BACnet OPC Server

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

BACnet OPC Server Users Manual

27 Sunnyside Grove
Bentleigh 3204
Australia

Contents
Introduction ............................................................................................................................................ 4
Installation .............................................................................................................................................. 8
System Requirements ......................................................................................................................... 8
Install ................................................................................................................................................... 9
Installed Files..................................................................................................................................... 11
Application Data................................................................................................................................ 12
Uninstall ............................................................................................................................................ 12
Getting Started...................................................................................................................................... 13
Start the BACnet OPC Server ............................................................................................................ 13
Tutorial .............................................................................................................................................. 16
User Interface ....................................................................................................................................... 21
Write Property .................................................................................................................................. 21
Logging .............................................................................................................................................. 22
Configuration ........................................................................................................................................ 23
Edit Ports ........................................................................................................................................... 23
BACnet/IP Port .............................................................................................................................. 24
BACnet Ethernet Port.................................................................................................................... 26
BACnet MSTP Port......................................................................................................................... 27
BACnet PTP Port ............................................................................................................................ 28
Device Settings .................................................................................................................................. 29
OPC Tags ........................................................................................................................................... 30
Automatic Tag Creation ................................................................................................................ 30
Browse BACnet Network............................................................................................................... 31
Tuning Policies .............................................................................................................................. 34
Configure Object Properties ......................................................................................................... 35
Device Groups ............................................................................................................................... 39
Rename OPC Tags ......................................................................................................................... 41
Writing to the Present Value ........................................................................................................ 42
Naming Conventions ..................................................................................................................... 43
Complex Data Types...................................................................................................................... 43

BACnet OPC Server V2.0 Users Manual

Page 2

27 Sunnyside Grove
Bentleigh 3204
Australia

Display ........................................................................................................................................... 44
OPC Alarm and Event (AE) Server ......................................................................................................... 45
Event Categories ............................................................................................................................... 45
Condition Names............................................................................................................................... 45
Sub Condition Names........................................................................................................................ 45
OPC Source field................................................................................................................................ 45
OPC Message field ............................................................................................................................ 45
BACnet Alarm Acknowledgement..................................................................................................... 46
OPC Historical Data Access (HDA) Server ............................................................................................. 47
Edit Trend log .................................................................................................................................... 47
Description of operation ....................................................................................................................... 49
Upgrading from older versions ............................................................................................................. 49
Backout strategy ............................................................................................................................... 50
Trouble Shooting................................................................................................................................... 51
Server does not start......................................................................................................................... 51
Unable to see other BACnet devices ................................................................................................ 51
BACnet Protocol Implementation Conformance Statement ................................................................ 52

BACnet OPC Server V2.0 Users Manual

Page 3

27 Sunnyside Grove
Bentleigh 3204
Australia

Introduction
The SCADA Engine BACnet OPC Server is a server that provides data access (DA), Alarms and Events
(AE), and Historical Data Access (HDA) between OPC clients and BACnet devices.
The Data Access (DA) server enables interchange of Data from a BACnet device to an OPC Client
using the following BACnet services:

Read Property
Read Multiple Properties
Write Property
Write Multiple Properties
Change of Value (COV) Notification

The SCADA Engine BACnet OPC Server supports reading and writing of all BACnet properties. This
makes it possible to configure the On/Off times in a BACnet Time Schedules as well as all other
configurable properties. A device discovery routine automates the creation of OPC Tags based on
the BACnet Devices connected to the network. Configuration data is saved offline in a database file
which can be exported to CSV format. There are no limits to the number of OPC Tags that can be
created in the OPC Server it is restricted by the available memory and CPU of the computer.
The Alarm and Events (AE) server enables interchange of BACnet Alarms from a BACnet device to an
OPC Client using the following services:

Confirmed Event Notification


Unconfirmed Event Notification
Acknowledge Alarm

When a BACnet Alarm is received the AE server translates it into an OPC Alarm using the message
text received from the BACnet Alarm. If an acknowledgement is required then the Alarm can be
acknowledged from an OPC Client.
The Historical Data Access (HDA) server enables interchange of BACnet Trend logs from a BACnet
device to an OPC Client using the following services:

Read Range

OPC Clients can access the (HDA) server using the OPC standard. The trend log data can be stored in
an internal database, or in a Microsoft SQL Server database.

BACnet OPC Server V2.0 Users Manual

Page 4

27 Sunnyside Grove
Bentleigh 3204
Australia

A BACnet system consists of a number of devices that connected to a computer network, typically on
an Ethernet network, but with the aid of routers the devices can be connected on an RS485 network.
Each device has a unique device ID to distinguish it from other devices. The SCADA Engine BACnet
OPC Server connects onto the BACnet network as shown in figure 1.

Figure 1 - BACnet Network

Within each BACnet device information is stored as a collection of objects each with a set of
standard properties. The BACnet specification contains a set of standard objects and properties and
provides the ability to add to this with proprietary objects and properties. There can be multiple
objects of the same type within the same device. The SCADA Engine BACnet OPC Server supports all
standard and proprietary objects and properties. The following is a list of standard BACnet Objects.

Accumulator Object Type


Analog Input Object Type
Analog Output Object Type
Analog Value Object Type
Averaging Object Type
Binary Input Object Type
Binary Output Object Type
Binary Value Object Type

BACnet OPC Server V2.0 Users Manual

Page 5

27 Sunnyside Grove
Bentleigh 3204
Australia

Calendar Object Type


Command Object Type
Device Object Type
Event Enrollment Object Type
File Object Type
Group Object Type
Life Safety Point Object Type
Life Safety Zone Object Type
Loop Object Type
Multi-state Input Object Type
Multi-state Output Object Type
Multi-state Value Object Type
Notification Class Object Type
Program Object Type
Pulse Converter Object Type
Schedule Object Type
Trend Log Object Type

BACnet OPC Server V2.0 Users Manual

Page 6

27 Sunnyside Grove
Bentleigh 3204
Australia

The addressing of BACnet data points is made up of the following items:

Device ID Uniquely identifies the Device on the BACnet network.


Object Type The type of object within the device.
Object Instance The Instance number of the object.
Property ID The property of the object.
Array Index Optional (only available if the data type is an array).

Figure 2 - BACnet Addressing

BACnet OPC Server V2.0 Users Manual

Page 7

27 Sunnyside Grove
Bentleigh 3204
Australia

Installation
This chapter describes how to install the SCADA BACnet OPC Server onto your PC. It is important that
you check the System Requirements section before following the installation section for a step by
step guide to the installation process.

