Rexa Manual x2 Iom 10-2014
Rexa Manual x2 Iom 10-2014
Rexa Manual x2 Iom 10-2014
Serial #____________________________
Model #___________________________
Application________________________
Tag # _____________________________
REXA
4 Manley Street
W. Bridgewater, MA 02379
(P) 508.584.1199
(F) 508.584.2525
Contents
FUNDAMENTAL SAFETY INFORMATION. . . . . . . . . . . . . . . . . . . . . . XI
WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Warning Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
RESIDUAL RISKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
When to Lock-Out/Tag-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
Procedures: Lock-Out/Tag-Out. . . . . . . . . . . . . . . . . . . . . . . . . xvi
Education and Discipline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvii
PRODUCT COMPLIANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . XIX
INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xix
EC Declaration of Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . xx
ATEX Declaration of Conformity. . . . . . . . . . . . . . . . . . . . . . . . . xxi
Declaration of Noise Emission. . . . . . . . . . . . . . . . . . . . . . . . . . xxii
Waiver of Translations Agreement. . . . . . . . . . . . . . . . . . . . . . xxiii
Waiver of Mains Supply Disconnect / Emergency Stop
Agreement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxiv
1 GENERAL INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 About Rexa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Factory Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Actuator Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1
1
2
ii Contents
1.6.4 Filling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 1.6.4-1 Castrol EDGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 1.6.4-2 Fill Valve with cover. . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 1.6.4-3 Fill the oil gun. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 1.6.4-4 Purge the air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 1.6.4-5 Oil Pump Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 1.6.4-6 Fill Valve with Schrader fitting. . . . . . . . . . . . . . . . . 15
1.6.5 Overfilling, Oil Weeping & Thermal Expansion . . . . . . . 16
1.6.6 Air Purging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.6.7 Reservoir Purging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 1.6.7-1 Reservoir Purging Ports . . . . . . . . . . . . . . . . . . . . . . 17
Figure 1.6.7-2 Full Indicator OKflush with front face . . . . . . . . . 18
1.6.8 Hydraulic System Purging. . . . . . . . . . . . . . . . . . . . . . . 18
Figure 1.6.8-1 Extend/CW and Retract/CCW Ports . . . . . . . . . . . . . 19
Figure 1.6.8-2 Bleed Kit (PN: K09275) . . . . . . . . . . . . . . . . . . . . . . 20
1.7 Tool Requirements (Power Module Only) . . . . . . . . . . . . . . . . 20
1.8 Theory Of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.8.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.8.2 Actuator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 1.8.2-1 B Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 1.8.2-2 C Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 1.8.2-3 D, & D Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 1.8.2-4 C &D Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.8.3 Control Sub-Assembly. . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 1.8.3 Typical Control Enclosure . . . . . . . . . . . . . . . . . . . . . . . 27
Table 1.8.3-1 Control Enclosure Terminal Blocks . . . . . . . . . . . . . . 28
Table 1.8.3-2 Actuator Terminal Blocks . . . . . . . . . . . . . . . . . . . . . 28
1.8.4 Operational Summary. . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 1.8.4-1 Hydraulic schematic . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 1.8.4-2 Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2 DELIVERY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Receipt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Unpacking System, Lifting. . . . . . . . . . . . . . . . . . . . . . .
2.4 Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.1 Operational and Maintenance Clearances. . . . . . . . . . .
2.4.2 Hazards Due to Height. . . . . . . . . . . . . . . . . . . . . . . . . .
31
31
31
32
32
32
32
33
3 ELECTRICAL INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Control Enclosure Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.1 Control Enclosure Installation. . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 3 Electrical Installation Block Diagram . . . . . . . . . . . . . . . . . 36
3.2 Main Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 3.2 Control Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 3.2 Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
iii
61
61
61
62
62
63
iv Contents
D-1
D-1
D-1
D-2
D-2
D-2
vi Contents
ON state:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OFF state:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E.4 Pulse Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . .
E.5 Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E-3
E-3
E-3
E-4
F-1
F-1
F-2
F-2
F-2
F-3
F-3
F-3
F-4
F-4
F-4
F-5
F-5
F-5
F-6
F-6
F-6
F-7
vii
viii Contents
ix
P-18
P-19
P-20
P-21
P-22
P-23
x Contents
xi
REXA actuators all produce extremely high forces, have hydraulic lines under
pressure and have dangerous electrical power input levels. In addition to these
standard characteristics, optional actuator constructions possess other hazards
such as coil and disk springs under compression and high pressure accumulator
bottles.
WARNINGS
Based on these hazards, the following could occur if this safety information is
not observed:
Death
Safety Considerations
xii
Safety Considerations
WARNING LABELS
Hazardous Voltage
Turn Off and Lock Out system power before servicing. Do Not
Operate this equipment from any power source that does not
match the voltage rating stamped on the equipment. Refer to
the manufacturers identification nameplate for operational
requirements.
General Warning
Refer to Installation Manual before servicing.
Attention
Important information provided. Do No Use this equipment for
any purpose not described in this manual.
Crush or Pinch Point Hazard
Turn Off and Lock Out system power before servicing.
Warn of Actuator movement if Spring Fail Unit.
Guard Warning
All Guards MUST be in place before operation. Failure to do so
may result in injury or damage to equipment.
Tripping, Slipping and Falling Hazards
These hazards can be avoided by cleaning spilled hydraulic oil in
a timely manner.
Using the actuator for uses other than what it is intended may result in
injury or death. Use the Actuator for its intended purpose ONLY.
RESIDUAL RISKS
This section is to help identify the risks associated with the Actuator System.
These items are identified as:
ACTUATOR & DRIVEN DEVICE CONNECTION:
The point at which the actuator couples to the driven device poses
the risk of injury due to pinch or crush point. Use appropriate
Lock-Out/Tag-Out procedures when connecting Actuator to the
driven device.
MANUAL OVERRIDE HANDWHEEL ASSEMBLY:
The Manual Override Handwheel Assembly is to remain declutched until it is required. The Motor Shaft Cover MUST be in
place during normal operation. Failure to do so poses a risk of
injury.
MANUAL OVERRIDE HANDWHEEL ASSEMBLY:
When the Manual Override, Handwheel Assembly is used, adhere
to proper Lock-Out/Tag-Out procedures.
