Long Line Application CARRIER-R22
Long Line Application CARRIER-R22
Long Line Application CARRIER-R22
Application Guide
and Service Manual
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................2
INTRODUCTION ..........................................................................2
INSTALLATION GUIDELINE ....................................................2
Residential New Construction ..................................................2
Add-On Replacement (Retrofit) ...............................................2
Seacoast (For Air Conditioners Only) .....................................2
ACCESSORY DESCRIPTIONS ...................................................2
Compressor Crankcase Heater..................................................2
Evaporator Freeze Thermostat..................................................2
Winter Start Control .................................................................2
Compressor Start AssistPTC ................................................2
Compressor Start AssistCapacitor/Relay..............................2
Low-Ambient Controller ..........................................................2
MotorMaster Control ............................................................2
Low-Ambient Pressure Switch.................................................2
Wind Baffle...............................................................................3
Coastal Filter.............................................................................3
Support Feet ..............................................................................3
Liquid-Line Solenoid Valve .....................................................3
Thermostatic-Expansion Valve.................................................3
Isolation Relay ..........................................................................3
Defrost Thermostats................................................................18
Defrost-Control Board ............................................................18
Fan Motors ..............................................................................22
Service Alarm Control Board.................................................23
Outdoor Thermostat(s)............................................................24
Compressor Plug.....................................................................24
Low-Voltage Terminals ..........................................................24
RECIPROCATING COMPRESSOR ..........................................25
Mechanical Failures ................................................................25
Electrical Failures ...................................................................26
System Cleanup After Burnout ..............................................27
Compressor Removal And Replacement ...............................28
COPELAND SCROLL COMPRESSOR ....................................28
Features ...................................................................................28
Troubleshooting ......................................................................28
Discharge Thermostat .............................................................28
Discharge Solenoid Valve ......................................................29
MILLENNIUM SCROLL COMPRESSOR ................................29
Features ...................................................................................29
Compressor Protection............................................................29
Troubleshooting ......................................................................29
Scroll-Compressor, 3Phase Monitor.....................................29
LOW-AMBIENT GUIDELINE.....................................................3
LONG-LINE GUIDELINE............................................................3
Approved Systems ....................................................................3
Interconnecting Tubing Sizing .................................................3
Metering Device Sizing ............................................................5
Liquid-Line Solenoid And Tubing Configuration ...................5
Charging Information................................................................6
2Speed Applications ...............................................................7
CABINET.....................................................................................10
Remove Top Cover-WeatherMaker ...................................10
Remove Fan-Motor Assembly-WeatherMaker ..................10
Information PlateWeatherMaker.....................................11
Control-Box CoverCube Products......................................11
Remove Top CoverCube Products.....................................11
Remove Fan-Motor AssemblyCube Products....................11
ELECTRICAL..............................................................................12
Aluminum Wire ......................................................................12
Contactors................................................................................13
Capacitors................................................................................14
Cycle Protector........................................................................16
Crankcase Heater ....................................................................16
Time-Delay Relay...................................................................17
Pressure Switches....................................................................18
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
PC 101
Catalog No. 563-732
Printed in U.S.A.
Form 38-10SM
Pg 1
11-00
Replaces: 38-1SM, 38-16XA
Tab 3a 5a 2a 5a
SAFETY CONSIDERATIONS
Service and repair of these units should be attempted only by
trained service technicians familiar with Carrier standard service
instructions and training manual.
ACCESSORY DESCRIPTIONS
Refer to Table 1 for an Accessory Usage Guide for Air Conditioners and Heat Pumps. See Model-specific product literature for
any kit part number. Refer to the appropriate section below for a
description of each accessory and its use.
Step 1Compressor Crankcase Heater
An electric heater which mounts to base of compressor to keep
lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes chance of refrigerant slugging and oil
pumpout. The crankcase heater may or may not include a
thermostat control. For units equipped with crankcase heaters,
apply power for 24 hr before starting compressor.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or
other conditions which may cause personal injury, death, or
property damage. Consult a qualified installer, service
agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product.
INTRODUCTION
This service manual enables a service technician to service, repair,
and maintain a family of similar air conditioners and heat pumps.
It covers standard single-speed products and 2speed products
only. For variable-speed products, refer to the respective service
manuals.
INSTALLATION GUIDELINE
Step 1Residential New Construction
Table 1Required Field-Installed Accessories for Air Conditioners and Heat Pumps
ACCESSORY
Crankcase Heater
Evaporator Freeze Thermostat
Winter Start Control
Accumulator
Compressor Start Assist
Capacitor and Relay
Low Ambient Controller,
MotorMaster Control,
or
Low-Ambient Pressure Switch
Wind Baffle
Coastal Filter
Support Feet
Liquid-Line Solenoid Valve
or
Hard-Shutoff TXV
Ball-Bearing Fan Motor
Isolation Relay
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(BELOW 55F)
Yes
Yes
Yes
No
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(OVER 50 FT)
Yes
No
No
No
REQUIRED FOR
SEA COAST
APPLICATIONS
(WITHIN 2 MILES)
No
No
No
No
Yes
Yes
No
Yes
No
No
No
No
No
See Long-Line
Application
Guideline
No
No
No
Yes
Recommended
No
Yes
Yes**
No
No
No
*For tubing line sets between 50 and 175 ft, refer to Residential Split-System Long-Line Application Guideline.
Only when low-pressure switch is used.
Required for Low-Ambient Controller (full modulation feature) and MotorMaster control only.
** Required on Heat Pumps only.
Four adhesive plastic feet which raise unit 4 in. above mounting
pad. This allows sand, dirt, and other debris to be flushed from unit
base; minimizes corrosion.
LONG-LINE GUIDELINE
This Long-Line Application Guideline applies to all Carrier
residential air conditioner and heat pump split systems that have a
nominal capacity of 18,000 to 60,000 Btuh. This guideline
provides required system changes and accessories necessary for
any residential product having piping requirements greater than 50
ft or installations where indoor unit is located above outdoor unit.
This guideline is intended to cover applications outside the
standard Installation Instructions. This guideline is for standard,
single-speed products. For applications involving 2-speed products, refer to Step 6 first.
NOTE: The presale literature for outdoor unit must be referred to
in conjunction with this guideline.
7/ x 3/ (5.56
32
8
x 9.53) SLOT
4 REQ'D
9/ (3.45) DIA HOLE
64
2 REQ'D
H
3/
8
6 1/16
(154.0)
(9.6)
TYP
1/
2
SUPPORT
(12.7)
TYP
7/
MAT'L: 18 GA STEEL
16
(11.6)
TYP
1
/2
(12.7)
TYP
K
B
16
7/
(11.6)
TYP
1/
4
1/
4
(6.3)
TYP
(6.3)
TYP
BAFFLE
SCREW
10 REQ'D
7/ x 2
32
(5.56 x 50.8) SLOT
MAT'L: 20 GA STEEL
SUPPORT
4 REQ'D
OUTDOOR
UNIT
BAFFLE
2 REQ'D
AA
BAFFLE ASSEMBLY
A95444
For reference only, the close cell insulation material specified for
accessory tubing kits is a compound of vinyl, neoprene, or nitrile
blends of these polymers. Performance requirements include
thermal range of 0 F to 200F (-17.8 C to 93 C) and a maximum
thermal conductivity of 0.28.
NOTE: Special consideration must be given to isolating interconnecting tubing from building structure. Isolate tubing so that
vibration or noise is not transmitted into structure.
Table 2Wind Baffle Dimensions for WeatherMaker Units with Star-Burst Top (In.)
UNIT SIZE
Small
Medium
Large
AA
UNIT HEIGHT
A
B
C
D
21-7/8
17
25-1/4 10-3/8 19-3/4
27-1/2
25-7/8
17
25-1/4 10-3/8 23-3/4
31-7/8
17
25-1/4 10-3/8 29-3/4
25-7/8
21
32
11-3/16 23-3/4
34-15/16
31-7/8
21
32
11-3/16 29-3/4
37-7/8
21
32
11-3/16 35-3/4
31-7/8
25-3/16
42
12-15/16 29-3/4
45
37-7/8
25-3/16
42
15-15/16 35-3/4
E
F
G
20-1/2
34
19-11/16
24-1/2
34
23-11/16
30-1/2
34
29-11/16
24-1/2
42
23-11/16
30-1/2
42
29-11/16
36-1/2
42
35-11/16
30-1/2 50-7/16 29-11/16
36-1/2 50-7/16 35-11/16
H
20-7/16
24-7/16
30-7/16
24-7/16
30-7/16
36-7/16
30-7/16
36-7/16
J
19-5/8
23-5/8
29-5/8
23-5/8
29-5/8
35-5/8
29-5/8
35-5/8
K
0
0
0
19-11/16
19-11/16
19-11/16
22-11/16
22-11/16
L
M
0
6-1/8
11-7/8 6-1/8
14-7/8 6-1/8
11-7/8 6-11/16
14-7/8 6-11/16
17-7/8 6-11/16
14-7/8 7-1/16
17-7/8 7-1/16
Table 3Wind Baffle Dimensions for WeatherMaker Units with Silencer System Top (In.)
