Introduction
This is the instruction manual for medium voltage direct inverter(HIVECTOL-E), <Part 1> Trouble shooting
guide.
<Part 1> describes how to investigate and repair any troubles. Since quick and appropriate
repairmen is required at a trouble occurrence, the composition of <Part 1> is centered on procedure flow
according to phenomena. Therefore not include operating principle, hardware specifications, etc., for which
please refer to relevant parts given hereunder.
Some trouble repairing works involve human safety items. Before the work, be sure to read through safety
precautions given on subsequent pages.
HIVECTOL-HVI-E
CAUTION
The main circuit voltage of 3000V11000V AC is applied in the panel. Do not get in nor
put any foreign matter in nor get a part of your body, rod or others near the panel when the main
circuit is energized.
In the panel, there are smoothing electrolytic capacitors and, even after turning off the main
circuit, a voltage may remain. Make it a rule to touch the electric circuitry only after checking
yourself whether any potential is present or not. Do the check by the galvanoscope after turning
off the LED display of the cell inverter.
Do not use the spare items other than our recommendation when replacing a part. Operation
when an equivalent function items other than recommendation are used is not guaranteed.
For avoiding electric shock, a protective cover is mounted on the high voltage section.
Do not remove the protective cover while the voltage is applied.
(There is no protective cover about the hanging door type. )
Before turning on, put in place the protective cover if removed for maintenance, etc.
(There is no protective cover about the hanging door type. )
Weight of cell inverter is 28kg. Be careful enough not to fall.
Be sure to use lifter of exclusive use for desertion of cell inverter.
Since it is dangerous, do not perform supporting directly by hands by any means.
HIVECTOL-HVI-E
CONTENTS
1. Outline of trouble shooting
1-1
1-3
1-3
1-4
1-4
1-5
1-7
1-8
1-9
2.8 Others
1-10
1-11
1-12
1-12
1-13
1-14
1-15
1-33
1-33
1-34
1-35
1-36
1-36
1-36
1-36
1-36
1-36
1-36
1-36
1-36
1-37
1-37
HIVECTOL-HVI-E
1-39
1-39
1-41
1-42
1-42
1-46
1-47
1-53
1-56
1-59
1-62
1-62
1-62
1-62
1-63
1-64
1-64
1-65
1-66
1-68
1-68
1-68
1-69
1-69
1-70
1-70
1-71
1-77
1-77
1-78
9.1 Fuse
1-78
1-79
1-80
1-80
HIVECTOL-HVI-E
1-1
HIVECTOL-HVI-E
<Symptom >
<Remedy >
Trouble
occurrence
YES
Major fault?
NO
(Light fault)
YES
System factor?
NO
After reset
1-2
HIVECTOL-HVI-E
Reset switch
Number of factors
Switch for
turn a page
Display of
details of faults
Graphic Panel
Emergency Stop(PBS)
Inverter Panel
Control Panel
Fig.2.1
1-3
HIVECTOL-HVI-E
Number of factors
Switch for
turn a page
Display of
details of faults
1-4
HIVECTOL-HVI-E
Fault message
START FAILURE
CTL POWER DROP
OVERCURRENT(SOFT)
OVERCURRENT(HARD)
OVERVOLTAGE
OVERLOAD
MAIN CIRCUIT POWER DROP
CONNECTOR NOT INSERTED
AC VOLTAGE ABNORMAL
AC CURRENT ABNORMAL
GROUND DETECTED
INV COOLING FAN STOP
TR COOLING FAN STOP TD
Contents
The start failed.
The AVR power supply for the control substrate has decreased.
The current that exceeded the maximum rating of the electric motor flowed.
The current that exceeded the maximum rating of the inverter device flowed.
The voltage of the motor exceeded the over voltage level.
The current that exceeded the rated load flowed to the motor for 1 minute or more.
The input voltage has decreased.
The connector of each PCB has the uninsertion connector.
The voltage detecting circuit did not function correctly.
The current detection circuit did not function correctly.
One phase of either of the three-phase circuit output did earth fault.
When the inverter board cooler fan drove, the inverter device stopped.
The transformer cooling fan stops when the VFD drives, and set time has passed.
CUBICLE OVERHEAT(>60)
TRANSFORMER OVERHEAT
U PHASE CELL FAULT
V PHASE CELL FAULT
W PHASE CELL FAULT
U PHASE SERIAL SIGNAL DOWN
V PHASE SERIAL SIGNAL DOWN
W PHASE SERIAL SIGNAL DOWN
1-5
HIVECTOL-HVI-E
When major faults have occurred, from the first to the third fault factors can chronologically be displayed.
