30, 60, 90, and 120 minutes
(factory-set at 90 minutes).

Table 12Defrost Timer Settings


SW1
On
Off
Off
On

SW2
Off
On
Off
On

SW3
30
60
90
120

To initiate a forced defrost, two options are available, depending


on the status of the defrost thermostat.
If defrost thermostat is closed, speedup pins (J1) must be shorted
by placing a Flathead screwdriver in between for 5 seconds and
releasing, to observe a complete defrost cycle. When the Quiet
Shift switch is selected, compressor will be turned off for two,
30second intervals during this complete defrost cycle. When
Quiet Shift switch is in factory-default OFF position, a normal and
complete defrost cycle will be observed.
If defrost thermostat is in open position and speedup pins are
shorted (with a Flathead screwdriver) for 5 seconds and released,
a short defrost cycle will be observed (actual length is dependent
upon the selected Quiet Shift position). When Quiet Shift switch is
in ON position, the length of defrost is 1 minute (30 seconds
compressor-off period followed by 30 seconds of defrost with
compressor operation). On return to heat operation, compressor
will again turn off for an additional 30 seconds and the fan for 40
seconds. When the Quiet Shift is in OFF position, only a brief
30second cycle will be observed.
If it is desirable to observe a complete defrost in warmer weather,
the thermostat must be closed as follows.
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan-motor lead from OF2 on control board
(See Fig. 22.). Tape to prevent grounding.
3. Restart unit in heating mode, allowing frost to accumulate on
outdoor coil.
4. After a few minutes in heating mode, liquid-line temperature
should drop below closing point of defrost thermostat (approximately 30 F).
NOTE: Unit will remain in defrost until defrost thermostat
reopens at approximately 80 F coil temperature at liquid line or
remainder of defrost cycle time.
5. Turn off power to outdoor unit and reconnect fan-motor lead
to OF2 on control board after above forced-defrost cycle.
Compressor Shut Down

21

OF1

DFT

OF2

T2 C C O
T1

O R W2 Y C

Y
P1
30

30

60

120

60

P3

ON

DFT

QUIET
SHIFT

90
INTERVAL TIMER OFF

J1

SPEEDUP

Speedup
Pins

CESO13007600
Quiet
Shift

Defrost interval
DIP switches
A99442

Fig. 22Defrost Control


This control has the option of shutting down the compressor for 30
seconds while going into and out of defrost modes. This is
accomplished by turning DIP switch 3 to the ON position. See Fig.
22 for switch position. Factory default is in the OFF position.

FEEDER TUBE
STUB TUBE

Five-Minute Time Delay


This control has a 5minute time delay on startup. The speedup
terminals can be used to bypass this delay. Momentary shorting
across the speedup terminals will, upon release, bypass 5minute
time delay. Do not short out the speedup terminals for more than
5 seconds, or defrost mode will be initiated.
Troubleshooting
Troubleshooting this control is done in the same manner as the
CES0130063 control with the exceptions listed above.

DEFROST
THERMOSTAT

DEFROST THERMOSTAT LOCATION


On most residential, outdoor heat-pump models, the defrost
thermostat is located on the return-bend side of the coil. The 5/16
OD feeder tube from the header will enter a 11/2 in. to 2in. long
3/8 OD stub prior to entering the coil. There is only one stub tube
per coil. All other feeder tubes enter the coil directly. The defrost
thermostat attaches to this stub tube. (See Fig. 23.)
Step 10Fan Motors

A97517

Fig. 23Defrost Thermostat Location

Turn off all power to unit before servicing or replacing fan


motor. Be sure unit main power switch is turned off. Failure
to do so may result in electric shock, death, or injury from
rotating fan blade.

Fan motor rotates the fan blade that either draws or blows air
through outdoor coil to perform heat exchange. Motors are totally
enclosed to increase reliability. This also eliminates need for rain
shield. For the correct position of the fan blade assembly, see Fig.
24 and Table 13.

The bearings are permanently lubricated; therefore, no oil ports are


provided.

22

TOP COVER

3 IN. SMALL & MEDIUM BASE UNITS


4 IN. LARGE BASE UNIT
FROM DISCHARGE LOUVER
TO TOP OF FAN BLADE

BASKET TOP
FAN
ORIFICE

A91428

FAN BLADE

STAR BURST TOP


A88347

Fig. 24Fan Position


For suspected electrical failures, check for loose or faulty electrical
connections or defective fan-motor capacitor. Fan motor is
equipped with thermal overload device in motor windings which
may open under adverse operating conditions. Allow time for
motor to cool so device can reset. Further checking of motor can
be done with an ohmmeter. Set scale on R X 1 position, check for
continuity between 3 leads. Replace motors that show an open
circuit in any of the windings. Place 1 lead of ohmmeter on each
motor lead. At same time, place other ohmmeter lead on motor
case (ground). Replace any motor that shows resistance to ground,
signs of arcing, burning, or overheating.

Table 13Fan Position


SILENCER SYSTEM AND BASKET TOP
Dimension A (In.)
Fan Blade
Part No.
Brookside
Revcor
LA01EB023
4-5/32

HC29GE208
LA01EC019
5-1/8

LA01EA026
4-5/8

HC31GE230/231
LA01RA015
4-7/8
4-5/8
HC33GE208
LA01EW049
5-1/4

HC33GE232
LA01RA015
4-29/32
4-17/32
HC34GE231
LA01RA015
5-5/32
4-25/32
HC34GE460
HC35GE208
LA01EW048
4-15/16

LA01EA025
5-7/8

HC35GE232
LA01RA024
5-11/32
5-3/32
LA01RA026
5-9/16
4-11/16
HC37GE208
LA01EA025
6-1/8
6-1/8
HC37GE230
LA01EW042
6-5/32
6-1/8
HC38GE221
LA01EA031
7-25/32

LA01EC018
5-11/16

HC39GE232
LA01RA026
5-1/2
4-3/4
LA01EA036
5-9/16

LA01EA024
5-3/32
4-27/32
HC39GE234
LA01EC018
5-1/2

LA01EA036
6-1/16

HC39GE461
LA01EC018
6-1/4

LA01RA026
6-1/16
5-7/32
HC40GE230
LA01EA024
5-9/32
5-11/32
HC40GE461
LA01EA024
5-27/32
5-19/32
BASEPAN DIMENSIONS FOR STAR BURST TOP (IN.)
Small
22-1/2 x 26-3/16
Medium
30 x 33
Large
38-5/8 x 42-1/16
Fan Motor
Part No.

Step 11Service Alarm Control Board


NOTE: If the proper night-setback thermostat is not used, the
service-alarm control will work, but there will be no light
indication on thermostat.
The service-alarm control provides immediate warning when
outdoor heat pump requires servicing. It turns on indoor
thermostat-malfunction light if compressor does not operate for
either heating or cooling. This enables owner to obtain timely
heat-pump service during heating season, reducing supplementary
electric heat costs, and during cooling season, reducing period of
heat discomfort.
The service alarm is an accessory device. Service alarm locks out
compressor under certain adverse operating conditions. System is
manually reset by shutting it off at thermostat subbase, then
turning it back on. If adverse condition is corrected, system
restarts.
One example of an adverse condition would be a system located in
a desert climate where high operating temperatures may cause
system to shut down on the high-pressure switch or on the
compressor internal overload.
Connect service alarm to outdoor-unit control-circuit-terminal
board. (See Fig. 25 and wiring diagram on unit.)
Connect all field line-power wires to unit in usual manner. Route
1 field line-power supply wire through metallic loop on bottom of
service alarm then to normal unit connection. Units with RLA of
less than 14 amps will require 2 passes through the metallic loop.

service alarm to L on indoor thermostat subbase is required.


Service alarm requires 2 inputs.
1. It must sense a 24v input from thermostat. As thermostat calls
for heating or cooling, it supplies 24v to service alarm device.
2. A current transformer (or induction loop) similar to a
clamp-on ammeter senses current draw in the compressor
lead. Induction loop must sense a minimum current draw
when thermostat is calling for heating or cooling.
NOTE: On a single-phase compressor, induction loop senses
current in common leg. On a 3-phase compressor, induction loop
senses current in any 1 of the phases.

Refer to Fig. 25 or 26 for wiring connections for service alarm or


service alarm with solid-state cycle-protector accessories, when
used.
NOTE: The wire from the X terminal on the service alarm to L on
the outdoor terminal board, indoor terminal board, and thermostat
subbase is field supplied and wired when using defrost controls
HK32FA003 or HK32FA006. When defrost control CES0110063
or CES0130024 is used, field-supplied wire from X terminal on

23

If service alarm needs replacing, shut off all power to unit


before attempting removal. Electrical shock can cause personal injury or death.
Troubleshooting service-alarm device is easy. With thermostat
calling for heating or cooling and compressor running, indoor
thermostat light should be off. If on, check for wiring errors or
replace the service alarm.
To check for correct operation, shut off circuit breaker or disconnect switch to outdoor unit while it is running. Signal light on
thermostat should light. If this does not occur, check for wiring
errors or replace the service alarm.
Step 12Outdoor Thermostat(s)
The outdoor thermostat(s) is/are installed in the control box. The
sensing bulb(s) remain/s in the control box. Outdoor thermostat
brings on stages of electric heat as outdoor temperature and
heat-pump output drops. Setting at which thermostat closes is
variable, depending on design of system. It is set at time of
installation and should not be changed without cause. Up to 2
outdoor thermostats may be installed. Some systems may not have
any thermostat. An outdoor thermostat can also be used to lock out
compressor operation at low ambients in condensing unit not
equipped with low-ambient control.
Although these devices are installed in control circuit (24v), turn
off all power to unit before attempting to troubleshoot thermostat.
Use a standard ohmmeter to check for continuity through thermostat. If you suspect thermostat is out of calibration, use calibrated
electronic thermometer to determine correct outdoor temperature.
Turn thermostat dial knob until switch closes. Observe this using
ohmmeter across switch. Read temperature setting when switch
closes. It should be close to reading observed using electronic
thermometer. Any setting within 5F is acceptable.
Step 13Compressor Plug

compressor terminals, and the mating female terminals are completely encapsulated in the plug. Therefore, the terminals are
isolated from any moisture so corrosion and resultant pitted or
discolored terminals are reduced. The plug is oriented to the relief
slot in the terminal box so the cover cannot be secured if wires are
not positioned in slot, assuring correct electrical connection at the
compressor. The plug can be removed by simultaneously pulling
while rocking the plug. However, these plugs are specialized and
vary in terminal orientation in the plug. Therefore, plugs can be
used on only the specific compressor or group as shown in Fig. 27.
For the Carlyle and Bristol compressors in Fig. 27, the triangle
formed by the fusite terminals points down, and the plug is
likewise oriented. The fusite terminals and plug-terminal orientation shown for the Tecumseh compressor is shown with the
triangle formed by the terminals pointing toward the top. The
configuration around the fusite terminals is the outline of the
terminal covers used on the specific compressors. The slot through
which the wires of the plug are routed is oriented on the bottom or
slightly to the left or right. The correct plug can be connected
easily to the compressor terminals and plug wires routed easily
through the slot in the terminal cover. Therefore, if a Carlyle or
Bristol compressor is substituted for a Tecumseh compressor, a
new plug must be installed. If the plug is not changed, proper
connection and routing of the plug wires through the terminal
cover will be impossible.
Step 14Low-Voltage Terminals
The low-voltage terminal designations, along with descriptions
and/or functions, are used on all split-system condensers and heat
pumps:
G.Energizes blower circuit from indoor thermostat.
EEnergizes emergency heat relay.
W2Energizes first-stage supplemental heat through defrost relay
(wht).
LEnergizes light on thermostat with service alarm.
W3Energizes second- or third-stage supplemental heat.
REnergizes 24v power from transformer (red).

The compressor electrical plug provides a quick-tight connection


to the compressor terminals. The plug completely covers the
HIGH AND/OR LOW PRESSURE
AND/OR DISCHARGE TEMPERATURE
SWITCH (IF USED)
DTS

24-VOLT WIRING

HPS
C

BRN

LPS

C
BLU

BLU YEL
YEL

C
THERMOSTAT
SUBBASE

INDOOR
UNIT
TERMINAL
BOARD

BLK

ORN

YEL

RED

OUTDOOR
UNIT
TERMINAL
BOARD
1

SERVICE ALARM
PASS SUPPLY WIRE THROUGH
METALLIC LOOP TWICE ON
UNITS WITH NAMEPLATE
RLA OF 14 AMPS OR LESS.
*METALLIC
LOOP

ONE FIELD
LINE VOLTAGE
SUPPLY WIRE

A88340

Fig. 25Service Alarm Wiring Connections


24

FIELD LINE VOLTAGE SUPPLY WIRE

YEL

CYCLE PROTECTOR
T1 T2 T3

SERVICE ALARM
X
3
2
1

HIGH AND/OR LOW PRESSURE


AND/OR DISCHARGE TEMPERATURE
SWITCH (IF USED)

VIO BLK
ORN
Y

DTS
L

YEL

BLK

BLK

BRN

YEL

BLU

LPS

BLU

HPS
BRN
A88339

THERMOSTAT INDOOR OUTDOOR


UNIT
SUBBASE
UNIT
TERMINAL TERMINAL
BOARD
BOARD
C

COMMON POTENTIAL
FACTORY WIRING (FIELD CONNECTED)
FIELD-SUPPLIED WIRING
CONTACTOR
A88339

Fig. 26Wiring Connections for Service Alarm and Cycle Protector


If compressor draws locked-rotor amps and all other external
sources of problems have been eliminated, compressor must be
replaced. Because compressor is a sealed unit, it is impossible to
determine exact mechanical failure. However, complete system
should be checked for abnormalities such as incorrect refrigerant
charge, restrictions, insufficient airflow across indoor or outdoor
coil, and so forth, which could be contributing to the failure.