FEEDBACK COVER:
Feedback Cover MUST be in place during operation. Failure to do
so may result in injury. Use proper Lock-Out/Tag-Out procedures
before accessing feedback housing.
SHOCK HAZARD:
Wire Cover must be in place during operation. Use proper LockOut/Tag-Out procedures before removing cover.
SHOCK HAZARD:
Control Enclosure Cover must be closed during normal operation.
Failure to do so may result in injury. Use proper Lock-Out/Tag-Out
Safety Considerations
xiv
Safety Considerations
instructions.
RELIEVING INTERNAL PRESSURE:
When the electric power is off or the motor is not turning, hydraulic
pressure remains locked within the cylinder and/or accumulator.
This internal pressure must be relieved before disconnecting any
hydraulic fitting. Open the bypass cylinder (3/16 hex) located on
the power module for fail in place units and manually override all
solenoid valves that are closed.
Note: Reservoir lines may contain up to 60 psi (4 bar) that cannot be relieved.
Note: Accumulators will still contain up to 2000 psi (138 bar) of nitrogen gas that
cannot be relieved.
Most equipment is installed along with safe switches allowing the equipment
to be disabled for minor repair. In general, these switches provide adequate
Safety Considerations
xvi
Safety Considerations
protection for minor repair, which is routine, repetitive, and necessary to the
normal use of the equipment. Lock-Out/Tag-Out procedures shall be used for
the following situations.
PROCEDURES: LOCK-OUT/TAG-OUT
The following are minimum recommended procedures to be followed for
Lock-Out/Tag-Out:
1. Notify all affected areas and employees of the impending Lock-Out situation,
the reason for it, and estimated start and duration times.
2. Equipment shutdown and isolation: Place all switches in the off or
safe position. Disconnect sources of power, ensuring all sources of
both primary and secondary power to the equipment are interrupted.
3. Dissipate residual energy. Shutting down equipment does not mean
there is no energy left in it. Check for trapped pressure, compressed
spring or residual electricity in the system.
4. Lock-Out or Tag-Out all in-line points of control. In most cases, there
may be more than one place, or more than one lock, if several people
are working on the equipment.
5. Lock-Out verification: Take nothing for granted. Verify that the lockedout switch or control cannot be overridden. Test the equipment to
be certain that the locked-out switch is de-energized, and not simply
malfunctioning. Test all control points and modes to be sure that the
equipment does not start.
6. Perform the work scheduled. Try to foresee all possible hazards. Ensure the new/repair work does not bypass the Lock-Out and reactivate
the system.
7. Lock and/or tag removal. All locks and tags are to be left in place
until all work is completely finished. This is especially true when more
than one employee is working on the equipment. A lock is never to be
removed except by the person who placed it there.
8. Equipment start-up. Make a final safety check before restarting equipment, to be certain it is safe to operate. Make sure of the following:
a) All tools and other items have been removed.
b) All machine guards are returned to their proper position. All electric,
hydraulic, pneumatic or other systems are properly reconnected.
c) All employees are clear of equipment.
Many of the Lock-Out/Tag-Out procedures appear to be common sense, and
they are. Following them will ensure safe operation calibration, maintenance
and repair of equipment and/or processes, without dangerous surprises or
injury.
Safety Considerations
xix
Product Compliance
INFORMATION
Inclusion of the following symbols indicates that the supplied REXA actuator
complies with applicable standards:
For the U.S. and Canada: A CSA mark with the indicators C and
US means that the product is certified for both the U.S. and
Canadian markets, to the applicable U.S. and Canadian standards.
The REXA Actuator/Drive with Control Enclosure is certified by
CSA for use in General Locations per EN 61010-1 and for Hazardous Locations Class 1, Division 2, Groups A, B, C and D or Class
1, Division 1, Groups C and D.
Product Compliance
xx
Product Compliance
EC DECLARATION OF CONFORMITY
ACCORDING TO:
MACHINERY DIRECTIVE 2006/42/EC
EMC DIRECTIVE 2004/108/EC
PED DIRECTIVE 97/23/EC (APPLIES WHERE APPLICABLE)
We, REXA, Inc.,
Hereby declare under our sole responsibility, the following products to be in compliance
by design according to the relevant essential health and safety requirements and harmonized standards mentioned. The Technical File may be produced by our EU representative below. In case of alteration of the product, not agreed upon by us, this declaration
will lose its validity.
Manufactured:
4 Manley Street
West Bridgewater, MA 02379 USA
EU Authorized Representative:
Koso Kent Introl Limited
Armytage Road
Brighouse, West Yorkshire HD6 1QF
Contact: Brian Richmond (QHSE Director)
or Jonathan Lodge (Technical Director)
Telephone: +44(0)1484 710311
Fax: +44(0)1484 407407
Brand Name:
(REXA)
Applicable Directives:
Machinery Directive 2006/42/EC including Low Voltage Directive
EMC Directive 2004/108/EC
PED Directive 97/23/EC; applies where applicable, to accumulator
systems
Applicable Harmonized Standards:
Health/Safety: Machinery Directive 2006/42/EC Annex I, EN60204-1:2006, EN ISO
12100:2010, EN61310-1:1995, EN61310-2:1995, EN ISO 13850:2006,
IEC61010-1:2001
EMC:
PED:
xxi
4 Manley Street
West Bridgewater, MA 02379 USA
EU Authorized Representative:
Koso Kent Introl Limited
Armytage Road
Brighouse, West Yorkshire HD6 1QF
Contact: Brian Richmond (QHSE Director)
or Jonathan Lodge (Technical Director)
Telephone: +44(0)1484 710311
Fax: +44(0)1484 407407
Brand Name:
(REXA)
-40C Ta 65C
ATEX:
EN50021:1999
PED:
xxii
Product Compliance
Idle
81 dB (A)
66 dB (A)
84 dB (A)
67 dB (A)
88 dB (c)
8.8 Bel
LpAm = 16 dB (A)
4 dB (A)
Measurements were made at a height of 1.5 m and 1 m from the Operator Position and all
four sides of the equipment.
The figures quoted are emission levels and are not necessarily safe working levels. While
there is a correlation between the emission and exposure levels this cannot be used reliably
to determine whether or not further precautions are required.
