Ec5000 1
Ec5000 1
Ec5000 1
VANT
AGE SERIES
ADV
ANTA
Conforms to EC Directive on
Electromagnetic Compatibility
Model EC5000
Speed Controller
Wide Application
Range
Fuel Limiting
Speed Ramping
Features
Both Isochronous and
Droop governing
Smoke reduction at
start/speed ramping
Direct compatibility with
Cummins EFC valve
Remote variable speed
capability
Controls 12 and 24
volt systems
Output short circuit
protected
Reverse polarity
protected
Load sharing capability
Description
The EC5000 operates directly from a battery system, measures the speed of an engine and supplies a
control signal to the actuator which controls engine fuel supply.
The engine speed signal is typically taken from a magnetic sensor mounted in proximity to the flywheel
teeth. The control unit will accept any signal if the frequency is proportional to engine speed and of the correct
amplitude and frequency. This speed input is compared to an internal SPEED setting and the difference is
amplified to drive the actuator to supply more or less fuel, thus controlling engine speed. A safety feature is
provided to turn off the actuator and prevent engine runaway if the speed input signal fails for more than 0.1
seconds. Speed is controlled isochronously or in droop mode (when the DROOP control is moved from its
full CCW position; the further CW, the more droop). Terminal 5 is grounded (to terminal 4) for DROOP
operation or left open for ISOCHRONOUS mode. During cranking, the actuator is commanded to the START
FUEL current setting to eliminate smoke from excess starting fuel. When starting in RUN mode or when
transitioning from IDLE to RUN, a built-in RAMP generator provides a smoothly controlled and adjustable rate
of speed change which also
Performance Specifications
prevents
excess
smoke.
Outputs
Adjustment for GAIN, STABILITY
Actuator output current, continuous
max up to 4.0A (8.0 A2)
and DEAD TIME allow simple field
Actuator output current, peak transient
nom 4.0 A1 (10A2)
optimization for a wide range of
engine/generator or pump
Isochronous/steady state SPEED stability
max 0.25%
combinations.
SPEED drift with temperature
max 1.0%
This unit may be operated with
nom 600 Hz/A1 (250 Hz/A)2
DROOP range3
a remote speed control on the
RAMP time
0-20 sec
FREQ TRIM input and in
conjunction with Synchronizer and
Inputs
a Load Sharing Unit.
Magnetic speed sensor voltage (PICKUP)
min
500 Hz - 4 kHz4,5
typ
-180 Hz/V4,5
Notes
typ
-900 Hz/V4,5
ISO/DROOP
IDLE
typ
60 mA8
Environmental
Temperature range
-40C<T<+65C (-40F<T<+150F)
Humidity
Vibration
Printed in U.S.A.
EG-EC5000
5/99