Micrologic

Control units 2.0 and 5.0


Low Voltage Products

User manual

We do more with electricity.


Micrologic
Control units 2.0 and 5.0

Discovering your control unit 2


Identifying your control unit 2
Overview of functions 4
Setting your control unit 6
Setting procedure 6
Setting the Micrologic 2.0 control unit 7
Setting the Micrologic 5.0 control unit 8
Testing the control unit 9
Technical appendix 10
Tripping curves 10
Changing the long-time rating plug 11
Thermal memory 12

1 Micrologic 2.0, 5.0 Schneider Electric


Discovering your Identifying your control unit
control unit Designations

All Compact NS800-3200 and Masterpact Micrologic 2.0: basic protection


NT and NW circuit breakers are equipped

E51352A
E51266B
Micrologic 2.0 t
with a Micrologic control unit that can be
changed on site.
Control units are designed to protect
power circuits and connected loads.

Micrologic 2.0 A 0 Ir Isd I


E51450A

Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm Long time + Instantaneous
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

instantaneous
Isd 4 5
3
2.5 6
2 8

X
1.5 10
x Ir
setting

Y
Micrologic 5.0: selective protection
Z
E51353A

E51354A
Micrologic 5.0 t

X: type of protection
c 2 for basic protection
c 5 for selective protection
c 6 for selective + earth-fault protection
c 7 for selective + earth-leakage protection.

Y: version number
Identification of the control-unit generation. 0 Ir Isd Ii I
"0" signifies the first generation.
Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm Long time + Short time + Instantaneous
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

Z: type of measurement Isd


3
short time

4
5
tsd
(s) .4 .4 .3
Ii
6
instantaneous
8
10
2.5 6 .3 .2 4 12

c A for "ammeter" 2
1.5
x Ir
10
setting
8 .2
on
.1 2 0
I t
delay
.1 3
2
x In
15
off

c P for "power meter"


c H for "harmonic meter"
c no indication = no measurements.

2 Micrologic 2.0, 5.0 Schneider Electric


Presentation

E51355A

E51356A
1 top fastener 1
2 bottom fastener
3 protective cover
4 cover opening point logic
2.0
Micro
5 lead-seal fixture for protective cover
6 long-time rating plug
10
7 screw for long-time rating plug
8 connection with circuit breaker

alarm

time tr 8 12
long
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 6 Ir
.5 1 @
.4 x In

5
6

3
4
2 8
E51357A

Adjustment dials
Micrologic 2.0 Micrologic 5.0

9 long-time current setting Ir


10 long-time tripping delay tr
11 short-time pickup Isd
12 short-time tripping delay tsd
13 instantaneous pick-up Isd
14 instantaneous pick-up Ii

15 LED indicating an overload


16 test connector

15 15
long time long time
Ir

.6
.7
.8
.9
tr
(s) 4
.95 2
8
12
16
alarm
7 Ir

.6
.7
.8
.9
tr
(s) 4
.95 2
8
12
16
alarm
7
9 .5
.4 1
.98 1
.5
20
24
9 .5
.4 1
.98 1
.5
20
24
x In x In at 6 Ir

instantaneous
at 6 Ir
5 instantaneous
5
10 10
short time
Isd Isd tsd Ii
3 4 5 3
4
5 (s) .4 .4 .3 6
8
10
2.5 6 2.5 6 .3 .2 4 12
2 8 2 8 .2 .1 3 15
13 1.5
x Ir
10
11 1.5
x Ir
10
on
.1 2 0
I t off
2
x In
off
setting setting delay

12
16 16
14

3 Micrologic 2.0, 5.0 Schneider Electric


Discovering your Overview of functions
control unit Current protection

Protection settings
Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.

Micrologic 2.0 Micrologic 5.0

E51358A

E51359A
t t
1 1
2
I t on
2
2
I t off
2
3
4
3 5
0 Ir Isd I
0 Ir Isd Ii I

1. current setting Ir 1. current setting Ir (long time)


(long time) 2. tripping delay tr (long time) for 6 x Ir
2. tripping delay tr 3. pick-up Isd (short time)
(long time) for 6 x Ir 4. tripping delay tsd (short time)
3. pick-up Isd 5. pick-up Ii (instantaneous)
(instantaneous)

Long-time protection
The long-time protection function protects cables (phases and neutral) against
overloads. This function is based on true rms measurements.

Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function
of the circuit breaker by taking into account the temperature rise in the cables.
The thermal memory assumes a cable cooling time of approximately 15 minutes.

Long-time current setting Ir and standard tripping delay tr


Micrologic control unit 2.0 and 5.0
current setting Ir = In x …(*) 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug
time delay (s) tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
accuracy 0 to -20% tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
* In: circuit breaker rating
Setting accuracy of the Ir setting may be enhanced by using a different long-time
rating plug.
See the technical appendix "Changing the long-time rating plug".

