Sel321 Setting PDF
Sel321 Setting PDF
Sel321 Setting PDF
in the
Computer-Aided Protection Engineering System
(CAPE)
Prepared for
CAPE Users Group
Four zones of phase and ground mho elements plus four zones of ground distance
quadrilateral elements, each reversible, with independent phase and ground timers
Voltage elements
Single-phase elements
Weak-infeed logic
Remote-end-just-opened (REJO) logic, using 50A, 50B, 50C and 3P50 IOC elements
Fault Locating
Power-swing blocking and tripping (but the out-of-step elements can be plotted in CAPE
CG)
Internal supervision of phase distance zones 1-4 by the Loss-of-Potential Logic, SinglePole Open Logic, and Out-of-Step Blocking Logic
Zone 1 extension
Switch-Onto-Fault Logic
Rated current
SEL-321-1_5A
SEL-321-1_1A
SEL-321-5_5A
SEL-321-5_1A
5.0 A
1.0 A
5.0 A
1.0 A
The following older STYLES are no longer distributed to new users in the
database cape_starter.gdb.
SEL-321-R100
SEL-321-R101
5.0 A
5.0 A
SEL-321-R101_1A
SEL-321-1-R101
1.0 A
5.0 A
50ABC
32QF
21P
50PP
PHASE
DISTANCE
50L
50G
32Q
21G
GROUND
DISTANCE
50N
TRIPPING LOGIC
OR
PILOT SIGNAL
67N
32Q
INSTANTANEOUS
OVERCURRENT
50Q
67Q
32Q
INSTANTANEOUS
OVERCURRENT
51NP
51N
32Q
GROUND TIME
OVERCURRENT
Z2 = Re
FG V
HI
e jMTA
IJ
K
The MTA is the tap setting Z1ANG. For forward faults, Z2 is usually negative and must be
less than the tap setting Z2F. For reverse faults, Z2 is positive and must be greater than
Z2R. For the optimum MTA, the positive-sequence line angle is a good approximation.
CAPE models these elements as DIST elements. All settings are made from the relay
common taps. You do not have to visit the individual element setting forms. You must set
the common taps as follows:
Z2F
50QF
Z2R
50QR
a2
See [1] for setting rules, or use the CAPE Relay Setting macro sel_321_nseq.
C. Distance Elements
Reach and torque angle settings are made from the relay common taps. You do not have to
visit the individual element setting forms. CAPE does not allow external supervision in the
SEL-321. The DIST elements are already internally supervised and the present code
allows only one supervisor per element.
To set the DIST elements you specify the common taps, which are listed in detail below.
The important settings are:
Enabling taps PMHOZ, GMHOZ and QUADZ (N,1,2,3,4). The default for these is N
(no operation).
A single line angle (MTA) set as Z1ANG degrees for all zones.
Zone reach (secondary ohms). For zone 1, for example, Z1P, Z1MG and XG1 are all
measured from the R-X origin to the MHO circle or QUAD reactance line in the MTA
direction.
Zero-sequence compensation taps (complex k0) for the GROUND DIST elements: k01M,
k01A for zone 1 and k0M, k0A for zones 2, 3 and 4.
Pickup taps for internal overcurrent supervision: 50PP phase and 50L and 50G ground.
Left part of ZLOAD characteristic; operates only for positivesequence current > 0.1 * rated current and for arg(Z1)
between 90 and 270 degrees (inward load)
Right part of ZLOAD characteristic; operates only for positivesequence current > 0.1 * rated current and for arg(Z1)
between -90 and 90 degrees (outward load)
Phase distance zones 1-4 are also supervised internally by the directional element 32QF or
32QR; these constraints are in the program code.
Operation of phase distance zones 1-4 is blocked by operation of either ZLOAD element
when Load-Encroachment Logic is enabled (tap ELE = Y). This constraint is in the
program code.
Ground distance zones 1-4 are also supervised internally by the directional element 32QF
or 32QR; these constraints are in the program code.
For DIST elements, you may set the Desired Primary Ohms and angle (degrees) for
informational purposes only.
D. Instantaneous Overcurrent
To set the IOC elements you specify the pickups, torque control and timer settings as
common taps. Also set the Enabling taps E50N and E50Q (N,1,2,3,4).