Fault factors are sampled every 60ms and faults produced within 60ms are regarded as occurring
simultaneously. For example, if 2 faults have occurred within first 60ms, both of them are handled as the
first fault factors and if, within next 60ms, 2 faults have further occurred, the 2 constitutes the second fault
factors. The second and the third faults are separated only if they are at least 60ms apart. For example, if
a fault has occurred 1 second after the first fault, the former is handled as the second fault and all faults
which occur at least 60ms thereafter are handled as the third faults.
(See Fig. 2.4.1)
60ms
Trouble
occurrence
60ms
60ms
1sec
Number of factors
Switch for
turn a page
Display of
details of faults
1-6
HIVECTOL-HVI-E
Reset switch
Number of factors
Switch for
turn a page
Display of
details of faults
Fault message
(ALARM)OVERLOAD RUNNING
(ALARM)SPEED REF VALUE ERROR(<2mA)
(ALARM)TR COOLING FAN STOP
Contents
Load of motor exceeds rated one.
The speed command signal(4-20mA) became 2mA or less.
When driving, the transformer panel cooling fan stopped.
(ALARM)CUBICLE OVERHEAT(>55)
(ALARM)TRANSFORMER OVERHEAT
(ALARM)MOTOR OVERHEAT
(ALARM)INV COOLING FAN STOP
(Note 2.5)
It becomes abnormalities when motor primary current integral value(KII4t)exceeds predetermined level.
For example, if motors of 150% 1min are operated at 150% and 30 sec over when detection level is
50%,failure will occur.
1-7
HIVECTOL-HVI-E
Fault code
Contents
0001
0002
0004
0008
0010
0020
0040
1-8
HIVECTOL-HVI-E
Fault message
DC OVERVOLTAGE
CELL CONTROL POWER DOWN
Contents
The DC voltage exceeded the over voltage level.
The input voltage of the DRVIF PCB has decreased.
1-9
HIVECTOL-HVI-E
2.8 Others
When the control circuit PCB is an off-line
mode, Figure 2.8 is displayed.
It is displayed, when control software is nonloading or DIPSW of a control PCB is an offline mode setup.
1-10
HIVECTOL-HVI-E
Signal name
Contents
MAJOR FAULT
EMERGENCY STOP
ALARM
7
8
1-11
HIVECTOL-HVI-E
LED
P48
Control panel
(Door open)
T he contents of display
color
Green
Green
Red
Green
Green
Green
Check terminal
Device
T P1
T P2
T P3
T P4
1-12
Maker use
Maker use
Maker use
Maker use
Contents
HIVECTOL-HVI-E
T he contents of display
color
Green
Red
Red
Green
1-13
HIVECTOL-HVI-E
Danger
Before investigating, checking or replacing the parts, turn off
power and check for presence of potential. Otherwise, there might be
an electric shock.
For any investigation, do not touch the panel interior with main
power ON.
Cell inverter unit has the following weight. When replacing the
unit, use the furnished lifter. Otherwise, you might get injured by tip
over or drop.
Caution
When locating a trouble, get trace-back data first, which contains an important
information for it. To cope with any necessity of replacing parts or circuit PCBs,
prepare required tools beforehand.
Some parts are mounted in locations where working space is hard to secure
and it is necessary to check beforehand whether the work is possible with
available tools or not.
1-14
HIVECTOL-HVI-E
Fault message
START FAILURE
CTL POWER DROP
OVERCURRENT(SOFT)
OVERCURRENT(HARD)
OVERVOLTAGE
OVERLOAD
MAIN CIRCUIT POWER DROP
CONNECTOR NOT INSERTED
AC VOLTAGE ABNORMAL
AC CURRENT ABNORMAL
GROUND DETECTED
INV COOLING FAN STOP
TR COOLING FAN STOP TD
CUBICLE OVERHEAT(>60)
TRANSFORMER OVERHEAT
U PHASE CELL FAULT
V PHASE CELL FAULT
W PHASE CELL FAULT
U PHASE SIRIAL SIGNAL DOWN
V PHASE SIRIAL SIGNAL DOWN
W PHASE SIRIAL SIGNAL DOWN
U PHASE DRVIF FAULT
V PHASE DRVIF FAULT
W PHASE DRVIF FAULT
Contents
Detail factor
The start failed
Note1
The AVR power supply for the control substrate has decreased.
Note2
The current that exceeded the maximum rating of the electric motor flowed.
H1
The current that exceeded the maximum rating of the inverter device flowed.
H1
The voltage of the motor exceeded the over voltage level.
H2
The current that exceeded the rated load flowed to the motor for 1 minute or more.