UNIT SIZE
Small
Medium
Large
AA
UNIT HEIGHT
A
B
C
D
23-13/16
17
25-1/4 10-3/8 19-3/4
27-1/2
27-13/16
17
25-1/4 10-3/8 23-3/4
33-13/16
17
25-1/4 10-3/8 29-3/4
27-13/16
21
32
11-3/16 23-3/4
34-15/16
33-13/16
21
32
11-3/16 29-3/4
39-13/16
21
32
11-3/16 35-3/4
33-13/16
25-3/16
42
12-15/16 29-3/4
45
39-13/16
25-3/16
42
15-15/16 35-3/4
E
F
G.
20-1/2
34
19-11/16
24-1/2
34
23-11/16
30-1/2
34
29-11/16
24-1/2
42
23-11/16
30-1/2
42
29-11/16
36-1/2
42
35-11/16
30-1/2 50-7/16 29-11/16
36-1/2 50-7/16 35-11/16
H.
20-7/16
24-7/16
30-7/16
24-7/16
30-7/16
36-7/16
30-7/16
36-7/16
J
19-5/8
23-5/8
29-5/8
23-5/8
29-5/8
35-5/8
29-5/8
35-5/8
K
0
0
0
19-11/16
19-11/16
19-11/16
22-11/16
22-11/16
L
M
0
6-1/8
11-7/8 6-1/8
14-7/8 6-1/8
11-7/8 6-11/16
14-7/8 6-11/16
17-7/8 6-11/16
14-7/8 7-1/16
17-7/8 7-1/16
EXAMPLE:
An 042 size heat pump is 75 ft above an 042 size fan coil.
The 042 size heat-pump presale literature specifies a size
80 indoor piston and size 63 outdoor piston.
To establish correct indoor piston size for a 75 ft vertical
separation, refer to Table 7. For a 75 ft equivalent line
length, the piston change is -5. Therefore subtract 5 from
the original indoor piston size of 80:
80 5 = 75
Table 9 provides common piston sizes. In this instance, 75
is not listed, therefore round DOWN to next piston size,
which would be 74.
To establish correct outdoor piston size for a 75 ft vertical
separation, refer to Table 8. For a 75 ft equivalent line
length, the piston change is +4. Therefore add 4 to the
original outdoor piston size of 63:
63 + 4 = 67
Since 67 is listed in Table 9, that is the piston which should
be used. If a 67 size piston were not listed, it would be
necessary to round UP to next piston size.
TXVs may be used instead of pistons for indoor-metering devices.
Some fan coils are equipped with a hard-shutoff, bi-flow TXV
standard, and no change is required. When sizing an accessory
TXV for long-line applications, TXV should be the same nominal
tonnage as outdoor unit. Refer to presale literature for kit part
numbers.
Step 4Liquid-Line Solenoid And Tubing Configuration
There are 2 types of liquid-line solenoids: 1 for single-flow
applications and the other for bi-flow applications. The purpose of
having 2 solenoids is to minimize the valve internal-pressure drop
in accordance with refrigerant flow direction and liquid migration
to the compressor. The bi-flow solenoid is designed to have
minimal refrigerant-pressure drop in either flow direction, which
makes it suitable for heat pump usage. Refer to Table 10 for
liquid-line solenoid kit part numbers.
NOTE: When installing a liquid-line solenoid, the system may
require a minimum 60-va low-voltage transformer.
7 7/8
(200.0)
3/
16
1/ (3.45) DIA
8
2 REQ'D
(4.6)
5 3/64
(128.0)
E
C
1/
1/
4
(12.7)
(6.4)
5 3/64
(128.0)
13/
64
7 8
(199.9)
7/
25/
64 (10.0)
(5.4)
TYP
1 21/32 (42.1)
BAFFLE - LEFT
MAT'L: 20 GA STEEL
1/
7 29/32 (200.8)
(12.7)
TYP
BAFFLE - RIGHT
MAT'L: 20 GA STEEL
1/
(5.56) DIA
2 REQ'D
2 1/2
(63.5)
A
2 1/2
(63.5)
1 21/32 (42.1)
4
1/
25
64
6 REQ'D
(10.0)
AA
4 9/64 (105.2)
45
TYP
64
23/
(9.2)
LEFT
SIDE
2 5/64
(52.6)
8 5/64 (205.3)
TYP
1/
4
(6.4)
1/ (12.7)
2
TYP
23/ (9.2)
64
SCREW
14 REQ'D
1/ (5.56) DIA
4
2 REQ'D
4 5764
(124.2) TYP
RIGHT
SIDE
OUTDOOR
UNIT
SUPPORT
3 REQ'D
SUPPORT
MAT'L: 18 GA STEEL
1/ (3.45) DIA.
8
4 REQ'D
BAFFLE ASSEMBLY
JH
A95446
EXAMPLE:
To calculate additional charge required for a 25ft line set:
25 ft 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge
AA
Small
18
Medium
22-1/2
Large
30
UNIT HEIGHT
21-15/16
23-15/16
25-15/16
27-15/16
29-15/16
31-15/16
33-15/16
21-15/16
23-15/16
25-15/16
27-15/16
29-15/16
31-15/16
33-15/16
35-15/16
37-15/16
25-15/16
27-15/16
29-15/16
31-15/16
33-15/16
35-15/16
37-15/16
39-15/16
A
19-7/8
21-7/8
23-7/8
25-7/8
27-7/8
29-7/8
31-7/8
19-7/8
21-7/8
23-7/8
25-7/8
27-7/8
29-7/8
31-7/8
33-7/8
35-7/8
23-7/8
25-7/8
27-7/8
29-7/8
31-7/8
33-7/8
35-7/8
37-7/8
B
13-3/4
13-3/4
13-3/4
13-3/4
13-3/4
13-3/4
13-3/4
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
18-5/16
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
25-3/4
C
28-1/8
28-1/8
28-1/8
28-1/8
28-1/8
28-1/8
28-1/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
32-5/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
40-1/8
D
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
10-11/16
E
20-1/4
20-1/4
20-1/4
20-1/4
20-1/4
20-1/4
20-1/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
24-3/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
32-1/4
F
11-11/16
11-11/16
11-11/16
11-11/16
11-11/16
11-11/16
11-11/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
16-3/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
23-11/16
G.
3-13/16
3-13/16
3-13/16
3-13/16
3-13/16
3-13/16
3-13/16
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
8-1/4
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
15-13/16
H.
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
35-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
35-13/16
37-13/16
J
17-13/16
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
17-13/16
19-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
21-13/16
23-13/16
25-13/16
27-13/16
29-13/16
31-13/16
33-13/16
35-13/16
42,000
48,000
60,000
LONG-LINE
VAPOR-LINE
DIAMETER
(IN.)
5/8
3/4
5/8
3/4
5/8
3/4
3/4
7/8
3/4
7/8
1-1/8
3/4
7/8
1-1/8
7/8
1-1/8
75
100
125
150
175
5
1
6
0
6
2
7
2
7
3
0
10
4
0
7
1
7
3
9
1
8
3
10
4
10
4
0
14
6
0
9
2
9
4
13
1
10
4
14
6
13
6
1
18
7
1
11
2
12
5
16
2
13
5
17
8
17
7
1
22
9
1
14
3
12
5
19
3
15
6
21
10
20
8
2
NR
11
2
16
3
14
7
22
4
17
7
NR
11
23
10
2
NR
13
2
19
4
*The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling Capacities data specified in outdoor unit-presale literature for any given
indoor/outdoor combination.
Vapor-line diameter that may be selected for a long-line application. If smaller vapor lines are selected but not specified within the table, large capacity losses will occur
and defrost capabilities will be reduced. If larger vapor lines are selected but not specified within the table, refrigerant oil return will be impaired due to velocity losses.
N/RNot recommended due to excessive loss of capacity.
Vapor tube diameter for the 036 and 048 is 7/8 in.; 060 is
11/8
Vapor refrigerant connection diameter for all sizes is 7/8 in.
DO NOT INSTALL EQUIVALENT INTERCONNECTING
TUBING LENGTHS GREATER THAN 100 FT.
2. Do not increase or decrease tubing sizes.
For other applications see the previous sections under Long-Line
Guidelines.
90 STD
35
38
40
42
46
49
51
52
55
57
59
61
63
90 LONG RAD
45 STD
A92498
CHATLEFF
32
33
35
36
37
38
39
40
41
42
43
45
47
49
51
52
53
55
57
59
61
62
63
ACCURATER
65
67
70
73
76
78
80
82
84
86
88
90
93
96
98
101
104
109
CHATLEFF
65
67
68
70
71
73
74
76
78
80
81
82
84
86
88
89
90
92
93
96
98
101
104
TYPE OF VALVE
Single Flow
Bi-Flow
PART NO.
KAALS0101LLS
KHALS0101LLS
175' MAX.
GROUND LEVEL
BASEMENT
A90074
175' MAX.
GROUND LEVEL
BASEMENT
A90075
TRAP
50' MAX.
GROUND LEVEL
A90076
Fig. 6Application with Air Conditioner or Heat Pump Installed with Indoor Unit Above Outdoor Unit
AIndianapolis
ECollierville
Positions 6 through 10Serial Number
Example:
3230 or 208230 or 208/230, 1 Phase, 60 Hertz
5230 or 208230 or 208/230, 3 Phase, 60 Hertz
6460, 3 Phase, 60 Hertz
7220/240, 1 Phase, 50 Hertz
8220, 3 Phase, 50 Hertz
9380/415, 3 Phase, 50 Hertz
Position 13Series
New units have a 0. As major component variations occur,
including compressor changes, fan motors, coil circuitry size, etc.,
the change is identified by increasing this digit in increments of 1.
Position 14Packaging
On split-system products, this digit will be 0.