YEnergizes contactor for first-stage cooling or first-stage heating for heat pumps (yel).
OEnergizes reversing valve on heat pumps (orn).
CCommon side of transformer (blk).
RECIPROCATING COMPRESSOR
The compressor is the heart of the refrigeration system. It pumps
refrigerant through the system. If it malfunctions, system capacity
and efficiency could be negatively affected.

RUNS, DOES NOT PUMP


In this type of failure, compressor motor runs and turns compressor, but compressor does not pump the refrigerant. A clamp-on
ammeter on common leg of a single-phase compressor, or any 1
lead of a 3-phase compressor, shows a very low current draw,
much lower than RLA (rated load amps) value stamped on
compressor nameplate. Because no refrigerant is being pumped,
there is no return gas to cool compressor motor. It eventually
overheats and shuts off on its internal protection.

The compressor is an electrical (as well as mechanical)


device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most
troubleshooting techniques. Refrigerants in system present
other safety hazards. Always wear safety glasses and gloves
when handling refrigerants.

RUNS, DOES NOT PUMP, HIGH-TO-LOW SIDE LEAK

Compressor failures are classified in 2 broad failure categories:


mechanical and electrical. Both types are discussed below.

In this type of failure, compressor motor runs and turns compressor, and compressor is pumping. Usually, an internal problem such
as blown head gasket or broken internal-discharge line causes
compressor to pump hot discharge gas back into its own shell
rather than through system.

Step 1Mechanical Failures


A compressor is a mechanical pump driven by an electric motor
contained in a welded or hermetic shell. In a mechanical failure,
motor or electrical circuit appears normal, but compressor does not
function normally.

Using pressure gages on service valves shows high suction and


low discharge pressure readings. Motor currents are lower than
normal. Because hot gas is being discharged into shell, the shell
becomes hot. The hot gas causes compressor motor to cycle off on
its internal protection.

Exercise extreme caution when reading compressor currents


when high-voltage power is on. Correct any of the problems
described below before installing and running a replacement
compressor. Wear safety glasses and gloves when handling
refrigerants.

RUNS AND PUMPS, LOW CAPACITY


This failure type is difficult to pinpoint because extent of damage
varies. Compressor is a pump with internal valves that enable
compressor to pump properly. The cylinder has a set of suction and
discharge valves. Any of these parts may become damaged or
broken, causing loss in pumping capacity. Severity of damage
determines amount of capacity loss. Use pressure gages to find any
abnormal system pressures if system charge and other conditions
are normal.

LOCKED ROTOR
In this type of failure, compressor motor and all starting components are normal. When compressor attempts to start, it draws
locked-rotor current and cycles off on the internal protection.
Locked-rotor current is measured by applying a clamp-on ammeter
around common (blk) lead of the compressor on a single-phase
compressor, or any 1 of the leads on a 3-phase compressor. Current
drawn when it attempts to start is then measured. LRA (lockedrotor amp) value is stamped on compressor nameplate.

An owner may complain that a unit is not handling the buildings


heating or cooling load. The compressor current draw may be
abnormally low or high. Although this type of failure does occur,
all other possible causes of capacity loss must be eliminated before
condemning compressor.

25

LEAD 3
BLUE

CARLYLE

BRISTOL
COPELAND

C S
R

Use safety glasses and gloves when handling refrigerants.


Sometimes a leak is detected at weld seam around girth of
compressor or a fitting that joins compressor shell. Many of these
leaks can be repaired and the compressor saved if correct procedure is followed.

1. Turn off all power to unit.


LEAD 2
YEL.

LEAD 1
BLK.

2. Remove and recover all refrigerant from system so that gage


pressures are 0 psi.
3. Clean area around leak to bare metal.

TECUMSEH
C
C

4. Apply flux and repair joint with silver solder. Do not use
low-temperature solder such as 50-50.

LEAD 1
BLK.

5. Clean off excess flux, check for leaks, and apply paint over
repaired area to prevent corrosion.

Do not use this method to repair a compressor leak due to severe


corrosion. Never attempt to repair a compressor leaking at electric
terminals. This type of failure requires compressor replacement.

LEAD 2
YEL.

LEAD 3
BLUE

TECUMSEH

LEAD 1
BLK.

Step 2Electrical Failures


The compressor mechanical pump is driven by an electric motor
within its hermetic shell. In electrical failures, compressor does not
run although external electrical and mechanical systems appear
normal. Compressor must be checked electrically for abnormalities.

LEAD 3
BLUE

Before troubleshooting compressor motor, review this description


of compressor motor-terminal identification.

S
R

SINGLE-PHASE MOTORS
To identify terminals C, S, and R:
1. Turn off all unit power.

LEAD 2
YEL.

2. Short the run and start capacitors to prevent shock.


3. Remove all wires from motor terminals.
4. Read resistance between all pairs of terminals using an
ohmmeter on 0-10 ohm scale.

MILLENNIUM

LEAD 1
BLK.

5. Determine 2 terminals that provide greatest resistance reading.


Through elimination, remaining terminal must be common (C).
Greatest resistance between common (C) and another terminal
indicates start winding because it has more turns. This terminal is
start (S). Remaining terminal will be run winding (R). (See Fig.
28.)

C
R S

LEAD 3
BLUE

NOTE: If compressor is hot, allow time to cool and internal line


break to reset. There is an internal line-break protector which must
be closed.

LEAD 2
YEL.
A94002

THREE-PHASE MOTORS

Fig. 27Compressor Plug

Resistance readings between all 3 sets of windings should be the


same.

NOISY COMPRESSOR
Noise may be caused by a variety of internal problems such as
loosened hardware, broken mounting springs, etc. System problems such as overcharged compressor (especially at start-up) or too
much oil in compressor may also cause excessive noise. Excess oil
in compressor is normally encountered only after a replacement
compressor has been added without purging oil from previous
compressor. As new compressor pumps, excess oil in system
returns and adds to volume already present, causing noise.
COMPRESSOR LEAKS

All compressors are equipped with internal motor protection. If


motor becomes hot for any reason, protector opens. Compressor
should always be allowed to cool and protector to close before
troubleshooting. Always turn off all power to unit and disconnect
leads at compressor terminals before taking readings.
Most common motor failures are due to either an open, grounded,
or short circuit. Directions below are specifically for single-phase
units; however, they also apply to 3-phase compressors. When a
single-phase compressor fails to start or run, 3 tests can help
determine the problem. First all possible external causes should be
eliminated, such as overloads, improper voltage, pressure equalization, defective capacitor(s), relays, wiring, etc. Compressor has
internal line-break overload, so be certain it is closed.
OPEN CIRCUIT

26

(EXAMPLE)
TO DETERMINE INTERNAL CONNECTIONS OF SINGLEPHASE MOTORS (C,S,R) EXCEPT SHADED-POLE

?
?

DEDUCTION:

POWER OFF!
?

(GREATEST RESISTANCE)
5.8 (OHM)

RUN WINDING (R)


START WINDING (S)

OHMMETER
0-10 SCALE

(SMALLEST RESISTANCE)
0.6

2 IS COMMON (C)
BY ELIMINATION

(REMAINING RESISTANCE)
5.2

2 IS COMMON,
THEREFORE, 1 IS

1
5.2

1
2
0.6

5.8

START WINDING (S)

2
3

3
3 IS RUN WINDING (R)

A88344

Fig. 28Identifying Internal Connections


SHORT CIRCUIT

To determine if any winding has a break in the internal wires and


current is unable to pass through:

To determine if any wires within windings have broken through


their insulation and made contact with other wires, thereby
shorting all or part of the winding(s), be sure the following
conditions are met:

1. Be sure all power is off.


2. Discharge all capacitors.
3. Remove wires from terminals C, S and R.

1. Correct motor-winding resistances must be known before


testing, either from previous readings or from manufacturers
specifications.

4. Check resistance from C-R, C-S and R-S using an ohmmeter


on 0-1000 ohm scale.
Because winding resistances are usually less than 10 ohms, each
reading appears to be approximately 0 ohm. If resistance remains
at 1000 ohms, an open or break exists, and compressor should be
replaced.

2. Temperature of windings must be as specified, usually about


70F.
3. Resistance-measuring instrument must have an accuracy
within 5-10 percent. This requires an accurate ohmmeter,
such as a Wheatstone bridge or null balance-type instrument.
4. Motor must be dry or free from direct contact with liquid
refrigerant.

Be sure internal line-break overload is not temporarily open.

MAKE THIS CRITICAL TEST

GROUND CIRCUIT

(Not advisable unless above conditions are met.)

To determine if a wire has broken or come in direct contact with


shell, causing a direct short to ground:

1. Be sure all power is off.

1. Be sure all power is off.

2. Discharge all capacitors.

2. Discharge all capacitors.

3. Remove wires from terminals C, S, and R.

3. Remove wires from terminals C, S, and R.

4. Place instrument probes together and determine probe and


lead wire resistance.

4. On hermetic compressors, allow crankcase heaters to remain


on for several hours before checking motor to ensure windings
are not saturated with refrigerant.

5. Check resistance readings from C-R, C-S, and R-S.


6. Subtract instrument probe and lead resistance from each
reading.

5. Use an ohmmeter on R X 10,000 ohm scale. A megohmmeter


may be used in place of ohmmeter. Follow manufacturers
instructions.

If any reading is within 20 percent of known resistance, motor is


probably normal. Usually a considerable difference in reading is
noted if a turn-to-turn short is present.

6. Place 1 meter probe on ground or on compressor shell. Make


a good metal-to-metal contact. Place other probe on terminals
C, S, and R in sequence.

Step 3System Cleanup After Burnout

7. Note meter scale.


8. If reading of zero or low resistance is obtained, motor is
grounded. Replace compressor.

Turn off all power to unit before proceeding. Wear safety


glasses and gloves when handling refrigerants. Acids formed
as a result of motor burnout can cause burns.

A compressor of 1ton capacity or less is probably grounded if


resistance is below 1 million ohms. On larger-sized, single-phase
compressors, resistance to ground should not be less than 1000
ohms per volt of operating voltage.
Example:
230 volts X 1000 ohms/volt = 230,000 ohms minimum

NOTE: To analyze level of suspected contamination from compressor burnout, use Total Test. See your distributor/branch.
Some compressor electrical failures can cause motor to overheat.
When this occurs, by-products, which include sludge, carbon, and

27

acids, contaminate system. If burnout is severe enough, system


must be cleaned before replacement compressor is installed. The 2
types of motor burnout are classified as mild or severe.

Scroll Gas Flow

In mild burnout, there is little or no detectable odor. Compressor


oil is clear or slightly discolored. An acid test of compressor oil
will be negative. This type of failure is treated the same as
mechanical failure. Liquid-line strainer should be removed and
liquid-line filter drier installed.

Compression in the scroll is


created by the interaction of
an orbiting spiral and a
stationary spiral. Gas enters
an outer opening as one of the
spirals orbits.

In a severe burnout, there is a strong, pungent, rotten-egg odor.


Compressor oil is very dark. Evidence of burning may be present
in tubing connected to compressor. An acid test of compressor oil
will be positive. Complete system must be reverse flushed with
refrigerant. AccuRater or TXV must be cleaned or replaced. In
a heat pump, accumulator and reversing valve are replaced. These
components are also removed and bypassed during reverseflushing procedure. Remove and discard liquid-line strainer. After
system is reassembled, install liquid-line and suction-line filter
driers. Run system for 2 hrs. Discard both driers and install new
liquid-line drier only.

2
The open passage is sealed off
as gas is drawn into the spiral.

3
As the spiral continues to orbit,
the gas is compressed into an
increasingly smaller pocket.

Step 4Compressor Removal And Replacement


Once it is determined that compressor has failed and the reason
established, compressor must be replaced.

Wear safety glasses and gloves when handling refrigerants


and when using brazing torch.

By the time the gas arrives at


the center port, discharge
pressure has been reached.

1. Shut off all power to unit.

5
Actually, during operation, all
six gas passages are in various
stages of compression at all
times, resulting in nearly continuous suction and discharge.

2. Remove and recover all refrigerant from system until pressure


gages read zero psi. Use all service ports.
3. Disconnect electrical leads from compressor. Disconnect or
remove crankcase heater and remove compressor-holddown
bolts.

A90198

Fig. 29Scroll Compressor Refrigerant Flow

4. Cut compressor from system with tubing cutters. Do not use


brazing torch for compressor removal. Oil vapor may ignite
when compressor is disconnected.

vacuum. If a pumpdown procedure is used, the scroll compressor


is capable of pumping into a vacuum very quickly, which could
cause fusite arcing and compressor failure. See Step 4 of Reciprocating Compressor section for removal and replacement.

5. Scratch matching marks on stubs in old compressor. Make


corresponding marks on replacement compressor.
6. Use torch to remove stubs from old compressor and to reinstall
them in replacement compressor.

Step 3Discharge Thermostat


Some scroll compressors have a discharge thermostat that reciprocating compressors do not have. This thermostat is mounted in a
well in the top of the compressor shell to sense if the discharge
temperature reaches 290F and shuts down the compressor to
prevent damage to it. When the temperature of the thermostat
reaches 140F, power is restored to the compressor.

7. Use copper couplings to tie compressor back into system.


8. Evacuate system, recharge, and check for normal system
operation.
9. Copeland CR-6 and scroll compressors have copper-plated,
steel-suction ports. Excess heat during brazing will burn off
copper plating. See Brazing section for additional information.