System Requirements
The minimum hardware requirements for the BACnet OPC Server are:

Intel Pentium 4 Processor


512 MB RAM
20 GB hard drive

The SCADA Engine BACnet OPC Server can be used with the following operating systems:

Microsoft Windows XP
Microsoft Windows 2003 Server
Microsoft Windows 2000
Microsoft Windows Vista
Microsoft Windows 2008 Server
Microsoft Windows 7

BACnet OPC Server V2.0 Users Manual

Page 8

27 Sunnyside Grove
Bentleigh 3204
Australia

Install
Log onto the system as Administrator before running the installation program, it cannot be installed
under a limited user account.
1. Place the SCADA Engine BACnet OPC Server CD into the CD drive, or double click on the
BACnetOPCServer_2.1.x.x.exe program.
2. The Windows Installer will start and you should see the following screen.
3. Click the next button.

BACnet OPC Server V2.0 Users Manual

Page 9

27 Sunnyside Grove
Bentleigh 3204
Australia

4. Select the folder location for installation and then click the next button

BACnet OPC Server V2.0 Users Manual

Page 10

27 Sunnyside Grove
Bentleigh 3204
Australia

Installed Files
The program files are installed by default into the C:\Program Files\SCADA Engine\BACnet OPC
Server directory on the hard drive. The table below lists all of the files installed into this location.

25/11/2012
25/11/2012
27/01/2013
10/03/2011
10/03/2011
10/03/2011
10/03/2011
25/11/2012
10/03/2011
29/01/2013
29/01/2013
29/01/2013
29/01/2013
29/01/2013
22/01/2013
29/01/2013
29/01/2013
25/11/2012
26/01/2013
25/11/2012
29/01/2013
10/03/2011
29/01/2013

08:44 AM
761 AddressBindings.csv
08:46 AM
9,167 baclog.txt
10:55 AM
2,527,232 BACnAPI.dll
09:21 AM
1,051,031 BACnet OPC Server.chm
09:21 AM
1,976,933 BACnet OPC Server.pdf
09:21 AM
663 BACnetOPCServer.config
09:21 AM
665 BACnetOPCServerUI.config
08:46 AM
1,916 bacnet_status.log
09:20 AM
666 BACnOpcHdaServer.config
10:55 AM
876,544 BACnOpcHdaServer.exe
10:58 AM
987,136 BACnOPCServer.exe
11:03 AM
2,138,112 BACnOPCServerUI.exe
10:42 AM
737,280 BACnSvrTest.exe
02:22 PM <DIR>
Dongle
05:02 PM
139,776 dpwin32.dll
02:22 PM <DIR>
Language
10:50 AM
1,982,464 log4cxx.dll
08:44 AM
10,198 ObjectOptions.csv
10:11 AM
5,488 OPCTags.csv
08:49 AM
536 scada_engine.lic
02:23 PM
0 test.txt
09:21 AM
440,557 WinPcap_3_0.exe
10:41 AM
311,296 WtOPCSvr.dll

BACnet OPC Server V2.0 Users Manual

Page 11

27 Sunnyside Grove
Bentleigh 3204
Australia

Application Data
Application data is stored onto the hard drive into the C:\Documents and Settings\All
Users\Application Data\SCADA Engine\BACnet OPC Server directory for Windows 2000, 2003 and
XP. It is stored into C:\ProgramData\SCADA Engine\BACnet OPC Server for Vista and Windows 7.
A database file is used to store OPC configuration data and log files are stored in the logging
directories.

Uninstall
To remove the BACnet OPC Server, go to the Control Panel and select Add/Remove programs. Locate
the entry for the BACnet OPC server and remove it.

BACnet OPC Server V2.0 Users Manual

Page 12

27 Sunnyside Grove
Bentleigh 3204
Australia

Getting Started
This section contains a tutorial with a step by step walk through of the automated configuration
process. This tutorial explains what you may need to configure in order to get your BACnet OPC
Server up and running.

Start the BACnet OPC Server


From the Start Menu select SCADA Engine BACnet OPC Server BACnet OPC Server to start the
SCADA BACnet OPC Server. You may see the following dialog box if the BACnet OPC Server service is
not running.

Select yes if you would like the application to start the Service, otherwise go to the control panel and
start the service manually.
On Windows XP you may see the following dialog. You will need to Uncheck the option Protect My
Computer

BACnet OPC Server V2.0 Users Manual

Page 13

27 Sunnyside Grove
Bentleigh 3204
Australia

After the Service has started you will see a registration dialog like the one below to indicate that the
application is running in evaluation mode. If you do not have a registration code and you are
evaluating the software then you will need to visit the website at
http://www.scadaengine.com/evaluation_codes.html to obtain an evaluation code. Otherwise you
can select the Online radio button to download an evaluation code automatically.

BACnet OPC Server V2.0 Users Manual

Page 14

27 Sunnyside Grove
Bentleigh 3204
Australia

If the application starts without error then you should see the following dialog box. There should be
no errors in the message window.

If there were problems starting the SCADA Engine BACnet OPC Server, then you should see some
errors in the message window. The most common error occurs when you are running another
BACnet application on the same PC as the SCADA Engine BACnet OPC Server. When this happens you
may get the following error:

Error in BACnet Server could not start driver - Only one usage of each socket address
(protocol/network address/port) is normally permitted.

This may happen if you are running the Cimetrics BACnet stack, or any other software that uses
BACnet port 47808. In this case you will need to disable the Cimetrics BACnet stack which can be
done from services in the control panel.

BACnet OPC Server V2.0 Users Manual

Page 15

27 Sunnyside Grove
Bentleigh 3204
Australia

Tutorial
Step 1 - Configure Port
From the tools menu select Configure Port. The application will default to BACnet/IP configured on
network 1. You may need to change the network number to suit your site.

Step 2 - Configure Device


From the tools menu section select Configure Device. The application will default to device instance
0 and is the ID of the BACnet OPC server. This should be changed to a new device instance when
used on site. Each device on the BACnet network number needs a unique device instance. The
BACnet installer will give you a device instance to use, in this example we will use instance 200. You
can leave the other options as their default values.

BACnet OPC Server V2.0 Users Manual

Page 16

27 Sunnyside Grove
Bentleigh 3204
Australia

Step 3 - Browse BACnet Network


You are now ready to Browse the BACnet Network and automatically create OPC Tags, from Edit
menu select "Browse BACnet Network" and this will bring up the following dialog box. You can
unselect some of the items if you don't need to perform these functions. Select OK to start scanning
the BACnet network.