Overload LED
E51360A

E51361A

long time long time


Ir tr alarm Ir tr alarm
.8 8 .8
.7 .9 (s) 4 12 .7 .9 (s) 4 8 12
.6 .95 2 16 .6 .95 2 16
.5 .98 1 20 .5 .98 1 20
.4 1 .5 24 .4 1 .5 24
x In at 6 Ir x In at 6 Ir

instantaneous short time instantaneous


Isd Isd tsd Ii
3 4 5 3 4 5 (s) .4 .4 .3 6 8 10
2.5 6 2.5 6 .3 .2 4 12
2 8 2 8 .2 .1 3 15
1.5
x Ir
10 1.5 10 .1 2 0 2 off
x Ir on I t off x In
setting setting delay

This LED signals that the long-time current setting Ir


has been overrun.

4 Micrologic 2.0, 5.0 Schneider Electric


Short-time protection
c the short-time protection function protects the distribution system against
impedant short-circuits.
c the short-time tripping delay can be used to ensure discrimination with
a downstream circuit breaker.
c this function carries out true rms measurements.

c the I2t ON and I2t OFF options enhance discrimination with downstream
protection devices.
c use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve;
v I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 Ir. Above 10 Ir, the time curve is constant.

Short-time pick-up Isd and tripping delay tsd


Micrologic control unit 2.0 and 5.0
pick-up accuracy ± 10% Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
time delay (ms) at 10 x Ir settings I2t OFF 0 0.1 0.2 0.3 0.4
I2t ON or I2t OFF I2t ON 0.1 0.2 0.3 0.4
tsd (max resettable time) 20 80 140 230 350
tsd (max break time) 80 140 200 320 500

Instantaneous protection
c the instantaneous-protection function protects the distribution system
against solid short-circuits. Contrary to the short-time protection function,
the tripping delay for instantaneous protection is not adjustable.
The tripping order is sent to the circuit breaker as soon as current exceeds
the set value, with a fixed time delay of 20 milliseconds.
c this function carries out true rms measurements.

Instantaneous pick-up Isd


Micrologic control unit 2.0
pick-up accuracy ± 10 % Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10

Instantaneous pick-up Ii
Micrologic control unit 5.0
pick-up accuracy ± 10 % li = In x … (*) 2 3 4 6 8 10 12 15 OFF

* In: circuit-breaker rating

Protection of the fourth pole on four-pole circuit breakers


Protection of the neutral conductor depends on the distribution system.
There are three possibilities:

Type of neutral Description


Neutral unprotected The distribution system does not require protection
of the neutral conductor.
Neutral protection The cross-sectional area of the neutral conductor is half
at 0.5 In that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to half the setting value
c the short-time pick-up Isd for the neutral is equal
to half the setting value
c the instantaneous pick-up Isd (Micrologic 2.0)
for the neutral is equal to half the setting value
c the instantaneous pick-up Ii (Micrologic 5.0)
for the neutral is equal to the setting value
Neutral protection at In The cross-sectional area of the neutral conductor is equal
to that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to the setting value
c the short-time pick-up Isd for the neutral is equal
to the setting value
c the instantaneous pick-ups Isd and Ii for the neutral
are equal to the setting value

5 Micrologic 2.0, 5.0 Schneider Electric


Setting Setting procedure
your control unit

Selecting the type of neutral protection


On four-pole circuit breakers, it is possible to select the type of neutral protection
using the three-position switch:

E51383A
c neutral unprotected
(4P 3D);
3D+N
/2 c neutral protection
4P 4D at 0.5 In (3D + N/2);
4P 3D c neutral protection
at In (4P 4D).

Setting procedure
Using the adjustment dials
E51363A

E51364A

E51365A
2.0 2.0 2.0
logic logic logic
Micro Micro Micro

1 2 3

Open the protective Select the desired Close the protective


cover. setting. cover and, if necessary,
install a lead seal to
protect the settings.

6 Micrologic 2.0, 5.0 Schneider Electric


Setting the Micrologic 2.0
control unit

The rating of the circuit breaker in this example is 2000 A.

E51366A
1

In = 2000 A
A
2000
In =

See pages 4 and 5 for information


Set the threshold values
on the available settings.
E60365A

E51368A t
long time
alarm
In = 2000 A Ir
Ir .8
.7 .9
.6 .95 Ir = 0.7 x In = 1400 A
.5 .98
.4 1 Isd = 3 x Ir = 4200 A
x In
instantaneous
Isd Isd
3 4 5
2.5 6 0 I
2 8
1.5 10
x Ir
setting

Set the tripping delay


E60366A

E51370A

long time tr = 1 second t


tr alarm
(s)
8
4 12
2 16
1 20
.5 24 tr
at 6 Ir

0 I

7 Micrologic 2.0, 5.0 Schneider Electric


Setting Setting the Micrologic 5.0
your control unit control unit

See pages 4 and 5 for information Set the threshold values


on the available settings.

