Instruction Sheet: Series Valve Temperature Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

VARITEL INGENIERIA ELECTRONICA S.A.

Series Valve Temperature Controller

Instruction Sheet
Thanks you very much for choosing Delta DTV series valve temperature controller. Please read this instruction sheet before using your DTV to ensure proper
operation. Keep this instruction handy for quick reference.

Warning
DANGER! CAUTION! ELECTRIC SHOCK! When the power is on, DO NOT touch the AC terminals in case an electric shock may occur. Make sure
the power is disconnected when you check the input power.
DTV is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments when used in a dangerous environment,
please make sure it is installed in an automatic safety protection device.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be sure to tighten them properly and
make sure the wire is connected to the correct terminal.
2. Prevent dust or metallic debris from falling into the device and cause malfunction. DO NOT modify or uninstall DTV series without being permitted. DO
NOT use empty terminals.
3. Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using DTV in premises which contain:
(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration
4. The power has to be switched off when wiring or changing temperature sensor.
5. Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple wire.
6. Use wires with resistance when extending or connecting the platinum resistance sensor.
7. Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load wire in order to prevent
interference and induced noise.
8. DTV is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an electric shock.
9. Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious damage may occur.
10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur.
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge. DO NOT touch the internal wiring within this period.
12. DO use dry cloth and DONOT use acid or alkaline liquid to clean the device.

Display, LED & Pushbuttons


PV: Present value
SV: Set value
%: Output percentage
AT: Auto-tuning indicator
A/M: Manual control indicator
OUT1/OUT2: Output indicator
ALM1/ALM2: Alarm output indicator
Manual/auto mode switch key
Selection/setup key

Ordering information

DTV 1
Series name

1 2 3 4
Panel size
(W H)

2 3 4 5

DTV: Delta V series valve temperature controller


4896: 1/8 DIN W48 H96 mm
9696: 1/4 DIN W96 H96 mm
R: Valve, relay output SPST (250VAC, 5A)

Switching page key


Left-shifting the digit

Specifications
Power input
Input power range
Power consumption
Display
Input temperature sensor
Control method
Control output type
Display scale
Sampling cycle
Vibration resistance
Shock resistance
Ambient temperature
Storage temperature
Operation altitude
Ambient humidity

AC100 ~ 240V, 50/60Hz


85% ~ 110%, rated voltage
Less than 5VA
2-line, 7-segment LED, 4bits and 2 bits of valve openness display
PV in red, SV and valve openness in green.
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Platinum resistance: Pt100, JPt100
Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mA
PID, PID programmable control, manual, On/Off
Relay output: SPST, Max. load 250V, 5A resistive load
1 digit after the decimal point, or no decimal point
Analog input: 0.15 sec; thermocouple/platinum resistance: 0.4 sec
10 ~ 55Hz 10m/s2 3 axes 10 min.
Max. 300m/s2 3 axes 6 directions, 3 times each
0C ~ +50C
-20C ~ +65C
Less than 2,000m
35% ~ 80% RH (non-condensing)

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.

Setting up Parameters

Switching Modes: DTV is in the operation mode when the power is switched on, displaying PV and SV. Press
initial setting mode. Press
for less than 3 seconds in the operation mode to enter the regulation mode. Press
mode to return to the operation mode.
Selecting parameters: In the operation, regulation or initial setting mode, press

to select parameters for setup.


to modify the settings. Press

Setting up number parameters: Find the parameters to be set up or modified. Use


be modified and the digit will flash. Press
to complete and save the setting.
Setting up non-number parameters: Find the parameter to be set up or modified and use
to complete and save the setting.
Press

Regulation
Mode

Press

for less than 3 secs

Operation
Mode

Press

Use

for more than 3 secs

PD control offset

Press

Heating hysteresis setting


(Set up when in On/Off control)
Press

Cooling hysteresis setting


(Set up when in On/Off control)

Press

Set up input type


Press

Press

Start setting up patterns


(Set up when in PID programmable control mode)
Press

Upper limit for the temperature range

Set up the position of decimal point


(Not for thermocouple B, R, S type)
Press

Lower limit for the temperature range

Press

Press

Press

Select control mode


(Enter step editing when PID programmable control
is selected. See the next table)
Press