The Device Scan Enable item will scan the BACnet network to locate devices if checked and it can
take several minutes on a large network. You may decide to uncheck this item if you need to
perform this function a second time.
If you know the Device ID that you would like to add OPC Tags for, then you can set the High and
Low Limits to correspond to the device. This will reduce the time taken to locate the device.
The Read Device Names checkbox will read the Object Name from each device and it can take
several minutes on a large network. You may decide to uncheck this item if you need to perform this
function a second time.
The Read Object Names checkbox will read the Object Name from each object in the device and it
can take several minutes on a large network. You may decide to uncheck this item if you need to
perform this function a second time.

BACnet OPC Server V2.0 Users Manual

Page 17

27 Sunnyside Grove
Bentleigh 3204
Australia

The Read Engineering Units checkbox will read the Engineering Units from each device and it can
take several minutes on a large network. You may decide to uncheck this item if you need to
perform this function a second time.
If the Add Recipients to all Notification Class Objects checkbox is checked then the OPC Server will
add a recipient corresponding to the BACnet OPC Server to each notification class object on the
network. Each Alarm generating device will then send an alarm or event to the SCADA Engine
BACnet OPC Server. This is required if the AE or HDA operation of the SCADA Engine BACnet OPC
Server is required.
If the Add Trend logs to HDA Server option is checked then a HDA item will be created for each
BACnet Trend log.

BACnet OPC Server V2.0 Users Manual

Page 18

27 Sunnyside Grove
Bentleigh 3204
Australia

The OPC Server will scan all of the devices on the network and read the device names from each
device. This can take several minutes on a large network. Once it has finished a dialog will be
displayed with a list of available BACnet Devices on the Network. You can highlight the devices for
which you want OPC Tags created for. Select OK after your selection has been made.

BACnet OPC Server V2.0 Users Manual

Page 19

27 Sunnyside Grove
Bentleigh 3204
Australia

While the BACnet Server is building the OPC Tag list, you will see the following progress bar which
indicates the status. It starts by reading the Object List from the device and then it builds up a list of
OPC Tags based on the Names of the Objects inside the device. You can Cancel from this operation
at any time and the BACnet Server will add the Objects located up to that point. If you Browse a
second time, the BACnet Server will start from the last object it was reading.

Step 4 - View the Real Time Data


After the OPC Tags have been built, the explorer will be populated with the OPC Tag list. The OPC
Tags are grouped in the same format as the BACnet Network which groups points by Device - Object
Type - Object Name. When you navigate to the list of names, the BACnet OPC server will display real
time data as shown below.

BACnet OPC Server V2.0 Users Manual

Page 20

27 Sunnyside Grove
Bentleigh 3204
Australia

User Interface
The SCADA Engine BACnet OPC Server has an explorer style user interface which displays BACnet
Objects and Trend logs in a tree view and list view. At the top of the tree is the BACnet Network
with device groups underneath this. Device Groups are a way of grouping devices together in a
logical fashion. Under the Device Group are all of the devices within that group, then object types
within a device, object instances and the properties.
When the Object Properties are displayed, a complete list of properties for that object are displayed.
The all property is used to get this information, but some devices do not support this feature.
When this occurs the list of properties will be a list of required properties only.

Write Property
From the user interface, any property can be written to by double clicking on the property in the list
view to bring up the write property dialog as shown below.

The current value is displayed and the new value is displayed beneath this. The write priority is
enabled if the present value property has been selected and is writable. When writing to the present
value property, it can be released by writing the value null
When the value is changed and the OK button is pressed the value will be written to the device using
a BACnet write property request.

BACnet OPC Server V2.0 Users Manual

Page 21

27 Sunnyside Grove
Bentleigh 3204
Australia

Logging
A log file is created in the directory of C:\Documents and Settings\All Users\Application Data\SCADA
Engine\BACnet OPC Server<USER>\Log directory for Windows 2000, 2003 and XP or
C:\ProgramData\SCADA Engine\BACnet OPC Server <USER>\Log for Vista or Windows 7.
The log file is configured to display ERROR and Information messages, but it can also be used to
collect debug information by editing the file C:\Program Files\SCADA Engine\BACnet OPC
Server\BACnetOPCServerUI.config. To change the logging level to debug, replace the line:
<priority value="INFO"/>
With:
<priority value="DEBUG"/>
Similar log files are created for the OPC Server service, and the HDA Server service.

BACnet OPC Server V2.0 Users Manual

Page 22

27 Sunnyside Grove
Bentleigh 3204
Australia

Configuration
This section contains a detailed guide to all of the configuration options available in the SCADA
Engine BACnet OPC Server.

Edit Ports
A port is a connection to the BACnet network and can be one of several different types including
BACnet Ethernet, BACnet/IP, BACnet MSTP and BACnet PTP. Each of these port types can be
considered as a different driver, two BACnet devices that are physically connected to each other
need to be using the same communication type such as BACnet/IP.
BACnet has the ability to combine all of the different communication types on the same network
through the use of routers. Most BACnet sites will have a combination of BACnet/IP devices and
BACnet MSTP devices. The most common configuration for the BACnet OPC server will be using 1
single BACnet/IP port; any BACnet MSTP devices will be accessible through the BACnet routers.
The ports can be configured by selecting the Tools - Configure Port from the menu which will bring
up the following Dialog Box.

Figure 3 - Edit Ports Dialog

Here you will see a list of ports, which normally will contain only 1 entry for BACnet/IP. Each port
needs to be assigned to a unique Network Number that corresponds to the network number used on
site. A network number can be considered to be a physical connection between 1 or more devices,
devices on different networks are accessible only via a router that connects the two networks
together.

BACnet OPC Server V2.0 Users Manual

Page 23

27 Sunnyside Grove
Bentleigh 3204
Australia

To edit a port, double click on the port in the list box, or highlight the port and select Edit. This will
bring up an Edit port Dialog with one of the following types:

BACnet Ethernet
BACnet/IP
BACnet MSTP
BACnet PTP

New ports can be added by select the Add Button.


A Port can be deleted by highlighting the port and selecting the Delete Button.
The List box contains the following columns.

The network name is for descriptive purposes only; you can use the name to give the port a
description.
The network field contains a Number between 1 and 65534 that Uniquely Identifies the
network.
The type field is one of four types:- IP, Ethernet, MSTP or PTP
The details field contains a summary of the port parameters.