Factors that influence the actual level of exposure of the workforce include characteristics
of the work room, the other sources of noise, etc. such as the number of machines and
other adjacent processes. Also, the permissible level of exposure can vary from country to
country.
This information, however, will enable the user of the machine to make a better evaluation
of the hazard and risk.
KOSO America
4 Manley Street
West Bridgewater, MA 02379
USA
xxiii
This document also waives the responsibility of translations of the following system
components and markings:
Individual wire and component marking identification is not required. The fully
assembled factory wired panel is only serviced by REXA personnel and not
the end user. However, end user terminations are readily identified.
Translations of the above mentioned may be made by the end user and/or the authorized
representative listed on this document. Any of which may be translated must bear the
statement Translation of Original Instructions within the document(s) header or footer.
EU Authorized Representative:
Koso Kent Introl Limited
Armytage Road
Brighouse, West Yorkshire HD6 1QF
Contact: Brian Richmond (QHSE Director)
or Jonathan Lodge (Technical Director)
Telephone: +44(0)1484 710311
Fax: +44(0)1484 407407
Product Compliance
xxiv
Product Compliance
WAIVER OF
MAINS SUPPLY DISCONNECT / EMERGENCY STOP
AGREEMENT
We, REXA, Inc.,
Hereby declare it the responsibility of the installer of this equipment to provide a suitable
disconnect for the Control Panel supplying power to the system.
The disconnect must:
Be suitable for the Voltage and Full Load Ampere Rating of all downstream
equipment supplied by the Panel;
Be approved for use as a disconnect for the country in which the system is
installed.
1 General Information
General Information
General Information
REXA
4 Manley Street
West Bridgewater, MA 02379
Note: It is important to have the model code and build number for both the
electronics and the actuator in addition to the serial number for the actuator so we
can provide better service.
This information can be found on the metal tags on the actuator and on the front
panel of the electronics. Reference the sections below on Actuator Identification
for more detailed explanation.
General Information
General Information
MODEL NUMBER
X2__
__ __ __ __ __ __ __ __-__
Thrust
Torque
Stroke
Rotation
Series 2
L Series Xpac Linear
R Series Xpac Rotary
D Series XPac Drive
R or D SERIES
L SERIES
Torque
Rotation
(lbfin) (degrees)
Thrust
(lb)
Strokes
(in inches)
2000
4000
5000
10000
15000
20000
30000
40000
50000
60000
80000
120000
.75, 2, 4 6, 8, 11
.75, 2, 4
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
.75, 2, 4, 6, 8, 11, 16, 22
2500
5000
10000
20000
50000
100000
200000
400000
90, 120
90, 120
90, 120
90, 120
90, 120
90, 120
90, 120
90, 120
Specifications
O-ring Lubricant
Thermal Grease
Thermalcote or equivalent
Parts Cleaner
Note: In special applications the type of oil used is system dependant and the user
should refer to the system documentation.
General Information
General Information
Temperature Range
Electronics
Temp. Range
Motor Type
Standard
High Temp.
-5F to +200F
-30F to +200F
-76F to +200F
-5F to +250F
(-20C to +93C)
(-34C to +93C)
(-60C to +93C)
(-20C to 121C)
+10F to +200F
-10F to +200F
-76F to +200F
-5F to +250F
(-12C to +93C)
(-23C to +93C)
(-60C to +93C) (-20C to 121C)
1
inch
thermal
Heat
tracing & 1 inch
None
None
insulation2
thermal insulation2
Separate Control Enclosure with CPU, motor driver, power supply, transient protection
and termination.
-40F to +140F (-40C to +60C)
-40F to +120F (-40C to +50C)
Stepper
Servo
1. High ambient temperatures affect oil viscosity which may affect actuator rated output.
2. These items are not supplied by REXA.
Temperature Range1
Electronics
Temp. Range
Motor Type
Standard
+10F to +200F
-10F to +200F
High Temp.
-76F to +200F
-5F to +250F
(-20C to
+121C)
Optional
Standard oil &
1 of thermal
Heat tracing & 1
High Temp.
cartridge heater
insulation2
therm2
Construction
Separate Control Enclosure with CPU, motor driver, power supply, transient protection
and termination.
-40F to +140F (-40C to +60C)
-40F to +120F (-40C to +50C)
Stepper
Servo
(-12C to +93C)
(-23C to +93C)
(-60C to +93C)
1. High ambient temperatures affect oil viscosity which may affect actuator rated output.
2. These items are not supplied by REXA.
Operating Temperatures
Actuator
T-Code
Electronics
Duty*
Notes
Actuator/Elec Cycle
B 115V
(-40C to +60C)
T3/T3C
S1
B 230V
(-40C to +40C)
T3/T3C
S8
24V B
(-40C to +65C)
T3/T3C
S1
48V B
(-40C to +65C)
T3C/T3C
S1
24V C
(-40C to +65C)
T3C/TC3
S1
C 115V
(-40C to +60C)
T3/T3C
S1
C 230V
(-40C to +40C)
T3/T3C
S8
2C 115V
(-40C to +60C)
T3/T3C
S1
(-40C to +65C)
T3C/T3C
S1
(-40C to +65C)
T3C/T3C
S1
(-40C to +55C)
T3C/T3C
S1
(-40C to +65C)
T3C/T3C
S1
(-40C to +65C)
T3C/T3C
S1
2D
(-40C to +55C)
T3C/T3C
S1
D,P9**
(-40C to +50C)
T3C/T3C
S8
1, 3
D,P40**
(-40C to +50C)
T3C/T3C
S8
2, 3
D 230V
Dual .5D
115V
Dual .5D
230V
Notes
1. Duty cycle for D,P9 PM motor is S1, booster motor will remain S8.
2. Duty cycle for D,P40 PM motor is S1, booster motor will remain at S8.
3. CSA duty cycle tested at 31.8% for continuous operation at maximum load and speed.
4. Uses internal 240 to 120 Vac step-down transformer P98246.
5. Uses 48 Vdc to 72 Vdc converter.
6. Uses 24 Vdc to 165 Vdc converter.
**
S1
Duty: Duty cycle S1 is defined as continuous operation at load.