The following supervise the distance zones:
IOC 50PP1
IOC 50PP2
IOC 50PP3
IOC 50PP4
IOC 50L1
IOC 50L2
IOC 50L3
IOC 50L4
IOC 50G1
IOC 50G2
IOC 50G3
IOC 50G4
IOC 50Q1
IOC 50Q2
IOC 50Q3
IOC 50Q4
IOC 67N1
IOC 67N2
IOC 67N3
IOC 67N4
IOC 67Q1
IOC 67Q2
IOC 67Q3
IOC 67Q4
6
Additional elements:
IOC 50H
IOC 50M
IOC 50ABC
U1:
U2:
U3:
U4:
Moderately Inverse
Inverse
Very Inverse
Extremely Inverse
US_MOD_INVERSE_501
U.S. Inverse
U.S. Very Inverse
U.S. Extrem. Inverse
U1
U2
U3
U4
C1:
C2:
C3:
C4:
Standard Inverse
Very Inverse
Extremely Inverse
Long Time Backup
IEC_A_STANDARD_INV
IEC_B_VERY_INVERSE
IEC_C_EXTREM_INVERSE
IEC_LONG_TIME_INV
C1
C2
C3
C4
CAPE uses a fixed dropout time of 1 cycle; the reset equation is not implemented.
The time-dial Common Tap ranges are 0.01 - 15 with step 0.01 for all STYLES, to cover the
ranges of both US curves (0.5 to 15) and IEC curves (0.01 to 1.0).
Phase TOC elements may be blocked by one of the forward or reverse load-encroachment
elements (ZLOUT or ZLIN), or may be supervised by the Zone 2 element M2P. These
options are included in the library model.
The three timers TX, TY and TZ are stored as AUX elements; CAPE automtically sets their
pickup and dropout times from the common taps.
Other timers are provided for record-keeping only. It is unlikely that they will be included
in the LZOP trip path.
H. Voltage Elements
27L
3P27
3P59
59L
Phase undervoltage
Three-phase undervoltage
Three-phase overvoltage
Phase overvoltage
59N
Zero-sequence overvoltage
(3V0)
Pickup_Time_Tap_Name
Dropout_Time_Tap_Name
TX
TY
TZ
TXPU
TYPU
TZPU
TXDO
TYDO
TZDO
V2
Z2 =
exp (-j MTA)
I2
The MTA is the tap setting Z1ANG. For forward faults, Z2 is usually negative and must be
less than the tap setting Z2F. For reverse faults, Z2 is positive and must be greater than
Z2R. For the optimum MTA, the line angle Z1ANG is a good approximation.
Abs(I2/I1) must exceed the setting a2, and abs (3*I2) must exceed the pickup 50QF
(forward) or 50RF (reverse).
B. Supervision of Distance Zones
The phase A ground elements will operate only if
abs(Ia) > pickup 50L for the zone
and
abs(3 * I0 > pickup 50G for the zone
Each ground distance element is supervised by the negative-sequence directional element,
directly in the program code.
The B-C phase (MHO) element will operate only if
abs(Ib-Ic) > pickup 50AB for the zone.
If fewer than three DIST phase loops operate, the phase element is also supervised by the
negative-sequence directional element, directly in the program code. If all three phase
loops operate, the phase element operation is restricted by the ZLOAD limit as in [1].
C. MHO and QUAD Elements
All three phase-phase or phase-ground loops are evaluated; the element asserts if any one
phase asserts.
In the phase distance elements, a memory-polarized mho comparator evaluates the three
phase-phase loops A-B, B-C and C-A. The zone will operate if any one of the three
loops operates according to the following equation (shown for loop A-B):
10
< Z REACH
VAB and IAB are the voltage and current in the loop. The MEM subscript denotes memory
(prefault) voltage in the loop. MTA is the tap setting Z1ANG. ZREACH is the reach of the zone
being evaluated (the circle diameter and the magnitude in the MTA direction).
The other two loops are evaluated similarly. The Operating CT Quantity and Operating VT
Quantity are set internally in the code as Three Phase (A or B or C).
For the ground distance elements, both the MHO element and the reactance portion of the
quadrilateral element compare the reach with its tap setting (e.g. Z1P, Z1MG, X1G) at the
line angle Z1ANG, not at 90 degrees. The quadrilateral element sees fault resistance up to
the tap setting (e.g. RG1) for a radial line. For a non-radial line, the remote-end infeed
reduces the resistive reach.
The ground distance comparator equations are quoted below from reference [2] for mho,
reactance, and resistance boundaries. The negative-sequence directional element
determines the boundary behind the relay.
Excerpt from [2] showing ground mho comparator equations for SEL-321 distance elements.
k0 is the zero-sequence compensation setting (Z0L/Z1L 1)/3 for the protected line. Ir = 3 I0
= residual current into the protected line.
11
Excerpt from [2] showing ground quad comparator equations for SEL-321 distance
elements.
The "S-bus" is the local bus at the relay. k0 and T are relay settings.
12
The ground quadrilateral element is bounded at the top by the reactance line. The tilt
angle T is set nonzero for a nonhomogeneous system (where the zero-sequence source
impedance angles at the line ends are different from the line angle). T should be estimated
for a single-line-ground fault as:
T = arg(fault current from line to ground) - arg (zero-sequence current from relay to fault).