Positions 15 and 16Not Used
These positions will contain dashes ( ).
Step 2Serial Number Identification
The unit serial number has 10 positions containing groups of
numbers and a letter that indicate specific information about the
unit. Listed below is the breakdown of the 10 positions.
Positions 1 and 2Week of Manufacture
Example:
01First week of a year
52Last week of a year
Positions 3 and 4Year of Manufacture
Example:
941994
Position 5Manufacturing Site
Example:
CABINET
Certain maintenance routines and repairs require removal of
cabinet panels. There are 4 basic cabinet designs for air conditioners and heat pumps. (See Fig. 8.) The horizontal discharge unit will
be discussed in a separate section of this manual.
Step 1Remove Top Cover-WeatherMaker
1. Turn off all power to outdoor and indoor units.
2. Remove screws holding top cover to coil grille and corner
posts.
3. Remove access panel.
4. Remove information plate.
5. Disconnect fan motor wires, cut wire ties, and remove wire
ties from control box. Refer to unit-wiring label.
6. Lift top cover from unit.
7. Reverse sequence for reassembly.
Step 2Remove Fan-Motor Assembly-WeatherMaker
1. Perform items 1 through 6 above.
2. Remove nuts holding fan-motor top cover.
3. Remove motor and fan blade assembly.
4. Reverse sequence for reassembly.
5. Prior to applying power, check that fan rotates freely.
10
150' MAX.
A90077
Fig. 7Application with Air Conditioner or Heat Pump Installed Above Indoor Unit
Step 3Information PlateWeatherMaker
5. Disconnect fan motor wires, cut any wire ties, and move wires
out of control box and through tube clamp on back of control
box.
6. Lift top cover from unit.
7. Reverse sequence for reassembly.
Step 6Remove Fan-Motor AssemblyCube Products
1. Perform items 1, 3, 4, and 5 above. (Note item 2 is not
required.)
2. Remove 4 screws holding wire basket to top cover.
3. Lift wire basket from unit.
4. Remove nuts holding fan motor to wire basket.
5. Remove motor and fan blade assembly.
6. Pull wires through wire raceway to change motor.
7. Reverse sequence for reassembly.
8. Prior to applying power, check that fan rotates freely.
The information plate is secured to the front of the control box and
provides a cover for it. (See Fig. 9.) This plate also provides a
surface to attach the wiring schematic, superheat-charging tables
with instructions, and warning labels. The plate has 2 tabs on the
top edge that are bent down at slightly more than 90. When the
information plate is removed, these tabs can be inserted into 2
mating slots in the bottom-front edge of the control box, and the
plate will hang down, forming a lower front panel. (See Fig. 10.)
This is convenient where access to the controls is required while
the unit is operating. The information plate on the small size casing
completely covers the opening below the control box. On larger
models, the information plate may not cover the entire opening. In
this instance, the top cover can be removed and placed on its side
to cover the additional space.
Step 4Control-Box CoverCube Products
This panel contains much of the same information as the information plate mentioned previously, but is designed only to cover the
control box.
Step 5Remove Top CoverCube Products
1. Turn off all power to outdoor and indoor units.
2. Remove 5 screws holding top cover to coil grille and coil tube
sheet.
3. Remove 2 screws holding control-box cover.
4. Remove 2 screws holding information plate.
11
A00009
SEFL JOSD
J SEFL
JOSDJ
SEFL JOSD
J SEFL
JOSDJ
SEFL JOSD
J SEFL
JOSDJ
SEFL JOSDJ
SEFL JOSDJ SEFL JOSDJ
SEFL JOSDJ SEFL JOSDJ PAASFLDLKREW
ATC
SEFL JOSDJ SEFL JOSDJ
UTUHD
SEFL JOSDJ SEFL JOSDJC
SEFL JOSDJ SEFL JOSDJH MD
SEFL JOSDJ R ITYALK
A88411
12
SEFL
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SDJ
SEFL
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SEFL
SDJ
JOSD
J SE
FL JO
SDJ
SEFL
JOSDJ
SEFL
JOSDJ SEFL JOS
SEFL
JOSDJ SEFL JOSDJ PAASFLD
SEFL
LKREW
JOSDJ SEFL JOSDJ ATC
SEFL
JOSDJ SEFL JOSDJ UTUHD
SEFL
JOSDJ SEFL JOSDJC MD
DJH
SEFL
JOSDJ R ITYALK
SEFL
JOSDJ
SEFL
JOSDJ SEFL JOS
SEFL
JOSDJ SEFL JOSDJ PAASFL
SEFL
DLKREW
JOSDJ SEFL JOSDJ ATC
SEFL
JOSDJ SEFL JOSDJ UTUHD
SEFL
JOSDJ SEFL JOSDJC MD
DJH
SEFL
JOSDJ R ITYALK
A88412
A88413
A88350
Fig. 11Contactor
connection will be exposed to moisture, it is very important to
cover the entire connection completely to prevent an electrochemical action that will cause the connection to fail very quickly. Do
not reduce the effective size of wire, such as cutting off strands so
that the wire will fit a connector. Proper size connectors should be
used. Check all factory and field electrical connections for
tightness. This should also be done after the unit has reached
operating temperatures, especially if aluminum conductors are
used.
Step 2Contactors
NOTE: The section applies to single-speed models only.
13
Step 3Capacitors
12.5-22.5 OHMS
12.5 OHM
(BEIGE COLOR)
25-45 OHMS
20-36 OHMS
BLUE
20 OHM
(BLUE COLOR)
25 OHM
(BLUE COLOR)
A88414
A91455
Fig. 12Capacitors
2. Capacitance testers are available which read value of capacitor. If value is not within 10 percent value stated on
capacitor, it should be changed. If capacitor is not open or
shorted, the capacitance value is calculated by measuring
voltage across capacitor and current it draws.
14
5. Discharge start capacitor by using a pair of insulated, needlenose pliers and shorting a 15,000ohm, 2watt resistor across
terminals.
NOTE: Some start capacitors already have a bleed resistor
attached. If so, it will discharge itself over a short period of time.
6. Run compressor 10 minutes. Stop and allow unit to sit idle for
5 minutes.
7. Check system pressure equalization.
8. Attempt to restart without capacitance boost.
If PTC thermistor device is inadequate as start device, a start
capacitor and relay may be added to system to ensure positive start.
Capacitor is wired in parallel with run capacitor through normally
closed set of contacts on a device called start relay. The relay coil
is wired across start and common terminals of compressor. The
added capacitance gets the compressor started. As compressor
comes up to speed, voltage across start and common terminals
increases to a value high enough to cause start relay to energize.
This opens normally closed contacts and removes start capacitor
from circuit. In actual practice, this occurs in a fraction of a
second.
NOTE: If bleed resistor is wired across start capacitor, it must be
disconnected to avoid erroneous readings when ohmmeter is
applied across capacitor.
To check start relay and capacitor:
1. Turn off all power to unit.
2. Discharge start and run capacitors as outlined earlier.
3. Most start capacitors will have a 15,000-ohm, 2-watt bleed
resistor. Disconnect these devices from system.
Start capacitor can be inspected visually. It is designed for short
duration or intermittent duty. If left in circuit for prolonged period,
start capacitor blows through a specially designed bleed hole. If it
appears blown, check for welded contacts in start relay. Start
capacitor can be checked by ohmmeter method discussed earlier.
Start relay is checked with ohmmeter. Check for continuity across
coil of relay. You should encounter a high resistance. Since relay
contacts are normally closed, you should read low resistance
L2
FIELD POWER
SUPPLY
L1
R
C
C
COMP
S
Start capacitor
(SC)
temporarily
connected
SC
RC
Capacitance boosting
A00195
T2
T1
T3
T1
T3
T2
HN67ZA002
A91438
HN67ZA008
A94005
T3 BLK
T1 YEL
T2 VIO
T3 BLK
T2
T1
T3
HN67PA025
HN67ZA003
A91440
A91439
across them. Both PTC device and capacitor-relay start system are
standard equipment on some of these units. They are also available
as accessories and may be field-installed.
Step 4Cycle Protector
Solid-state cycle-protector device protects unit compressor by
preventing short cycling. After a system shutdown, cycle protector
provides for a 5 2-minute delay before compressor restarts. On
normal start-up, a 5-minute delay occurs before thermostat closes.
After thermostat closes, cycle protector device provides a 3-sec
delay on HN67PA025, HN67ZA003, and HN67ZA008. (See Fig.
15, 16, and 17.)
Cycle-protector device is simple to troubleshoot. Only a voltmeter
capable of reading 24v is needed. Device is in control circuit;
therefore, troubleshooting is safe with control power (24v) on and
high-voltage power off.
With high-voltage power off, attach voltmeter leads across T1 and
T3 and set thermostat so that Y terminal is energized. Make sure
all protective devices in series with Y terminal are closed.
Voltmeter should read 24v across T1 and T3. With 24v still
applied, move voltmeter lead from T1 terminal to T2 terminal
across T2 and T3. After 5 2 minutes, voltmeter should read 24v,
indicating control is functioning normally. If no time delay is
encountered or device never times out, change control.
16
OPERATING
TIME
OPERATING
TIME
3
SEC
5 MIN
T1
_
T1
_
T2
T2
5 MIN
HN67ZA002
A91436
A91437
YEL
SAFETY
CONTROL
TERMINAL
BOARD
CONNECTION
YEL
YEL
YEL
T1
BRN
TERMINAL
BOARD
CONNECTION
VIO
LOGIC
T3
BLK
T2
A88415
DSV
CH
11
21
A91426
17
Solid-state defrost boards used on heat pumps replace electromechanical timer and defrost relay found on older defrost systems.