General Information
General Information
S8
Duty: Duty cycle S8 is defined as periodic duty with rest period between operation, variable load/speeds.
*Duty Cycle definitions taken from IEC 60034-1 applies to all rotating electrical machines.
Monthly
Check the oil indicator for proper oil level. Add oil if necessary following
the instructions in section 1.6.4. When oil is added, a visual inspection of
the actuator is needed to determine where the loss of oil occurred and the
necessary repair required.
Note: Ambient temperature swings will affect the oil indicator position.
Quarterly
Perform a visual inspection of the actuators for damage, oil leakage, obstruction
and hazards. Repair items found damaged during this inspection in accordance
with company procedures. During this inspection, check the following items at
a minimum:
Mounting hardware and fasteners are tight
Oil level is correct
Tubing and fittings are tight
Tubing is not touching or rubbing
Power module fasteners are tight
Actuator can hold position without re correcting
Oil leaks
Spring washer stack for damage (not all models)
Check for moisture ingression or contaminants under the feedback
housing, wire cover and in the electronics enclosure
Ground wire connectivity
Ensure the feedback signal on the actuator is stable
Inspect wiring for cuts, abrasions or tears
General Information
10
General Information
1.6 OIL
The REXA Xpac Actuator is a sealed, self-contained, hydraulic positioning
system in which oil is pumped from one side of a double acting cylinder to the
other. An internal oil reservoir provides a source of make up oil for thermal
expansion and is an integral component within the module. As the size of
the actuator cylinders increase so does the need for additional make up oil,
therefore larger systems will have external reservoir bottles in addition to the
standard internal reservoir.
A closed-loop hydraulic system means that the oil in the actuator is isolated
from the environment and immune to degradation with time as a result of
exposure to moisture and other atmospheric elements. Since the hydraulic
system is sealed and spring-loaded, it is also unaffected by the orientation in
which the actuator is applied.
A periodic, visual inspection of the REXA Xpac Actuator is required in order to
verify that the hydraulic system has not been compromised for any reason. Any
external signs of a major oil leak or repeated refilling of the unit will indicate
damage to the actuator that will require servicing of the unit and investigation for
a cause.
11
Larger units will require additional make up oil and an external reservoir will be
plumbed in series with the internal reservoir. The internal reservoir will still show
the oil level however there is also an indicator rod in the external reservoir. At an
ambient condition of 70F it should be protruding out approximately 3- inches
as measured from the base of the bushing shown in Figure 1.6.2-4.
General Information
12
General Information
13
1.6.4 Filling
If the addition of oil is required, it should be filled with Castrol EDGE SAE
5W-50 motor oil (Figure 1.6.4-1). In special applications the type of oil used is
system dependant and the user should refer to the system documentation. The
actuator does not need to be taken out of service when adding oil.
Note: Although Castrol Edge oil is recommended, oil of equal quality may be used.
PROCEDURE (9 steps):
General Information
14
General Information
15
the oil Pump) with a suitable device like a small screwdriver or punch
until you get clean, air-free oil (Figure 1.6.4-5).
General Information
16
General Information
17
General Information
18
General Information
3. Slowly unthread the highest purge point fastener and have an oil catch
pan ready. It may not be necessary to fully remove these plugs as air
will purge out with a few threads still installed.
4. Retighten the plug before proceeding.
5. Refill to the correct oil level.
Note: Some actuator orientation will not allow for proper purging and the actuator
may need to be removed and re-orientated for purging, then re-installed. The
best position for purging is with purge port 1 facing up.
To purge the actuator of air, it is recommended that you use the REXA bleed kit
(P/N: K09275) See Figure 1.6.8-2 for details.
19
1. Change the Max Man Spd to 30% or less. (Refer to section 6.1.5.)
2. Open the manual bypass to relieve internal pressure. (Refer to C.5.)
NOTE: Some units can have a solenoid instead of a manual bypass; ensure that
the solenoid is open before proceeding. (Refer to section 1.8.4.)
3. Locate the best available pressure ports to bleed air from the system.
The best position is the highest point that is accessible and will allow air
to escape the system. Keep in mind that the porting may be located on
the module, cylinder, manual hydraulic pump or SCL, etc.
4. Attach the REXA bleed kit (Figure 1.6.8-2) to the open ports Extend/CW
and Retract/CCW. Follow the hydraulic lines to differentiate between
pressure direction (Figure 1.6.8-1).
General Information
20
General Information
21
The Xpac consists of two major components, the actuator (cylinder, feedback
and Electraulic power module) and the control enclosure. The actuator is installed
on the driven device, while the enclosure is remotely mounted. Connecting the
actuator and enclosure are the module cable and the feedback cable.
1.8.2 Actuator
The heart of the actuator is the Electraulic Power Module. Consisting of a motor,
gear pump, flow match valve (FMV), make-up oil reservoir, heater, thermostat
and bypass solenoid (spring fail units only), the Power Module delivers oil
at a nominal 2000 psi to a hydraulic cylinder. Four different size modules, B,
C, D and D, are available meeting hazardous area but non-explosion proof
requirements. For applications requiring hazardous area and explosion proof
approvals, two different power modules, C and D are available. The major
functional difference between the sizes is pumping volume and thus, the
maximum stroking speed of an actuator.
The B and C modules are driven with a stepper motor and therefore have a
slower frequency response then the D series modules which are driven with
General Information
22
General Information
servo motors. More detailed information on the frequency response and flow
rates can be found in product/technical memos. The only visible difference
among all 4 sizes of modules is the motor.
There are three types of hydraulic cylinders. On smaller size linear actuators
(thrust of 10000 lb or less and strokes of 6 inches or less), the L series cylinder
is manufactured from a solid block of aluminum. Larger size C series cylinders
are made of a fabricated tie-rod construction. The third type, used on rotary
(series R) and drive (series D) units, is a rack and pinion rotary design.
A position sensor, provides feedback position to the control electronics. The
feedback assembly is sealed in a NEMA 4X cover and mounted within or
adjacent to the cylinders. The connection of the position sensor is by direct
mechanical means.
The B and C modules shown in Figure 1.8.2-1&2 are the two sizes of stepping
motor modules. They both have cylindrical motor cases. The motor case
lengths are depicted in Figure 1.8.2-1&2 for module identification purposes.