Press

Press

Press

Press

Set up alarm mode 1


Press

Set up alarm mode 2

Press

Key-locked mode

Set up system alarm


Press

Enable/disable communication write-in

Press

Upper limit adjusting with feedback


Output percentage of valve feedback
output
(Displayed when there is valve feedback)
(Displayed when in valve feedback mode)
Press
Press

Select ASCII/RTU communication format

Lower limit adjusting with feedback


D/A value of valve feedback
output
(Displayed when there is valve feedback)
(Displayed when in valve feedback mode)
Press

Press
Back to top

Press

Set up communication address

Press

Press

Press

Set up baud rate

Adjusting PV offset
Press

Upper limit for control output


Press

Set up data length

Lower limit for control output


Press

Press

Displaying and adjusting output percentage


(Displayed when in PID mode and manual RUN)
Press

Valve DeadBand Setting

Select heating or cooling

open

Press

Lower limit for alarm 2


(Adjustable when ALA2 is enabled)

Upper limit for alarm 1


(Adjustable when ALA1 is enabled)

Time from valve fully closed to fully

Press
Set up temperature unit
(Not displayed when in analog input mode)

Press

Upper limit for alarm 2


Switch for valve feedback setting
(Adjustable when ALA2 is enabled)
Press

Press

Control loop RUN/STOP

Heating/cooling control cycle


Lower limit for alarm 1
(Adjustable when ALA1 is enabled)
Press

Auto adjusting feedback value


(Displayed when in valve feedback mode
and STOP)
Press

Initial Setting
Mode
Initial Setting Mode

to set up SV

Select the PID group (0 ~ 4)


(4 groups of PID are available in PID control.
n = 4: PID is auto-selected. See the next
table.)
Press

to modify the setting. The parameter will flash at this time.

Operation Mode

Auto-tuning
(Set up when in PID control and RUN)
Press

to move to the desired digit to

Press

Press

Regulation Mode

for more than 3 seconds to enter the


once in the regulation or initial setting

Back to top

Set up stop bit


Press

Back to top

Select the PID group: The user can select one of the 4 groups. When n = 4, the program will automatically select the PID group that is the closest to the SV.

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.


Regulation Mode

Operation Mode

Select the PID group (n = 0~4)

Set up the temperature SV for PID group 3

Press

PID group 0 ~ 3

Press

Initial Setting Mode

Set up the temperature SV for PID group 0

Press

Set up the proportion band for PID group 0

Set up the proportion band for PID group 3

Press

Press

Set up the Ti value for PID group 0

Set up the Ti value for PID group 3

Press

Press

Set up the Td value for PID group 0

Set up the Td value for PID group 3

Press

Press

Set up the integration offset for PID group 0,


Set up the integration offset for PID group 3,
AT auto-setting
AT auto-setting

PD control offset

Pres
Editing patterns and steps: In parameter

, select

Regulation Mode

for editing. Take pattern 0 for example:


Operation Mode

Select the pattern No. to be edited

Select OFF

Press

Leave pattern and step editing

Initial Setting Mode


Select the actual number of steps in the

Edit the temperature in step 0

Select No.

PD control offset

Press

program

Press
Edit the time for step 0
(unit: hour/minute)

Continue the setup in

Press

Set up the number of additional cycles (0 ~


99)

Press

Press

Press

Set up the link pattern.


OFF = end of program

Set up from step 0 ~ step 7 in order


Edit the temperature in step 7
Press

Press

Return to select the pattern No. to be edited

Edit the time for step 7


(unit: hour/minute)
Following the actual number of steps

Output Control

DTV offers heating and cooling outputs.


In parameter

, you can select either to operate heating control or cooling control. Select
Heating hysteresis

Cooling hysteresis

for heating output and

for cooling output.