H3
The input voltage has decreased.
H4
The connector of each PCB has the uninsertion connector.
H5
The voltage detecting circuit did not function correctly.
H6
The current detection circuit did not function correctly.
H7
One phase of either of the three-phase circuit output did earth fault.
H8
When the inverter board cooler fan drove, the inverter device stopped.
H9
The transformer cooling fan stops when the VSD drives, and set time has passed.
H9
H10
The contact at the temperature detection (60) in the cubicle operated.
The winding temperature of a multiple transformer exceeded the trip setting value.
H11
The failure occurred by the U phase cell inverter.
Note3
The failure occurred by the V phase cell inverter.
Note3
The failure occurred by the W phase cell inverter.
Note3
Optical serial communications of U phase detected abnormality (disconnection) .
H12
Optical serial communications of V phase detected abnormality (disconnection) .
H12
Optical serial communications of W phase detected abnormality (disconnection) .
H12
The driver interface substrate of U phase did not function correctly.
H13
The driver interface substrate of V phase did not function correctly.
H13
The driver interface substrate of W phase did not function correctly.
H13
Note 1. Refer to table 4.1.2(Start fault factor).
Note 2. Refer to table 4.2.3(Light fault).
Note 3. Refer to table 4.1.3(Cell inverter Start fault factor).
Fault message
U PHASE SIRIAL SIGNAL DOWN
V PHASE SIRIAL SIGNAL DOWN
W PHASE SIRIAL SIGNAL DOWN
U PHASE CELL NO. SETTING ERROR
V PHASE CELL NO. SETTING ERROR
W PHASE CELL NO. SETTING ERROR
PRECHARGING BUSY
MAIN CIRCUIT BREAKER ABNORMAL
Contents
It was in the state of the optical cable disconnection of U phase.
It was in the state of the optical cable disconnection of V phase.
It was in the state of the optical cable disconnection of W phase.
The U-phase cell number was not set correctly.
The V-phase cell number was not set correctly.
The W-phase cell number was not set correctly.
Optical transmission did not function correctly within a set time.
The circuit breaker was not closed by the close command.
Detail factor
H12
H12
H12
H16
H16
H16
H17
-
Fault message
DC OVERVOLTAGE
CELL CONTROL POWER DOWN
Contents
The DC voltage exceeded the over voltage level.
The input voltage of the DRVIF PCB has decreased.
1-15
Detail factor
H14
H15
HIVECTOL-HVI-E
Fault No.H1
OVERCURRENT(HARD)
OVERCURRENT(SOFT)
GP
display
Display screen
Fault factor display
Detector composition
Over current detection detects output voltage of current detector connected between inverter and motor with
comparator of soft and hard circuit in control PCB as compared with over current level.
HCTU
HVS026
CTL
INV
AI
IM
HCTW
CMP
Soft detection
Major fault stop
Fault display
OC level
Hard detection
CP
DI
HCTU
HCTW
CTL
(3)
(4)
(5)
!
DANGER
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
V/00C00380 1mV
V/00C00094 5%
1-16
HIVECTOL-HVI-E
Fault No.H2
GP
display
Display screen
OVERVOLTAGE(SOFT)
Detector composition
Output over voltage carries out AI of the output voltage FB to control PCB, and compares and detects motor
primary voltage FB and output over voltage level which were calculated by soft circuit.
CTL
HVS026
PTUV
INV
CMP
IM
Major fault
stop
Fault display
PTVW
Detection level
AI
V1
arithmetic
FLT
AI
CTL
FLT
PTUV
PTVW
Control PCB
Filter
Voltage detector UV(PT)
Voltage detector VW(PT)
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-17
HIVECTOL-HVI-E
Fault No.H3
GP
display
Display screen
OVERLOAD
Detector composition
It carries out AI using the inverter AC detected by current detector into control PCB,
overload characteristic is calculated by I4t integral arithmetic of soft circuit, and overload is detected.
HVS026
CTL
t
HCTU
CMP
I4
INV
IM
Overload
detection level
HCTW
Major fault
stop
Fault display
AI
CMP
I1
arithmetic
AI
HCTU
HCTW
CTL
Integral starting
current level
(3)
(4)
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
V/C00120 (1%+100%)
1-18
HIVECTOL-HVI-E
Fault No.H4
GP
display
Display screen
Detector composition
Main circuit power failure is detected by comparator of hard circuit in control PCB in voltage of multiplex
transformer tertiary winding as compared with power failure detection level. Power return is comparing
with Power return detection level at soft circuit.