With the exception of pump and motor size, these two modules share many of
the same components so both modules will be depicted on one rebuild diagram
for each of the applicable service sections.
23
General Information
24
General Information
The 1/2D and D modules shown in Figure 1.8.2-3 are the two sizes of servo
motor modules. They both have square case motors. The motor case lengths
are depicted in Figure 1.8.2-3 for module identification purposes. Again, with
the exception of pump and motor size, these two modules share many of the
same components so both modules will be depicted on one rebuild diagram for
each of the applicable service sections.
1/2D-Module
D-Module
25
The C and D explosion proof modules shown in Figure 1.8.2-4 are two sizes
of power modules offered for applications requiring hazardous area and
explosion proof approvals. The motor case lengths are depicted in Figure
1.8.2-4 for module identification purposes. With the exception of pump, motor
size, and cover, these modules share many of the same componenets as the
non-explosion proof modules so both modules will be depicted on one rebuild
diagram for each of the applicable service sections.
C- Module
D-Module
General Information
26
General Information
27
General Information
28
General Information
10 lbfin Max.
Operating Temperature
-40F to +221F
(-40C to +105C)
MATERIAL
Contact
Screw
Insulator Body
Polycarbonate, UL 94V-0,
Black
ELECTRICAL
Voltage Rating
300 Vac
Current Rating
20 Amp
Wire Range
12-24 AWG
12 lbfin Max.
Operating Temperature
-40F to +250F
(-40C to +125C)
MATERIAL
Contact
Copper Alloy
Screw
Insulator Body
Voltage Rating
300 Vac
Current Rating
20 Amp
Wire Range
10-28 AWG
29
30
General Information
Each actuator has an internal hydraulic bypass circuit. This circuit creates a
direct connection from one side of the hydraulic cylinder to the other. It is useful
for relieving internal pressure in the actuator and allowing an external load to
move the actuator. The nut labeled bypass on the actuator face as shown in
Figure 1.8.4-2 controls this circuit. Turning this bypass in all the way puts the
unit in its normal operation. Turning the bypass out 1 to 2 turns will open this
bypass circuit.
Note: This bypass nut is only on units without internal solenoids.
Each pressure gauge on the actuator has its own on/off isolation valve (Figure
1.8.4-2). This valve should remain off unless pressure is being read from the
gauge. This will protect the gauge from constant cycling, thus extending its life.
When closing this valve you will create an internal pressure trap in the gauge;
therefore, you should not expect to see 0 psi when off.
Gauge
Gauge
CW Off
CCW On
CW Off
CCW On
Bypass
CW Off
CCW On
31
2 Delivery
2.1 RECEIPT
REXA makes every effort to package products to avoid damage in shipping.
Upon receipt inspect the crate and make note of any physical damage. If severe
damage is present, then consideration should be given to rejecting the shipment
and contacting the shipping company concerning in-transit damage claims.
2.2 STORAGE
If the actuator and control enclosure sub-assemblies are not immediately
installed, provisions for storage must be made. The equipment should not
be removed from the original containers and should be protected from the
elements. The ambient environment must be:
Cleanno airborne particles or contaminants.
Non Corrosiveminute quantities of gases can concentrate in a
confined area.
Dryrelative humidity must be sufficiently low to prevent moisture
condensation on chilled metal components.
Temperaturerecommended storage temperature is between
Delivery
32 Delivery
2.3 UNPACKING
The REXA Xpac actuator is shipped filled with oil and ready to be installed.
It has been operated, tested and thoroughly inspected. After removing the
actuator from the packaging, inspect it for any signs of mechanical damage
that may have occurred during shipping. Immediately report any damage to the
factory.
Compare the contents to the packing list included with every shipment.
Immediately report any discrepancies to the factory.
Volts to Ground
0600
Condition 1
900 mm (3 ft)
Exposed live parts are on one side and no live or grounded parts are on the
other side of the working space. Or, exposed live parts on both sides are
effectively guarded by wood or other suitable insulating materials. Insulated
wire or insulated busbars operating at not over 300 V to ground shall not be
considered as live parts.
33
Delivery
35
3 Electrical Installation
CONTROL ENCLOSURE OVERVIEW
The Block Diagram (Figure 3) on the following page gives a general overview of
the Control Enclosure and Actuator installation.
Note: Not all actuators will have all the options shown in Figure 3.
Optional Construction:
Hazardous Locations: CSA Class 1, Div. 2, Groups A, B, C & D,
T3
Available Units: All units in Table 1.4.2-3 are available
Protection Method: Non-Incendive (non-sparking), limitation of
surface temperatures
Ambient Temperature: 40 to +104F (-40 to +40C)
Hazardous Locations: CSA Class 1, Div.1, Groups C & D, T3
Available Units: All units in Table 1.4.2-3 are available except
D-P9 AND D-P40
Protection Method: Explosion Proof and Intrinsically Safe
Ambient Temperature: Refer to Table 1.4.2-3
Electrical Installation
37
Electrical Installation
38
Electrical Installation
Incoming Voltage*
Maximum
Current
Required
VA
Rating
B Module
4.0 amp
500
C Module
8.5 amp
1100
D Module
20.0 amp
2400
D Module
10.0 amp
2400
2D Module
20.0 amp
4800
D,P9
25.0 amp
9000
D,P40
50.0 amp
21000
39
Be suitable for the Voltage and Full Load Ampere Rating of all downstream equipment supplied by the Panel;
The supply disconnecting device shall be one of the following types:
(a) Switch-disconnector with fuses, in accordance with IEC 60947-3,
utilization category AC-23B or DC-23B.
(b) As above, except one that has an auxiliary contact that in all cases
causes switching devices to break the load circuit before the opening of
the main contacts of the disconnector.
(c) A circuit breaker suitable as an isolation device per IEC 60947-2.
(d) Any other switching device in accordance with an IEC product
standard that also meets the isolation requirements of IEC 60947-1 and
is appropriate for on-load switching of the largest motor or other inductive loads.
Be approved for use as a disconnect for the country in which this equipment is installed.
Be provided with a Lock Out Tag Out capability in the Off (Down) position.
The Handle must be RED in color to indicate it is suitable as an E-Stop
device.