Output

ON
Heating

Cooling

PV

OFF

Heating

Cooling

Set point

PV

Set point

Figure 1: Output operation when in On/Off control

Figure 2: PID control

Key-locked Function
: Lock all the keys on the panel.
: Only SV can be modified.
: Only SV and auto/manual mode can be modified (The control mode has to be PID control).
Press

and

at the same time to unlock the keys.

Types of Temperature Sensors & Temperature Range


Input Sensor Type

Register Value

Display

Range

0 ~ 50mV analog input

17

-999 ~ 9,999

4 ~ 20mA analog input

16

-999 ~ 9,999

0 ~ 20mA analog input

15

-999 ~ 9,999

0V ~ 10V analog input

14

-999 ~ 9,999

0V ~ 5V analog input

13

-999 ~ 9,999

Platinum resistance (Pt100)

12

-200 ~ 600C

Platinum resistance (JPt100)

11

-20 ~ 400C

Thermocouple TXK type

10

-200 ~ 800C

Thermocouple U type

-200 ~ 500C

Thermocouple L type

-200 ~ 850C

Thermocouple B type

100 ~ 1,800C

Thermocouple S type

0 ~ 1,700C

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.


Thermocouple R type

Input Sensor Type

Register Value
5

Display

Range
0 ~ 1,700C

Thermocouple N type

-200 ~ 1,300C

Thermocouple E type

0 ~ 600C

Thermocouple T type

-200 ~ 400C

Thermocouple J type

-100 ~ 1,200C

Thermocouple K type

-200 ~ 1,300C

Note 1: The current input is built-in with a 249 precision resistor. See How to Set up Current Input section.
Note 2: The default setting is Pt100 input.
Note 3: To display the decimal point, you have to set up the parameter
(in the operation mode). The decimal point display is available for all modes
except for thermocouple B, R, and S type.
Note 4: The range for analog input is -999 ~ 9,999. Take 0 ~ 20mA for example, -999 refers to 0mA input and 9,999 refers to 20mA input. If we change the
range into 0 ~ 2,000, 0 will thus refer to 0mA input and 2,000 refers to 20mA input (1 display scale = 0.01mA).

Alarm Output

DTV offers 2 groups of alarm outputs and 17 modes for each group under the initial setting mode. When the PV exceeds or falls below SV, the alarm output
will be enabled. See the table below for the 17 alarm output modes.
Mode
0

Alarm Type

Alarm Output Operation


Off

No alarm

Alarm output is enabled when the temperature reaches upper and lower limits.
Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV - AL-L.

Alarm output will be enabled when the temperature reaches the upper limit.
Alarm will be enabled when the PV exceeds SV + AL-H.

Alarm output is enabled when the temperature reaches the lower limit.
Alarm will be enabled when the PV falls below SV AL-L.

ON
OFF
AL-L

SV

AL-H

SV

AL-H

ON
OFF

ON
OFF
AL-L

SV

AL-L

SV

ON
OFF

Alarm output will be enabled when the PV is between SV + AL-H and SV AL-L.

Alarm output is enabled when the temperature reaches the absolute value of the upper and lower limits.
Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.

Alarm output is enabled when the temperature reaches the absolute value of the upper limit.
Alarm will be enabled when the PV exceeds AL-H.

Alarm output is enabled when the temperature reaches the absolute value of the lower limit.
Alarm will be enabled when the PV falls below AL-L.

Standby upper/lower limit alarm: Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or
falls below SV AL-L.

AL-H

ON
OFF
AL-L

AL-H

ON
OFF
AL-H
ON
OFF
AL-L
ON
OFF
AL-L

SV

AL-H

SV

AL-H

ON

Upper limit standby alarm: Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H.

OFF
ON

10

Lower limit standby alarm: Alarm will be enabled when the PV reaches SV and falls below SV AL-L.

OFF
AL-L

11

Upper limit hysteresis alarm: Alarm will be enabled when the PV exceeds SV + AL-H. Alarm will be disabled
when the PV falls below SV + AL-L.

12

Lower limit hysteresis alarm: Alarm will be enabled when the PV falls below SV AL-H. Alarm will be
disabled when the PV exceeds SV AL-L.