CTL
HVS026
Main TR
AI
<
CMP
Power return
disregard level
TR for moment
power failure detection
CP
DI
Power failure
level set
CTL
TR
TD
TD
Major fault
stop
Fault display
Control PCB
Transformer
Time Delay
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1%
1mV
1-19
HIVECTOL-HVI-E
Fault No.H5
GP
display
Display screen
Detector composition
It carries out DI of the abnormalities in connector insertion in hard circuit in control PCB, and detects them
by soft circuit.
CTL
HVS026
CN3
CN8
CN9
CN10
CN1
CN12
DI
Major fault
stop
Fault display
CTL
Control PCB
CN3,812
Connector
Main causality of fault
(1) Un-inserting of connector .
(2) Fault of control PCB .
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-20
HIVECTOL-HVI-E
Fault No.H6
GP
display
Display screen
AC VOLTAGE ABNORMAL
Detector composition
It carries out AI of the output voltage FB to control PCB, and it compares output voltage unusual level from
difference of voltage reference and voltage FB, and detects by soft circuit. Detection level is proportional to
voltage directive.
CTL
HVS026
PTUV
INV
CMP
IM
Major fault
stop
Fault display
V*
PTVW
Disregard level
AI
V1
arithmetic
AI
CTL
Control PCB
PTUV Voltage detector UV(PT)
PTVW Voltage detector VW(PT)
Voltage
reference
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
5%
HIVECTOL-HVI-E
Fault No.H7
GP
display
Display screen
AC CURRENT ABNORMAL
Detector composition
It carries out AI of the current FB to control PCB, and current value detects under on abnormal level by soft
circuit as compared with output current abnormal level.
CTL
HCTU
INV
HVS026
CMP
IM
HCTW
Major fault
stop
Fault display
Detection level
AI
I1
arithmetic
AI
<< soft circuit >>
CTL
Control PCB
HCTU U phase current detector
HCTW W phase current detector
Main causality of fault
(1) Open circuit of current FB line, output cable, and motor
(2) Looseness of connector or TB
(3) Fault of current detector
(4) Fault of cell inverter
(5) Incorrect setup of output current abnormal level
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1%
HIVECTOL-HVI-E
Fault No.H8
GP
display
Display screen
GROUND DETECTED
Detector composition
Ground detection carries out AI of the ground voltage to control PCB, and detects it by soft circuit as
compared with ground detection level. Detection level is proportional to speed.
Neutral point
CTL
GDT
HVS026
HVS610
AI
CMP
Major fault
stop
speed
Fault display
detection level
EB
CTL
GDT
IF
FLT
Control PCB
Ground detection PCB
I/F PCB
Filter
FLT
<< hard circuit >>
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-23
0.1V
HIVECTOL-HVI-E
Fault No.H9
GP
display
Display screen
Detector composition
Abnormality in cooling fan are operation of thermal relay for taking care of cooling fan (ceiling fan) of
inverter board, or voltage reduction detection of cooling fan. Therefore, it carries out DI of electromagnetic
contactor for cooling fan motion, and the contact of power source normal detection relay, and detects by
soft circuit.
AC400/440V
FFB*
49F*
88F*
FAN
CTL
HVS026
88F*
52
DI5
NOT
Major fault
stop
Fault display
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-24
HIVECTOL-HVI-E
Fault No.H10
GP
display
Display screen
CUBICLE OVERHEAT
Detector composition
Temperature rise in cubicle carries out DI of the thermo switch (it turns on at 55) installed in inverter
cubicle to control PCB, and detects it by soft circuit.
CTL
26C
HVS026
Major fault
stop
DI6
Fault display
<< soft circuit >>
CTL
26C
Control PCB
Thermo switch for cubicles
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-25
HIVECTOL-HVI-E
Fault No.H11
GP
display
Display screen
TRANSFORMER OVERHEAT
Detector composition
Multiplex transformer superheating carries out DI of the thermo switch installed in transformer board to
control PCB, and detects it by soft circuit.
CTL
TR
HVS026
T1
DI
H1
Fault display
<< soft circuit >>
Major fault
stop
Control PCB
Transformer cubicle
Transformer attached thermometer
Transformer attached thermo switch
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-26
HIVECTOL-HVI-E
Fault No.H12
GP
display
Display screen
Detector composition
When light which is carrying out loop for every four cell inverters (see the 6.4th term for details) intercepts,
it causes abnormalities in transmission. It generated in fault of Optical cable broken and driver interface
PCB, and has detected in soft circuit of control PCB.