The scroll compressor pumps refrigerant through the system by the


interaction of a stationary and an orbiting scroll. (See Fig. 29.) The
scroll compressor has no dynamic suction or discharge valves, and
it is more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. Due to the design of the scroll compressor, the
internal compression components unload (equalize pressure) on
shutdown. The white oil (Sontex 200LT) used in the scroll is
compatible with 3GS oil, which can be used if additional oil is
required. (See Table 14 for oil recharge requirements.)

To determine if the thermostat is operating properly, either attach


the thermocouple of an electronic thermometer to the dome of the
compressor near the thermostat, or remove the thermostat and
place the thermocouple inside the well. The electronic thermometer must be capable of reading at least 300F. Start the unit and let
it run for at least 15 minutes to obtain normal operating conditions.
Watch the thermometer to see if it is approaching 270F. If the
thermocouple is located on the dome near the discharge thermostat, there could be a 20 difference between well and dome
temperatures. If the temperature approaches 270F, repair system
problem, such as low charge, blocked condenser coil, and so forth.
If the temperature does not approach 270F, replace discharge
thermostat.

Step 2Troubleshooting

Replacing Discharge Thermostat

Troubleshooting mechanical or electrical problems in a scroll


compressor is the same as for a reciprocating compressor, except
that a scroll compressor should never be allowed to pump into a

To replace the discharge thermostat, refer to the Installation


Instructions packaged with the replacement discharge-thermostat
kit. (See Fig. 30.)

COPELAND SCROLL COMPRESSOR


Step 1Features

28

PLASTIC CAP

Table 14Compressor Oil Recharge


RECHARGE
(FL. OZ.)
Carlyle/Scroll
J Type
44
SC, SRD450AC
34
SR
52
SRH482, SRY482
68
SRH602, SRY602
70
Copeland
CRG3, CRH3, CRJ3, CRK3, CRL3
51
CRN5, CRP5, CRT5, CTH1, CTL1
66
CRC4, CRZ4
36
CR16K6 Through CR42K6
42
*ZR18K1
19
*ZR23K1, ZR28K1
24
*ZR34K1
30
*ZR40K1
34
*ZR49K1-PFV
56
*ZR49K2-TF5, ZR49K2-TFD
56
*ZR61K2-PFV
56
*ZR61K2-TF5, ZR61K2-TFD
66
Tecumseh
AV55
50
AW55
30
AG
60
Bristol
H23A
52
H23B
37
H24A3, H24A4
47
H24A5
52
H25A, H26A
62
H25B, H26B, H29B
32
COMPRESSOR MODEL

OIL TYPE
Suniso 3GS

BLUE SEALANT
Zerol 150
w/3 percent
Syn-O-Ad

PRONG

GROMMET
Suniso 3GS

THERMAL GREASE

THERMOSTAT

Suniso 3GS
A90198

Fig. 30Location of Discharge Thermostat


The Millennium flapper valve eliminates the refrigerant unloading
by not allowing the discharge head to run backwards because of its
location. The Millennium scroll compressor uses Zerol 150 oil
with 3 percent Syn-O-Ad and is the only oil recommended for oil
recharge. See Table 14 for recharge requirements.

Suniso 3GS

*Copeland scrolls are charged initially with Sontex 200LT white oil. Since this
oil is not commercially available, use 3GS.

Step 2Compressor Protection


Millennium scroll compressors are protected by an internal linebreak mounted on the motor windings. Internal protectors respond
to overcurrent and high temperature. These protectors are
automatic-reset devices containing a snap-action, bi-metal switch.

Step 4Discharge Solenoid Valve


Some larger units equipped with scroll compressors contain a
solenoid valve that is piped between the discharge tube and suction
tube of the compressor. The purpose of the solenoid valve is to
cause a rapid pressure equalization around the compressor, thus
reducing the normal shutdown sound created by reverse rotation of
the scroll. The solenoid valve is normally closed and is wired
across high-voltage line 1 to load terminals of the contactor. (See
Fig. 18.) The solenoid-valve assembly also requires a check valve
piped in the discharge tube between the solenoid-valve tee and the
condenser coil, or reversing valve on heat pumps. The purpose of
the check valve is to prevent refrigerant from bypassing through
the solenoid valve into the suction tube when the unit cycles off.

Step 3Troubleshooting
Troubleshooting mechanical and electrical problems in a scroll
compressor is similar to a reciprocating compressor, except that a
scroll compressor should never be allowed to pump into a vacuum.
The scroll compressor is capable of pumping into a vacuum very
quickly, which could cause fusite arcing and compressor failure.
See Step 4 of Reciprocating Compressor section for removal and
replacement.
Step 4Scroll-Compressor, 3Phase Monitor
CES0130075 PHASE MONITOR

MILLENNIUM SCROLL COMPRESSOR

This control is factory-installed on all 3phase, scroll-compressor


models. (See Fig. 31 and 32.) On start-up, the control will energize
the pilot relay for 2 seconds. The monitor will check for correct
compressor rotation. If rotation is correct, unit will continue to run.
If rotation is incorrect, the control will break the 24vac power at
the contactor and an LED light on the control will flash. If LED is
flashing, turn off power, reverse L1 and L3 field-power leads, and
restart unit. This control will check incoming power at every
restart.

Step 1Features
The scroll compressor pumps refrigerant through the system by the
interaction of a stationary and an orbiting scroll. (See Fig. 29.) The
scroll compressor has no dynamic suction or discharge valves, and
it is more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The Millennium scroll varies from the Copeland
scroll in that the Millennium has a shutdown flapper valve located
between the scroll plates and the discharge head, whereas the
Copeland has a check device at the discharge connection after the
discharge head. The Copeland discharge head unloads when the
compressor shuts down. The scroll plate actually runs backwards
while it unloads. A 1 to 3 second unloading of refrigerant occurs.

OLYMPIA SERIES HORIZONTAL UNITS


Step 1General
This family of units has horizontal airflow which allows for greater
installation flexibility. The blow-through design of the coil, along

29

A00010

Fig. 31CES0130075 3Phase Monitor Board


L2

L1
COMP
CONT
EQUIP
GND

T2

T1

L3
11

21

T3

*CH

CONT

CAP
23

OFM

L1

L2

L3

13

LOGIC
CESO130075
CONT

CONT
*HPS

*LPS

T2
LOGIC
T1
*LLS

T3
CTD

Y
IFR
G
R

R
INDOOR
THERMOSTAT

EXTERNAL POWER SUPPLY 24 V


A00011

Fig. 32CESO130075 3Phase Monitor Wiring Diagram


30

with an isolated compressor compartment, greatly reduces the


overall sound level of the unit. The unit utilizes front and back
seating valves. The heat-pump heating piston is a Chatleff-type.
(See Fig. 33.)

continuous through coil sections. Dirt and debris may pass through
first section, become trapped between the rows of fins, and restrict
condenser airflow. Use a flashlight to determine if dirt or debris
has collected between coil sections. Clean coil as follows:
1. Turn off power to unit.

Step 2Remove Fan Motor

2. Flush coil from the outside to remove dirt using water from a
hose or other suitable equipment. Be sure to flush all dirt and
debris from drain holes in base of unit.

1. Turn off power to unit.


2. Remove air-inlet grille.
3. Measure distance from outside top edge of fan blade to outside
edge of fan deck. (See Fig. 34.)

TWO-SPEED SYSTEM

4. Remove fan blade.

Step 1Cautions and Warnings

5. Loosen cinch bolt holding bellyband around motor.


6. Unplug motor leads.
7. Spread bellyband and remove motor.

For proper unit operation and reliability, the 2-speed units


must be installed with the factory-supplied balance port, hard
shutoff TXV. Do not install with indoor coils having piston or
capillary-tube metering devices.

8. Reverse order to reinstall.


NOTE: When installing fan blade on motor, use dimension
measured in item 3.

Do not install equivalent interconnecting tubing lengths


greater than 100 ft. Do not decrease or increase interconnecting tubing diameters.
SERVICE
VALVE

To avoid electrical shock, bleed resistor must be connected


across run capacitor. Replace if missing or damaged.

TEFLON SEAL

Contactor is mechanically interlocked. Do not disable mechanical interlock. Compressor damage may occur.
PISTON
WITH
ORIFICE

SCREEN
CAP

Contactor control voltage is 240vac.


A92069

Fig. 33Heat-Pump Service Valve/Piston


Do not attempt to operate this equipment below 55F outdoor
ambient temperature.

FAN BLADE

NOTE: Sections that follow describe the 38TDA and 38YDA


products, which started production March, 1994. For 38TD and
38YD products, refer to the Split-System Service Manual dated
3-94, Catalog No. 563799.
Step 2System Functions
OUTSIDE EDGE OF
FAN DECK

OUTSIDE EDGE
OF GRILLE

COOLING OPERATION
The 2-speed products utilize a 2-stage-cooling indoor thermostat.
With a call for first-stage cooling (Y1), the outdoor fan and
low-speed compressor are energized. If low speed cannot satisfy
the cooling demand, high speed will be energized (Y1 and Y2) by
the second stage of the indoor thermostat. The thermostat has a 2
differential between first and second stages. After second stage is
satisfied, the unit returns to low-speed operation until first stage is
satisfied or until second stage is again required.

DIMENSION FROM
OUTSIDE TOP EDGE OF
BLADE TO OUTSIDE EDGE
OF FAN DECK.

A92070

Fig. 34Fan Position

HEATING OPERATION (HEAT PUMP ONLY)

Step 3Cleaning Coil

The 2-speed products utilize a 2-stage-heating indoor thermostat.


The first stage of heating is heat-pump operation (Y1). Auxiliary
backup heat is controlled by second stage (W2). There is a 2
differential between first and second stage. The control board
determines the compressor speed based on ambient temperature.
See Table 15 for ambient temperatures at which speed changes

Coil should be washed clean with water or blown clean with


compressed air. The blow-through design causes dirt and debris to
build up on the inside of coil.
Clean coil annually or as required by location or outdoor air
conditions. Inspect coil monthly and clean as required. Fins are not

31

occur. When high-speed, heat-pump heating is required, the


control provides a Y2 (24vac) signal back to the thermostat to
energize high-speed-indicator LED.

LM1 LM2

S2

S1

PW2 PW1

P1

18

K7

AMBIENT TEMPERATURE (F)


High Speed
Low Speed
30 or less
31 or greater
33 or less
34 or greater
40 or less
41 or greater

FURN INT
OFF

ON

50
20

15

40

10

30

35
45

85

25

90

ZONE

95

105 OFF

LED FUNCTION LIGHTS

90

30

SPEED-UP

100

036
048
060

T2

Table 15Ambient Temperature for High- and


Low-Speed Operation
UNIT
SIZE

DFT1 DFT2 T1

STAGE 2 DEFROST BALANCE


LATCH
TIME
POINT

When using the factory-authorized indoor thermostats with the


2-speed outdoor units, there are 2 locations where system-function
LED-indicator lights are available. The indoor thermostat provides
indicator lights for high- and low-speed operation, system malfunction, and auxiliary heat for heat pumps. The 2-speed control
board has an LED which provides signals for several system
operations. See Table 16 for LED functions, indicator locations,
and definitions. Table 16 also provides the order of signal
importance if more than 1 signal should occur. The signal to the
indoor thermostat is supplied by the low-voltage L lead.

A93568

Fig. 36Speedup Terminals


OUTDOOR FAN-MOTOR OPERATION

THREE-SECOND TIME DELAY

The 2-speed control energizes the outdoor fan any time the
compressor is operating. The outdoor fan remains energized during
the 1-minute, speed-change time delay and if a pressure switch or
compressor PTC overload should trip.

Any time the control receives a 24v input, such as Y1 or Y2, there
is a 3-sec time delay before the control function is initiated. This
helps prevent nuisance trips and thermostat jiggling.

If the outdoor fan motor wont run, check the header-pin housing.
(See Fig. 39.) There SHOULD BE a jumper wire between
terminals 15 and 16.

ONE-MINUTE SPEED-CHANGE TIME DELAY

Heat Pumps

When the compressor changes speeds from high to low or low to


high, there is a 1-minute time delay before the compressor restarts.
The outdoor fan motor remains running.

After the termination of a defrost cycle, the outdoor fan delays


come on for 20 sec. This allows the refrigeration system to recover
the outdoor coil heat and minimize the steam cloud effect.

FIVE-MINUTE TIME DELAY

SECOND-STAGE LATCHING

The 2-speed control logic contains a 5-minute time delay that


prevents the unit from short cycling after a thermostat-off cycle or
power interruption. The unit can be forced to operate immediately
by momentarily touching a jumper between the speed-up terminals
of the control board. (See Fig. 35 and 36.) The speed-up feature
will not bypass any other function or time delay.

When low-speed cooling operation no longer satisfies the first


stage of the indoor thermostat, the indoor temperature will increase
by 2 until second stage is energized. After high-speed cooling
satisfies second stage, it returns to low-speed cooling operation. If
desired, the installer may select to have high-speed cooling by
energizing Y1. High speed will stay energized until Y1 is satisfied.
This eliminates the temperature drop between the first and second
stages of indoor thermostat, holding room temperature closer to set
point.

HIGH VOLTAGE

L2

LO

HI

CCH

LOW VOLTAGE

ODF

LM1 LM2
O

DFT1 DFT2 T1

1
K1

K2

K3

K4

K5

T2

S2

S1

To utilize this function, the unit capacity should be plotted versus


the heat gain of the structure which provides the systems balance
point when the structure requires high-speed capacity. (See Fig.
37.)

PW2 PW1

K6

P1

18

K7
FURN INT
OFF

ON

Second-stage latching can be selected by rotating the potentiometer (POT) to the desired outdoor second-stage latching temperature (See Fig. 36.) The temperatures that can be selected are 85,
90, 95, 100, and 105F. The POT is factory-set at 105F.