The defrost-control board can be field-set to check need for defrost
every 30, 50, or 90 minutes of operating time by connecting the
jumper (labeled W1 on the circuit board) to the terminal for the
defrost time desired. The board is set at factory for 90 minutes. The
defrost period is field-selectable, depending upon geographic areas
and defrost demands. Two types of defrost boards are used. Their
functions are described in the sections to follow.
LOW-PRESSURE SWITCH
Located on suction line of condensing unit only, the low-pressure
switch protects against low-suction pressures caused by such
events as loss of charge, low airflow across indoor coil, dirty
filters, and so forth. It opens on a pressure drop at about 27 psi. If
system pressure is above this, switch should be closed. To check
switch, turn off all power to unit, disconnect leads on switch, and
apply ohmmeter leads across switch. You should have continuity
on a good switch. Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this
device for troubleshooting unless you are reasonably certain that a
problem exists. If switch must be removed, remove and recover all
system charge so that pressure gages read 0 psi.
Apply heat with torch to solder joint and remove switch. Wear
safety glasses when using torch. Have quenching cloth available.
Oil vapor in line may ignite when switch is removed. Braze in
1/4-in. flare fitting and screw on replacement pressure switch.
HIGH-PRESSURE SWITCH
Located on discharge line, the high-pressure switch protects
against high-discharge pressures caused by such events as overcharge, condenser-fan motor failure, system restriction, and so
forth. It opens on pressure rise at about 435 psi. If system pressures
go above this setting during abnormal conditions, the switch
opens. Do not attempt to simulate these system abnormalities as
high pressures pose a serious safety hazard. High-pressure switch
is also checked with an ohmmeter similar to checking low-pressure
switch. If system pressure is below 435 psi, the switch shows
continuity. It is replaced in the same manner as low-pressure
switch. Observe all safety precautions.
9. Remove protective cover from TP1 and TP2 speed-up terminals. Install jumper wire on speed-up terminals. This reduces
the timing sequence to 1/60 of original time. (See Fig. 20.)
Since Fig. 20 shows timing cycle set at 30 minutes, unit
initiates defrost within approximately 30 sec; if setting is at 50
minutes, within 50 sec; 90 minutes, within 90 sec. When you
hear the reversing valve change position, remove protective
cover/jumper. Otherwise, control will terminate normal 10minute defrost cycle in approximately 10 sec.
18
OF2 OF1
OF2
OF1
E
W2
14
L
W3
DFT
T2
TI DFT
TEST 30 50 90
W1
O
R
W2
Y
30 50
W1
CES0110063,
CES0130024
HK32FA003/HK32FA006
A91442
A88402
6. Remove protective cover from TP1 and TP2 speed-up terminals and install jumper wire on the speed-up terminals.
19
OF1 OF2
G
OF2
OF1
W2
14
L
G
W3
T2
TI DFT
TEST 30 50 90
W1
DFT
O
R
50 90
W2
W1
Y
C
HK32FA003/HK32FA006
CES0110063,
CES0130024
A88404
A91444
OF2
OF1
OF2 OF1
G
E
W2
14
L
W3
G C
C
DFT
T2
TI DFT
TEST 30 50 90
W1
30 50
R
W2
W1
Y
C
HK32FA003/HK32FA006
CES0110063,
CES0130024
A88403
A91443
20
MINIMUM
MAXIMUM
30-minute cycle
50-minute cycle
90-minute cycle
10-minute cycle
5 minutes
27
45
81
9
4.5
33
55
99
11
5.5
SPEED-UP
(NOMINAL)
7 sec
12 sec
21 sec
2 sec
1 sec
Defrost Settings
The defrost control is a time/temperature control which includes a
field-selectable time period (DIP switch 1 and 2 on board, see
Table 12) between defrost cycles of 30, 60, 90, and 120 minutes
(factory-set at 90 minutes).
SW2
Off
On
Off
On
SW3
30
60
90
120
21
OF1
DFT
OF2
T2 C C O
T1
O R W2 Y C
Y
P1
30
30
60
120
60
P3
ON
DFT
QUIET
SHIFT
90
INTERVAL TIMER OFF
J1
SPEEDUP
Speedup
Pins
CESO13007600
Quiet
Shift
Defrost interval
DIP switches
A99442
FEEDER TUBE
STUB TUBE
DEFROST
THERMOSTAT
A97517
Fan motor rotates the fan blade that either draws or blows air
through outdoor coil to perform heat exchange. Motors are totally
enclosed to increase reliability. This also eliminates need for rain
shield. For the correct position of the fan blade assembly, see Fig.
24 and Table 13.
22
TOP COVER
BASKET TOP
FAN
ORIFICE
A91428
FAN BLADE
HC29GE208
LA01EC019
5-1/8
LA01EA026
4-5/8
HC31GE230/231
LA01RA015
4-7/8
4-5/8
HC33GE208
LA01EW049
5-1/4
HC33GE232
LA01RA015
4-29/32
4-17/32
HC34GE231
LA01RA015
5-5/32
4-25/32
HC34GE460
HC35GE208
LA01EW048
4-15/16
LA01EA025
5-7/8
HC35GE232
LA01RA024
5-11/32
5-3/32
LA01RA026
5-9/16
4-11/16
HC37GE208
LA01EA025
6-1/8
6-1/8
HC37GE230
LA01EW042
6-5/32
6-1/8
HC38GE221
LA01EA031
7-25/32
LA01EC018
5-11/16
HC39GE232
LA01RA026
5-1/2
4-3/4
LA01EA036
5-9/16
LA01EA024
5-3/32
4-27/32
HC39GE234
LA01EC018
5-1/2
LA01EA036
6-1/16
HC39GE461
LA01EC018
6-1/4
LA01RA026
6-1/16
5-7/32
HC40GE230
LA01EA024
5-9/32
5-11/32
HC40GE461
LA01EA024
5-27/32
5-19/32
BASEPAN DIMENSIONS FOR STAR BURST TOP (IN.)
Small
22-1/2 x 26-3/16
Medium
30 x 33
Large
38-5/8 x 42-1/16
Fan Motor
Part No.
23
compressor terminals, and the mating female terminals are completely encapsulated in the plug. Therefore, the terminals are
isolated from any moisture so corrosion and resultant pitted or
discolored terminals are reduced. The plug is oriented to the relief
slot in the terminal box so the cover cannot be secured if wires are
not positioned in slot, assuring correct electrical connection at the
compressor. The plug can be removed by simultaneously pulling
while rocking the plug. However, these plugs are specialized and
vary in terminal orientation in the plug. Therefore, plugs can be
used on only the specific compressor or group as shown in Fig. 27.
For the Carlyle and Bristol compressors in Fig. 27, the triangle
formed by the fusite terminals points down, and the plug is
likewise oriented. The fusite terminals and plug-terminal orientation shown for the Tecumseh compressor is shown with the
triangle formed by the terminals pointing toward the top. The
configuration around the fusite terminals is the outline of the
terminal covers used on the specific compressors. The slot through
which the wires of the plug are routed is oriented on the bottom or
slightly to the left or right. The correct plug can be connected
easily to the compressor terminals and plug wires routed easily
through the slot in the terminal cover. Therefore, if a Carlyle or
Bristol compressor is substituted for a Tecumseh compressor, a
new plug must be installed. If the plug is not changed, proper
connection and routing of the plug wires through the terminal
cover will be impossible.
Step 14Low-Voltage Terminals
The low-voltage terminal designations, along with descriptions
and/or functions, are used on all split-system condensers and heat
pumps:
G.Energizes blower circuit from indoor thermostat.
EEnergizes emergency heat relay.
W2Energizes first-stage supplemental heat through defrost relay
(wht).
LEnergizes light on thermostat with service alarm.
W3Energizes second- or third-stage supplemental heat.
REnergizes 24v power from transformer (red).
24-VOLT WIRING
HPS
C
BRN
LPS
C
BLU
BLU YEL
YEL
C
THERMOSTAT
SUBBASE
INDOOR
UNIT
TERMINAL
BOARD
BLK
ORN
YEL
RED
OUTDOOR
UNIT
TERMINAL
BOARD
1
SERVICE ALARM
PASS SUPPLY WIRE THROUGH
METALLIC LOOP TWICE ON
UNITS WITH NAMEPLATE
RLA OF 14 AMPS OR LESS.
*METALLIC
LOOP
ONE FIELD
LINE VOLTAGE
SUPPLY WIRE
A88340
YEL
CYCLE PROTECTOR
T1 T2 T3
SERVICE ALARM
X
3
2
1
VIO BLK
ORN
Y
DTS
L
YEL
BLK
BLK
BRN
YEL
BLU
LPS
BLU
HPS
BRN
A88339
COMMON POTENTIAL
FACTORY WIRING (FIELD CONNECTED)
FIELD-SUPPLIED WIRING
CONTACTOR
A88339
YEnergizes contactor for first-stage cooling or first-stage heating for heat pumps (yel).
OEnergizes reversing valve on heat pumps (orn).
CCommon side of transformer (blk).
RECIPROCATING COMPRESSOR
The compressor is the heart of the refrigeration system. It pumps
refrigerant through the system. If it malfunctions, system capacity
and efficiency could be negatively affected.