CTL
HVS026
DRVIF
HVS750
O/E
DRVIF
DI
52
Major fault stop
Fault display
HVS750
DRVIF
HVS750
Control PCB
Driver Interface PCB
Electricity / optical signal conversion device
Light / electrical signal converter
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-27
HIVECTOL-HVI-E
Fault No.H13
GP
display
Display screen
Detector composition
* When cell inverter breaks down (refer to fault factor table 4.1.2), it has notified * cell inverter fault to
control PCB by intercepting output of optical sign by driver interface PCB. It is carrying out loop of the
optical cable for every four cell inverters (see the 6.4th term for details).
"**" shows serial number of broken cell inverter.
CTL
HVS026
DRVIF
HVS750
O/E
DRVIF
DI
52
Major fault stop
Fault display
HVS750
DRVIF
HVS750
Control PCB
Driver Interface PCB
Electricity / optical signal conversion device
Light / electrical signal converter
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-28
HIVECTOL-HVI-E
Fault No.H14
GP
display
Display screen
DC OVERVOLTAGE
Detector composition
As compared with over voltage detection level, it detects direct current over voltage, and is carrying out DI
of the direct current voltage inputted into driver interface PCB to control PCB.
Cell INV
HVS750
CTL
E/O
O/E
HVS026
DI
52
HFC1
CNV
Voltage
reduction
detection
HFC2
DRVIF
O/E
DRVIF
S/P
E/O
CTL
Control PCB
HFC1,2 High rap Fuse
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
HIVECTOL-HVI-E
Fault No.H15
GP
display
Display screen
Detector composition
Driver power source depression detects voltage reduction of power source for driver PCBs of each cell
inverter within driver interface PCB, and is carrying out DI to control PCB.
Cell INV
HVS750
CTL
E/O
O/E
HVS026
DI
52
HFC1
OV
detection
CNV
HFC2
DRVIF
CTL
DRV
Control PCB
Driver PCB
O/E
HFC1,2
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
HIVECTOL-HVI-E
Fault No.H16
GP
display
Display screen
Detector composition
Abnormalities in DIP switch setting detect condition of DIP switch of driver interface PCB of each cell
inverter by driver interface PCB, and it is carrying out DI to control PCB. As compared with normal setting
condition, it has detected using the DI signal.
CTL
DRVIF
HVS026
52
Major fault stop
Fault display
DIP
Switch
Condition
detection
O/E
E/O
DI
CMP
Set value
<< soft circuit >>
HVS750
CTL
O/E
DRVIF
E/O
Control PCB
Light / electrical signal converter
Driver Interface PCB
Electricity / optical signal conversion device
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-31
HIVECTOL-HVI-E
Fault No.H17
GP
display
Display screen
PRECHARGING BUSY
Detector composition
Initial charge tie up carried out DI (optical transmission) of the voltage establishment by driver interface
PCB from main circuit voltage of each cell inverter during initial charge, and has detected it by soft circuit.
It generates also at the time of DIP switch un-setting of driver interface PCB up.
Cell-INV Unit
CTL
DRVIF
HVS026
HVS750
Under initial charge
CMP
E/O
DI
Major fault
stop
Fault display
Power source
establishment level
CTL
Control PCB
E/O
Electricity / optical signal conversion device
DRVIF Driver interface PCB
Main causality of fault
(1) Initial charge power source blockage
(2) Bad conditions of initial charge circuit
(3) Fault of driver interface PCB ,Un-setting of DIP switch up.
(4) Depression of driver and driver interface power source
(5) Open circuit of optical cable
(6) Fault of cell inverter
Be sure to make sure that the High voltage direct inverter unit is set to the following condition before
starting enquiry.
Make sure that High voltage direct inverter unit is stopped operatingCheck blockage of power
receive breaker.
Make sure that the master circuit DC voltage is0VLED putting out lights in cell inverter
1-32
HIVECTOL-HVI-E
Fault message
(ALARM)OVERLOAD ALARM
(ALARM)SPEED COMMAND ERROR
(ALARM)TRANSFORMER UNIT
No.
1
Fault message
(ALARM) SPEED COMMAND ERROR
No.
1
Fault message
(ALARM)OVERLOAD ALARM
(ALARM) TRANSFORMER
UNIT COOLING FAN STOP
Action
The motor load exceeded the rated load.
Check whether the cooling fan of the transformer unit has stopped. (The serious
failure Transformer Unit Cooling Fan TD will occur within a set time while the
circuit breaker is ON.)
(ALARM) MULTUPLEX TRANSFORMER Check the ambient temperature, operation conditions (overload), filter clogging,
OVERHEAT
cooling fan operation, and DI circuit error. (The serious failure Unit Temperature
Rise will occur when the unit temperature exceeds the preset temperature.