SPEED-UP

STAGE 2 DEFROST BALANCE


LATCH
TIME
POINT

LED 1

ZONE SELECTION
If the stage2 latch POT is set to ZONE position, the compressor
operating speed in either heat or cool mode is determined by the
Y1 and/or Y2 inputs. The system operates in low speed with a Y1
input and high speed with Y2 or Y1-and-Y2 input. This allows the
multistage-zoning system to determine what speed is needed
regardless of outdoor temperature or switchover point.

A93569

Fig. 35Two-Speed Control Board


TWO-MINUTE LOW-SPEED MINIMUM
If the unit has not operated within the past 30 minutes, the unit
operates for a minimum of 2 minutes in low speed upon the next
thermostat high or low demand.

DEFROST TIME SELECTION


The defrost interval can be field selected, depending on local or
geographic requirements. It is factory set at 90 minutes and can be
changed to either 30 or 50 minutes by rotating the defrost-time
POT. (See Fig. 36.)

CRANKCASE-HEATER OPERATION
The 2-speed control energizes the crankcase heater during the
units off cycle when the outdoor ambient is below 75F.

32

Table 16Function Light Code and Display Location


CODE
Constant flash
No pause
1 flash
w/pause
2 flashes
w/pause
3 flashes
w/pause
4 flashes
w/pause

TSTAT

UNIT

DEFINITION
No demand
Stand by

POSSIBLE CAUSE

Low-speed operation

High-speed operation

Ambient thermistor failure

Coil thermistor failure

3 flashes
pause
4 flashes

Thermistor out of range**

5 flashes
w/pause

Pressure switch trip


(LM1/LM2)

6 flashes
w/pause

Compressor PTCs out of limit

Constant light
No pause
No flash

Board failure

Thermistor drift, wrong location


Incorrect wiring
Incorrect refrigerant charge
Dirty indoor/outdoor coil
Dirty outdoor coil
Refrigerant overcharge
Wrong indoor coil
Low refrigerant charge
Compressor mechanical problem
Dirty indoor/outdoor coil
Equipment or electrical service
not grounded

*Function light signals order of importance; in case of multiple-signal request, 1 is most important.
Signal at thermostat will occur after 3 consecutive attempted restarts and lockout has occurred.
Will be energized if pressure switch remains open for 1 hr.
**Check both thermistors to determine which is faulty.

delay in the outdoor fan being energized. If the stage2 latch POT
is set to ZONE and the heat pump is in low speed, it defrosts in low
speed.
FIELD-INITIATED FORCED DEFROST
By placing a jumper across the speedup terminals for a minimum
of 5 sec and then removing it, the unit initiates a defrost cycle. (See
Fig. 36.) The cycle occurs only if the outdoor ambient is less than
50F, regardless of outdoor coil temperature. The cycle terminates
when the coil thermistor reaches 80F ( 5) or the defrost period
reaches a maximum of 10 minutes.
FURNACE INTERFACE
This feature provides a heat-pump lockout upon a demand for
auxiliary heat (W2) and must be used when interfacing a heat
pump with a gas/oil furnace. Field selection of the furnaceinterface option is done by connecting the factory-supplied jumper
to the ON position of the 3 terminal connectors. (See Fig. 35.)
When the option is selected, the heat pump will be locked out of
operation any time there is a thermostat demand for W2 or the
outdoor ambient is below the balance-point POT-setting selection.
(See Fig. 36.) When the unit requires defrost, auxiliary heat (W2)
energizes the furnace. After defrost is terminated, the heat pump
shuts down and the furnace satisfies the thermostat. To utilize this
function, the economic and/or thermal balance point must be
determined. See the appropriate heat pump balance-point worksheet available from your distributor or branch.
BALANCE POINT
This feature can be used in 2 different options: furnace interface or
electric-heat staging. Refer to the Furnace Interface section for its
application. If the heat pump is installed with a fan coil with
multistages of electric heat, this option can be used to stage the
banks of heat by outdoor ambient. This eliminates the need for
accessory outdoor thermostats.
When using this option to stage electric heat, first stage is
energized by a W2 demand, and second stage is energized by a W3
demand. Select the W3 desired temperature by rotating the

70

60

HIGH

SPEE

50
BTU (1000'S)

HIGH SPEED
BALANCE POINT

D CA

PACIT

40
LOW S

PEED

30

CAPA

STRUCTURE
BALANCE POINT

CITY

20
LOW SPEED
BALANCE POINT
10

50

60

70

80

90

100

110

120

TEMPERATURE (F)
A91282

Fig. 37Typical Cooling Balance Points


DEFROST
The 2-speed control logic for the defrost function is the standard
time and temperature initiated, time or temperature terminated.
Defrost occurs only at outdoor temperatures less than 50F. The
control initiates defrost when the outdoor coil thermistor is 30F (
2) or less, and the selected defrost time (interval) has been
accumulated during unit operation. Termination occurs when the
coil thermistor reaches 80F ( 5) or the defrost period reaches a
maximum of 10 minutes.
Defrost always occurs in high speed unless the stage2 latch POT
is set at ZONE. During defrost the unit operates in high speed,
energizes the reversing valve (O) and auxiliary heat (W2), and
de-energizes the outdoor fan. Upon termination, there is a 20-sec

33

The outdoor unit is equipped with high- and low-pressure


switches, wired in series. If a pressure switch opens, the control
provides a 5-minute time delay in outdoor unit operation with the
outdoor fan running. A malfunction signal appears on the control
when a pressure switch opens. If the switch remains open for 1 hr
or longer, a malfunction signal is provided at the L terminal of the
indoor thermostat.

balance-point POT. (See Fig. 36.) Temperatures that may be


selected are 10, 15, 20, 25, 30, 35, 40, and 45F. The POT
is factory-set at 45F.
LOW-SPEED HEATING WITH AUXILIARY HEAT
If the system is operating in low-speed heating and there is a
demand for auxiliary heat (W2), the system changes to high-speed
operation. W2 is energized unless the low-voltage control wiring is
configured as described in Fig. 38.
TWO SPEED
THERMOSTAT

FAN
COIL

TWO SPEED
HEAT PUMP

W2

W2

W2

Step 3Factory Defaults


Factory defaults have been provided in the event of failure of the
ambient thermistor, outdoor-coil thermistor, and/or furnace interface jumper. Refer to Table 18 for default and function.
Step 4Major Components

CONTROL
LOGIC

W3

TWO-SPEED CONTROL
The 2-speed control board controls the following functions:

W3

High- and low-compressor contactor operation


Outdoor fan-motor operation
Crankcase-heater operation
Compressor protection
Pressure-switch monitoring
Second-stage latching
Time delays
5-minute time-delay speedup (bypass)
Heat pumps:

A93572

Fig. 38Low-Voltage Control Wiring


AUXILIARY HEAT (W2) LOCKOUT
In some areas, it is necessary to disable the auxiliary heat, except
for defrost, until the outdoor ambient is less than the structures
balance point. This is accomplished by using the low-voltage
wiring as shown in Fig. 38. Wire the 24vac W2 signal from the
indoor thermostat to W3 of the control, and W2 of the control to
W2 of the indoor unit. When the outdoor ambient is less than the
setting of the balance-point POT, the 24vac signal energizes the
auxiliary heat (W2) of the indoor unit.

Time/temperature defrost
Defrost-interval selection
Furnace interface
Electric-heat staging
HEADER-PIN HOUSING

EMERGENCY HEAT

The header-pin housing is the plastic assembly which holds the


stripped-lead ends for field connections. The 2-speed control
receives the 24vac low-voltage control-system inputs through the
housing/pins. The housing also contains jumpers which the control
uses for system configuration, such as heat pump versus air
conditioner. See Fig. 39 for header-pin housing configurations.

If the 2-speed control receives a call for auxiliary heat (W2)


without a heat-pump heating (Y1) call, the second auxiliary stage
(W3) is energized. This ensures all available heat is energized if
the indoor thermostat is switched to emergency heat.
COMPRESSOR PTC-OVERLOAD PROTECTION
The control senses the resistance of the compressor internal
positive-temperature coefficient (PTC) overloads. If the resistance
of the PTCs is out of range, the control shuts off the unit until the
resistance range is acceptable. See Table 17 for compressor PTC
ranges.

TWO-SPEED COMPRESSOR

C - TRANSFORMER COMMON

R - TRANSFORMER LINE

Table 17Compressor PTC Ranges

COMPRESSOR INTERNAL-PTC RESISTANCE


Safe Range (77F)
1.5k to 7.8k ohms
To trip
26k to 34k ohms
To reset
8.4k to 10k ohms

When the control turns off the outdoor unit due to out-of-range
PTCs, the unit remains off for 15 minutes with the outdoor fan
running. After 15 minutes, the control checks the resistance every
5 minutes until it reaches the reset range. During this time, a
malfunction signal appears on the control board. If this happens,
remove the wires on control board at S1 and S2 and measure the
resistance across the leads. When the resistance reaches 8,400 to
10,000 ohms, system operation may be resumed. If the resistance
remains outside this range, a quick check of the leads at the
compressor should be made. Loose connections can cause inaccurate readings. If a PTC trip occurs 3 times, the control will lock out
the outdoor-unit operation and provide malfunction signals at both
the control and indoor thermostat.

W2 - FIRST STAGE AUXILIARY HEAT

O - REVERSING VALVE

Y2 - SECOND STAGE COOLING/HEAT PUMP

Y1 - FIRST STAGE COOLING/HEAT PUMP

W3 - SECOND STAGE AUXILIARY HEAT

10

L - MALFUNCTION LIGHT

11
12

4 - TON

13
14

5 - TON

IF NO JUMPER IS
INSTALLED, DEFAULT
IS 3 - TON

15
16
17
18

JUMPER FOR
HEAT PUMP ONLY
A93576

Fig. 39Header-Pin Housing

PRESSURE SWITCH PROTECTION

34

Table 18Factory Defaults


FAILED COMPONENT

FUNCTION
Crankcase Heater
Second-Stage Latching
Furnace Interface

Ambient Thermistor

Heating Switchover Speed Point


Defrost Initiation
Outdoor Thermostat for
Auxiliary Heat

Outdoor Coil Thermistor

Defrost Initiation and Termination

Furnace Interface Jumper

Furnace Interface

The 2-speed compressor contains motor windings that provide


low-speed, 4pole (1750 rpm) and high-speed, 2pole (3500 rpm)
operation. Refer to Fig. 40 to determine which windings are
energized at each speed. Refer to Compressor Winding-Check
section under Troubleshooting and Table 19 for appropriate
winding resistances.

Table 19Two-Speed Compressor (Winding Resistance at 70F 2)


WINDING
T1-T2
T1-T3
T1-T7
T1-T8

The 2-speed compressor is also protected by an internal-pressure


relief (IPR), which relieves discharge gas into the compressor shell
(low side) when the differential between suction and discharge
pressures exceeds 500 psi. The compressor is also protected by 3
PTC devices attached to the motor windings. The PTCs resistance
is sensed by the 2-speed control board. See Table 17 for resistance
ranges.

T7

3 TON
0.80
3.20
1.30
3.10

4 TON
0.70
2.20
1.00
2.20

5 TON
0.60
1.80
1.00
2.00

The 2-speed products are equipped with mechanically interlocked


contactors. Each contactor has interconnecting linkage, providing
independent interlocks.
The 2-speed control provides the electrical interlock. The contactors are supplied with 240-v coils, which reduce the va requirements of the low-voltage (24vac) control system.

MECHANICALLY INTERLOCKED CONTACTORS

T3 T8

DEFAULT
Energized during any off cycle
Does not function
Balance point does not function, but
interface still energizes furnace and
locks out heat pump with a call for W2
Unit only runs in highcompressor speed
Defrost is initiated based on coil
temperature only
Anytime there is a call for W2,
W3 is also energized.
Defrost occurs at each time interval,
but terminates after 5 minutes
Does not function

T2

TEMPERATURE THERMISTORS

T1

Thermistors are electronic devices which sense temperature. As


the temperature increases, the resistance decreases. Two thermistors are used to sense temperature: one senses outdoor ambient,
and the other senses coil temperature (heat pump only). Refer to
Fig. 41 for resistance values versus temperature.

EXTERNAL MAIN

If the outdoor ambient thermistor should fail, a malfunction signal


appears on the indoor thermostat and 2-speed control. The control
does not initiate second-stage latching, crankcase heater is turned
on during all off-cycles, heating defaults to high speed, and defrost
initiates on demand from coil thermistor. (See Table 18.)
If the outdoor coil thermistor should fail, a malfunction signal
appears on the indoor thermostat and 2-speed control. The control
defrosts every 90 minutes of heating operation and terminates in 5
minutes. (See Table 15.)

MAIN WINDING

ICM OUTDOOR FAN MOTOR


4 POLE START

The outdoor integral-control motor (ICM) is a variable-speed


motor which operates from 400 to 900 rpm. The motor is a DC
permanent magnet-type motor with the electronic controls integrated into its rear cover. The control package includes a small
diode bridge, capacitors, and power-switching devices. It converts
AC to DC power and switches the DC power to the motor
windings on and off at various rates to control the motor speed.
The commutative speed of the motor windings is determined by a
pulse-width modulated (PWM) signal which is received from the
control board on the motor-control lines.

2 POLE START
HIGH SPEED
(L1) T1 + T7
(L2) T2 + T3

LOW SPEED
(L1) T1
(L2) T7 + T8

A92015

The PWM signal is created by turning a DC signal on and off once


within a given period of time. The signal-on time relative to the
signal-total period defines the percent of the PWM. For example,
if the period is 5 sec and the control power is turned on for 1 sec

Fig. 40Energizing Windings

35

4. Use an ohmmeter on 0-1000 ohm scale to check resistance.


(See Fig. 40, 42, and 43 and Table 19.)

