1250 1500kva PDF
1250 1500kva PDF
1250 1500kva PDF
Unmatched warranty
- Cummins K50 series diesel engine
generating sets are a truly cost effective solution
to long term power need backed by industry best,
2 years / 5000 hrs warranty, for the entire
generating set.
- With superior experience in
technology, design capability
and commitment reliability and
quality we offer an unmatched
5 years or 5000 hours
(including above 2 years)
warranty coverage on 5
critical components (5C) of the
engine Cylinder Head, Camshaft, Crankshaft,
Cylinder Block, Connecting Rod against
manufacturing defect
Cummins advantage
Special features of Cummins K50 series engines
like STC (Step Timing Controls) injectors, low
temperature aftercooler, square cumbustion
chamber, optimised turbocharging and precision
heavy duty camshaft make these engines the
ultimate in exceptional fuel efficiency all across the
operating range.
Standard scope
Engine: Cummins K50 series direct injection, water cooled
engine, 16 cylinder, 4 stroke, rated at 1500 RPM, conforming to
ISO 3046 / IS 13018 has the following specifications:
- Cummins PT fuel pump
- Cummins heavy duty ESTC injectors
- Holset turbocharger, pulse tuned exhaust manifold,
stainless steel exhaust flexible connections
- Radiator or heat exchanger, coolant inhibitor
- Plate type lube oil cooler
- Outboard aftercoolers
- Full flow paper element filters - fuel, lube oil and by-pass
- Dry type replaceable paper element air cleaner with
restriction indicator
- Flywheel housing & flywheel to suit single/ double bearing
alternator
- Holset flexible coupling for double bearing alternator
- Starting motor Electric, battery charging alternator
- Cummins PowerCommand microprocessor based genset
controller
- First fill lube oil and coolant
Alternator: Stamford brushless alternator
-
Accessories:
-
Optionals
Engine: Heavy duty air cleaner, Lube oil / Coolant heater
with thermostatic switch
Alternator: Double bearing
Control Panel: AMF control panel, Battery charger,
Remote/Auto start panel, Auto/Manual synchronizing panel,
Audio/Visual annunciation for faults
Alternator data
- Line-to-neutral and line-to-line AC volts
- 3-phase AC current
- Frequency
- kW, kvar, power factor kVA (three phase and total)
Engine data
- DC voltage
- Engine speed
- Lube oil pressure
- Coolant temperature/ low level
- Comprehensive FAE data (where applicable)
Other data
- Genset model data
- Start attempts, starts, running hours, kW hours
- Load profile (operating hours at % load in 5% increments)
- Fault history
- Data logging and fault simulation (requires InPower)
Digital governing
- Integrated digital electronic isochronous governor
- Temperature dynamic governing
Technical data
C1250 D5 P
1250
415 Volts, 50 Hz
0.8 (lag)
3 phase
C1500 D5 P
1500
415 Volts, 50 Hz
0.8 (lag)
3 phase
Cummins
KTA 50 G3
16 Vee
Turbocharged-Aftercooled
159 mm x 159 mm
50.3 ltrs
1470 bhp (1097 kWm)
190.8 ltr/hr
251.8 ltr/hr
0.3 ltr/hr
6824 kg
2978 x 2080 x 1780 mm
13.9 : 1
7.95 m/s
Electronic / A1
177 ltrs
440 ltrs
81.6 m 3/min
27357 ltrs/sec
529 oC
Cummins
KTA 50 G8-I
16 Vee
Turbocharged-Aftercooled
159 mm x 159 mm
50.3 ltrs
1735 bhp (1294 kWm)
231 ltr/hr
301.7 ltr/hr
0.35 ltr/hr
7205 kg
2978 x 2080 x 1780 mm
14.9:1
7.95 m/s
Electronic / A1
177 ltrs
510 ltrs
95.5 m3/min
28400 ltrs/sec
481 oC
Stamford
HCK6Z
+ 0.5%
Class H
IP 23
2 / 3 Pitch
Double layer lap
Dynamically balanced
No load < 1.8 %, non distorting
balanced linear load < 5 %
Better than 50
Better than 2%
Stamford
PI734C
+ 0.5%
Class H
IP 23
2 / 3 Pitch
Double layer lap
Dynamically balanced
No load < 1.8 %, non distorting
balanced linear load < 5 %
Better than 50
Better than 2%
Engine specifications
Make
Model
No. of cylinders
Aspiration
Bore x Stroke
Displacement
Output - Prime
Fuel consumption @ 75% load with Radiator & Fan
Fuel consumption @ 100% load
Typical oil consumption @ 100% load
Total wet weight ( engine + radiator)
Length x Width x Height (engine)
Compression Ratio
Piston Speed
Governor / Class
Lubricating oil sytem capacity
Coolant capacity (engine + radiator)
Combustion air intake @ 100% load (+/- 5%)
Fan air flow across radiator
Exhaust Temperature
Alternator specifications
Make
Frame size / Model No.
Voltage Regulation
Insulation
Standard Enclosure
Winding Pitch
Stator Winding
Rotor
Wave form distortion
Telephone Interference Factor
Total Harmonic Factor
Conformance standards
IS/IEC 60034-1, IS 1460, ISO 8528, ISO 3046, IS 13018, ISO 9001
Rating definitions
Prime Power (PRP):
Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten
percent overload capability is available in accordance with ISO 3046, IS 13018
- Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460
- Oil consumption data is based on oil having specific gravity of 0.89 and meeting CH4 API categories
- Fuel consumption tolerance is +5%
Rating
(kVA)
1250 kVA
1500 kVA
Length
(mm)
6165
6090
Width
(mm)
2235
2075
Height
(mm)
2877
2850
Weight
(kgs.) (Dry)
10800
12250
Authorised Representative