14
15

Programmable STOP: Alarm will be enabled when the program is in STOP status.
Programmable RAMP UP: Alarm will be enabled when the program is in RAMP UP status.

16

Programmable RAMP DOWN: Alarm will be enabled when the program is in RAMP DOWN status.

17
18

Programmable SOAK: Alarm will be enabled when the program is in SOAK status.
Programmable RUN: Alarm will be enabled when the program is in RUN status.

SV

ON
OFF
AL-L

AL-H

ON
OFF
AL-H

AL-L

Note: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L. There is no mode 13 (reserved for CT function).

PID Programmable Control

Functions and Parameter Setting:


The PID programmable control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0 ~ 7) and parameters: link pattern, cycle and the
number of steps.
Start Pattern
: This parameter can be set in the operation mode. The user can set up which pattern is the start pattern for the programmable control.
This function is only available when the program is in STOP status.
Step: Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV) has to rise to temperature X after the
period of execution time T. If the result of the set point X is the same as that of the previous setting, the process is called Soak; otherwise, it is called Ramp.
Therefore, the programmable control is also known as Ramp/Soak control.
The default setting of the first step program is Soak control. The temperature will first rise to the set point X and remain at X. The total execution time is T.
Link Pattern: For example, if the parameter
is set as

is set as 2, it refers to the execution of pattern 2 will follow the execution of pattern 0. If the link pattern

, it refers to the program will end after the execution of the pattern is completed and the temperature will remain at the SV for the last step.

Cycle: The additional number of cycles for a pattern. For example, if the parameter
additionally, totaling the executions to 3 times including the original one.

is set as 2, it refers to pattern 4 has to execute twice

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.


The Number of Steps: The number of steps in each pattern (range: 0 ~ 7). For example, if the parameter
execute step 0 ~ step 2 and other steps will not be executed.

is set as 2, it refers to pattern 7 will

The Execution:
1. When the parameter

is set as

2. When the parameter

is set as

, the program will stop and the control output will be disabled.

3. When the parameter

is set as

, the program will stop and the temperature will stop at the SV before the program stops. When you select

, the program will start its execution from step 0 of the start pattern.

again, the program will execute again from step 0 of the start pattern.
4. When the parameter

is set as

, the program will stop and the temperature will stop at the SV before the program stops. When you select

again, the program will resume the step before the program stops and execute by the remaining time.
Display:
In PID programmable control, some SVs are re-set as P-XX. P refers to the current pattern and XX refers to the current step. Press
display.
Select

and press

. SV will display the target temperature for the current step.

Select

and press

. SV will display the remaining time of the current step.

to modify the

PID Control

In PID control, you can select any one of the 4 groups of PID parameter (P, I, D, IOF). After auto-tuning, the PID value and the temperature SV will be stored
into the selected PID parameter.
~
: PIDn, n = 0 ~ 4. 0 ~ 3 are the corresponding selected PID parameter.
refers to auto-selected PID and the program will
~
corresponding to n = 0 ~ 3.
automatically select a most useful PID parameter based on the current SV. SV displays will be
~
: The SV for the selected PID parameter, can be set by the user or auto-generated by auto-tuning.

Valve Control

Heaters and coolers can be used to control the temperature and the openness of the valve in order to control the flow of the medium. Current and voltage
can control the openness of the valve; however, the most direct and economic way to control the openness of the valve is the relay. To control the valve by
voltage and current, you can use the DTB series analog output controller. If you tend to use relay for the control output, you have to choose the valve
function in DTV series. The two control outputs are relay output for the forward/reverse running of the motor to drive the opening and closing of the valve.
Control output1 controls the opening of the valve and control output 2 controls the closing of the valve in order to adjust the position of the valve. In order to
detect the position of the valve, DTV is able to receive feedback signal and no feedback signal. When there is no feedback signal and the valve is fully
open, control output 1 will output continuously. If at the moment the valve is fully closed, control output 2 will output continuously. If the valve you use is with
feedback output, you can connect the output of the valve to the feedback part of DTV and set
to On to precisely control the openness of the valve. If
there is no feedback signal or the feedback signal is incorrect, and the pre-set openness of the valve is not reached after twice as long as the time set in the
, the program will automatically switch back to the no feedback state. To ensure the correctness of the valve control, please make sure
parameter
that you have set up the parameters below:
: Time required from the valve fully closed to fully open. This parameter has to be correct when the valve is without feedback signal; otherwise, the
accuracy for the temperature control will be affected. The PID control will correspond to the openness of the valve according to the setting of this parameter.
: DeadBand value of the valve. The parameter is to prevent frequent movement of the valve. For example, assume the DeadBand is 4%, PID control
will correspond to the openness of the valve within 4% and the valve will not move within the range unless the value is accumulated and exceeds 4%. If the
Deadband value is too small and the valve is set to have feedback signals, moving back and forth of the valve will shorten the life of the valve motor.
: With or without feedback signals.
When
a)