THERMISTOR CURVE

Because winding resistances are usually less than 10 ohm, each


reading will appear to be approximately zero ohm. If during any
check the resistance remains at 1000 ohm, an open or break exists,
and the motor or compressor should be replaced.

90

RESISTANCE (KOHMS)

80
70

Ground

60

To determine if any wire has broken and come in direct contact


with the housing or shell, causing a direct short to ground:

50
40

1. Be sure all power is off.

30

2. Discharge all capacitors.

20

3. Remove wires from T1, T2, T3, T7, and T8.

10
120

4. Allow crankcase heater to remain on for several hrs before


checking motor to ensure that windings are not saturated with
refrigerant.

A91431

5. Using an ohmmeter on R X 10,000 ohm scale, place 1 meter


probe on ground motor or compressor frame. Make a good
metal-to-metal contact. Place other probe on terminals T1, T2,
T3, T7, and T8 in sequence. Note meter scale.

0
0

20

40
60
80
TEMPERATURE (DEG. F)

100

Fig. 41Resistance Values Versus Temperature

If any reading of zero or low resistance is obtained, the motor is


grounding. Replace the compressor.

then off, the signal will remain off for 4 sec before turning on again
to start the next cycle. The PWM is called a 20percent duty-cycle
signal. If the on time is increased to 4 sec of the 5 sec period, the
PWM is called an 80percent duty-cycle signal. The ICM reads the
PWM signal and increases the motor speed linearly from minimum
speed to maximum speed with the percent duty-cycle value of the
supplied PWM signal.

Short
This is an extremely critical test and is not advised unless the
following conditions are met.
The correct motor-winding resistances must be known before
testing. See Table 19 for cold-motor winding resistance.

EMI FILTER

The temperature of the windings must be specified, 70F 2F.

An electromagnetic-interference (EMI) filter is installed on the


high-voltage input to the ICM to prevent electromagnetic signals
generated by the ICM from interfering with other home appliances,
such as radios or televisions.

The resistance-measuring instrument must have an accurate ohmmeter (such as a Wheatstone bridge or null balance-type instrument).

Step 5LED Function/Malfunction Lights

The motor must be dry or free from direct contact with liquid
refrigerant.

The 2-speed control is


function/malfunction light.

equipped

with

an

LED

To determine if any wires have broken through their insulation and


come in direct contact with each other, thereby shorting all or
part of the winding(s):

NOTE: Only malfunction signal appears at thermostat. Both


function and malfunction signals appear at control board. (See Fig.
35 for LED location.) Table 16 provides the function/malfunction
code, location, and definition.

1. Be sure all power is off.


2. Discharge all capacitors.
3. Remove wires from terminals T1, T2, T3, T7, and T8.

Step 6Troubleshooting

4. Subtract instrument probe and lead resistance from each


reading. If any reading is within 20 percent of the known
resistance from Table 19, the motor probably does not have a
short. Usually a considerable difference will be noted if a
turn-to-turn short is present.

NOTE: Troubleshooting charts for air conditioning and heat


pump units are provided in the back of this manual see Fig. 54,
55, and 56.
COMPRESSOR WINDING CHECK

CONTROL-BOARD FAILURE

The 2-speed compressor is nothing more than 2 single-phase


motors within 1 compressor shell. When the compressor fails to
start or run, there are 3 tests that can be made: open, ground, or
short. This compressor has no internal line-break overload; however, it does have PTC motor protectors. See Compressor PTCOverload Protection section for PTC overload information.

The control board continuously monitors its own operation and the
operation of the system. The diagnostic feature allows easy
troubleshooting of the control and system in the field. If a failure
occurs, the LED light on the control will flash a failure code. If the
failure is internal to the control board, the light will stay on
continuously (no flash). Before replacing control board, reset the
24v power. If the fault clears, check to ensure the indoor and
outdoor unit and electrical service are properly grounded. If the
entire system is grounded, the control board should be replaced, as
the control is not field reparable. If the control-board light is
flashing, see LED and Table 16 for function/malfunction definition. Cycling 24 vac to control board resets previous error
messages and any lockouts which have occurred. See Table 20 for
more information regarding control-board operation.

NOTE: To ensure accurate ohm measurements, place ohmmeter


probes on flat surface of compressor-terminal tabs, not the brass
mounting screw.
Open
To determine if a winding has an actual break in the internal wires
and current is unable to pass through:
1. Be sure all power is off.
2. Discharge all capacitors.
3. Remove wires from terminals T1, T2, T3, T7, and T8.

36

SCHEMATIC DIAGRAM
(LADDER FORM)

L1
C1

11

L2
C2

21

24

C2

17

T7
27

COMP
MAIN

T2
EXT
MAIN

SC

14

T1

LOW
START

HIGH
START

T8

T3

C2

EQUIP
GND

15

BR

25

HS
SR

C2

1
16

CAP
F

26
C1

12

22
C1

5
LS
SR

1
13

23
A91446

Fig. 42Low-Speed Windings


SCHEMATIC DIAGRAM
(LADDER FORM)

L1

L2
C2

C1

11

21

24

C2

17

T7
27

T2

COMP
MAIN

LOW
START

EXT
MAIN

SC

14

T1
HIGH
START

T8

T3

C2

EQUIP
GND

H
BR

15

25

2
HS
SR

C2

1
CAP

16

26
C1

12

22

C1

5
LS
SR

1
13

23
A91445

Fig. 43High-Speed Windings


37

Table 2024v Pin Connection Troubleshooting


MODE OF OPERATION
18-PIN CONNECTOR
All
Low-speed Cooling
High-speed Cooling
Low-speed Heating

TERMINAL
DESIGNATION
R-C
Y1,0-C
Y1, Y2, 0-C
Y1-C
Y1-C

LOCATION ON
CONTROL BOARD
2-1
8,6-1
8,7,6-1
8-1
8-1

VOLTAGE
PATH
Input
Input
Input
Input
Input

VOLTAGE
REQUIRED
24
24
24
24
24

Y2-C

7-1

Output

24

Y1-C

8-1

Input

24

Y2, W2, 0-C

7,5,6-1

Output

24

Second Stage of
Auxiliary Heat

Y1, W2-C
W3, Y2-C

7,5-1
9,8-1

Input
Output

24
24

Cooling Secondstage Latching

Y1, Y2, 0-C

8,7,6-1

Input

24

High-speed Heating

Defrost

POSSIBLE SOURCE
OF PROBLEM
Check transformer (secondary)
Check thermostat
Check thermostat
Check thermostat
Check thermostat
Outdoor temperature below
speed; change temperature
Check thermostat
Outdoor temperature below 50F;
Coil temperature less than 30F
Check thermostat
Check balance-point setting
Ambient thermistor failure;
Check second-stage POT

In a straight cooling system, compressed hot gas leaves compressor and enters condensing coil. As gas passes through condenser
coil, it rejects heat and condenses into liquid. The liquid leaves
condensing unit through liquid line and enters metering device at
indoor coil. As it passes through metering device, it becomes a
gas-liquid mixture. As it passes through indoor coil, it absorbs heat
and refrigerant and is again compressed to a hot gas. The cycle
then repeats.

CONTROL-BOARD POWER INPUTS AND OUTPUTS


See Fig. 35 and 39 for inputs and outputs.
BLEED RESISTOR
The bleed resistor is a 150k, 2watt resistor across the compressorrun capacitor to protect service technician from injury by electrical
shock. Capacitor will bleed-off approximately 1 minute after
power to outdoor unit is turned off. If run capacitor is changed out,
be sure to place bleed resistor on new capacitor. If bleed resistor is
damaged, replace resistor.

In a heat pump, the basic cycle is the same. (See Fig. 44.)
Reversing valve in system decides which coil, indoor or outdoor,
becomes evaporator or condenser. It rejects heat into the home
after heat is absorbed by outdoor evaporator coil, thus the home is
heated.

START CAPACITOR AND RELAY


The 2-speed system has a second start relay in the control box. One
start relay is for low-speed start, and the second is for high-speed
start. Both start relays use a common start capacitor. When
servicing this equipment, be certain system starts in both low- and
high-speed operation.

In cooling cycle, the indoor coil becomes the evaporator. It absorbs


heat from the home and rejects it through the outdoor condenser
coil, thus the home is cooled.

INTEGRAL-CONTROL MOTOR (ICM)

A unique feature of the heat pump is that metering devices are


designed to meter refrigerant in one direction of flow and allow
refrigerant to pass unhindered in the other direction. If indoormetering device is metering refrigerant, the outdoor device bypasses refrigerant and vice versa. This allows both coils to serve a
dual function.

If the outdoor fan motor fails to start and run, first check the
high-voltage supply. The unit need not be running to check high
voltage, but the power must be on. With a voltmeter, check for
230vac on the brn and blk motor leads at the EMI filter, if
installed. If the 230vac is not present, check the supply and the
EMI filter for faulty connections, faulty wiring, or faulty EMI
filter. Repair or replace as necessary.

Step 2Leak Detection

If the 230vac is present, use a voltmeter on a DC voltage scale to


check the control-line voltage to the fan motor. At full fan-motor
speed, the voltmeter should indicate 20-40vdc with the motor
disconnected and 16-20vdc with the motor connected. The fan
motor runs at full speed whenever the outdoor temperature is
greater than 90F or when the compressor is at high speed
(cooling), and less than 22F (heating). The voltage reading will be
lower at temperatures in between.

Always wear safety glasses and gloves when handling refrigerants.


New installations should be checked for leaks prior to complete
charging.
If a system has lost all or most of its charge, system must be
pressurized again, up to approximately 150 lb minimum. This can
be done by adding refrigerant using normal charging procedures,
or it may be pressurized with nitrogen (less expensive than
refrigerant). Nitrogen also leaks faster than R-22 and is not
absorbed by refrigeration oil. Nitrogen cannot, however, be
detected by a leak detector. (See Fig. 45.)

First check voltage with the motor disconnected. If no control


voltage is present, check control-board connections. If connections
are good, replace the control board.
If voltage is present, reconnect the motor and check again. Shut
down the unit to reconnect the motor and restart the unit to
complete this troubleshooting procedure. If control voltage is no
longer present or motor fails to respond, check motor connections.
If connections are good, replace the motor.

Due to the high pressure of nitrogen, it should never be used


without a pressure regulator on the tank.

REFRIGERATION SYSTEM
Step 1Refrigeration Cycle

Leaks in a system pressurized with refrigerant can be spotted with


a leak detector which detects extremely small refrigerant leaks.

In a refrigeration system, refrigerant moves heat from one place to


another. It is useful to understand flow of refrigerant in a system.

38

This section of brazing is not intended to teach a technician how to


braze. There are books and classes which teach and refine brazing
techniques. The basic points above are listed only as a reminder.

COOLING CYCLE
REVERSING VALVE
(ENERGIZED)
OUTDOOR FAN

INDOOR
FAN

INDOOR COIL
ACCUMULATOR

SUCTION SERVICE
PORT AT SERVICE
VALVE (CLG CYCLE)

COMP
STRAINER

OUTDOOR
COIL

STRAINER
(METERING)

HEAT PUMP
ACCESSORY
FILTER DRIER
(DUAL FLOW)

SUCTION
SERVICE
PORT
(BYPASSING)

LIQUID LINE
PRESSURE SWITCH

LIQUID LINE SERVICE PORT


AT SERVICE VALVE (CLG CYCLE)

A88400

Fig. 44Heat Pump Refrigerant-Flow Diagrams


This discussion assumes that system is pressurized with either all
refrigerant or a mixture of nitrogen and refrigerant.
If system has been operating for some time, make first check for
a leak visually. Since refrigerant carries a small quantity of oil,
traces of oil at any joint or connection is an indication that
refrigerant is leaking at that point.
A simple and inexpensive method of testing for leaks is to use soap
bubbles. Any solution of water and soap may be used. Soap
solution is applied to all joints and connections in system. A small
pinhole leak is located by tracing bubbles in soap solution around
leak.
Use electronic leak detector to check for leaks. This unquestionably is the most efficient and easiest method for checking leaks.
There are various types of electronic leak detectors. Generally
speaking, they are all portable, and most are lightweight, consisting of a box with several switches and a probe or sniffer. Detector
is turned on and probe is passed around all fittings and connections
in system. Leak is detected by either a movement of a pointer on
detector dial, by a buzzing sound, or a light.

A88401

Fig. 45Leak Detector


Step 4Service Valves

In all instances, when a leak is found, system charge must be bled


down and leak repaired before final charging and operation. After
leak testing or leak is repaired, evacuate system, and recharge with
correct refrigerant charge.

Never attempt to make repairs to existing service valves. Unit


operates under high pressure. Damaged seats and o-rings
should not be replaced. Replacement of entire service valve is
required. Tampering with damaged valves can cause personal
injury or death. Service valve must be replaced by properly
trained service technician.

Step 3Brazing
When brazing is required in the refrigeration system, certain basics
should be remembered. The following are a few of the basic rules.
1. Clean joints make the best joints. To clean:
a. Remove all oxidation from surfaces to a shiny finish before
brazing.

Service valves provide a means for holding original factory charge


in outdoor unit prior to hookup to indoor coil. They also contain
gage ports for measuring system pressures and provide shutoff
convenience for certain types of repairs. (See Fig. 46.)

b. Remove all flux residue with brush and water while


material is still hot.
2. Use sil-fos or phos-copper for copper-to-copper only. No
flux is required.

Two types of service valves are used in outdoor residential


equipment. The first type is a front-seating valve, which has a
service port that contains a Schrader fitting. The service port is
always pressurized after the valve is moved off the front-seat
position.

3. Silver solder is used on copper-to-brass, copper-to-steel, or


copper-to-copper. Flux is required when using silver solder.
4. Fluxes should be used carefully. Avoid excessive application
and do not allow fluxes to enter into the system.