In this type of failure, compressor motor runs and turns compressor, and compressor is pumping. Usually, an internal problem such
as blown head gasket or broken internal-discharge line causes
compressor to pump hot discharge gas back into its own shell
rather than through system.
LOCKED ROTOR
In this type of failure, compressor motor and all starting components are normal. When compressor attempts to start, it draws
locked-rotor current and cycles off on the internal protection.
Locked-rotor current is measured by applying a clamp-on ammeter
around common (blk) lead of the compressor on a single-phase
compressor, or any 1 of the leads on a 3-phase compressor. Current
drawn when it attempts to start is then measured. LRA (lockedrotor amp) value is stamped on compressor nameplate.
25
LEAD 3
BLUE
CARLYLE
BRISTOL
COPELAND
C S
R
LEAD 1
BLK.
TECUMSEH
C
C
4. Apply flux and repair joint with silver solder. Do not use
low-temperature solder such as 50-50.
LEAD 1
BLK.
5. Clean off excess flux, check for leaks, and apply paint over
repaired area to prevent corrosion.
LEAD 2
YEL.
LEAD 3
BLUE
TECUMSEH
LEAD 1
BLK.
LEAD 3
BLUE
S
R
SINGLE-PHASE MOTORS
To identify terminals C, S, and R:
1. Turn off all unit power.
LEAD 2
YEL.
MILLENNIUM
LEAD 1
BLK.
C
R S
LEAD 3
BLUE
LEAD 2
YEL.
A94002
THREE-PHASE MOTORS
NOISY COMPRESSOR
Noise may be caused by a variety of internal problems such as
loosened hardware, broken mounting springs, etc. System problems such as overcharged compressor (especially at start-up) or too
much oil in compressor may also cause excessive noise. Excess oil
in compressor is normally encountered only after a replacement
compressor has been added without purging oil from previous
compressor. As new compressor pumps, excess oil in system
returns and adds to volume already present, causing noise.
COMPRESSOR LEAKS
26
(EXAMPLE)
TO DETERMINE INTERNAL CONNECTIONS OF SINGLEPHASE MOTORS (C,S,R) EXCEPT SHADED-POLE
?
?
DEDUCTION:
POWER OFF!
?
(GREATEST RESISTANCE)
5.8 (OHM)
OHMMETER
0-10 SCALE
(SMALLEST RESISTANCE)
0.6
2 IS COMMON (C)
BY ELIMINATION
(REMAINING RESISTANCE)
5.2
2 IS COMMON,
THEREFORE, 1 IS
1
5.2
1
2
0.6
5.8
2
3
3
3 IS RUN WINDING (R)
A88344
GROUND CIRCUIT
NOTE: To analyze level of suspected contamination from compressor burnout, use Total Test. See your distributor/branch.
Some compressor electrical failures can cause motor to overheat.
When this occurs, by-products, which include sludge, carbon, and
27
2
The open passage is sealed off
as gas is drawn into the spiral.
3
As the spiral continues to orbit,
the gas is compressed into an
increasingly smaller pocket.
5
Actually, during operation, all
six gas passages are in various
stages of compression at all
times, resulting in nearly continuous suction and discharge.
A90198
Step 2Troubleshooting
28
PLASTIC CAP
OIL TYPE
Suniso 3GS
BLUE SEALANT
Zerol 150
w/3 percent
Syn-O-Ad
PRONG
GROMMET
Suniso 3GS
THERMAL GREASE
THERMOSTAT
Suniso 3GS
A90198
Suniso 3GS
*Copeland scrolls are charged initially with Sontex 200LT white oil. Since this
oil is not commercially available, use 3GS.
Step 3Troubleshooting
Troubleshooting mechanical and electrical problems in a scroll
compressor is similar to a reciprocating compressor, except that a
scroll compressor should never be allowed to pump into a vacuum.
The scroll compressor is capable of pumping into a vacuum very
quickly, which could cause fusite arcing and compressor failure.
See Step 4 of Reciprocating Compressor section for removal and
replacement.
Step 4Scroll-Compressor, 3Phase Monitor
CES0130075 PHASE MONITOR
Step 1Features
The scroll compressor pumps refrigerant through the system by the
interaction of a stationary and an orbiting scroll. (See Fig. 29.) The
scroll compressor has no dynamic suction or discharge valves, and
it is more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The Millennium scroll varies from the Copeland
scroll in that the Millennium has a shutdown flapper valve located
between the scroll plates and the discharge head, whereas the
Copeland has a check device at the discharge connection after the
discharge head. The Copeland discharge head unloads when the
compressor shuts down. The scroll plate actually runs backwards
while it unloads. A 1 to 3 second unloading of refrigerant occurs.
29
A00010
L1
COMP
CONT
EQUIP
GND
T2
T1
L3
11
21
T3
*CH
CONT
CAP
23
OFM
L1
L2
L3
13
LOGIC
CESO130075
CONT
CONT
*HPS
*LPS
T2
LOGIC
T1
*LLS
T3
CTD
Y
IFR
G
R
R
INDOOR
THERMOSTAT
continuous through coil sections. Dirt and debris may pass through
first section, become trapped between the rows of fins, and restrict
condenser airflow. Use a flashlight to determine if dirt or debris
has collected between coil sections. Clean coil as follows:
1. Turn off power to unit.
2. Flush coil from the outside to remove dirt using water from a
hose or other suitable equipment. Be sure to flush all dirt and
debris from drain holes in base of unit.
TWO-SPEED SYSTEM
TEFLON SEAL
Contactor is mechanically interlocked. Do not disable mechanical interlock. Compressor damage may occur.
PISTON
WITH
ORIFICE
SCREEN
CAP
FAN BLADE
OUTSIDE EDGE
OF GRILLE
COOLING OPERATION
The 2-speed products utilize a 2-stage-cooling indoor thermostat.
With a call for first-stage cooling (Y1), the outdoor fan and
low-speed compressor are energized. If low speed cannot satisfy
the cooling demand, high speed will be energized (Y1 and Y2) by
the second stage of the indoor thermostat. The thermostat has a 2
differential between first and second stages. After second stage is
satisfied, the unit returns to low-speed operation until first stage is
satisfied or until second stage is again required.
DIMENSION FROM
OUTSIDE TOP EDGE OF
BLADE TO OUTSIDE EDGE
OF FAN DECK.
A92070
31
LM1 LM2
S2
S1
PW2 PW1
P1
18
K7
FURN INT
OFF
ON
50
20
15
40
10
30
35
45
85
25
90
ZONE
95
105 OFF
90
30
SPEED-UP
100
036
048
060
T2
DFT1 DFT2 T1
A93568
The 2-speed control energizes the outdoor fan any time the
compressor is operating. The outdoor fan remains energized during
the 1-minute, speed-change time delay and if a pressure switch or
compressor PTC overload should trip.
Any time the control receives a 24v input, such as Y1 or Y2, there
is a 3-sec time delay before the control function is initiated. This
helps prevent nuisance trips and thermostat jiggling.
If the outdoor fan motor wont run, check the header-pin housing.
(See Fig. 39.) There SHOULD BE a jumper wire between
terminals 15 and 16.
Heat Pumps
SECOND-STAGE LATCHING
HIGH VOLTAGE
L2
LO
HI
CCH
LOW VOLTAGE
ODF
LM1 LM2
O
DFT1 DFT2 T1
1
K1
K2
K3
K4
K5
T2
S2
S1
PW2 PW1
K6
P1
18
K7
FURN INT
OFF
ON
Second-stage latching can be selected by rotating the potentiometer (POT) to the desired outdoor second-stage latching temperature (See Fig. 36.) The temperatures that can be selected are 85,
90, 95, 100, and 105F. The POT is factory-set at 105F.
SPEED-UP
LED 1
ZONE SELECTION
If the stage2 latch POT is set to ZONE position, the compressor
operating speed in either heat or cool mode is determined by the
Y1 and/or Y2 inputs. The system operates in low speed with a Y1
input and high speed with Y2 or Y1-and-Y2 input. This allows the
multistage-zoning system to determine what speed is needed
regardless of outdoor temperature or switchover point.
A93569
CRANKCASE-HEATER OPERATION
The 2-speed control energizes the crankcase heater during the
units off cycle when the outdoor ambient is below 75F.
32
TSTAT
UNIT
DEFINITION
No demand
Stand by
POSSIBLE CAUSE
Low-speed operation
High-speed operation
3 flashes
pause
4 flashes
5 flashes
w/pause
6 flashes
w/pause
Constant light
No pause
No flash
Board failure
*Function light signals order of importance; in case of multiple-signal request, 1 is most important.
Signal at thermostat will occur after 3 consecutive attempted restarts and lockout has occurred.
Will be energized if pressure switch remains open for 1 hr.
**Check both thermistors to determine which is faulty.
delay in the outdoor fan being energized. If the stage2 latch POT
is set to ZONE and the heat pump is in low speed, it defrosts in low
speed.
FIELD-INITIATED FORCED DEFROST
By placing a jumper across the speedup terminals for a minimum
of 5 sec and then removing it, the unit initiates a defrost cycle. (See
Fig. 36.) The cycle occurs only if the outdoor ambient is less than
50F, regardless of outdoor coil temperature. The cycle terminates
when the coil thermistor reaches 80F ( 5) or the defrost period
reaches a maximum of 10 minutes.