I2t OFF curve I2t ON curve


E60367A

long time In = 2000 A


Ir alarm

E51372A

E51373A
.8 .9 t t
.7 Ir = 0.7 x In = 1400 A Ir Ir
.6 .95
.5 .98
.4 1
Isd = 2 x Ir = 2800 A
x In
short time instantaneous Ii = 3 x In = 6000 A Isd Isd
Isd 4 5 Ii
3 6 8 10
2.5 6 4 12 Ii Ii
2 8 3 15
1.5 10 2 off 0 I 0 I
x Ir x In
setting

Set the tripping delay


E60368A

long time tr = 1 second I2t OFF curve I2t ON curve


tr alarm
E51375A

E51376A
(s) 8 12 t t
4
2 16
1 20
.5 24 tsd = 0.2 seconds tr tr
at 6 Ir

short time
tsd
(s) .4 .4 .3 tsd tsd
.3 .2 I2t on I2t off
.2 .1
.1 2 0 0 I 0 I
on I t
delay

8 Micrologic 2.0, 5.0 Schneider Electric


Testing the control unit

See the user manual To test the control unit, connect the portable test kit via the test connector
for the portable test kit.

E51363A

E51377A
2.0 2.0
logic logic
Micro Micro

9 Micrologic 2.0, 5.0 Schneider Electric


Technical appendix Tripping curves

Long-time and instantaneous protection - Micrologic 2.0

E60369A
10 000
5 000 Ir = 0.4…1 x In

2 000
1 000
500

200
100 tr = 0.5…24 s
50

20
10
5
t(s)
2
Isd = 1.5…10 x Ir
1
.5

.2
.1
.05

.02
.01
.005

.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir

Long-time, short-time and instantaneous


protection - Micrologic 5.0
E60370A

10 000
5 000 Ir = 0.4…1 x In

2 000
1 000
500 tr = 0.5…24 s

200
100
50

20
10
5
t(s) Isd = 1.5…10 x Ir
2
1
I2t ON
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
0.1 0. 1
.1 I2t OFF
0 0
.05
Ii = 2…15 x In . OFF (1)
.02
.01
.005

.002
.001
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
x Ir x In

10 Micrologic 2.0, 5.0 Schneider Electric


Changing the long-time
rating plug

Select the long-time rating plug


A number of setting ranges for the long-time current setting are available on
Micrologic 2.0 and 5.0 control units by changing the long-time rating plug.
The available rating plugs are listed below:

Part number Setting range for the Ir value


33542 standard 0.4 to 1 x Ir
33543 low setting 0.4 to 0.8 x Ir
33544 high setting 0.8 to 1 x Ir
33545 without long-time protection

Caution.
Change the long-time rating plug
Following any modifications
Proceed in the following manner.
to the long-time rating plug,
all control-unit protection parameters 1. Open the circuit breaker.
must be checked. 2. Open the protective 3. Completely remove the long-
cover of the control unit. time rating plug screw.

E51484A
E51483A

If no long-time rating plug is installed,


the control unit continues to operate
under the following downgraded 4. Snap out the rating plug. 5. Clip in the new rating plug.
conditions:
c the long-time current setting Ir is 0.4,
E51486A
E51485A

whatever the position of the


adjustment dial;
c the long-time tripping delay tr
corresponds to the value indicated
by the adjustment dial.

alarm
alarm
long
time tr 8 12
long
time tr 8 12 (s) 4 16
(s) 4 16 Ir .8 .9
Ir .8 .9 .7 2 20
2 .95
.7 .95 20 1 24
1 .6 .98
.6 .98 24 .5 @ 6 Ir
.5 @ 6 Ir .5 1
.5 1 .4 x In
.4 x In

6. Refit the screw for the 7. Check and/or modify the


long-time rating plug. control-unit settings

11 Micrologic 2.0, 5.0 Schneider Electric


Technical appendix Thermal memory

Thermal memory
The thermal memory is a means to simulate temperature rise and cooling caused
by changes in the flow of current in the conductors.

These changes may be caused by:


c repetitive motor starting;
c loads fluctuating near the protection settings;
c repeated circuit-breaker closing on a fault.

Control units without a thermal memory (contrary to bimetal strip thermal


protection) do not react to the above types of overloads because they do not
last long enough to cause tripping.
However, each overload produces a temperature rise and the cumulative effect
can lead to dangerous overheating.

Control units with a thermal memory record the temperature rise caused
by each overload. Even very short overloads produce a temperature rise
that is stored in the memory.
This information stored in the thermal memory reduces the tripping time.

Micrologic control units and thermal memory


All Micrologic control units are equipped as standard with a thermal memory.

c for all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend on the tripping delay in question:
v if the tripping delay is short, the time constant is low;
v if the tripping delay is long, the time constant is high.

c for long-time protection, following tripping, the cooling curve is simulated


by the control unit. Closing of the circuit breaker prior to the end of the time
constant (approximately 15 minutes) reduces the tripping time indicated
in the tripping curves.

12 Micrologic 2.0, 5.0 Schneider Electric


Schneider Electric Industries SA As standards, specifications and designs develop from time, always ask for confirmation of the
information given in this publication.