The second type is a combination front-seating/back-seating valve,


which has a metal-to-metal seat in both the open and closed
positions. When it is fully back-seated, the service port is not

5. Proper brazing temperature of copper is when it is heated to a


dull red color.

39

STEM

SERVICE PORT
W/SCHRADER
CORE

FIELD
SIDE
STEM

SERVICE PORT
W/SCHRADER CORE
FIELD
SIDE
SEAT

SEAT

BAR STOCK FRONT SEATING VALVE

FORGED FRONT SEATING VALVE

A91447

A91448

Fig. 46Service Valves


The service valve cannot be field repaired; therefore, only a
complete valve or valve stem and service-port caps are available
for replacement.

pressurized. To pressurize the service port, this valve must be


moved off the back-seating position. This valve does not contain a
Schrader fitting. Both types of service valves are designed for
sweat connection to the field tubing.

If the service valve is to be replaced, a metal barrier must be


inserted between the valve and the unit to prevent damaging the
unit exterior from the heat of the brazing operations.

The service valves in the outdoor unit come from the factory
front-seated. This means that the refrigerant charge is isolated from
the line-set connection ports. Some heat pumps are shipped with
sweat-adapter tube. This tube must be installed on the liquidservice valve. After connecting the sweat adapter to the liquidservice valve of a heat pump, the valves are ready for brazing. The
interconnecting tubing (line set) can be brazed to the service valves
using either silver-bearing or non-silver-bearing brazing material.
Consult local codes.

Wear safety glasses and gloves when handling refrigerants.


Pumpdown Procedure
Service valves provide a convenient shutoff valve useful for
certain refrigeration-system repairs. System may be pumped down
to make repairs on low side without losing complete refrigerant
charge.

Before brazing the line set to the valves, the belled ends of the
sweat connections on the service valves must be cleaned so that no
brass plating remains on either the inside or outside of the bell
joint. To prevent damage to the valve and/or cap O ring, use a
wet cloth or other acceptable heat-sinking material on the valve
before brazing. To prevent damage to the unit, use a metal barrier
between brazing area and unit.

1. Attach pressure gage to suction service-valve gage port.


2. Front seat liquid-line valve.
3. Start unit in cooling mode. Run until suction pressure reaches
5 psig (35kPa). Do not allow compressor to pump to a
vacuum.

After the brazing operation and the refrigerant tubing and evaporator coil have been evacuated, the valve stem can be turned
counterclockwise until it opens or back-seats, which releases
refrigerant into tubing and evaporator coil. The system can now be
operated.

4. Shut unit off. Front seat suction valve.


NOTE: All outdoor unit coils will hold only factory-supplied
amount of refrigerant. Excess refrigerant, such as in long-line
applications, may cause unit to relieve pressure through internal
pressure-relief valve (indicated by sudden rise of suction pressure)
before suction pressure reaches 5 psig (35kPa). If this occurs, shut
off unit immediately, front seat suction valve, and recover remaining pressure.

Back-seating service valves must be back-seated (turned counterclockwise until seated) before the service-port caps can be removed and hoses of gage manifold connected. In this position,
refrigerant has access from and through outdoor and indoor unit.
The service valve-stem cap is tightened to 20 2 ft/lb torque and
the service-port caps to 9 2 ft/lb torque. The seating surface of
the valve stem has a knife-set edge against which the caps are
tightened to attain a metal-to-metal seal. If accessory pressure
switches are used, the service valve must be cracked. Then, the
knife-set stem cap becomes the primary seal.

Step 5AccuRater (Bypass-Type) Heat Pumps Only


AccuRater piston has a refrigerant-metering hole through it. The
retainer forms a stop for piston in refrigerant-bypass mode and a
sealing surface for liquid-line flare connection. (See Fig. 47). To
check, clean, or replace piston:

40

PISTON BODY

FEEDER
TUBES

PISTON
(ORIENT AS SHOWN)
BRASS
HEX NUT

STRAINER

PISTON
PISTON RETAINER

PISTON
RETAINER

TEFLON
SEAL

FLARE ADAPTER

BRASS
HEX
BODY

INTERNAL STRAINER
PRODUCTION
EXCEPT 1992

A91138

Fig. 47AccuRater Components

A94004

With unit operating, other items can be checked, such as frost or


condensate water on refrigerant lines.

WEATHERMAKER PRODUCTS EXCEPT 1992 PRODUCTION


1. Shut off power to unit.

The sound made by a reversing valve as it begins or ends defrost


is a whooshing sound, as the valve reverses and pressures in
system equalize. An experienced service technician detects this
sound and uses it as a valuable troubleshooting tool.

2. Pump unit down using pumpdown procedure described in this


service manual.
3. Loosen nut and remove liquid-line flare connection from
AccuRater.

Using a remote measuring device, check inlet and outlet line


temperatures. DO NOT touch lines. If reversing valve is operating
normally, inlet and outlet temperatures on appropriate lines should
be close. Any difference would be due to heat loss or gain across
valve body. Temperatures are best checked with a remote-reading,
electronic-type thermometer with multiple probes. Route thermocouple leads to inside of coil area through service-valve mountingplate area underneath coil. Fig. 49 and 50 show test points (TP) on
reversing valve for recording temperatures. Insulate points for
more accurate reading.

4. Pull retainer out of body, being careful not to scratch flaresealing surface. If retainer does not pull out easily, carefully
use locking pliers to remove it.
5. Slide piston out by inserting a small, soft wire with small
kinks through metering hole. Do not damage metering hole,
sealing surface around piston cones, or fluted portion of
piston.
6. Clean piston refrigerant-metering hole.
7. Install a new retainer O-ring or retainer assembly before
reassembling bypass-type AccuRater.

If valve is defective:
1. Shut off all power to unit and remove all charge from system.

WEATHERMAKER AND CUBE PRODUCTS PRODUCED


IN 1992

2. Check valve design. If valve is of the 3-port design and new


replacement is of the 4-port design, replacement of the
solenoid coil and wire leads is necessary. Valve bodies are
interchangeable, but solenoid and wires are not. Three-port
reversing valve and solenoid coil with leads must be used
together. New solenoid coil cannot be used on a 3-port valve.
Four-port reversing valve uses solenoid with quick-connect
terminals for leads connection. Old solenoid coil cannot be
used on 4-port reversing valve. If for any reason a new wire
cord is not available, cut the leads on the old solenoid coil as
close to the coil as possible. Terminate the leads with 2 female
1/4-in. quick-connects. Connect terminals to new solenoid and
tape connection to insulate and provide moisture barrier.
Replace these wires as soon as wire cord is available. See
RCD (Replacement Component Catalog) for proper cord part
number.

1. Shut off power to unit.


2. Reclaim outdoor-unit refrigerant.
3. Loosen brass hex nut and remove line from brass hex body.
4. Slide piston out by inserting a small, soft wire with small
kinks through metering hole. Do not damage metering hole,
sealing surface around piston cones, or fluted portion of
piston.
5. Clean piston refrigerant-metering hole.
6. Always replace Teflon seal with new seal. Never try to reuse
old seals.
7. Reassemble brass nut and brass hex body. Be sure orientation
is as shown in Fig. 47.
Step 6Reversing Valve

3. Remove solenoid coil from valve body. Remove valve by


cutting it from system with tubing cutter. Repair person should
cut in such a way that stubs can be easily brazed back into
system. Do not use a hacksaw. This introduces chips into
system that cause failure. After defective valve is removed,
wrap it in wet rag and carefully unbraze stubs. Save stubs for
future use. Because defective valve is not overheated, it can be
analyzed for cause of failure when it is returned.

In heat pumps, changeover between heating and cooling modes is


accomplished with a valve that reverses flow of refrigerant in
system. (See Fig. 48) This reversing-valve device is easy to
troubleshoot and replace. The reversing-valve solenoid can be
checked with power off with an ohmmeter. Check for continuity
and shorting to ground. With control-circuit (24v) power on, check
for correct voltage at solenoid coil. Check for overheated solenoid.

41

NEW SOLENOID COIL

4TH PORT
3 PORT DESIGN
4 PORT DESIGN
A91457

A91456

Fig. 48Reversing Valve


4. Braze new valve onto used stubs. Keep stubs oriented correctly. Scratch corresponding matching marks on old valve
and stubs and on new valve body to aid in lining up new valve
properly. When brazing stubs into valve, protect valve body
with wet rag to prevent overheating.

FROM
OUTDOOR
COIL

5. Use slip couplings to install new valve with stubs back into
system. Even if stubs are long, wrap valve with a wet rag to
prevent overheating.

TP-4

6. After valve is brazed in, check for leaks. Evacuate and charge
system. Operate system in both modes several times to be sure
valve functions properly.

INSULATE
FOR
ACCURATE
READING

TP-2

TP-1

ELECTRONIC
THERMOMETER

TO
ACCUMULATOR

TP-3

TO INDOOR COIL
VIA SERVICE VALVE
ON OUTDOOR COIL

FROM COMPRESSOR
DISCHARGE LINE

FROM INDOOR COIL VIA


SERVICE VALVE ON
OUTDOOR COIL

TP-4

TP-3

INSULATE FOR
ACCURATE
READING

Step 7Thermostatic-Expansion Valves (TXV)


TO OUTDOOR
COIL

TO
ACCUMULATOR

TP-2

A88341

Fig. 50Reversing Valve (Heating Mode, Solenoid


De-Energized)
allows rapid bleed-through of pressure after system shutdown until
pressure equalization occurs within approximately 1 to 2 minutes.
Hard Shutoff (HSO)Has no bleed port and allows no bleedthrough after system shutdown. No pressure equalization occurs.
Because of unequalized system pressures, a start capacitor and
relay must be installed on single-phase reciprocating compressors
to start the compressor.
See Table 21 for TXV superheat settings. These settings are
factory-set and are not field adjustable. Table 21 settings are for
Carrier-approved accessories and factory-installed TXVs only.

TP-1

FROM COMPRESSOR
DISCHARGE LINE

A88342

Fig. 49Reversing Valve (Cooling Mode or Defrost


Mode, Solenoid Energized)
The types of TXVs used in condensing-unit and heat-pump
systems are as follows:
Rapid-Pressure Balance (RPB)Has a special bleed port that

42

Table 21TXV Superheat Setting at Outlet of Evaporator Coil


INSTALLATION
Field Accessory
Field Accessory
Field Accessory/Factory-Installed
Factory-Installed
Factory-Shipped/Field-Installed

TXV TYPE
RPB/HSO
RPB/HSO
HSO
HSO
HSO

PRODUCT USAGE
Air Conditioner Indoor Unit
Heat Pump Indoor Unit
Indoor Fan Coil Unit
2-Speed Heat Pump Outdoor Unit
2-Speed Indoor Unit

Step 8Thermostatic-Expansion Valve (Bi-Flow TXV)

SUPERHEAT SETTING
10
6
6
4
4

2. Remove and recover refrigerant from system through service


valves.

The standard TXV is a metering device that is used in condensing


and heat-pump systems to adjust to changing load conditions by
maintaining a preset superheat temperature at the outlet of the
evaporator coil. The volume of refrigerant metered through the
valve seat is dependent upon:

3. Remove top cover. (See Remove Top Cover section.)


4. Remove screws in base pan to coil grille.
5. Remove coil grille from unit.
6. Remove screws on corner-post (WeatherMaker) servicevalve panel (Cube unit) holding coil-tube sheet.

1. Superheat temperature sensed by cap-tube sensing bulb on


suction tube at outlet of evaporator coil. As long as this bulb
and cap tube contains some liquid refrigerant, this temperature
is converted into suction pressure pushing downward on the
diaphragm, which tends to open the valve via the pushrods.

Cut tubes to reduce the possibility of fire and personal injury.

2. The suction pressure at the outlet of the evaporator coil is


transferred via the external equalizer tube to the underside of
the diaphragm.

7. Use midget-tubing cutter to cut liquid and vapor lines at both


sides of coil. Cut in convenient location for easy reassembly
with copper-slip couplings.

3. The needle valve on the pin carrier is spring-loaded, which


also exerts pressure on the underside of the diaphragm via the
pushrods, which tends to close the valve. Therefore, bulb
pressure equals evaporator pressure (at outlet of coil) plus
spring pressure. If the load increases, the temperature increases at the bulb, which increases the pressure on the topside
of the diaphragm, which pushes the pin carrier away from the
seat, opening the valve and increasing the flow of refrigerant.
The increased refrigerant flow causes increased leaving
evaporator pressure, which is transferred via the equalizer tube
to the underside of the diaphragm. This tends to cause the
pin-carrier spring pressure to close the valve. The refrigerant
flow is effectively stabilized to the load demand with negligible change in superheat. The bi-flow TXV is used on
split-system heat pumps. In the cooling mode, the TXV
operates the same as the standard TXV previously explained.
(See Fig. 51.)
However, when the system is switched to the heating mode of
operation, the refrigerant flow is reversed. The bi-flow TXV
has an additional internal-check valve and external tubing.
(See Fig. 52.) These additions allow the refrigerant to bypass
the TXV when refrigerant flow is reversed with only a 1- to
2-psig pressure drop through the device. When the heat pump
switches to the defrost mode, the refrigerant flows through a
completely open (unthrottled) TXV, and the bulb senses the
residual heat of the outlet tube of the coil that had been
operating in the heating mode (about 85F and 155 psig). This
temporary, unthrottled valve decreases the indoor-pressure
drop, which in turn increases the refrigerant-flow rate, decreases overall defrost time, and enhances defrost efficiency.