3.2.2 Grounding
Protective Earth Ground
A dedicated Protective Bonding Conductor (Protective Earth, PE) must be
provided. The conductor must be connected to the terminal labeled PE or
Protective bonding provides protection against electrical shock and
should be provided at both Control and Actuator.
Electrical Installation
40
Electrical Installation
3.2.5 Cordage
It is the responsibility of the Installer of this equipment to supply a suitable
length of heavy duty supply cordage. It should meet the following requirements:
It must be approved for use in the country in which this equipment is
installed or bear the <HAR> Mark.
The maximum length of the cordage should not exceed the values
established by the National Electric Code of the country in which it is
installed.
41
The outer jacketing of the cordage should be rated for exposure to water,
oil and other similar substances.
The Voltage and Ampere rating of this equipment, as noted on the
Manufacturers Identification Label, should be consulted when selecting
the proper size (mm2) of the cordage.
A suitable industrial style attachment plug should be selected for connecting to the branch circuit. As an alternative, the end that terminates
at the building supply source may be permanently connected in accordance with local wiring rules.
The supply cordage should be routed to the Control Cabinet in a manner
that does not allow it to be stepped on, pinched, subject to abrasion,
excessive bending, become a trip hazard or subject to other abuse.
Refer to REXA interconnect drawings for details of interconnect cable
requirements.
Electrical Installation
42
Electrical Installation
Branch Fuse(s)
B, 115 Vac
none
B, 230 Vac
none
B, 24 Vdc
B, 48 Vdc
C, 115 Vac
none
none
C, 24 Vdc
D, 115 Vac
none
D, 230 Vac
none
none
none
none
24/48
Vdc
Power
Supply
115 V Power
Supply
Power
Supply
Fuse
Location
Description
Voltage
(V)
Amperage
(A)
SC I/R
(A)
43
Type
Size
F1
250
35
GMC
5 20mm
F2
24 Vdc Supply
250
35
GMC
5 20mm
GMA
5 20mm
A15QS
Form 101
GMA
5 20mm
5 20mm
4
8
F3
250
35
F4
Trip Solenoid
150
100000
F5
Fail Solenoid
250
35
F6
Fail Solenoid
250
35
GMA
F7
Heater
250
35
GMA
5 20mm
F8
Heater
250
35
GMA
5 20mm
F1
250
35
GMC
5 20mm
F2
24 Vdc Supply
250
35
GMC
5 20mm
F3
250
35
GMA
5 20mm
F4
Trip Solenoid
150
100000
A15QS
Form 101
F5
Fail Solenoid
250
100
GMA
5 20mm
F7
Heater
250
100
GMA
5 20mm
Branch
Fuse
Protection
3.3 CABLES
Each Actuator and Control Sub-Assembly are interconnected by a set of cables.
These cables are supplied by REXA. The following will help you identify the
cables.
Electrical Installation
44
Electrical Installation
Insulation:
COLOR CODE
1. RED
2. WHITE
3. BLACK
Jacket: GRAY
Cable O.D.:
0.230-0.250
45
Insulation:
COLOR CODE
PAIR 1 BLUE WITH BLUE
TRIAD BROWN & BROWN & GREEN/YELLOW
Jacket: GRAY
Cable O.D.:
0.4-0.45
Electrical Installation
46
Electrical Installation
Insulation:
COLOR CODE
1. ORANGE
2. BLUE
3. GRAY
4. GREEN
Jacket: GRAY
Cable O.D.:
0.60-0.65
47
Insulation:
Jacket: BLACK
Cable O.D.:
0.70
Max. Length
Feedback Cable
Step or Servo
700 ft
Module Cable
Stepper
300 ft*
Servo
700 ft
Resolver Cable
Servo
700 ft
Heater/Solenoid Cable
Servo
700 ft
* 300 ft limit is for 16 AWG Cable. Consult factory for longer lengths.
Electrical Installation
48
Electrical Installation
If Feedback and Resolver cables are run with other equipment cables,
be sure those cables are signal level only. No high power Cables.
Power Module Cable(s) for Stepper Motor units can be in the same
conduit with each other, but must be separate from the Feedback Cable.
Conduit and Conduit fittings suitable for the environment must be used.
Failure to do so may cause ingress of contaminants or water into the
enclosure.
49
Must maintain IP66 for steel, IP67 for stainless and fiberglass electronics
enclosures, as well as actuator assembly.
Follow the National Electrical Code (NEC) and appropriate Local Codes
for installation of Industrial equipment.
Electrical Installation
50
Mechanical Installation
4 Mechanical Installation
The Xpac can operate any device requiring force and stroke or torque and
rotation. These include louvers, dampers, variable speed drives and valves.
While the instructions below are primarily focused on valves, they also apply to
any device that may be controlled by the Xpac.
51
With the actuator separated from its mounting, rotate the driven device
to the closed position.
Note: Be aware that not all bolt patterns are square; refer to layout drawing for
reference.
b)
c)
d)
e)
f)
Check alignment of assembly. Ensure that the actuator face and mounting bracket are parallel, with no gaps.
g)
Mechanical Installation
52
Mechanical Installation
53
the spring axis. Installation of the driven device within 5 of this position is
acceptable.
Actuators are usually shipped in the fail position. Refer to Appendix M, Manual
Operators, for information concerning the Handwheel or Manual Hydraulic Pump.
CAUTION!
a)
With the actuator separated from its mounting, rotate the driven device
to the fail position.
Note: Be aware that not all bolt patterns are square; refer to layout drawing for
reference.
b)
c)
d)
f)
Check alignment of assembly. Ensure that the actuator face and mounting bracket are parallel, with no gaps.
Mechanical Installation
54
Mechanical Installation
The following operation requires the unit to be in the closed position; if it is not,
use the handwheel or manual hydraulic pump. Refer to Appendix M, Manual
Operators, for information concerning the Handwheel or Manual Hydraulic
Pump. If the unit is not supplied with a Handwheel or Manual Hydraulic Pump,
the unit must be connected to the electronics and manual operation used to
drive it to the closed position. Refer to Manual Mode in section 6.
a)
With the actuator separated from its mounting, rotate the driven device
to the closed position.