T is a function of fault location and the network impedances. It is independent of load. If T
is set exactly, the reach is independent of load. If T varies along the line, T should be set at
its value for a fault on the line-end bus, negative or zero but not positive. A negative value
of T tilts the reactance line down to the right. Then any error in T causes underreach rather
than overreach, increasing security.
When you apply a fault and plot it in Coordination Graphics, the apparent impedance that
is reported and displayed (for the ground distance element) depends on the type of unit that
is enabled in the relay.
If both the MHO and QUAD units are enabled, then, the apparent impedance is the
ground-current compensated value given by
ZAPP =
VA
IA + 3I0 K 0
The above value is shown and reported irrespective of which of the two units operated.
If the QUAD unit is the only one enabled, the apparent impedance is not a single
calculation. It is made up of two parts: (a) the calculation of the reactance according to
equation 18 above (excerpt from [2]), and (b) the calculation of the fault resistance RF
according to equation 20 above (excerpt from [2]).
It is important to note that equation 18 is not a true reactance measurement, but
measurement along the angle Z1ANG. Also, RF is the estimate of the fault resistance
component, and does not include the resistance of the protected line to the point of fault.
Therefore, the calculated apparent impedance must be manipulated a little bit before it can
be plotted in CG, and reported.
D. Fault Identification Selection (FIDS) Logic [3]
This identifies the faulted phases in ground faults. If the ground current (3I0) is greater
than 0.1 * rated current, the phase and ground distance elements are blocked for selected
phases. Otherwise, any phase can cause tripping.
Let I0 and Ia2 be the relay zero-sequence and negative-sequence currents (the phase A
sequence components).
13
Let arg (Ia2/I0) = S, when both 3*Ia2 and 3*I0 magnitudes exceed 0.1 * rated current.
If -30 <= S <= 30 degrees, the fault is A-G or B-C-G and is measured by elements A-G and
B-C only. The remaining elements are blocked.
If -30 <= arg (Ib2/I0) <= 30 degrees, the fault is B-G or C-A-G and is measured by elements
B-G and C-A only. Here Ib2 is the phase B component of negative sequence current:
14
TOC 51N
Neutral
TOC 51P
TOC 51Q
Three-phase
Negative-Sequence (3*INR)
For DIST elements the Contact Logic Code is usually blank except for Zone 1. Suggested
values for Zone 1 Contact Logic are:
DIST M1P
DIST Z1G
M1P
Z1G
If you want to use the elements 50PP, 50L, or 50G in your trip logic, you can define the
following intermediate contact logic codes in the Contact Logic Data.
50PP = 50PP1 or 50PP2 or 50PP3 or 50PP4
50L = 50L1 or 50L2 or 50L3 or 50L4
50G = 50G1 or 50G2 or 50G3 or 50G4
Example of Contact Logic Data:
SEL321_TRIP
SEL321_TOC
SEL321_DIST
SEL321_Z1
SEL321_T2
SEL321_T3
SEL321_T4
(DIST OR TOC)
(51P OR 51Q OR 51N)
(SEL321_Z1 OR SEL321_T2 OR SEL321_T3 OR SEL321_T4)
(M1P OR Z1G)
(Z2PD OR Z2GD)
(Z3PD OR Z3GD)
(Z4PD OR Z4GD)
15
Line Settings
Z1MAG
Z1ANG
Z0MAG
Z0ANG
LL
CTR
PTR
Enable Zones of Distance Settings (N = none, 1 = zone 1 only; 2= zones 1 and 2, etc.)
PMHOZ
GMHOZ
QUADZ
XG3
XG4
RG1
RG2
RG3
RG4
50G1
50G2
50G3
50G4
k0M
k0A
Load Encroachment
ELE
ZLF
ZLR
PLAF
NLAF
PLAR
NLAR
18
Voltage Element
EVOLT
59N
27L
59L
59PB
59PBD
59PR
59PRD
a1
References
1. SEL-321, SEL-321-1, and SEL 321-2 Phase and Ground Distance Relay, Directional
Overcurrent Relay, and Fault Locator Instruction Manual, Schweitzer Engineering
Laboratories, Inc., Pullman WA; November 20, 1996.
2. S. E. Zocholl, Three-Phase Circuit Analysis and the Mysterious k0 Factor, 22nd
Annual Western Protective Relay Conference, Spokane, Washington; October 1995.
3. E. O. Schweitzer III and Jeff Roberts, Distance Relay Element Design, 46th Annual
Conference for Protective Relay Engineers, Texas A & M University, College Station,
Texas; April 12-14, 1993.
20