BACnet/IP Port
BACnet/IP is the most common connection to the BACnet Network, and in order to connect to the
network you should consult the BACnet Installer to determine which UDP Port is being used and the
Network Number. Be aware that BACnet Ethernet is different to BACnet/IP. Many installers do not
realize that most BACnet devices can be configured to use either BACnet Ethernet or BACnet/IP and
often do not identify which one is being used. BACnet/IP was introduced after BACnet Ethernet and
is often referred to as Anex J. Both protocols operate over an Ethernet connection, however all
devices must be configured to use the same protocol.

BACnet OPC Server V2.0 Users Manual

Page 24

27 Sunnyside Grove
Bentleigh 3204
Australia

BACnet OPC Server V2.0 Users Manual

Page 25

27 Sunnyside Grove
Bentleigh 3204
Australia

The BACnet Port dialog has the following parameters available for configuration.

Name: The network name is for descriptive purposes only; you can use the name to give the
port a description.
Network: The network field contains a Number between 1 and 65534 that Uniquely
Identifies the network.
Port: This identifies the UDP Port used by BACnet, the default value is 47808 (BAC0).
Foreign Device: When this box is ticked, the BACnet OPC Server will act as a foreign device
and can be connected to a BBMD. This option is available if the BACnet OPC Server is not
located on the same IP subnet as the other BACnet devices.
Time To Live: This option is available only when the Foreign Device Tickbox has been
selected. It is used by the BACnet OPC Server when registering as a foreign device.
Address: This option is available only when the Foreign Device Tickbox has been selected.
This is the Address of the BBMD.
Port: This option is available only when the Foreign Device Tickbox has been selected. This is
the port number of the BBMD.

BACnet Ethernet Port


BACnet Ethernet connects directly to the Ethernet network and does not use TCP/UDP, you will need
to ask the BACnet installer for the network number that is being used. Be aware that BACnet
Ethernet is different to BACnet/IP. Many installers do not realize that most BACnet devices can be
configured to use either BACnet Ethernet or BACnet/IP and often do not identify which one is being
used. BACnet/IP was introduced after BACnet Ethernet and is often referred to as Anex J. Both
protocols operate over an Ethernet connection, however all devices must be configured to use the
same protocol.

BACnet OPC Server V2.0 Users Manual

Page 26

27 Sunnyside Grove
Bentleigh 3204
Australia

The BACnet Ethernet dialog has the following parameters available for configuration.

Name: The network name is for descriptive purposes only; you can use the name to give the
port a description.
Network: The network field contains a Number between 1 and 65534 that Uniquely
Identifies the network.
Adapter: A list of Ethernet Adapters identifies which ethernet adapter will be used to
connect to the network.

BACnet MSTP Port


BACnet MSTP is used by most field devices. The field devices are in turn connected to a global
controller which acts as a router from BACnet/IP to MSTP. In most cases it is not necessary to
connect directly to the MSTP network. MSTP operates over RS485 which means an RS485 card
would need to be purchased in order to use this driver. The RS232 port on a PC does not support the
maximum Baud Rate of 76800, an RS485 card normally does support the higher baud rates.

BACnet OPC Server V2.0 Users Manual

Page 27

27 Sunnyside Grove
Bentleigh 3204
Australia

This dialog has the following parameters available for configuration.

Name: The network name is for descriptive purposes only; you can use the name to give the
port a description.
Network: The network field contains a Number between 1 and 65534 that Uniquely
Identifies the network.
Serial: This is the Com Port Number
Baud: This is the Baud Rate
MAC Address: The MAC Address of the port in the range of 0 to 127.
Max Master: The Maximum MAC Address on the Network in the range of 0 to 127, reducing
this figure may result in increased performance..
Max Info Frames: The number of frames to send before passing the token, enables a device
to use more bandwidth.

BACnet PTP Port


BACnet PTP is typically used by remote workstations to dial up into a site via modems. It is the least
reliable of connections and does not give the same performance as other types of connections.

This dialog has the following parameters available for configuration.

Name: The network name is for descriptive purposes only, you can use the name to give the
port a description.
Network: The network field contains a Number between 1 and 65534 that Uniquely
Identifies the network.
Serial: This is the Com Port Number
Baud: This is the Baud Rate

BACnet OPC Server V2.0 Users Manual

Page 28

27 Sunnyside Grove
Bentleigh 3204
Australia

Device Settings
The BACnet OPC Server acts as a BACnet device and requires a unique Device ID. You should consult
the BACnet Installer for a Device ID.
To change the Device Settings, select Tools - Configure Device from the menu and the following
Dialog Box will appear.

The following items in the dialog box can be edited.

Name: The Name Field can be used to change the Object Name in the Device Object of the
BACnet OPC Server.
Instance: This is the Device ID of the BACnet OPC Server, each Device requires a unique
device ID on the BACnet network. The default stting is 0. The accepted range is 0 to
4194303.
APDU Timeout: This is the time the driver will wait for an expected response from the device
before retrying or going on to the next request. The default setting is 500 milliseconds. The
accepted range is 300 to 30000 milliseconds
APDU Segment Timeout: This is the time the driver will wait for an expected response from
the device before retrying or going on to the next request. The default setting is 500
milliseconds. The accepted range is 300 to 30000 milliseconds
APDU Retries: The retry attempts setting determines the number of times the driver will
retry a confirmed request before giving up. The default setting is 3 retries. The accepted
range is 0 to 5.

BACnet OPC Server V2.0 Users Manual

Page 29

27 Sunnyside Grove
Bentleigh 3204
Australia

OPC Tags
This section describes all of the configuration options available for the OPC Tags.
Automatic Tag Creation
The SCADA Engine BACnet OPC Server supports the automatic creation of OPC Tags by using BACnet
Services to discover device IDs and Names.
The Naming convention is configurable and it can be built up from the following fields:

GROUP NAME is used to describe device groups. By default the OPC Server will group
devices based on the network number. The group name can be changed and devices can be
moved from one group to another.
DEVICE ID is the instance number of the device
DEVICE NAME is the name of the device
OBJECT TYPE is the type of object
OBJECT INSTANCE is the instance number of the object
OBJECT NAME is the name of the object.
PROPERTY NAME is the name of the property

For example a complete OPC Tag name might be:


All.Group Name.(0)Device Name.AnalogInput.(0)Object Name.presentValue
To Rename the OPC Tags, select Rename OPC Tags from the edit menu to bring up the following
dialog box.