(ALARM)CUBICLE OVERHEAT(>55)
(ALARM)TRANSFORMER OVERHEAT
Action
The motor load exceeded the rated load.
The speed command signal (420 mA) dropped to 2 mA or less.
The cooling fan of the transformer unit stopped during the operation.
The unit temperature detection contact (55 degrees) was activated.
The winding temperature of the multiplex transformer exceeded the alarm set value.
Table 4.2.1.2 Action for minor failure that allows you to continue operation
Action
Check the speed command and set the speed within the set value.
Table 4.2.1.3 Action for minor failure that becomes a serious failure
1-33
HIVECTOL-HVI-E
Enlargement
PUSH
1-34
HIVECTOL-HVI-E
Figure 4.2.3 Installation position of AVR for control source and the control PCB.
1-35
HIVECTOL-HVI-E
1-36
HIVECTOL-HVI-E
NO
Abnormal
Normal
YES
Restart available
1-37
Connector insertion
HIVECTOL-HVI-E
At normal
running
Contents of signal
Hard Suppression
OFF
Remarks
Emergency stop command signal
DI1
DI2
DI3
ON
52 answerback signals
DI4
T ransformer overheat
OFF
DI5
ON
DI6
OFF
DI7
ON
DI8
DI9
DI10
OFF
DI11
DI12
DI13
DI14
DI15
(Note)
ON
According to system, as for DI 1,2, 8, 9, 1114, the contents of signal and condition at the
(Note)
At normal
running
Contents of signal
Inverter heavy fault
ON
DO1
DO2
DO3
DO4
DO5
DO6
DO7
Remarks
Heavy fault accrual sign (turn off by
failure)
According to system, as for DO17, the contents of signal and condition at the time of
HIVECTOL-HVI-E
The initial setting screen (Figure 5.1.1) appears when the M.TOOL for Windows starts.
Connect the serial interface connector (COM1) of PC, and the connector on the display unit
on the surface of a control panel (Fig. 5.1.2) by a RS-232C cable.
* Make connection of PC and a RS-232C cable first at the time of connection.
Select communication device and type name, in the initial setting screen (Figure 5.1.1).
Startup completed
1-39
HIVECTOL-HVI-E
Graphic panel
VSD(VFD)
Control panel
Maintenance tool connector
Acrylic cover
Fig. 5.1.2 Allocation of connecter for communication in display unit of the face of a board
1-40
HIVECTOL-HVI-E
Please select
" 1. Collection of Logging data"
1-41
HIVECTOL-HVI-E
1-42
HIVECTOL-HVI-E
If [1. Normal Data Collection] is selected, the screen for selecting the data to be collected (Figure
5.3.2) appears. Use either the [] or [] key to select the data to be collected, and press the [Enter] key.
The lowest number in the [No.] column on the screen shows the latest failure data.
The State column shows the following information:
[Uncollection]: There is uncollected data in the area.
[Collected]: The data in the area has been collected.
[No data]: There is no data in the area.
The [Logging stop time] column shows the time and date of when a failure occurs.
Press the [R] key. Then, the latest information in the control board will be read and the screen will be
updated.
1-43
HIVECTOL-HVI-E
When you choose the data, the screen moves to Output file name input screen (Figure 5.3.3), on
which you may enter up to Sixty-four half-size (one-byte) characters as the output file name.
If the same file name as you have just entered already exists, a message " The file already exists. Can I
overwrite? [Y/N] " appears on the screen. If you wish to overwrite, push the [Y]. If you change the name
to another, push the [N] and re-enter the file name.
1-44
HIVECTOL-HVI-E
Now you have finished data acquiring. The contents of the acquired data may be displayed by
choosing the menu option [2. Display of Logging data] on the Trace back menu screen.(Figure 5.2.2)
1-45
HIVECTOL-HVI-E
CAUTION
When you choose forced data acquiring, logging stops for about one to three seconds. In case that serious
fault occurs during logging stop, the fault data cannot be stored in the flash memory.
1-46
HIVECTOL-HVI-E
Please select
2.Display of Logging data
1-47
HIVECTOL-HVI-E
When you choose a file, the screen moves to Figure 5.4.3, on which you may use the
[] or [] key, and push the [Enter] key.
Please select
1.Numeric Display
Please select
1.Display
1-48
HIVECTOL-HVI-E
When you choose the menu option [1. Display] on Figure 5.4.4 Selection screen at output point, the
screen moves to Figure 5.4.5 Numeric display data selection screen . Use the [] or [] key to choose an
appropriate menu option, and push the [Enter] key.
If you choose the menu option [1. 0.3ms Cycle Logging], Figure 5.4.6 appears and
if you choose the menu option [2. 30ms Cycle Logging], then Figure 5.4.7 appears.