FURNACE INTERFACE
This feature provides a heat-pump lockout upon a demand for
auxiliary heat (W2) and must be used when interfacing a heat
pump with a gas/oil furnace. Field selection of the furnaceinterface option is done by connecting the factory-supplied jumper
to the ON position of the 3 terminal connectors. (See Fig. 35.)
When the option is selected, the heat pump will be locked out of
operation any time there is a thermostat demand for W2 or the
outdoor ambient is below the balance-point POT-setting selection.
(See Fig. 36.) When the unit requires defrost, auxiliary heat (W2)
energizes the furnace. After defrost is terminated, the heat pump
shuts down and the furnace satisfies the thermostat. To utilize this
function, the economic and/or thermal balance point must be
determined. See the appropriate heat pump balance-point worksheet available from your distributor or branch.
BALANCE POINT
This feature can be used in 2 different options: furnace interface or
electric-heat staging. Refer to the Furnace Interface section for its
application. If the heat pump is installed with a fan coil with
multistages of electric heat, this option can be used to stage the
banks of heat by outdoor ambient. This eliminates the need for
accessory outdoor thermostats.
When using this option to stage electric heat, first stage is
energized by a W2 demand, and second stage is energized by a W3
demand. Select the W3 desired temperature by rotating the
70
60
HIGH
SPEE
50
BTU (1000'S)
HIGH SPEED
BALANCE POINT
D CA
PACIT
40
LOW S
PEED
30
CAPA
STRUCTURE
BALANCE POINT
CITY
20
LOW SPEED
BALANCE POINT
10
50
60
70
80
90
100
110
120
TEMPERATURE (F)
A91282
33
FAN
COIL
TWO SPEED
HEAT PUMP
W2
W2
W2
CONTROL
LOGIC
W3
TWO-SPEED CONTROL
The 2-speed control board controls the following functions:
W3
A93572
Time/temperature defrost
Defrost-interval selection
Furnace interface
Electric-heat staging
HEADER-PIN HOUSING
EMERGENCY HEAT
TWO-SPEED COMPRESSOR
C - TRANSFORMER COMMON
R - TRANSFORMER LINE
When the control turns off the outdoor unit due to out-of-range
PTCs, the unit remains off for 15 minutes with the outdoor fan
running. After 15 minutes, the control checks the resistance every
5 minutes until it reaches the reset range. During this time, a
malfunction signal appears on the control board. If this happens,
remove the wires on control board at S1 and S2 and measure the
resistance across the leads. When the resistance reaches 8,400 to
10,000 ohms, system operation may be resumed. If the resistance
remains outside this range, a quick check of the leads at the
compressor should be made. Loose connections can cause inaccurate readings. If a PTC trip occurs 3 times, the control will lock out
the outdoor-unit operation and provide malfunction signals at both
the control and indoor thermostat.
O - REVERSING VALVE
10
L - MALFUNCTION LIGHT
11
12
4 - TON
13
14
5 - TON
IF NO JUMPER IS
INSTALLED, DEFAULT
IS 3 - TON
15
16
17
18
JUMPER FOR
HEAT PUMP ONLY
A93576
34
FUNCTION
Crankcase Heater
Second-Stage Latching
Furnace Interface
Ambient Thermistor
Furnace Interface
T7
3 TON
0.80
3.20
1.30
3.10
4 TON
0.70
2.20
1.00
2.20
5 TON
0.60
1.80
1.00
2.00
T3 T8
DEFAULT
Energized during any off cycle
Does not function
Balance point does not function, but
interface still energizes furnace and
locks out heat pump with a call for W2
Unit only runs in highcompressor speed
Defrost is initiated based on coil
temperature only
Anytime there is a call for W2,
W3 is also energized.
Defrost occurs at each time interval,
but terminates after 5 minutes
Does not function
T2
TEMPERATURE THERMISTORS
T1
EXTERNAL MAIN
MAIN WINDING
2 POLE START
HIGH SPEED
(L1) T1 + T7
(L2) T2 + T3
LOW SPEED
(L1) T1
(L2) T7 + T8
A92015
35
THERMISTOR CURVE
90
RESISTANCE (KOHMS)
80
70
Ground
60
50
40
30
20
10
120
A91431
0
0
20
40
60
80
TEMPERATURE (DEG. F)
100
then off, the signal will remain off for 4 sec before turning on again
to start the next cycle. The PWM is called a 20percent duty-cycle
signal. If the on time is increased to 4 sec of the 5 sec period, the
PWM is called an 80percent duty-cycle signal. The ICM reads the
PWM signal and increases the motor speed linearly from minimum
speed to maximum speed with the percent duty-cycle value of the
supplied PWM signal.
Short
This is an extremely critical test and is not advised unless the
following conditions are met.
The correct motor-winding resistances must be known before
testing. See Table 19 for cold-motor winding resistance.
EMI FILTER
The resistance-measuring instrument must have an accurate ohmmeter (such as a Wheatstone bridge or null balance-type instrument).
The motor must be dry or free from direct contact with liquid
refrigerant.
equipped
with
an
LED
Step 6Troubleshooting
CONTROL-BOARD FAILURE
The control board continuously monitors its own operation and the
operation of the system. The diagnostic feature allows easy
troubleshooting of the control and system in the field. If a failure
occurs, the LED light on the control will flash a failure code. If the
failure is internal to the control board, the light will stay on
continuously (no flash). Before replacing control board, reset the
24v power. If the fault clears, check to ensure the indoor and
outdoor unit and electrical service are properly grounded. If the
entire system is grounded, the control board should be replaced, as
the control is not field reparable. If the control-board light is
flashing, see LED and Table 16 for function/malfunction definition. Cycling 24 vac to control board resets previous error
messages and any lockouts which have occurred. See Table 20 for
more information regarding control-board operation.
36
SCHEMATIC DIAGRAM
(LADDER FORM)
L1
C1
11
L2
C2
21
24
C2
17
T7
27
COMP
MAIN
T2
EXT
MAIN
SC
14
T1
LOW
START
HIGH
START
T8
T3
C2
EQUIP
GND
15
BR
25
HS
SR
C2
1
16
CAP
F
26
C1
12
22
C1
5
LS
SR
1
13
23
A91446
L1
L2
C2
C1
11
21
24
C2
17
T7
27
T2
COMP
MAIN
LOW
START
EXT
MAIN
SC
14
T1
HIGH
START
T8
T3
C2
EQUIP
GND
H
BR
15
25
2
HS
SR
C2
1
CAP
16
26
C1
12
22
C1
5
LS
SR
1
13
23
A91445
TERMINAL
DESIGNATION
R-C
Y1,0-C
Y1, Y2, 0-C
Y1-C
Y1-C
LOCATION ON
CONTROL BOARD
2-1
8,6-1
8,7,6-1
8-1
8-1
VOLTAGE
PATH
Input
Input
Input
Input
Input
VOLTAGE
REQUIRED
24
24
24
24
24
Y2-C
7-1
Output
24
Y1-C
8-1
Input
24
7,5,6-1
Output
24
Second Stage of
Auxiliary Heat
Y1, W2-C
W3, Y2-C
7,5-1
9,8-1
Input
Output
24
24
8,7,6-1
Input
24
High-speed Heating
Defrost
POSSIBLE SOURCE
OF PROBLEM
Check transformer (secondary)
Check thermostat
Check thermostat
Check thermostat
Check thermostat
Outdoor temperature below
speed; change temperature
Check thermostat
Outdoor temperature below 50F;
Coil temperature less than 30F
Check thermostat
Check balance-point setting
Ambient thermistor failure;
Check second-stage POT
In a straight cooling system, compressed hot gas leaves compressor and enters condensing coil. As gas passes through condenser
coil, it rejects heat and condenses into liquid. The liquid leaves
condensing unit through liquid line and enters metering device at
indoor coil. As it passes through metering device, it becomes a
gas-liquid mixture. As it passes through indoor coil, it absorbs heat
and refrigerant and is again compressed to a hot gas. The cycle
then repeats.
In a heat pump, the basic cycle is the same. (See Fig. 44.)
Reversing valve in system decides which coil, indoor or outdoor,
becomes evaporator or condenser. It rejects heat into the home
after heat is absorbed by outdoor evaporator coil, thus the home is
heated.
If the outdoor fan motor fails to start and run, first check the
high-voltage supply. The unit need not be running to check high
voltage, but the power must be on. With a voltmeter, check for
230vac on the brn and blk motor leads at the EMI filter, if
installed. If the 230vac is not present, check the supply and the
EMI filter for faulty connections, faulty wiring, or faulty EMI
filter. Repair or replace as necessary.
REFRIGERATION SYSTEM
Step 1Refrigeration Cycle
38
COOLING CYCLE
REVERSING VALVE
(ENERGIZED)
OUTDOOR FAN
INDOOR
FAN
INDOOR COIL
ACCUMULATOR
SUCTION SERVICE
PORT AT SERVICE
VALVE (CLG CYCLE)
COMP
STRAINER
OUTDOOR
COIL
STRAINER
(METERING)
HEAT PUMP
ACCESSORY
FILTER DRIER
(DUAL FLOW)
SUCTION
SERVICE
PORT
(BYPASSING)
LIQUID LINE
PRESSURE SWITCH
A88400
A88401
Step 3Brazing
When brazing is required in the refrigeration system, certain basics
should be remembered. The following are a few of the basic rules.
1. Clean joints make the best joints. To clean:
a. Remove all oxidation from surfaces to a shiny finish before
brazing.