BACnet OPC Server V2.0 Users Manual

Page 30

27 Sunnyside Grove
Bentleigh 3204
Australia

Browse BACnet Network


From the edit menu select "Edit - Browse BACnet Network" and this will bring up the following
dialog box. You can unselect some of the items if you don't need to perform these functions. Select
OK to start scanning the BACnet network.

The Device Scan Enable item will scan the BACnet network to locate devices if checked and it can
take several minutes on a large network. You may decide to uncheck this item if you need to
perform this function a second time.
If you know the Device ID that you would like to add OPC Tags for, then you can set the High and
Low Limits to correspond to the device. This will reduce the time taken to locate the device.
The Read Device Names checkbox will read the Object Name from each device and it can take
several minutes on a large network. You may decide to uncheck this item if you need to perform this
function a second time.
The Read Object Names checkbox will read the Object Name from each object in the device and it
can take several minutes on a large network. You may decide to uncheck this item if you need to
perform this function a second time.

BACnet OPC Server V2.0 Users Manual

Page 31

27 Sunnyside Grove
Bentleigh 3204
Australia

The Read Engineering Units checkbox will read the Engineering Units from each device and it can
take several minutes on a large network. You may decide to uncheck this item if you need to
perform this function a second time.
If the Add Recipients to all Notification Class Objects checkbox is checked then the OPC Server will
add a recipient corresponding to the BACnet OPC Server to each notification class object on the
network. Each Alarm generating device will then send an alarm or event to the SCADA Engine
BACnet OPC Server. This is required if the AE or HDA operation of the SCADA Engine BACnet OPC
Server is required.
If the Add Trend logs to HDA Server option is checked then a HDA item will be created for each
BACnet Trend log.
The OPC Server will scan all of the devices on the network and read the device names from each
device. This can take several minutes on a large network. Once it has finished a dialog will be
displayed with a list of available BACnet Devices on the Network. You can highlight the devices for
which you want OPC Tags created for.

BACnet OPC Server V2.0 Users Manual

Page 32

27 Sunnyside Grove
Bentleigh 3204
Australia

While the BACnet Server is building the OPC Tag list, you will see the following progress bar which
indicates the status. It starts by reading the Object List from the device and then it builds up a list of
OPC Tags based on the Names of the Objects inside the device. You can Cancel from this operation
at any time and the BACnet Server will add the Objects located up to that point. If you Browse a
second time, the BACnet Server will start from the last object it was reading.

BACnet OPC Server V2.0 Users Manual

Page 33

27 Sunnyside Grove
Bentleigh 3204
Australia

Tuning Policies
The BACnet OPC Server has 4 configurable tuning policies where the scan rate, service type, update
rate and resubscription interval can be selected for each property type. Each device is configured to
use 1 of the tuning policies. The tuning policies can be changed from the menu option Tools
Configure Tuning Policies. This will bring up the following dialog box. From this screen you can select
the tuning policy you wish to edit and then change the Maximum Number of properties to fetch in a
readPropertyMultiple request.

BACnet OPC Server V2.0 Users Manual

Page 34

27 Sunnyside Grove
Bentleigh 3204
Australia

Configure Object Properties


The BACnet OPC Server uses a configurable list of Object Types and Properties when Automatically
Creating the OPC Tag Database. You can use the filter options to define the names of proprietary
objects and properties.
To configure the objects and properties click on the Configure Object Properties button from the
Configure Tuning Policies dialog box to bring up the form below.

For each object type a list of properties will be listed, when a property is highlighted the property
options for that property will be updated.
Service Type
The Service Type can be readPoperty, readPropertyMultiple, ConfirmedCOV or UnconfirmedCOV. If
readProperty or readPropertyMultiple is used then the data is polled using the update interval as the
time between successive polls. If Confirmed or Unconfirmed COV notifications are used then a
subscribeCOV notification is sent and the data is updated when a COV notification is received.
Update Interval

BACnet OPC Server V2.0 Users Manual

Page 35

27 Sunnyside Grove
Bentleigh 3204
Australia

If readProperty or ReadPropertyMultiple services are used then the OPC Server will poll for the data
using the update interval setting as the time between successive requests.
COV Resubscription Interval
The COV resubscription interval is the time between sending another BACnet Subscribe COV service.
This setting is used only when COVs are used to update the value.
OPC Native Data Type
This is the data type to use on the OPC side.
Is Writable
If this option is checked then the OPC Tag will be set to Is Writable.

BACnet OPC Server V2.0 Users Manual

Page 36

27 Sunnyside Grove
Bentleigh 3204
Australia

Configure Properties
This option will bring up a dialog box to allow the properties to be configured for each object type.
Each property has a corresponding enumeration number, the supplier of the BACnet device will be
able to advise which properties and corresponding enumeration number is used on the device.
BACnet supports proprietary properties, and the SCADA Engine BACnet OPC Server allows for
proprietary properties to be added to the list of standard properties for each object type.
Pressing the Configure Properties dialog box will display the following dialog box.

The left hand list box contains a list of available properties, while the right hand list box is a list of
properties for the object. Properties can be added or removed from the object by selecting the
arrow left or arrow right buttons.

BACnet OPC Server V2.0 Users Manual

Page 37

27 Sunnyside Grove
Bentleigh 3204
Australia

The property names can be configured by selecting Configure Property Names to bring up the
following dialog box.

The list box contains a complete list of properties and proprietary properties, which can be extended
by selecting the Add button. To add a proprietary property, the enumeration number and name
must be entered. As shown below.

BACnet OPC Server V2.0 Users Manual

Page 38

27 Sunnyside Grove
Bentleigh 3204
Australia

Device Groups
Device Groups provide a way to group devices into the OPC Tag hierarchy. The Device Group name
can be added to the OPC Tag Name to provide an extra level in the tag hierarchy. This makes it
easier for the engineer to determine the location of the OPC Tag.
This is useful on large sites where there may by many devices. A typical grouping may be for building
1 and building 2. Each building may have 2 devices in it. To make this grouping, right click on the
BACnet Network item of the tree view as shown below.

BACnet OPC Server V2.0 Users Manual

Page 39

27 Sunnyside Grove
Bentleigh 3204
Australia

Select Add Device Group from the popup menu and add the devices that belong to this group as
shown below. Select Ok when done.