Note: Be aware that not all bolt patterns are square; refer to layout drawing for
reference.
b)
c)
d)
e)
f)
Check alignment of assembly. Ensure that the actuator face and mounting bracket are parallel, with no gaps.
g)
55
CAUTION!
a)
With the actuator separated from its mounting, rotate the driven device
to the retracted position.
b)
Retract the actuator stem to a position that will allow mounting the
actuator without contacting the valve stem. If the optional handwheel is
not available, the unit must be connected to the electronics and manual
operation used to drive it to the closed position. Refer to Manual Mode
in section 6.
c)
Place the actuator onto the driven devices mating surface and loosely
install the mounting hardware.
d)
Extend the actuator stem until the coupling contacts the valve stem.
e)
Thread the driven device stem into the coupling for a distance of at
least one and one half times the stem diameter and use a lock nut
against the coupling to prevent the stem from rotating out.
Note: There are wrench flats machined on the actuator stem for this purpose. No
damage will occur if the actuator stem is rotated.
f)
Mechanical Installation
56
Mechanical Installation
g)
Securely tighten the mounting connection. Visually inspect the stem for
any noticeable indication of bending.
For all other orientations, support the actuator in a manner that prevents any
noticeable indication of stem bending. Securely tighten the mating connection.
Manually stroke the actuator and carefully observe the stem for any evidence of
lateral (side to side) misalignment.
h) For verification, once the mounting hardware is tight and the actuator is
installed, de couple the actuator shaft. If any movement of the actuator
shaft can be seen during the process, loosen the mounting hardware,
realign the actuator and repeat steps f, g and h.
57
CAUTION!
CAUTION!
Mechanical Installation
58
Mechanical Installation
a)
With the actuator separated from its mounting, rotate the driven device
to the retracted position.
b)
Retract the actuator stem to a position that will allow mounting the
actuator without contacting the valve stem. If the optional handwheel is
not available, the unit must be connected to the electronics and manual
operation used to drive it to the closed position. Refer to Manual Mode
in section 6.
c)
Place the actuator onto the driven devices mating surface and loosely
install the mounting hardware.
d)
Extend the actuator stem until the coupling contacts the valve stem.
e)
Thread the driven device stem into the coupling for a distance of at least
one and one half times the stem diameter and use a lock nut against the
coupling to prevent the stem from rotating out.
Note: There are wrench flats machined on the actuator stem for this purpose. No
damage will occur if the actuator stem is rotated.
f)
g)
Securely tighten the mounting connection. Visually inspect the stem for
any noticeable indication of bending.
For all other orientations, support the actuator in a manner that prevents any
noticeable indication of stem bending. Securely tighten the mating connection.
Manually stroke the actuator and carefully observe the stem for any evidence of
lateral (side to side) misalignment.
h) For verification, once the mounting hardware is tight and the actuator is
installed, de couple the actuator shaft. If any movement of the actuator
shaft can be seen during the process, loosen the mounting hardware,
realign the actuator and repeat steps f, g and h.
59
.56
.81
1.00
20 lbft
200 lbft
650 lbft
30 lbft
250 lbft
700 lbft
Mechanical Installation
60
Mechanical Installation
The connecting link and other linkage should be selected to withstand the
maximum load imposed by the drive. This will vary depending upon the
effective length of the arm. The following equation should be used to determine
the minimum safe working load of the connecting linkage:
Load=
For most installations, the optimum alignment of the drive arm and the driven
(damper) arm is when they are parallel to each other and perpendicular
to the connecting linkage at mid-rotation. Refer to Figure 4.4.2-2. This is
accomplished by a combination of linkage length and drive arm adjustments.
A slotted spline connection between the drive arm and shaft provides multiple
mating angles (5-10 intervals).
61
5 Start-Up Considerations
Start-Up Considerations
62
Start-Up Considerations
5.2 ALIGNMENT
Any noticeable bending of the actuator stem or driven device should be
immediately corrected. Not only will operation be impaired, but damage to the
actuator seals and bushings or driven device may occur. When mounting the
actuator to the driven device the actuator shafts and couplings MUST align
properly.
Start-Up Considerations
64
Start-Up Considerations
DRIVE
Drive units can create an extraordinary amount of force. Any misalignment of
the drive/driven arms, or incorrect linkage arrangements, can cause damage to
the actuator or the driven device. All mechanical connections and stroke limits
should be set carefully and inspected.
Note: If the actuator is stroked beyond the factory set cylinder limit, the display
will show CylEnd while the down key is held. If the enter key is pressed, the display
will show TooLow. Position Lo will need to be calibrated higher until this warning
goes away.
arrow.
or
arrow.
arrow.
Start-Up Considerations
66
Start-Up Considerations
The Actuator has now been calibrated. It is recommended at this point that
all Current Status be reset to 0. Refer to Current Status menu section for
procedure.
To enter the Auto mode:
Simultaneously press Auto ( ) and ENTER ( ).
Line 1 of the display will change to Auto followed by the Current
Status.
Line 2 will be blank.
When the keys are released
Line 2 will display the current Position.
Once mounted, the spring stops should be adjusted to a position that transfers
torque onto the driven device at the fail position.
2
3
CAUTION!
Note: Each actuator is tested and shipped from the factory with the thread seal
and jam nut lightly torquedenough to seal during factory acceptance testing.
This procedure assures that the sealing rubber is undamaged and will properly
seal once the stroke adjustor is fully adjusted in the field by the end user, and the
threaded elements are firmly tightened to full torque.
Start-Up Considerations
68
Start-Up Considerations
Clockwise Adjuster
6. Using light oil and a small brush or squirt can, generously lubricate the
thread seal rubber and the threads of the adjustment screw.
7. Carefully pry the thread seal washer away from the end cap and then
pull and twist it back and forth to carefully slide it along the adjustment
screw threads to gain adjustment clearance.
8. The actuator stroke adjustment can now be made using the threaded
adjustment rod. This rod has a hollow hex in the end to allow easy
adjustment.
WARNING:
As the stroke adjusters are turned in, fluid will be displaced
and need to leak out of the system. Failure to exhaust fluid
will damage internal components of the actuator.
9. The actuator is shipped from the factory with this adjustment rod
threaded fully out to the end of travel to give the full rotation of the
actuator. The adjustment screw can only be rotated clockwise (inward)
from this shipped position.