39
STEM
SERVICE PORT
W/SCHRADER
CORE
FIELD
SIDE
STEM
SERVICE PORT
W/SCHRADER CORE
FIELD
SIDE
SEAT
SEAT
A91447
A91448
The service valves in the outdoor unit come from the factory
front-seated. This means that the refrigerant charge is isolated from
the line-set connection ports. Some heat pumps are shipped with
sweat-adapter tube. This tube must be installed on the liquidservice valve. After connecting the sweat adapter to the liquidservice valve of a heat pump, the valves are ready for brazing. The
interconnecting tubing (line set) can be brazed to the service valves
using either silver-bearing or non-silver-bearing brazing material.
Consult local codes.
Before brazing the line set to the valves, the belled ends of the
sweat connections on the service valves must be cleaned so that no
brass plating remains on either the inside or outside of the bell
joint. To prevent damage to the valve and/or cap O ring, use a
wet cloth or other acceptable heat-sinking material on the valve
before brazing. To prevent damage to the unit, use a metal barrier
between brazing area and unit.
After the brazing operation and the refrigerant tubing and evaporator coil have been evacuated, the valve stem can be turned
counterclockwise until it opens or back-seats, which releases
refrigerant into tubing and evaporator coil. The system can now be
operated.
Back-seating service valves must be back-seated (turned counterclockwise until seated) before the service-port caps can be removed and hoses of gage manifold connected. In this position,
refrigerant has access from and through outdoor and indoor unit.
The service valve-stem cap is tightened to 20 2 ft/lb torque and
the service-port caps to 9 2 ft/lb torque. The seating surface of
the valve stem has a knife-set edge against which the caps are
tightened to attain a metal-to-metal seal. If accessory pressure
switches are used, the service valve must be cracked. Then, the
knife-set stem cap becomes the primary seal.
40
PISTON BODY
FEEDER
TUBES
PISTON
(ORIENT AS SHOWN)
BRASS
HEX NUT
STRAINER
PISTON
PISTON RETAINER
PISTON
RETAINER
TEFLON
SEAL
FLARE ADAPTER
BRASS
HEX
BODY
INTERNAL STRAINER
PRODUCTION
EXCEPT 1992
A91138
A94004
4. Pull retainer out of body, being careful not to scratch flaresealing surface. If retainer does not pull out easily, carefully
use locking pliers to remove it.
5. Slide piston out by inserting a small, soft wire with small
kinks through metering hole. Do not damage metering hole,
sealing surface around piston cones, or fluted portion of
piston.
6. Clean piston refrigerant-metering hole.
7. Install a new retainer O-ring or retainer assembly before
reassembling bypass-type AccuRater.
If valve is defective:
1. Shut off all power to unit and remove all charge from system.
41
4TH PORT
3 PORT DESIGN
4 PORT DESIGN
A91457
A91456
FROM
OUTDOOR
COIL
5. Use slip couplings to install new valve with stubs back into
system. Even if stubs are long, wrap valve with a wet rag to
prevent overheating.
TP-4
6. After valve is brazed in, check for leaks. Evacuate and charge
system. Operate system in both modes several times to be sure
valve functions properly.
INSULATE
FOR
ACCURATE
READING
TP-2
TP-1
ELECTRONIC
THERMOMETER
TO
ACCUMULATOR
TP-3
TO INDOOR COIL
VIA SERVICE VALVE
ON OUTDOOR COIL
FROM COMPRESSOR
DISCHARGE LINE
TP-4
TP-3
INSULATE FOR
ACCURATE
READING
TO
ACCUMULATOR
TP-2
A88341
TP-1
FROM COMPRESSOR
DISCHARGE LINE
A88342
42
TXV TYPE
RPB/HSO
RPB/HSO
HSO
HSO
HSO
PRODUCT USAGE
Air Conditioner Indoor Unit
Heat Pump Indoor Unit
Indoor Fan Coil Unit
2-Speed Heat Pump Outdoor Unit
2-Speed Indoor Unit
SUPERHEAT SETTING
10
6
6
4
4
To change accumulator:
43
CAPILLARY TUBE
DIAPHRAGM
BYPASS TXV
PUSHRODS
FEEDER TUBES
INLET
COIL
OUTLET
NEEDLE
VALVE
SPRING
DISTRIBUTOR
BULB
CHECK VALVE
(CLOSED)
BYPASS TUBE
A88406
CAPILLARY TUBE
DIAPHRAGM
BYPASS TXV
PUSHRODS
FEEDER TUBES
INLET
COIL
OUTLET
NEEDLE
VALVE
SPRING
BULB
DISTRIBUTOR
CHECK VALVE
(OPEN)
BYPASS TUBE
A88405
8. Pour and measure oil quantity (if any) from old accumulator.
If more than 20 percent of oil charge is trapped in accumulator, add oil to compressor to make up for this loss.
DEEP-VACUUM METHOD
430 FUSE
ELEMENT
A88410
Fig. 53Accumulator
Step 12Contaminant Removal
TRIPLE-EVACUATION METHOD
The triple-evacuation method can be used where the vacuum pump
is capable of pumping down to only 28 in. of mercury vacuum, and
the system does not contain any liquid water. The procedure is as
follows.
5. Measure indoor-air (entering indoor coil), wet-bulb temperature with a sling psychrometer.
6. Locate outdoor temperature and evaporator entering air wetbulb temperature in Table 22. At this intersection note the
superheat.
45
50
9
7
52
12
10
6
54
14
12
10
7
5
8
12
15
18
21
25
8
11
15
19
22
5
9
13
16
20
6
10
14
18
8
12
15
5
9
13
6
11
72
40
38
36
33
31
28
26
24
22
20
17
15
14
74
42
40
38
36
34
31
30
27
25
23
22
20
18
76
45
43
41
39
37
35
33
31
29
27
26
25
23
Where a dash appears, do not attempt to charge system under these conditions or refrigerant slugging may occur.
46
61.5
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
64.2
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
82.4
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
85.7
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91
Table 24Subcooling at Liquid-Service Valve for Units Produced Through December, 1992
WEATHERMAKER AIR CONDITIONERS
MODEL
SERIES
014
018
024
030
036
038
042
048
060
38TG
0
14
17
13
15
13
13
15
19
1
14
17
13
15
12
13
14
22
38TH
2
14
0
14
14
17
9
16
16
18
18
1
14
14
17
10
16
19
14
18
2
14
14
17
10
16
19
18
18
38TK
3
15
0
6
7
8
6
12
12
14
14
1
6
7
8
6
12
12
14
14
10
5
38TKB
3
13
11
13
11
9
16
11
18
11
38TMA
38TM
38TR
15
16
15
11
15
11
8
12
9
13
11
10
11
10
12
15
11
12
38TD
High
Low
0
0
12
9
12
9
12
9
38YG
0
7
18
18
13
18
13
22
23
1
7
18
18
13
18
11
17
23
2
7
18
18
13
18
11
15
23
38YH
3
14
16
16
20
14
18
19
13
16
16
20
14
18
14
13
38YK
0
11
11
10
10
15
13
14
11
11
10
10
15
13
14
38YKA
38YKB
38YMA
10
13
11
11
12
9
6
10
13
10
15
15
7
5
10
12
12
12
10
47
38YR
0
9
11
9
9
11
10
12
10
11
10
10
12
11
7
38YD
COOLING
HEATING
High
Low
High
Low
0
0
0
0
12
7
18
15
14
9
25
18
14
9
22
21
CUBE UNIT
AIR CONDITIONERS
38CK
0
1
15
16
14
11
12
12
18
16
18
17
17
21
MODEL
SERIES
014
018
024
030
036
042
048
060
CUBE UNIT
HEAT PUMPS
38YC
0
1
11
14
14
8
9
10
11
7
17
12
10
38GN
1
10
12
12
HORIZONTAL
AIR CONDITIONERS
38GNA
38HDA
0
0
17
20
19
17
20
22
18
23
38QRA
0
10
19
18
26
17
17
0
76
79
82
85
88
91
94
97
100
103
106
109
112
115
118
121
124
127
130
133
136
139
142
145
5
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125
128
131
134
137
140
25
51
54
57
60
63
66
69
72
75
78
81
84
87
90
93
96
99
102
105
108
111
114
117
120
4. If there are any discrepancies in the operating cycle, troubleshoot to find the cause, and correct.
2. Clean motor and blade with soft brush or cloth. Be careful not
to disturb balance weights on fan blade.
REFRIGERANT CIRCUIT
1. Check the refrigerant charge using the superheat or subcooling
method, whichever is applicable. If low on charge, check unit
for leaks using an electronic leak detector.
FINAL CHECKOUT
After the unit has been operating, the following items should be
checked:
48
4. Check to be sure all panels and screws are in place and tight.
Special consideration must be given to the installation and maintenance of condensing units and heat pumps installed in seacoast
or desert locations. Salt and the alkali content of the sand adhere
to the aluminum fins of the coil and can cause premature coil
failure due to corrosion.
2. Cleaning coil by flushing out sand from between coil fins and
out of base pan as frequently as inspection determines
necessary.
3. Protecting the unit in off season with cover that allows air to
circulate through but prevents sand from sifting in (such as
canvas material). Do not use plastic as plastic will hold
moisture.