1-49
HIVECTOL-HVI-E
[space][3]
[Enter]
Select End
10
11
12
Aborts entering numeric key entry, returning the screen to Figure 5.4.5.
[]
[]
[PrtSc]
1-50
HIVECTOL-HVI-E
1-51
HIVECTOL-HVI-E
1-52
HIVECTOL-HVI-E
Please select
2.Display of Logging data
1-53
HIVECTOL-HVI-E
When you finish choosing the file, the screen moves to Figure 5.5.3 Logging data display menu
screen . Use the [] or [] key to choose the menu option [2. Trend display], and push the [Enter] key
Please select
2.Trend Display
1-54
HIVECTOL-HVI-E
To choose a menu option, enter the leftmost number of the output item in two digits. Up to eight items
may be chosen. When you finish choosing an item you wish to output, push the [Enter] key. Choosing an
item and pushing the [Enter] key allow you to move the screen to Figure 5.5.5 Trend display screen .
To exit, push the [ESC] key. (The screen returns to Figure 5.5.3 Logging data display menu screen .)
[Example]
A case that displays the numbers 1, 3, 10, 11, and 12 on Figure 5.5.4.
[space][1]
[space][3]
[Enter]
Select End
10
11
12
1-55
HIVECTOL-HVI-E
Please select
2.Display of Logging data
1-56
HIVECTOL-HVI-E
When you finish choosing the file, the screen moves to Figure 5.6.3 Logging data display menu
screen Use the [] or [] key to choose the menu option [3. Fault Factor Display], and push the [Enter]
key.
Please select
3.Fault Factor Display
HIVECTOL-HVI-E
1-58
HIVECTOL-HVI-E
Please select
2.Display of Logging data
1-59
HIVECTOL-HVI-E
When you finish choosing the file, the screen moves to Figure 5.7.3 Logging data display menu
screen Use the [] or [] key to choose the menu option [4. Cell Inverter Fault Factor Display], and push
the [Enter] key.
Please select
4.Cell INV Fault Factor Display
1-60
HIVECTOL-HVI-E
In the cell inverter fault factor display screen (Fig. 5.7.4), when a cell inverter is chosen using the
[], [], [] or [] key and a [Enter] key is pressed, the fault factor of the corresponding "cell inverter"
will be displayed.
Moreover, the cell inverter which fault generated is displayed as "(fault)" after a name.
In the figure, all cell inverter faults are displayed for explanation.
1-61
HIVECTOL-HVI-E
CAUTION
Before conducting continuity check, be sure to shut off all the power supply
connection between C-E in the state of OFF, the property of this diode
short
Continuity
short
(Be careful not to impress more than voltage DC15V by gate at the time
6.1.1 Property of IGBT
Use 1000V mugger. Since normal value does not exist, judge resistance by comparison
1-62
HIVECTOL-HVI-E
1-63
HIVECTOL-HVI-E
HVS026
GUTA
GURA
GVTA
Gate
signal
HVS750
SIN
V6
HVS750
SIN
U2
V5
HVS750
SIN
SOUT
W6
V2
W5
HVS750
SIN
SOUT
HVS750
SIN
W2
SOUT
V1
HVS750
SIN
SOUT
SOUT
SOUT
U1
HVS750
SIN
HVS750
SIN
loopback
signal
SOUT
SOUT
HVS750
SIN
GWRA
Gate
signal
loopback
signal
SOUT
U5
GWTA
Gate
signal
loopback
signal
U6
GVRA
HVS750
SIN
SOUT
W1
SOUT
1-64
HVS750
SIN
HVS750
SIN
SOUT
HIVECTOL-HVI-E
Transmitting side
GURA
GVRA
GWRA
Receiving side
HVS750
GT
E/O
Optical serial
transmission
: U, V, W (phase is expressed)
: A(Regular)B (Back up)
SOUT
E/O
GR
O/E
SIN
O/E
Optical serial
transmission
Short circuit
pulse detection
Driver power
U-V24V source DC36V Rectifier circuit
detection
DC36
OV detection
OC detection
R phase fuse broken detection
T phase fuse broken detection
DIP switch set point
Cell Inverter
1-65
HIVECTOL-HVI-E
YES
Has "abnormalities in
transmission" occurred?
NO
NO
YES
YES
Fault of control
PCB HVS026
NO
Investigate like following where
it has run out.
Optical cable is
normal.
1-66
HIVECTOL-HVI-E
Remove optical cable and investigate whether leading edge of cable has
shone. Red light is observed when having not disconnected.