BACnet OPC Server V2.0 Users Manual

Page 40

27 Sunnyside Grove
Bentleigh 3204
Australia

Rename OPC Tags


The OPC Tag Names can be renamed to use a configurable naming convention. To do this right click
on the BACnet Network or Device Group for which you want to rename tags for. This will bring
up the Rename Tags dialog as shown below.

Using the Check boxes you can select which items are to be included in the OPC Tag name. Select OK
when done and all of the tags will be renamed to follow the convention you have specified.
This option may be required if you decide to add device groups and regroup the devices.

BACnet OPC Server V2.0 Users Manual

Page 41

27 Sunnyside Grove
Bentleigh 3204
Australia

Writing to the Present Value


BACnet Outputs and Value Objects can be commanded using a write priority between 1 and 16
where 16 is the least significant. If commands have been issued at different priorities then the
command at the lower priority is used to control the present value. The command values are stored
in a property called the priority Array which contains 16 values corresponding to a write at a priority
between 1 and 16.
For example there is an analog output which has not been written to with a write property request
and it has a value under automatic control of 70. A write is made to this object with a value of 50 at
priority 16. Its present value will become 50 and the priority Array at index 16 will have a value of
50, all other values in the priority array will be null. If a second write of 20 is made at priority 10,
then the present value will be set to 20 and the priority array at index 10 will be 20.
The commanded values can be released by writing a NULL at the priority to be released.
To do this with the SCADA Engine BACnet OPC Server, the string NULL must be sent as the write
value.

BACnet OPC Server V2.0 Users Manual

Page 42

27 Sunnyside Grove
Bentleigh 3204
Australia

Naming Conventions
BACnet Arrays
BACnet data may be an array data type and a single element can be referenced from an OPC Client
by adding a colon, property, colon and then the index number after the OPC Tag name as shown
below.
<OPC Tag Name>:<Array Index>
For example to read index 8 from the priority array of OPC Tag All.New Group.(1) Hello.(1)
AnalogOutput.(0) My New Object.(87) priorityArray, the following Tag name would be used:All.New Group.(1) Hello.(1) AnalogOutput.(0) My New Object.(87) priorityArray:8
Write Priority
When writing to the present value object, the default write priority would be used. In some
instances it may be required to write using a different write priority. This can be done by adding a
colon and the write priority to the OPC Tag Name as follows.
<OPC Tag Name>:<Write Priority>
For example to write to the present value using write priority of OPC Tag All.New Group.(1) Hello.(1)
AnalogOutput.(0) My New Object.(85) presentValue, the following Tag name would be used:All.New Group.(1) Hello.(1) AnalogOutput.(0) My New Object.(85) presentValue: 8
Complex Data Types
The SCADA Engine BACnet OPC Server supports reading and writing of complex data points. The
complex data is represented as a string. A complex data type is enclosed by a brace {}, so
the time value data type is represented as {09:00 0.00,9,1} where 09:00 0.00 is the
time and 9,1 is the value where 9 corresponds to an enumerated data type. For this
example the complex data represents On at 9:00 am.
Each array or list element is enclosed by a brace, so {{09:00 0.00,9,1}} is an element
of a list of time values. Each array or list is enclosed by a brace and the items within are
separated by a comma, so the Time Values array is {{{09:00 0.00,9,1}},{{17:00
0.00,9,0}}}} which represents On at 9:00 am Off at 5:00 pm.
The weekly schedule property of a time schedule object is an array of 7 Daily Schedules
with each daily schedule corresponding to a day in the week. A daily schedule is a list of
time values. The entire weekly schedule would be represented as {{{{{{09:00
0.00,9,1}},{{17:00 0.00,9,0}}}}},{{{}}},{{{}}},{{{}}},{{{}}},{{{}}},{{{}}}}

BACnet OPC Server V2.0 Users Manual

Page 43

27 Sunnyside Grove
Bentleigh 3204
Australia

Display
A special data type for display type is available which will format the present value property of
Analog, Binary and Multistate objects into a string.
For analog objects using the resolution property and unit properties are read from the device, the
units are added after the value, while the resolution property is used to format the analog value to
the correct number of digits.
For binary objects, the active and inactive texts are read and then used to display the value.
For multistate objects, the state text property is used to represent the value as a string.

BACnet OPC Server V2.0 Users Manual

Page 44

27 Sunnyside Grove
Bentleigh 3204
Australia

OPC Alarm and Event (AE) Server


The SCADA Engine BACnet OPC Server incorporates an OPC Alarm and Event (AE) Server which will
translate a BACnet Alarm into an OPC Alarm.
In BACnet Alarms are transmitted using the BACnet ConfirmedEventNotification and
UnconfirmedEventNotification services. Each Alarm transmitting device needs to be configured to
send alarms to the SCADA Engine BACnet OPC Server. Once the alarms are received an OPC alarm is
sent to all OPC Clients that have subscribed for alarms. The message text from the BACnet device is
sent to the OPC Client.

Event Categories
The OPC Server has 2 Event Categories for System Alarms and BACnet Alarms. System Alarms are
OPC Simple Events and they transfer system events from the OPC Server. BACnet Alarms are
configured as Conditional Events and are generated by a BACnet Confirmed or Unconfirmed Event
Notification.

Condition Names
The Condition Names correspond to the BACnet Notify Type :

Alarm
Event

Sub Condition Names


The Condition Names correspond to the BACnet Event States :

Normal
Fault
OffNormal
HighLimit
LowLimit
LifeSafetyAlarm

OPC Source field


The OPC Source field is taken from the corresponding OPC Tag in the OPC Server if it exists. If no
corresponding tag is found then the OPC Server will construct a source name using the Device ID,
Object Type and Instance of the BACnet Event.

OPC Message field


The OPC Message field is taken from the message field of the BACnet Alarm, if no message exists
then this field will be empty.

BACnet OPC Server V2.0 Users Manual

Page 45

27 Sunnyside Grove
Bentleigh 3204
Australia

BACnet Alarm Acknowledgement


The OPC Server supports BACnet Alarm Acknowledgement, if an Acknowledgement is required then
the OPC Server will generate an OPC Alarm with the AckRequired flag set to true. When an OPC
Client Acknowledges an Alarm the OPC Server Server will send a BACnet Acknowledge Service to the
BACnet device. When the BACnet device receives the acknowledgement it will generate a BACnet
Event Message with the Notify Type set to Acknowledge. This will generate an OPC Alarm with the
message set to "Alarm Acknowledged".