49
AIR CONDITIONER
TROUBLESHOOTING CHART
NO COOLING OR
INSUFFICIENT
COOLING
COMPRESSOR
WILL NOT RUN
COMPRESSOR
RUNS BUT
CYCLES ON
INTERNAL
OVERLOAD
COMPRESSOR
RUNS BUT
INSUFFICIENT
COOLING
CONTACTOR
OPEN
CONTACTOR
CLOSED
OUTDOOR FAN
STOPPED OR
CYCLING ON
OVERLOAD
LOOSE LEAD
AT FAN MOTOR
LOW SUCTION
PRESSURE
HIGH SUCTION
LOW HEAD
PRESSURE
HIGH SUCTION
LOW
SUPERHEAT
POWER SUPPLY
COMPRESSOR
POWER SUPPLY
OPEN
OUTDOOR AIR
RESTRICTED OR
RECIRCULATING
MOTOR
DEFECTIVE
DIRTY AIR
FILTERS
DEFECTIVE
COMPRESSOR
VALVES
UNIT
OVERCHARGED
DEFECTIVE
LOW-VOLTAGE
TRANSFORMER
LOOSE LEADS AT
COMPRESSOR
RESTRICTED
DISCHARGE
TUBE
INCORRECT
OFM
CAPACITOR
DUCT
RESTRICTED
INTERNAL
PRESSURE
RELIEF OPEN
INCORRECT
SIZE
PISTON
OPEN
THERMOSTAT
FAULTY START
GEAR (1-PH)
OVERCHARGE
OR NONCONDENSABLES
IN SYSTEM
DAMPERS
PARTLY CLOSED
OPEN CONTROL
CIRCUIT
OPEN SHORTED
OR GROUNDED
COMPRESSOR
MOTOR
WINDINGS
LOW
REFRIGERANT
CHARGE
INDOOR COIL
FROSTED
LOSS OF
CHARGE
COMPRESSOR
STUCK
LINE VOLTAGE
TOO HIGH OR
LOW
SLIGHTLY
LOW ON
REFRIGERANT
CONTACTOR OR
COIL DEFECTIVE
COMPRESSOR
INTERNAL
PROTECTION
OPEN
DEFECTIVE RUN
CAPACITOR
LIQUID LINE
SLIGHTLY
RESTRICTED
LOOSE
ELECTRICAL
CONNECTION
DEFECTIVE RUN
CAPACITOR
COMPRESSOR
BEARINGS
PISTON
RESTRICTED
HIGH
SUPERHEAT
INCORRECT
SIZE
PISTON
INDOOR COIL
STRAINER
RESTRICTED
INDOOR
BLOWER MOTOR
DEFECTIVE OR
CYCLING ON OL
A90208
50
HEAT PUMP
TROUBLESHOOTINGCOOLING CYCLE
NO COOLING OR
INSUFFICIENT
COOLING
COMPRESSOR
RUNS BUT
CYCLES ON
INTERNAL
OVERLOAD
COMPRESSOR
WILL NOT RUN
COMPRESSOR
RUNS BUT
INSUFFICIENT
COOLING
CONTACTOR
OPEN
CONTACTOR
CLOSED
OUTDOOR FAN
STOPPED OR
CYCLING ON
OVERLOAD
LOOSE LEAD
AT FAN MOTOR
LOW SUCTION
PRESSURE
HIGH SUCTION
LOW HEAD
PRESSURE
HIGH SUCTION
LOW
SUPERHEAT
POWER SUPPLY
COMPRESSOR
POWER SUPPLY
OPEN
OUTDOOR AIR
RESTRICTED OR
RECIRCULATING
DEFROST RELAY
N.C. CONTACTS
OPEN
DIRTY AIR
FILTERS
REVERSING
VALVE HUNG UP
OR INTERNAL
LEAK
UNIT
OVERCHARGED
DEFECTIVE
LOW-VOLTAGE
TRANSFORMER
LOOSE LEADS AT
COMPRESSOR
DAMAGED OR
STUCK
REVERSING
VALVE
MOTOR
DEFECTIVE
DUCT
RESTRICTED
DEFECTIVE
COMPRESSOR
VALVES
INCORRECT
SIZE
PISTON
OPEN
THERMOSTAT
FAULTY START
GEAR (1-PH)
RESTRICTED
DISCHARGE
TUBE
INCORRECT
OFM
CAPACITOR
DAMPERS
PARTLY CLOSED
INTERNAL
PRESSURE
RELIEF OPEN
OPEN CONTROL
CIRCUIT
OPEN SHORTED
OR GROUNDED
COMPRESSOR
MOTOR
WINDINGS
OVERCHARGE
OR NONCONDENSABLES
IN SYSTEM
DEFECTIVE
DEFROST
THERMOSTAT
INDOOR COIL
FROSTED
LOSS OF
CHARGE
COMPRESSOR
STUCK
LOW
REFRIGERANT
CHARGE
SLIGHTLY
LOW ON
REFRIGERANT
CONTACTOR OR
COIL DEFECTIVE
COMPRESSOR
INTERNAL
PROTECTION
OPEN
LINE VOLTAGE
TOO HIGH OR
LOW
LIQUID LINE
SLIGHTLY
RESTRICTED
LOOSE
ELECTRICAL
CONNECTION
DEFECTIVE RUN
CAPACITOR
DEFECTIVE RUN
CAPACITOR
PISTON
RESTRICTED
COMPRESSOR
BEARINGS
INCORRECT
SIZE
PISTON
HIGH
SUPERHEAT
INDOOR COIL
STRAINER
RESTRICTED
INDOOR
BLOWER MOTOR
DEFECTIVE OR
CYCLING ON OL
A90207
51
HEAT PUMP
TROUBLESHOOTINGHEATING CYCLE
NO HEATING OR
INSUFFICIENT
HEATING
COMPRESSOR
RUNS BUT
CYCLES ON
INTERNAL
OVERLOAD
COMPRESSOR
WILL NOT RUN
COMPRESSOR
RUNS
INSUFFICIENT
HEATING
CONTACT
OPEN
CONTACTOR
CLOSED
DIRTY FILTERS
OR INDOOR
COIL
DEFECTIVE LOWVOLTAGE
TRANSFORMER
COMPRESSOR
POWER SUPPLY
INDOOR FAN
STOPPED OR
CYCLING ON
OVERLOAD
DEFECTIVE FAN
MOTOR
CAPACITOR
OUTDOOR FAN
STOPPED
OUTDOOR FAN
RUNNING
OUTDOOR
THERMOSTAT
DEFECTIVE
REMOTE
CONTROL
CENTER
DEFECTIVE
LOOSE LEADS AT
COMPRESSOR
DAMAGED
REVERSING
VALVE
LOOSE LEADS
AT
FAN MOTOR
LOOSE LEADS
AT OUTDOOR
FAN MOTOR
REVERSING
VALVE STUCK
ODT SETTING
TOO LOW
CONTACTOR
COIL OPEN OR
SHORTED
FAULTY START
GEAR (1-PH)
RESTRICTION IN
DISCHARGE LINE
FAN MOTOR
BURNED
OUT
INTERNAL FAN
MOTOR KLIXON
OPEN
RESTRICTED
LIQUID LINE
CAP TUBE
PINCHED OR
BULB NOT
SENSING TRUE
ODT
OPEN INDOOR
THERMOSTAT
COMPRESSOR
STUCK
OVERCHARGE
OR NONCONDENSABLES
IN SYSTEM
FAN MOTOR
BURNED OUT
PISTON
RESTRICTED OR
IS CLOGGED
STRIP HEATER
RELAY OR
CONTACTOR
DEFECTIVE
LIQUID-LINE
PRESSURE
SWITCH OPEN
COMPRESSOR
INTERNAL
OVERLOAD
OPEN
LOW
REFRIGERANT
CHARGE
DEFROST RELAY
N.C. CONTACTS
OPEN ON
CIRCUIT BOARD
UNDERCHARGED
OPENING IN
POWER CIRCUIT
TO HEATER
ELEMENTS
LOSS OF
CHARGE
OPEN SHORTED
OR GROUNDED
COMPRESSOR
WINDINGS
LINE VOLTAGE
TOO HIGH OR
LOW
OUTDOOR COIL
DIRTY
BROKEN FUSE
LINK
OPEN CONTROL
CIRCUIT
DEFECTIVE RUN
CAPACITOR
DEFECTIVE RUN
CAPACITOR
(1-PH)
STRAINER
RESTRICTED
BROKEN
HEATER
ELEMENT
COMPRESSOR
BEARINGS
OUTDOOR COIL
HEAVILY
FROSTED
OPEN (KLIXON)
OVER
TEMPERATURE
THERMOSTAT
DEFECTIVE
ROOM
THERMOSTAT
(2ND STAGE)
STRIP HEATERS
NOT OPERATING
LOW SUCTION
LOW HEAD
HIGH-LOAD
CONDITION
FAN MOTOR
CONTACTS
WELDED CLOSED
IN DEFROST
RELAY
DEFECTIVE
DEFROST
THERMOSTAT
REVERSING
VALVE JAMMED
IN MIDPOSITION
REVERSING
VALVE DID NOT
SHIFT
DEFROST
THERMOSTAT IN
POOR PHYSICAL
CONTACT WITH
TUBE
HIGH
SUPERHEAT
UNIT NOT
PROPERLY
CHARGED
DEFECTIVE
CIRCUIT BOARD
BAD ELECTRICAL
CONNECTION
ANYWHERE IN
DEFROST
CIRCUIT
A90206
3810sm
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
PC 101
Catalog No. 563-732
Printed in U.S.A.
Form 38-10SM
Pg 52
11-00
Replaces: 38-1SM, 38-16XA
Tab 3a 5a 2a 5a