1-67
HIVECTOL-HVI-E
Screws(A)
Screws(B)
Fig. 7.1.1 Close-up of inverter board
Optical cable
CAUTION
1-68
HIVECTOL-HVI-E
Cell Inverter
Lifter's plinth
Cell Inverter
Lifter's plinth
Lifter for maintenance
Cell inverter and lifter (for reference)
Fig. 7.3 Drawer of cell inverter (for reference)Note1
Note1 : The cell inverter of the photograph and figure is the references.
CAUTION
1-69
HIVECTOL-HVI-E
Screw
Control PCB
1-70
HIVECTOL-HVI-E
10
11
12
13
14
15
16
DIPS1
HVS026
[Explanation of DIPSW1 ]
1-16 short offline mode
2-15 open online mode
3-14 open Not used
4-13 open Not used
5-12 open Not used
6-11 open Not used
7-10 short maker use
8- 9 short maker use
HIVECTOLE
1-71
HIVECTOL-HVI-E
Please select
" 1. Loading (File to PCB)"
1-72
HIVECTOL-HVI-E
1-73
HIVECTOL-HVI-E
(4) When you finish choosing [Y] or [N] for loading or not loading, respectively,
the file loading is started.
During loading, the following messages are displayed on screen of Fig. 8.2.7 one by one.
0 clearing of the program area. Please wait for a while
(Zero-clearing done)
The file is being loaded. Please wait for a while.
(Loading)
Data is written in flash memory. Please wait for a while.
(Storing done)
Loading the file ended. Please push any key.
By pushing the space key, the screen returns to the menu screen Figure 8.2.5.
(5) Now the loading is finished.
After loading is finished, be sure to check the file by comparison.
Comparison check of MPU1 program
(1) On Figure 8.2.5 File operation menu screen , choose the menu option [2.Compare of File].
(Use the [] or [] key to choose an appropriate menu option, and push the [Enter] key.)
(2) The screen moves to Figure 8.2.8 File selection screen. Choose a file you wish to compare
on this screen.
(Use the [] or [] key to choose an appropriate menu option, and push the [Enter] key.)
1-74
HIVECTOL-HVI-E
1-75
HIVECTOL-HVI-E
(4) When you finish choosing [Y] or [N] for comparing or not comparing, respectively, the file
comparison is started. During comparison, the following messages are displayed on screen of Fig. 8.2.9
one by one.
Files are being compared. Please wait for a while.
(Comparing normally done)
The comparison of files ended. Please press some keys.
When comparison is finished, the screen returns to the menu screen Figure 8.2.5. by pushing the space
key. If the comparison failed, try to reload the program.
(5) Now the comparison is finished.
Confirmation
Confirm that face of a board display unit changes to "operation screen" display (Fig. 8.2.10).
When it does not change to "operation screen" display, please confirm whether LED 1, 3, and 5 of control
PCB (HVS026) is on.
When the light is not switched on, please perform loading again.
1-76
HIVECTOL-HVI-E
offline mode
online mode
Not used
Not used
Not used
Not used
maker used
maker used
DIPS2
1-16
2-15
3-14
4-13
5-12
6-11
7-10
8-9
maker used
maker used
maker used
maker used
maker used
maker used
maker used
maker used
Function
ON:offline
ON:online
OFF:online
OFF:offline
Function
Standard
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
Standard
ON
ON
ON
ON
ON
ON
ON
ON
1-77
HIVECTOL-HVI-E
9.1 Fuse
Fuse is attached in surface bus bar.
Bolt is bound tight by fuse directly. Fig. 9.1 is an example of the exchange method of fuse.
As for the structure of a bus bar, with equipment, a difference does not have measure in an exchange
procedure in things.
(a)
(b) Confirm the voltage of the principal circuit is 0V without fail before working next.
(c)
Remove the bolt for the fixation of the fuse. At this time, when power is added to the bolt too much,
Cell Inverter
Bolts (2/Fuse)
Fuse
CAUTION
HIVECTOL-HVI-E
Open the door of control panel and confirm the position of Fig9.2.
(b) Confirm the voltage of the principal circuit is 0V without fail before working next.
(c)
Inverter panel
PULL
Copper bar
Current detector
1-79
HIVECTOL-HVI-E
Reset
switch
CELL
SELECT
Figure 10.1 LED mounting scheme on the digital readout
Perform fault reset operation according to the following procedures.
A reset lamp is completion of the fault reset by putting out lights.
However, since fault reset is possible also when parts are damaged by major fault, "4. Trouble shooting by
fault factors " Follow, and carry out resumption of operation after removing fault factor.
Reset
switch
CELL
SELECT
1-80