is set as On, it refers to with feedback signals and the following parameters will be displayed.

: Automatically adjusting the upper/lower limit of the valve feedback. This parameter will only be displayed when
is set as
. When
this parameter is set as On, the relay will enable the forward and reverse running of the motor in order to calculate the time needed from the valve fully
closed to fully open and the feedback signal of fully closed and open. The feedback signal is the hardware D/A value of the valve control, which is for the
calculation of the valve controller.

b)

: Upper limit of the valve signal. Set

as On, can be set automatically or manually.

c)

: Lower limit of the valve signal. Set

as On, can be set automatically or manually.

Auto/Manual Mode Switch

A/M indicator On refers to manual mode; A/M indicator Off refers to auto mode. Besides On/Off, PID, programmable and manual controls, the valve control
is also able to forcibly switch to manual control (fixing the openness of the valve, unit: % from valve fully closed to fully open) when in PID control mode. You
simply need to press
in PID control mode to switch to manual mode and A/M indicator will be On. Press
again to return to PID control and A/M
indicator will be Off.

Upper/Lower Limits of Valve Openness

Assume we would like the maximum openness of the valve to be 80% and the minimum to be 20%, set the parameter
and the valve openness of PID control, programmable control and manual control will fall within this range.

as 80 and

as 20,

RS-485 Communication

1. Supports transmission speed 2,400bps, 4,800bps, 9,600bps, 19,200bps and 38,400bps; does not support communication format 7, N, 1/8, E, 2/8, O, 2.
Communication protocol: Modbus (ASCII or RTU). Function: 03H (able to read max. 8 words in the register), 06H (able to write 1 word into the register),
01H (able to read max. 16 bits of data), 05H (able to write 1 bit into the register).
2. Address and content of the data register.
Address

Content

1000H

Present temperature value (PV)

1001H

Set point (SV)

Explanation
Unit: 0.1 degree, updated every 0.4 second.
The read values below indicate the occurrence of errors:
8002H: temperature not acquired yet
8003H: temperature sensor not connected
8004H: wrong sensor type
8006H: unable to acquire temperature, ADC input error
8007H: unable to read/write the memory
Unit: 0.1 degree

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.


Address
1002H
1003H
1004H
1005H
1006H
1009H
100AH
100BH
100CH
100DH
1010H
1012H
1014H
1015H
1016H
1017H
1018H
1019H
101AH
101BH
101CH
101DH
101EH
101FH
1020H
1021H
1023H
1024H
1025H
1026H
1027H
102AH
102BH
102CH
102FH
1030H
1040H ~
1047H
1050H ~
1057H
1060H ~
1067H

Content
Upper limit of temperature range
Lower limit of temperature range
Input sensor type
Control method
Selecting heating/cooling control
Proportion band value
Ti value
Td value
Default integration value
Offset compensation value for proportional control
(when Ti = 0)
SV of output hysteresis
Read/write of output percentage
Upper limit regulation for analog linear output
Lower limit regulation for analog linear output
Temperature offset regulation value
Analog decimal point setting
Time from valve fully closed to fully open
DeadBand setting of valve
Upper limit for valve feedback signal
Lower limit for valve feedback signal
PID group setting
SV for the corresponding PID setting
Upper limit for control output
Lower limit for control output
Output mode for alarm 1
Output mode for alarm 2
System alarm setting
Upper limit for alarm 1
Lower limit for alarm 1
Upper limit for alarm 2
Lower limit for alarm 2
Read/write LED status
Read/write key status
Panel lock status
Software version
No. of start pattern