BACnet OPC Server V2.0 Users Manual

Page 46

27 Sunnyside Grove
Bentleigh 3204
Australia

OPC Historical Data Access (HDA) Server


The SCADA Engine BACnet OPC Server incorporates a HDA Server running as a separate service. The
HDA items are mapped to BACnet Trend log objects and the data is updated using the BACnet Read
Range service. As part of the automatic OPC Tag creation HDA Items will be created from BACnet
Trend log objects.

Edit Trend log


You can edit a BACnet Trend log by right clicking an item on the tree view to bring up the following
dialog.

Tag Name
The Tag name is the name that is displayed from an OPC Client.
Description
The description is the title of the trend log that will appear in an OPC Client
Device ID
This is the BACnet device ID for the BACnet Trend log object.
Instance
This is the BACnet object instance number for the BACnet Trend log object.

BACnet OPC Server V2.0 Users Manual

Page 47

27 Sunnyside Grove
Bentleigh 3204
Australia

Maximum Samples
This is the maximum number of samples that will be held in the offline database of the BACnet OPC
Server.
The Advanced tab has some additional settings for the trend log object as shown by the figure
below.

Engineering Units
The engineering units of the trend log.
Normal Maximum
This is the maximum normal value.
Normal Minimum
This is the Minimum normal value.
Maximum Time Interval
This is the maximum time interval.
Minimum Time Interval
This is the minimum time interval.

BACnet OPC Server V2.0 Users Manual

Page 48

27 Sunnyside Grove
Bentleigh 3204
Australia

Description of operation
During the Device Discovery phase, the BACnet OPC Server performs the following functions.
1.
2.
3.
4.
5.
6.

Send out BACnet whoIs Services to discover each and every BACnet Device on the network.
Read all devices names.
Read the list of objects from every device.
Read all object names
Read all properties from each object type in every device.
Store the object data into the database.

The OPC namespace can be very large on a BACnet System because each property is represented as
an OPC tag. For example a BACnet network with 100 devices each with 100 objects with 10
properties per object will produce an OPC namespace of 100,000 OPC tags.
The BACnet OPC Server does not load the namespace into memory. Data is loaded on demand when
requested by an OPC Client and then unloaded after a client has finished requesting the data. This
helps to reduce the network traffic as well as the resources required by the OPC Server. When no
OPC Clients are connected, the OPC Server will make periodic requests for the status of each device
on the network, otherwise no network traffic occurs. When an OPC Client connects to the BACnet
OPC Server and subscribes to an OPC Tag, the OPC Server will start to collect data for that tag.
The installer should be aware that when more points subscribed by an OPC Client, the network
traffic will increase accordingly.

Upgrading from older versions


Previous versions of the BACnet OPC Server stored each OPC tag name into a CSV file called
OPC_Tags.csv which was loaded into memory each time the OPC Server was started. It is possible to
import the CSV file into the new version of the BACnet OPC Server in order to retain the OPC Tag
names. After importing the CSV file, it is no longer used by the BACnet OPC Server. If the CSV file is
not used, then the names of the OPC tags in the new version will not match the old version and the
OPC Client may need some reengineering.
In order to upgrade from previous versions of the BACnet OPC Server, the configuration files should
first be backed up. The files to backup located are located in the folder C:\Program Files\SCADA
Engine\BACnet OPC Server. All .csv files should be backed up and placed in a new location.
Once all of the files have been backed up, install the new version of the OPC Server onto the PC.
During the installation you will be asked to remove the previous version of the OPC Server.
Start the BACnet OPC Server and then select the file import menu. From this menu you can import
the tables for the following items :-

BACnet OPC Server V2.0 Users Manual

Page 49

27 Sunnyside Grove
Bentleigh 3204
Australia

1. Engineering Units. This csv file is stored in a file called engineering_units.csv and it contains a
list of names for each of the BACnet Engineering Units.
2. Object Types. This csv file is stored in a file called object_types.csv and contains a list of
object type names. Proprietary objects can be given real names by editing this csv file.
3. Property Types. This csv file is stored in a file called property_types.csv and contains a list of
property names. Proprietary properties can be given real names by editing this csv file.

Once these tables have been imported, the OPC_Tags.csv file can be imported. The site will now
contain an OPC Tag Namespace with tag names that correspond to the previous version of the
BACnet OPC Server. It will also contain a full list of all BACnet properties.

Backout strategy
If for any reason the upgrade is not successful, the new version can be uninstalled and the previous
version installed. The OPC_Tags.csv file can be reloaded into the previous version.

BACnet OPC Server V2.0 Users Manual

Page 50

27 Sunnyside Grove
Bentleigh 3204
Australia

Trouble Shooting
Server does not start
The most common error that may occur is that the SCADA Engine BACnet OPC Server cannot start up
because another application is already running. When this happens you will see the following error
message in the Message Window:

Error in BACnet Server could not start driver - Only one usage of each socket address
(protocol/network address/port) is normally permitted.

This may happen if you are running the Cimetrics BACnet stack, or any other software that uses
BACnet port 47808. In this case you will need to disable the Cimetrics BACnet stack which can be
done from services in the control panel, or shut down the other BACnet application.

Unable to see other BACnet devices


Confirm that all devices on the network are using the same protocol type and are connected
correctly to the network.

BACnet OPC Server V2.0 Users Manual

Page 51

27 Sunnyside Grove
Bentleigh 3204
Australia

BACnet Protocol Implementation Conformance Statement


Product
Product

SCADA Engine BACnet Server API


Date Tested:

Model Number

Protocol Revision

Software Version

Firmware Version

SE-BSDKDB-WIN
SE-BSDKDB-LIN

135-2004
Version 1
Revision 4

2.0.20

2.0.20

31 March 2009

Vendor Information
SCADA Engine
27 Sunnyside Grove.
Bentleigh 3204,
Australia
www.scadaengine.com

Product Description

The SCADA Engine BACnet Server API is a software toolset which can be used to build a BACnet Server or
BACnet Operator Workstation.