8. Lift coil vertically from basepan. Place aside carefully.


9. Reverse procedure to reinstall coil.
Step 10Liquid-Line Strainer (Heat Pumps Only)
The liquid-line strainer is upstream of the heating piston. The
strainer catches debris in the liquid line during heating mode. If it
becomes plugged, system operation and pressure become abnormal, and the compressor may become hot and cycle off on the
overloads or pressure relief.
If the strainer must be replaced, shut off all power to the unit. See
Fig. 47 for strainer location.
Step 11Accumulator
The accumulator is a device always found in heat pumps and found
in some condensing-unit models. Under some light-load conditions on indoor coils and on outdoor coil with heat pump in heating
mode, some liquid refrigerant is present in suction gas returning to
compressor. The accumulator stores liquid and allows it to boil off
into a vapor so it can be safely returned to compressor. Since a
compressor is designed to pump refrigerant in its gaseous state,
introduction of liquid into it could cause severe damage or total
failure of compressor.
The accumulator is a passive device which seldom needs replacing. Occasionally, its internal oil-return orifice or bleed hole may
become plugged. Some oil is contained in refrigerant returning to
compressor. It cannot boil off in accumulator with liquid refrigerant. The bleed hole allows a small amount of oil and refrigerant to
enter the return line where velocity of refrigerant returns it to
compressor. If bleed hole plugs, oil is trapped in accumulator, and
compressor will eventually fail from lack of lubrication. If bleed
hole is plugged, accumulator must be changed. Bleed hole is so
tiny that cleaning efforts are usually not successful. The accumulator has a fusible element located in the bottom-end bell. (See Fig.
53.) This fusible element melts at 430F and vents the refrigerant,
if this temperature is reached either internal or external to the
system. If fuse melts, the accumulator must be replaced.

Step 9Coil Removal


Coils on this family of units are easy to remove, if required for
compressor removal or replacement coil.

Wear safety glasses and gloves when handling refrigerants.

To change accumulator:

To remove or replace coil:

1. Shut off all power to unit.

1. Shut off all power to unit.

2. Remove and reclaim all refrigerant from system.

43

CAPILLARY TUBE

DIAPHRAGM
BYPASS TXV

PUSHRODS
FEEDER TUBES
INLET
COIL

OUTLET
NEEDLE
VALVE
SPRING
DISTRIBUTOR

BULB

CHECK VALVE
(CLOSED)

EXTERNAL EQUALIZER TUBE

BYPASS TUBE

A88406

Fig. 51TXV in Cooling Mode

CAPILLARY TUBE

DIAPHRAGM
BYPASS TXV

PUSHRODS
FEEDER TUBES
INLET
COIL

OUTLET
NEEDLE
VALVE
SPRING

BULB

DISTRIBUTOR
CHECK VALVE
(OPEN)

EXTERNAL EQUALIZER TUBE

BYPASS TUBE

A88405

Fig. 52TXV in Heating Mode


44

NOTE: Coil may be removed for access to accumulator. Refer to


appropriate sections of service manual for instructions.

4. Close the service valve.


5. Allow system to stand for 1 hr, during which time the dry
refrigerant will be able to diffuse throughout the system,
absorbing moisture.

Wear safety glasses and gloves when working on refrigerants


and when using brazing torch.

This procedure is repeated 3 times, after which the system will be


free of any contaminants and water vapor.

3. When accumulator is exposed, remove it from system with


tubing cutter.

Step 13System Charging


For all approved combinations, system must be charged correctly
for normal system operation and reliable operation of components.

4. Scratch matching marks on tubing stubs and old accumulator.


Scratch matching marks on new accumulator. Unbraze stubs
from old accumulator and braze into new accumulator.
5. Thoroughly rinse any flux residue from joints and paint with
corrosion-resistant coating such as zinc-rich paint.

Always wear safety glasses and gloves when handling refrigerants.

6. Reinstall accumulator into system with copper-slip couplings.


7. Evacuate and charge system.

If system has lost all charge, weigh in charge using dial-a-charge


or digital scale.

8. Pour and measure oil quantity (if any) from old accumulator.
If more than 20 percent of oil charge is trapped in accumulator, add oil to compressor to make up for this loss.

System charge should be fine-tuned by using the superheat or


subcooling method, whichever is appropriate. These methods are
covered in the Checking Charge section below.
NOTE: Heat-pump check charts are for checking charge and
performance and for adding a small amount of charge. During
heating mode, correct method of charging is the weight method. In
heating mode, check should be made approximately 15 minutes
after a defrost with unit running with a clean coil. In cooling cycle,
system should run at least 10 minutes for temperatures and
pressures to stabilize. All charts assume there are no system
abnormalities and indoor coil airflows are correct. If system
abnormalities exist, correct them before checking system charge.
Step 14Checking Charge

Proper evacuation of a unit removes non-condensibles and assures


a tight, dry system before charging. The 2 methods used to
evacuate a system are the deep-vacuum method and the tripleevacuation method.

Superheat charging is the process of charging refrigerant into a


system until the temperature (superheat) of the suction gas entering
the compressor reaches a prescribed value. Small variations of
charge affect suction-gas superheat temperatures greatly. Therefore, this method of charging is very accurate. This method can be
used only on split-system condensing units and heat pumps
(operating in the cooling mode) with fixed-restrictor-type metering
devices such as AccuRater, cap tube, and so forth. For units
using a TXV, the subcooling method must be used. Heat pumps
must be operating in the cooling mode. To charge by superheat, a
service technician needs an accurate superheat thermocouple or
thermistor-type thermometer, a sling psychrometer, and a gage
manifold. Do not use mercury or small-dial-type thermometers as
they are not adequate for this type of measurement. Then use one
of the following procedures:

DEEP-VACUUM METHOD

SUPERHEAT CHARGING METHOD

430 FUSE
ELEMENT
A88410

Fig. 53Accumulator
Step 12Contaminant Removal

The deep-vacuum method requires a vacuum pump capable of


pulling a vacuum of 1000 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep-vacuum
method is the most positive way of assuring a system is free of air
and liquid water.

1. Operate a unit a minimum of 10 minutes before checking


charge.
2. Measure vapor pressure by attaching a gage to vapor valveservice port.
3. Measure vapor-line temperature by attaching a service thermometer to unit vapor line near vapor valve. On a heat pump,
attach to the suction tube between the accumulator and the
compressor. Insulate thermometer for accurate readings.

TRIPLE-EVACUATION METHOD
The triple-evacuation method can be used where the vacuum pump
is capable of pumping down to only 28 in. of mercury vacuum, and
the system does not contain any liquid water. The procedure is as
follows.

4. Measure outdoor-air, dry-bulb temperature with a second


thermometer.

1. Pump the system down to 28 in. of mercury vacuum and allow


pump to continue to operate for additional 15 minutes.

5. Measure indoor-air (entering indoor coil), wet-bulb temperature with a sling psychrometer.

2. Close service valves and shut off vacuum pump.

6. Locate outdoor temperature and evaporator entering air wetbulb temperature in Table 22. At this intersection note the
superheat.

3. Connect a refrigerant cylinder to the system and open until


system pressure is 2 psig.

45

Table 22Superheat Charging Table


OUTDOOR TEMP (F)
55
60
65
70
75
80
85
90
95
100
105
110
115

50
9
7

52
12
10
6

54
14
12
10
7

INDOOR COIL ENTERING AIR TEMP (F WET BULB)


56
58
60
62
64
66
68
70
17
20
23
26
29
32
35
37
15
18
21
24
27
30
33
35
13
16
19
21
24
27
30
33
10
13
16
19
21
24
27
30
6
9
12
15
18
21
24
28

5
8
12
15
18
21
25

8
11
15
19
22

5
9
13
16
20

6
10
14
18

8
12
15

5
9
13

6
11

72
40
38
36
33
31
28
26
24
22
20
17
15
14

74
42
40
38
36
34
31
30
27
25
23
22
20
18

76
45
43
41
39
37
35
33
31
29
27
26
25
23

Where a dash appears, do not attempt to charge system under these conditions or refrigerant slugging may occur.

7. Locate superheat temperature located in previous step and


vapor pressure in Table 23. At this intersection note vapor-line
temperature.
8. If unit has a higher vapor-line temperature than charted
temperature, add refrigerant until charted temperature is
reached.
9. If unit has a lower vapor-line temperature than charted
temperature, bleed refrigerant until charted temperature is
reached.
10. If outdoor-air temperature or pressure at vapor valve changes,
charge to new vapor-line temperature indicated on chart.
SUBCOOLING CHARGING METHOD
1. Operate unit a minimum of 15 minutes before checking
charge.
2. Measure liquid service-valve pressure by attaching an accurate
gage to the service port.
3. Measure the liquid-line temperature by attaching an accurate
thermistor-type or electronic thermometer to the liquid line
near the outdoor coil.
4. Refer to unit-rating plate to find required subcooling temperature for units produced during or after January 1993. For units
produced through December 1992, refer to Table 24. Find the
point at which the required subcooling temperature intersects
the measured liquid service-valve pressure on Table 25.
5. To obtain the required subcooling temperature at a specific
liquid-line pressure, add refrigerant if liquid-line temperature
is higher than indicated or remove refrigerant if temperature is
lower. Allow a tolerance of 3F.

Disconnect all electrical power to unit before performing any


maintenance or service on outdoor unit. Remember to disconnect power supply to air handler as this unit supplies
low-voltage power to the outdoor unit. Electric shock can
cause personal injury or death.
The minimum maintenance that should be performed on this
equipment is as follows.
1. Check outdoor coil for cleanliness each month during the
heating (heat pump only) or cooling season and clean as
necessary, but clean at least once each heating (heat pump
only) and cooling season.
2. Check fan motor and blade for cleanliness each heating and
cooling season and clean as necessary.
3. Check electrical connections for tightness and controls for
proper operation each heating (heat pump only) or cooling
season and service as necessary.

Because of possible damage to the equipment or personal


injury, maintenance should be performed by qualified personnel only.
COIL CLEANING
1. Remove top cover. See Remove Top Cover section.

CARE AND MAINTENANCE


To assure high performance and minimize possible equipment
malfunction, it is essential that maintenance be performed periodically on this equipment. The frequency with which maintenance is
performed is dependent on such factors as hours of operation,
geographic location, and local environmental conditions.

Coil fin damage can result in higher operating costs or


compressor damage. Do not use flame, high-pressure water,
steam, or volatile or corrosive cleaners on fins or tubing.
2. Clean coil using vacuum cleaner and its crevice tool. Move
crevice tool vertically, close to area being cleaned, making
sure tool touches only the dirt on the fins and not the fins. To
prevent fin damage, do not scrub fins with tool or move tool
horizontally against fins.
3. If oil deposits are present, spray coil with ordinary household
detergent. Wait 10 minutes, and proceed to next step.
4. Using garden hose, spray coil vertically downward with
constant stream of water at moderate pressure. Keep nozzle at
a 15 to 20 angle, about 3 in. from coil face and 18 in. from
tube. Spray so debris is washed out of coil and basepan.

46

Table 23Required Vapor Temperature (F)


SUPERHEAT TEMP
(F)

61.5
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75

0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40

VAPOR PRESSURE AT SERVICE PORT (PSIG)


67.1
70.0
73.0
76.0
79.2
39
41
43
45
47
41
43
45
47
49
43
45
47
49
51
45
47
49
51
53
47
49
51
53
55
49
51
53
55
57
51
53
55
57
59
53
55
57
59
61
55
57
59
61
63
57
59
61
63
65
59
61
63
65
67
61
63
65
67
69
63
65
67
69
71
65
67
69
71
73
67
69
71
73
75
69
71
73
75
77
71
73
75
77
79
73
75
77
79
81
75
77
79
81
83
77
79
81
83
85
79
81
83
85
87

64.2
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77

82.4
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89

85.7
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91

Table 24Subcooling at Liquid-Service Valve for Units Produced Through December, 1992
WEATHERMAKER AIR CONDITIONERS
MODEL
SERIES
014
018
024
030
036
038
042
048
060

38TG
0
14
17
13
15
13

13
15
19

1
14
17
13
15
12

13
14
22

38TH
2

14

0
14
14
17
9
16

16
18
18

1
14
14
17
10
16

19
14
18

2
14
14
17
10
16

19
18
18

38TK
3

15

0
6
7
8
6
12

12
14
14

1
6
7
8
6
12

12
14
14

10
5

38TKB
3

13

11
13
11
9
16
11
18
11

38TMA

38TM

38TR

15
16
15

11
15
11

8
12
9
13

11
10

11
10
12

15
11
12

38TD
High
Low
0
0

12
9

12
9
12
9

WEATHERMAKER HEAT PUMPS


MODEL
SERIES
014
018
024
030
036
042
048
060

38YG
0
7
18
18
13
18
13
22
23

1
7
18
18
13
18
11
17
23

2
7
18
18
13
18
11
15
23

38YH
3

14

16
16
20
14
18
19
13

16
16
20
14
18
14
13

38YK
0

11
11
10
10
15
13
14

11
11
10
10
15
13
14

38YKA

38YKB

38YMA

10
13
11
11
12

9
6
10
13
10
15
15

7
5
10
12
12
12
10

47

38YR
0

9
11
9
9
11
10
12

10
11
10
10
12
11
7

38YD
COOLING
HEATING
High
Low
High
Low
0
0
0
0

12
7
18
15

14
9
25
18
14
9
22
21

CUBE UNIT
AIR CONDITIONERS
38CK
0
1

15
16
14
11
12
12
18
16
18
17

17

21

MODEL
SERIES
014
018
024
030
036
042
048
060

CUBE UNIT
HEAT PUMPS
38YC
0
1

11
14
14
8
9
10
11
7
17

12

10

38GN
1
10
12

12

HORIZONTAL
AIR CONDITIONERS
38GNA
38HDA
0
0

17
20
19
17

20

22

18

23

38QRA
0

10
19
18
26

17
17

Table 25Required Liquid-Line Temperature


PRESSURE (PSIG)
AT SERVICE FITTING
134
141
148
156
163
171
179
187
196
205
214
223
233
243
253
264
274
285
297
309
321
331
346
359

0
76
79
82
85
88
91
94
97
100
103
106
109
112
115
118
121
124
127
130
133
136
139
142
145

5
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125
128
131
134
137
140

REQUIRED SUBCOOLING TEMPERATURE (F)


10
15
20
66
61
56
69
64
59
72
67
62
75
70
65
78
73
68
81
76
71
84
79
74
87
82
77
90
85
80
93
88
83
96
91
86
99
94
89
102
97
92
105
100
95
108
103
98
111
106
101
114
109
104
117
112
107
120
115
110
123
118
113
126
121
116
129
124
119
132
127
122
135
130
125

25
51
54
57
60
63
66
69
72
75
78
81
84
87
90
93
96
99
102
105
108
111
114
117
120

if old one is burned or corroded and crimp tightly.