Explanation
The content shall not be bigger than the range.
The content shall not be smaller than the range.
See Types of Temperature Sensors and Temperature Range" table.
0: PID; 1: On/Off; 2: manual control; 3: PID programmable control
0: heating; 1: cooling
0.1 ~ 999.9
0 ~ 9,999
0 ~ 9,999
0 ~ 100%, unit: 0.1%

0 ~ 9,999
Unit: 0.1%, only applicable in manual control mode
1 scale = 2.8A = 1.3mV
1 scale = 2.8A = 1.3mV
-99.9 ~ +99.9, unit: 0.1
0~3
0.1 ~ 999.9
0 ~ 100%, unit: 0.1%
0 ~ 1,024
0 ~ 1,024
0~4
In valid range. Unit: 0.1
Lower limit for control output ~ 100%, unit: 0.1%
0 ~ Upper limit for control output, unit: 0.1%
See Alarm Output section.
See Alarm Output section.
0: None (default); 1 ~ 2: Set alarm 1 ~ alarm 2
See Alarm Output section.
See Alarm Output section.
See Alarm Output section.
See Alarm Output section.
b0: F; b1: C; b2: ALM2; b3: x; b4: OUT1; b5: OUT2; b6: AT; b7: ALM1
b0: Set; b1: Select; b2: Up; b3: Down; 0 refers to push.
0: normal; 1: lock all; 11: SV adjustable; 111: SV adjustable, A/M available
V1.00 refers to 0x100
0~7

Number of steps in a pattern

0 ~ 7 = N refers to the pattern will be executed from step 0 to step N.

Additional number of cycles for a pattern

0 ~ 99 refers to the pattern will be executed for 1 ~ 100 times.

No. of the link pattern for the current pattern

0 ~ 8. 8 refers to end of the program; 0 ~ 7 refers to the next pattern No. following the
current pattern.

0 ~ 100%, unit: 0.1%

SV temperature for pattern0 ~ 7


-999 ~ 9,999
SV for pattern 0 is set in 2000H ~ 2007H
Execution
time
for
pattern
0
~
7
2080H ~
0 ~ 900 (Every scale = 1 minute)
20BFH Time for pattern 0 is set in 2080H ~ 2087H
3. Address and content of the bit register (read bits are stored starting from LAB and written data is FF00H, set the bit as 1. 0000H sets the bit data as 0.)
0810H
Selecting communication write-in
Communication write-in forbidden: 0 (default), allowed: 1
0811H
Selecting temperature unit
0: F; 1: C/linear input (default)
0812H
Position of the decimal point
0 or 1. Available for all modes except for thermocouple type B, S, R.
0813H
Read/write auto-tuning (AT)
0: AT stops (default); 1: AT starts
0814H
RUN/STOP of the control
0: stop; 1: run (default)
0815H
Programmable control RUN/STOP
0: run (default); 1: stop
0816H
Programmable control RUN/PAUSE
0: run (default); 1: pause
0817H
Read/write valve feedback
0: without feedback (default); 1: with feedback
0818H
Read/write AT of valve feedback
0: AT stops (default); 1: AT starts
4. Communication transmission format: command 01: read bit, 05: write bit, 03: read word, 06: write word.
ASCII Mode
Read Command
Read Response Message
Write Command
Write Response Message

Start word
Start word
Start word
Start word
2000H ~
203FH

Machine address 1
Machine address 0
Command 1
Command 0

Read start address of data/bit

0
1
0
3
1
0
0
0

0
1
0
1
0
8
1
0

Machine address 1
Machine address 0
Command 1
Command 0
Length of response
data (byte)
Data content in
1000H/081xH

0
1
0
3
0
4
0
1

0
1
0
1
0
2
1
7

Machine address 1
Machine address 0
Command 1
Command 0

Write data address

0
1
0
6
1
0
0
1

0
1
0
5
0
8
1
0

Machine address 1
Machine address 0
Command 1
Command 0

Write data address

0
1
0
6
1
0
0
1

0
1
0
5
0
8
1
0

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.