BACnet Standardized Device Profile


Product

Device Profile

Tested

BACnet Application Specific Controller (B-ASC)


SE-BSDKDB-WIN

BACnet Operator Workstation (B-OWS)


BACnet Application Specific Controller (B-ASC)

SE-BSDKDB-LIN

BACnet Operator Workstation (B-OWS)

BACnet OPC Server V2.0 Users Manual

Page 52

27 Sunnyside Grove
Bentleigh 3204
Australia

Supported BIBBs

Product

SE-BSDKDB-WIN

SE-BSDKDB-LIN

Supported
BIBBs

BIBB Name

DS-RP-A

Data Sharing-ReadProperty-A

DS-RP-B

Data Sharing-ReadProperty-B

DS-RPM-A

Data Sharing-ReadPropertyMultiple-A

DS-RPM-B

Data Sharing-ReadPropertyMultiple-B

DS-WP-A

Data Sharing-WriteProperty-A

DS-WP-B

Data Sharing-WriteProperty-B

DS-WPM-A

Data Sharing-WritePropertyMultiple-A

DS-WPM-B

Data Sharing-WritePropertyMultiple-B

DS-COV-A

Data Sharing-COV-A

DS-COV-B

Data Sharing-COV-B

DS-COVP-A

Data Sharing-COVP-A

DS-COVP-B

Data Sharing-COVP-B

DS-COVU-A

Data Sharing-COV-Unsolicited-A

DS-COVU-B

Data Sharing-COV-Unsolicited-B

SCHED-A

Scheduling-A

SCHED-I-B

Scheduling-Internal-B

SCHED-E-B

Scheduling-External-A

T-VMT-A

Trending-Viewing and Modifying Trends-A

T-VMT-I-B

Trending-Viewing and Modifying Trends-Internal-B

T-VMT-E-B

Trending-Viewing and Modifying Trends-External-B

T-ATR-A

Trending-Automated Trend Retrieval-A

BACnet OPC Server V2.0 Users Manual

Page 53

27 Sunnyside Grove
Bentleigh 3204
Australia

Product

Supported
BIBBs

BIBB Name

T-ATR-B

Trending-Automated Trend Retrieval-B

NM-CE-A

Network Management-Connection Establishment-A

NM-CE-B

Network Management-Connection Establishment-B

AE-N-A

Alarm and Event-Notification-A

AE-N-I-B

Alarm and Event-Notification Internal-B

AE-N-E-B

Alarm and Event-Notification External-B

AE-ACK-A

Alarm and Event-ACK-A

AE-ACK-B

Alarm and Event-ACK-B

AE-ASUM-A

Alarm and Event-Alarm Summary-A

AE-ASUM-B

Alarm and Event-Alarm Summary-B

AE-ESUM-A

Alarm and Event-Enrollment Summary-A

AE-ESUM-B

Alarm and Event-Enrollment Summary-B

AE-INFO-A

Alarm and Event-Information-A

AE-INFO-B

Alarm and Event-Information-B

AE-LS-A

Alarm and Event-LifeSafety-A

AE-LS-B

Alarm and Event-LifeSafety-B

DM-RD-A

Device Management-ReinitializeDevice-A

DM-RD-B

Device Management-ReinitializeDevice-B

DM-DDB-A

Device Management-Dynamic Device Binding-A

DM-DDB-B

Device Management-Dynamic Device Binding-B

DM-DOB-A

Device Management-Dynamic Object Binding-A

BACnet OPC Server V2.0 Users Manual

Page 54

27 Sunnyside Grove
Bentleigh 3204
Australia

Product

Supported
BIBBs

BIBB Name

DM-DOB-B

Device Management-Dynamic Object Binding-B

DM-DCC-A

Device Management-DeviceCommunicationControl-A

DM-DCC-B

Device Management-DeviceCommunicationControl-B

DM-PT-A

Device Management-Private Transfer-A

DM-PT-B

Device Management-Private Transfer-B

DM-TM-A

Device Management-Text Message-A

DM-TM-B

Device Management-Text Message-B

DM-TS-A

Device Management-TimeSynchronization-A

DM-TS-B

Device Management-TimeSynchronization-B

DM-UTC-A

Device Management-UTCTimeSynchronization-A

DM-UTC-B

Device Management-UTCTimeSynchronization-B

DM-LM-A

Device Management-List Manipulation-A

DM-LM-B

Device Management-List Manipulation-B

DM-OCD-A

Device Management-Object Creation and Deletion-A

DM-OCD-B

Device Management- Object Creation and Deletion -B

BACnet OPC Server V2.0 Users Manual

Page 55

27 Sunnyside Grove
Bentleigh 3204
Australia

Standard Object Types Supported


Product

SE-BSDKDB-WIN
SE-BSDKDB-LIN

Object Type

Creatable

Deletable

Analog Input

Yes

Yes

Analog Output

Yes

Yes

Analog Value

Yes

Yes

Binary Input

Yes

Yes

Binary Output

Yes

Yes

Binary Value

Yes

Yes

Calendar

Yes

Yes

Device

No

No

Event Enrollment

Yes

Yes

File

Yes

Yes

Loop

Yes

Yes

Multi-state Value

Yes

Yes

Notification Class

Yes

Yes

Program

Yes

Yes

Schedule

Yes

Yes

Trend Log

Yes

Yes

LifeSafetyPoint

Yes

Yes

LifeSafetyZone

Yes

Yes

Accumulator

Yes

Yes

PulseConverter

Yes

Yes

Tested

Data Link Layer Options


Product

Data Link

BACnet/IP (Annex J)
SE-BSDKDB-WIN
SE-BSDKDB-LIN

Options

Can communicate as a
Direct BACnet/IP device.
Can register as a Foreign
BACnet/IP device.

Ethernet (ISO 8802-3)


MS/TP Master

9600, 19200, 38400, 76800

PTP

Tested

Segmentation Capability
Product

SE-BSDKDB-WIN
SE-BSDKDB-LIN

Segmentation Type

Supported

Window Size
(MS/TP product limited to 1)

Able to transmit segmented messages

Yes

Configurable

Able to receive segmented messages

Yes

Configurable

BACnet OPC Server V2.0 Users Manual

Page 56

Tested

27 Sunnyside Grove
Bentleigh 3204
Australia

Device Address Binding


Product

SE-BSDKDB-WIN
SE-BSDKDB-LIN

Static Binding Supported

Tested

Yes

Networking Options
Product

SE-BSDKDB-WIN
SE-BSDKDB-LIN

Router Option

Router

Options

Tested

Multiple BACnet/IP,
Multiple Ethernet,
Multiple MS/TP
Multiple PTP

Character Sets

Product

Character Sets supported


ANSI X3.4

SE-BSDKDB-WIN

SE-BSDKDB-LIN

IBM Microsoft DBCS


ISO 8859-1

BACnet OPC Server V2.0 Users Manual

Page 57

You might also like