5. Restore power to unit.


CLEANING OUTDOOR FAN MOTOR AND BLADE

3. Reconnect electrical power to the indoor and outdoor units and


observe unit through 1 complete operating cycle.

1. Remove fan motor and blade. Refer to Remove Fan-Motor


Assembly section of this manual. Be careful not to bend or
dent fan blade.

4. If there are any discrepancies in the operating cycle, troubleshoot to find the cause, and correct.

2. Clean motor and blade with soft brush or cloth. Be careful not
to disturb balance weights on fan blade.

REFRIGERANT CIRCUIT
1. Check the refrigerant charge using the superheat or subcooling
method, whichever is applicable. If low on charge, check unit
for leaks using an electronic leak detector.

3. Check fan-blade setscrew for tightness.


4. Reinstall fan motor and blade to top cover and check for
alignment.

2. If any leaks are found, recover or isolate charge (pumpdown)


if applicable and make necessary repairs.

5. Reinstall top cover and position blade as per Fig. 24.

3. Evacuate, recharge, and operate unit through entire cycle.

6. Reconnect electrical power and check for proper operation.

FINAL CHECKOUT

ELECTRICAL CONTROLS AND WIRING

After the unit has been operating, the following items should be
checked:

1. Disconnect power to both the outdoor and indoor units.


2. Check all electrical connections for tightness. Tighten all
screws on electrical connections. If any connections appear to
be burned or smoky, disassemble the connection, clean all
parts and stripped wires, and reassemble. Use a new connector

1. Check that unit operational noise is not excessive due to


vibration of components, tubing, panels, etc. If present, isolate
problem and correct.

48

2. Check to be sure caps are installed on service valves and that


they are tight.

mounting rack are available as accessories and can be used to


elevate the unit.

3. Check to be sure tools, loose parts, and debris are removed


from the unit.

3. Addition of coastal filter (see pre-sale literature for accessory


listing).

4. Check to be sure all panels and screws are in place and tight.

Special maintenance requirements are as follows:

Desert and Seacoast Locations

1. Frequent inspection of coil and base pan, especially after


storms and/or high winds.

Special consideration must be given to the installation and maintenance of condensing units and heat pumps installed in seacoast
or desert locations. Salt and the alkali content of the sand adhere
to the aluminum fins of the coil and can cause premature coil
failure due to corrosion.

2. Cleaning coil by flushing out sand from between coil fins and
out of base pan as frequently as inspection determines
necessary.
3. Protecting the unit in off season with cover that allows air to
circulate through but prevents sand from sifting in (such as
canvas material). Do not use plastic as plastic will hold
moisture.

Preventive measures can be taken during installations, such as:


1. Locating the unit on side of structure opposite the prevailing
winds.
2. Elevating the unit to height where drifting sand cannot pile up
against coil. Four-in.-high mounting feet or an 18-in.-high

49

AIR CONDITIONER
TROUBLESHOOTING CHART
NO COOLING OR
INSUFFICIENT
COOLING

COMPRESSOR
WILL NOT RUN

COMPRESSOR
RUNS BUT
CYCLES ON
INTERNAL
OVERLOAD

COMPRESSOR
RUNS BUT
INSUFFICIENT
COOLING

CONTACTOR
OPEN

CONTACTOR
CLOSED

OUTDOOR FAN
STOPPED OR
CYCLING ON
OVERLOAD

LOOSE LEAD
AT FAN MOTOR

LOW SUCTION
PRESSURE

HIGH SUCTION
LOW HEAD
PRESSURE

HIGH SUCTION
LOW
SUPERHEAT

POWER SUPPLY

COMPRESSOR
POWER SUPPLY
OPEN

OUTDOOR AIR
RESTRICTED OR
RECIRCULATING

MOTOR
DEFECTIVE

DIRTY AIR
FILTERS

DEFECTIVE
COMPRESSOR
VALVES

UNIT
OVERCHARGED

DEFECTIVE
LOW-VOLTAGE
TRANSFORMER

LOOSE LEADS AT
COMPRESSOR

RESTRICTED
DISCHARGE
TUBE

INCORRECT
OFM
CAPACITOR

DUCT
RESTRICTED

INTERNAL
PRESSURE
RELIEF OPEN

INCORRECT
SIZE
PISTON

OPEN
THERMOSTAT

FAULTY START
GEAR (1-PH)

OVERCHARGE
OR NONCONDENSABLES
IN SYSTEM

DAMPERS
PARTLY CLOSED

OPEN CONTROL
CIRCUIT

OPEN SHORTED
OR GROUNDED
COMPRESSOR
MOTOR
WINDINGS

LOW
REFRIGERANT
CHARGE

INDOOR COIL
FROSTED

LOSS OF
CHARGE

COMPRESSOR
STUCK

LINE VOLTAGE
TOO HIGH OR
LOW

SLIGHTLY
LOW ON
REFRIGERANT

CONTACTOR OR
COIL DEFECTIVE

COMPRESSOR
INTERNAL
PROTECTION
OPEN

DEFECTIVE RUN
CAPACITOR

LIQUID LINE
SLIGHTLY
RESTRICTED

LOOSE
ELECTRICAL
CONNECTION

DEFECTIVE RUN
CAPACITOR

COMPRESSOR
BEARINGS

PISTON
RESTRICTED

HIGH
SUPERHEAT

INCORRECT
SIZE
PISTON

INDOOR COIL
STRAINER
RESTRICTED

INDOOR
BLOWER MOTOR
DEFECTIVE OR
CYCLING ON OL

A90208

Fig. 54Air-Conditioner Troubleshooting Chart

50

HEAT PUMP
TROUBLESHOOTINGCOOLING CYCLE
NO COOLING OR
INSUFFICIENT
COOLING

COMPRESSOR
RUNS BUT
CYCLES ON
INTERNAL
OVERLOAD

COMPRESSOR
WILL NOT RUN

COMPRESSOR
RUNS BUT
INSUFFICIENT
COOLING

CONTACTOR
OPEN

CONTACTOR
CLOSED

OUTDOOR FAN
STOPPED OR
CYCLING ON
OVERLOAD

LOOSE LEAD
AT FAN MOTOR

LOW SUCTION
PRESSURE

HIGH SUCTION
LOW HEAD
PRESSURE

HIGH SUCTION
LOW
SUPERHEAT

POWER SUPPLY

COMPRESSOR
POWER SUPPLY
OPEN

OUTDOOR AIR
RESTRICTED OR
RECIRCULATING

DEFROST RELAY
N.C. CONTACTS
OPEN

DIRTY AIR
FILTERS

REVERSING
VALVE HUNG UP
OR INTERNAL
LEAK

UNIT
OVERCHARGED

DEFECTIVE
LOW-VOLTAGE
TRANSFORMER

LOOSE LEADS AT
COMPRESSOR

DAMAGED OR
STUCK
REVERSING
VALVE

MOTOR
DEFECTIVE

DUCT
RESTRICTED

DEFECTIVE
COMPRESSOR
VALVES

INCORRECT
SIZE
PISTON

OPEN
THERMOSTAT

FAULTY START
GEAR (1-PH)

RESTRICTED
DISCHARGE
TUBE

INCORRECT
OFM
CAPACITOR

DAMPERS
PARTLY CLOSED

INTERNAL
PRESSURE
RELIEF OPEN

OPEN CONTROL
CIRCUIT

OPEN SHORTED
OR GROUNDED
COMPRESSOR
MOTOR
WINDINGS

OVERCHARGE
OR NONCONDENSABLES
IN SYSTEM

DEFECTIVE
DEFROST
THERMOSTAT

INDOOR COIL
FROSTED

LOSS OF
CHARGE

COMPRESSOR
STUCK

LOW
REFRIGERANT
CHARGE

SLIGHTLY
LOW ON
REFRIGERANT

CONTACTOR OR
COIL DEFECTIVE

COMPRESSOR
INTERNAL
PROTECTION
OPEN

LINE VOLTAGE
TOO HIGH OR
LOW

LIQUID LINE
SLIGHTLY
RESTRICTED

LOOSE
ELECTRICAL
CONNECTION

DEFECTIVE RUN
CAPACITOR

DEFECTIVE RUN
CAPACITOR

PISTON
RESTRICTED

COMPRESSOR
BEARINGS

INCORRECT
SIZE
PISTON

HIGH
SUPERHEAT

INDOOR COIL
STRAINER
RESTRICTED

INDOOR
BLOWER MOTOR
DEFECTIVE OR
CYCLING ON OL

A90207

Fig. 55Heat-Pump Troubleshooting Chart Cooling Cycle

51

HEAT PUMP
TROUBLESHOOTINGHEATING CYCLE
NO HEATING OR
INSUFFICIENT
HEATING

COMPRESSOR
RUNS BUT
CYCLES ON
INTERNAL
OVERLOAD

COMPRESSOR
WILL NOT RUN

COMPRESSOR
RUNS
INSUFFICIENT
HEATING

CONTACT
OPEN

CONTACTOR
CLOSED

DIRTY FILTERS
OR INDOOR
COIL

DEFECTIVE LOWVOLTAGE
TRANSFORMER

COMPRESSOR
POWER SUPPLY

INDOOR FAN
STOPPED OR
CYCLING ON
OVERLOAD

DEFECTIVE FAN
MOTOR
CAPACITOR

OUTDOOR FAN
STOPPED

OUTDOOR FAN
RUNNING

OUTDOOR
THERMOSTAT
DEFECTIVE

REMOTE
CONTROL
CENTER
DEFECTIVE

LOOSE LEADS AT
COMPRESSOR

DAMAGED
REVERSING
VALVE

LOOSE LEADS
AT
FAN MOTOR

LOOSE LEADS
AT OUTDOOR
FAN MOTOR

REVERSING
VALVE STUCK

ODT SETTING
TOO LOW

CONTACTOR
COIL OPEN OR
SHORTED

FAULTY START
GEAR (1-PH)

RESTRICTION IN
DISCHARGE LINE

FAN MOTOR
BURNED
OUT

INTERNAL FAN
MOTOR KLIXON
OPEN

RESTRICTED
LIQUID LINE

CAP TUBE
PINCHED OR
BULB NOT
SENSING TRUE
ODT

OPEN INDOOR
THERMOSTAT

COMPRESSOR
STUCK

OVERCHARGE
OR NONCONDENSABLES
IN SYSTEM

FAN MOTOR
BURNED OUT

PISTON
RESTRICTED OR
IS CLOGGED

STRIP HEATER
RELAY OR
CONTACTOR
DEFECTIVE

LIQUID-LINE
PRESSURE
SWITCH OPEN

COMPRESSOR
INTERNAL
OVERLOAD
OPEN

LOW
REFRIGERANT
CHARGE

DEFROST RELAY
N.C. CONTACTS
OPEN ON
CIRCUIT BOARD

UNDERCHARGED

OPENING IN
POWER CIRCUIT
TO HEATER
ELEMENTS

LOSS OF
CHARGE

OPEN SHORTED
OR GROUNDED
COMPRESSOR
WINDINGS

LINE VOLTAGE
TOO HIGH OR
LOW

OUTDOOR COIL
DIRTY

BROKEN FUSE
LINK

OPEN CONTROL
CIRCUIT

DEFECTIVE RUN
CAPACITOR

DEFECTIVE RUN
CAPACITOR
(1-PH)

STRAINER
RESTRICTED

BROKEN
HEATER
ELEMENT

COMPRESSOR
BEARINGS

OUTDOOR COIL
HEAVILY
FROSTED

OPEN (KLIXON)
OVER
TEMPERATURE
THERMOSTAT
DEFECTIVE
ROOM
THERMOSTAT
(2ND STAGE)

STRIP HEATERS
NOT OPERATING

LOW SUCTION
LOW HEAD

HIGH-LOAD
CONDITION

FAN MOTOR
CONTACTS
WELDED CLOSED
IN DEFROST
RELAY

DEFECTIVE
DEFROST
THERMOSTAT

REVERSING
VALVE JAMMED
IN MIDPOSITION

REVERSING
VALVE DID NOT
SHIFT

DEFROST
THERMOSTAT IN
POOR PHYSICAL
CONTACT WITH
TUBE

HIGH
SUPERHEAT

UNIT NOT
PROPERLY
CHARGED

DEFECTIVE
CIRCUIT BOARD

BAD ELECTRICAL
CONNECTION
ANYWHERE IN
DEFROST
CIRCUIT

A90206

Fig. 56Heat-Pump Troubleshooting Chart Heating Cycle

Copyright 2000 CARRIER Corp. 7310 W. Morris St. Indianapolis, IN 46231

3810sm

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
PC 101
Catalog No. 563-732
Printed in U.S.A.
Form 38-10SM
Pg 52
11-00
Replaces: 38-1SM, 38-16XA
Tab 3a 5a 2a 5a

You might also like