Read Command

Read Response Message


Write Command
Write Response Message
F
0
0
F
0
4
1
3
F
3
Read length of data/bit
Write data content
Write data content
(word/bit)
0
E
0
E
0
8
0
8
Data content in
1001H
LRC1 check
0
LRC1
F
E
LRC1
F
LRC0 check
0
LRC 0
D
3
LRC 0
D
End word 1
LRC1 check
0
E
End word 1
CR
CR
End word 1
CR
End word 0
LRC0 check
3
3
End word 0
LF
LF
End word 0
LF
End word 1
CR
CR
End word 0
LF
LF
LRC check: Sum up from machine address to data content, e.g. 01H + 03H + 10H + 00H + 00H + 02H = 16H. Obtain 2s complement EA.
0
0
0
2
E
A
CR
LF

0
0
0
9
D
C
CR
LF

Data content in
1000H/081xH

F
F
0
0
E
3
CR
LF

RTU Mode
Read Command
Machine address
Command
Read start address of data
Read length of data (bit/word)
CRC low byte
CRC high byte

01H
03H
10H
00H
00H
02H
C0H
CBH

Read Response Message


01H Machine address 01H
01H
01H
Command
03H
01H
08H Length of response
04H 02H
data (byte)
10H
00H
01H
17H
Data content 1
09H
F4H
01H
BBH
03H
Data content 2
A9H
20H
CRC low byte
BBH 77H
CRC high byte
15H
88H

Write Command
Machine address 01H
Command
06H
10H
Write data address
01H
03H
Write data content
20H
CRC low byte
DDH
CRC high byte
E2H

01H
05H
08H
10H
FFH
00H
8FH
9FH

Write Response Message


Machine address
01H
01H
Command
06H
05H
10H
08H
Write data address
01H
10H
03H
FFH
Write data content
20H
00H
CRC low byte
DDH 8FH
CRC high byte
E2H
9FH

CRC (Cyclical Redundancy Check) is obtained by the following steps.


1. Load in a 16-bit register FFFFH as the CRC register.
2. Do an exclusive OR operation of the first byte of the data and low byte of CRC register, and place the operation result back to the CRC register.
3. Right shift the bits in the CRC register and fill the high bits with 0. Check the removed lowest bit.
4. If the removed lowest bit is 0, repeat step 3. Otherwise, do an exclusive OR operation of the CRC register and the value A001H and place the operation
result back to the CRC register.
5. Repeat step 3 and 4 until the 8 bits (1 byte) are all right shifted.
6. Repeat step 2 and 5 and calcualte all the bits to obtain CRC check.
Please be aware of the high/low byte transmission order in the CRC register.

How to Mount

How to Install Mounting Bracket

1. Insert DTV into the panel cutout


2. Insert the mounting bracket into the mounting groove at the top and
bottom of DTV.
3. Push the mounting bracket forward until the bracket stops at the
panel wall.
4. Tighten the screw.

Dimensions

DTV4896

DTV9696

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

VARITEL INGENIERIA ELECTRONICA S.A.

Panel Cutout

DTV4896/DTV9696
96*96

+0.6

120.0 min.

110.0 min.

91 0

91.5 0

120.0 min.

60.0 min.

+0.6

48*96

Terminals

DTV4896R/DTV9696R

+0.6

44.5 0

+0.6

91 0

How to Set up Current Input


For normal input (default)

Current input (4 ~ 20mA, 0 ~ 20mA)


JU MP ER

JP1

PIN HEA DE R

J UMP ER

JP1

PIN HE A DE R

DEFAU LT SE TTI NG

[email protected] WWW.VARITEL.COM - TEL:(54) 11- 4243-1171 FAX::(54) 11- 4292-7545


MANUEL BALIA 456 LOMAS DE ZAMORA (B1832CCJ) BUENOS AIRES - ARGENTINA

You might also like