Caution: A mechanical lock at the end of the threads restricts inadvertent
disassembly outward. Rotating the adjustment screw counterclockwise (outward)
from this end position may cause damage to the hardware.
Start-Up Considerations
70
Start-Up Considerations
11. The number of adjustment screw rotations needed to achieve the 5 degree rotational adjustment of the actuator depends on the size (model)
of the actuator and the pitch of the adjustment thread on the adjustment
screw. The Table 5.5.1 shows this relationship.
12. After final positioning of the adjustment screw to achieve the desired
actuator rotation, readjust the position of the thread seal along the
adjustment screw threads to contact the end cap. Caution: use generous lubrication during this step to assure no damage to the rubber seal
by the threads.
13. Reposition the countersunk washer and the jam nut and torque the jam
nut to the requirements of the Table 5.5.1.
14. Tighten the hydraulic fitting that was loosened in step 4.
R2500/R5000
3.3
50
R10000/R20000
2.0
150
R50000/R100000
2.0
300
R200000/R400000
1.2
375
to provide the desired actuator stop position. The total adjustment range is 5
degrees minimum. Table 5.5.1 shows the adjustment achieved from one turn of
the adjustor.
The jam nut is repositioned after adjustment is complete and torqued to the final
tightness value specified.
Jam nut
Drive square
Adjustment
screw
Figure 5.5.2 R200000/R400000 Stroke Adjuster
Start-Up Considerations
72
o Setup
o Automatic (Auto)
o Manual (Local Man, RemoteMan)
) and
Note: The actuator will no longer follow a control signal when in setup mode.
To scroll from column to column, you must have the column header in the
display and press ENTER ( ). This will scroll from left to right and then repeat.
To scroll up and down a column, use the
and
arrows.
X2 Control
Parameters
Menu
Only if
Flow Char = On
Only if
Sol. Seat = On
Requires
Special
Construction
Only if
Signal Type
= Analog
Signal Hi
Only if
Signal Type
= Analog
Signal Lo
Position Hi
Position Lo
CALIBRATE
CS 90% Pt
CS 10% Pt
Only if
Signal Type
= Analog or
Commun
Flow Char
Cal. Stroke
Sol. Seat
Seat Load
Seat Ld Cyl
Only if
Signal Type
= Analog or
Commun
Bumpless
NA if Signal
Type = 1 Cont
Min Mod
Max Hi Spd
Deadband
Accum Pres
Accum Dir
Rechrg Time
Warn Pres
Rechrg Pres
Accumulator
Surge Offpt
Only if
Surge Bkpt
= Off
Version
Close Pres
Open Pres
Password
00000
Xmitter
Hi
Xmitter
Low
Pos
Xmitter
SB - only if
Sig. Type = Analog
Accum. = No &
Booster Pump = Off
BP - only if
Drive Type = Servo
& Surge Bkpt = Off
Only if
Surge Bkpt
Off
See SB below
Surge Bkpt
See BP below
Boost Pump
Relay #2
Relay #1
Drive Type
Stall Time
OUTPUTS
DRIVES
Power On
Trip
Only if
Signal Type
= Commun
Shed Time
Only if
Signal Type
= Analog or
Commun
Failsafe
Only if
Signal Type
= Pulse
Pulse Inc
Only if
Signal Type
= Pulse
Pulse Dur
Signal Type
INPUTS
If 2-Speed =
Bkpt >> Lo
Up/Dn >> Dn
Only if
2-Speed
= Bkpt
Speed Bkpt
Max Dn Spd
Max Lo Spd
2-Speed
Lo Accel
Accel Bkpt
Hi Accel
Gain
If 2-Speed
= Up/Dn
Max UP Spd
SPEED/
ACCEL
CONTROL
Strokes x1k
Starts x1k
Over Temp
Low Oil
Strokes x1k
Starts x1k
Over Temp
Low Oil
Cl Pres bad
Op Pres bad
Op Pres bad
Cl Pres bad
Stall
SLC Stop
Direction
CS bad
Fb bad
SLC Fb bad
Shed Time
Pressure bd
Drive fault
A/D Fail
Mem Fail
HISTORIC
STATS
Stall
SLC Stop
Direction
CS bad
Fb bad
SLC Fb bad
Shed Time
Pressure bd
Drive fault
A/D Fail
Mem Fail
CURRENT
STATS
76
Signal Lo is the Input Signal, typically 4 mA, that corresponds to Position Lo.
Signal Hi is the Input Signal, typically 20 mA, that corresponds to Position Hi.
Signal Lo and Signal Hi are only visible in the menu if Signal Type = Analog.
Range: 0.0 to 25.0 mA
Note: Unknwn appears if control signal failure occurs while calibrating.
Error appears, briefly, if an unacceptable value is entered. The unacceptable
value is rejected and the previous value is retained.
Note: If Failsafe does not = Off, input signal value must be greater than 2.5 mA
and the span must be greater than 3.8 mA. Refer to INPUTS menu.
Note: If Failsafe = Off, the span for Signal Hi must be greater than 3.8 mA or vice
versa.
78
Deadband sets the maximum deviation allowed between Input Signal and
current position before actuator movement in Auto mode.
Units: % of calibrated stroke
Range: 0.05 to 5.00 % of calibrated stroke`
The deadband should not be set any smaller than the process requires. Check
to ensure the actuator is not reacting to noise in the control signal, but to
actual signal changes.
Bumpless {Bumpless Transfer} sets the total time the actuator takes to travel
from its current position to a new target control position when the actuator is
switched from either Manual or Setup into Auto. This feature is designed as
a safeguard in the event the control signal was changed while the actuator
was not in Auto mode. When the unit is switched into Auto and the Bumpless
parameter is On, the actuator seeks the new target position at less than normal
speed. The actuator will take 100 small steps to reach the new target position in
the time set as the bumpless parameter. A delay will be defined between each
step until the actuator reaches the new target position.
This feature only appears in the menu if the incoming control signal parameter
Signal Type is set to Analog or Commun.
If Bumpless is set to any value other than Off when the actuator is switched
to Auto and the deviation between the incoming control signal and the
actuators current position is LESS than ten times the dead band parameter,
the operation of the actuator is the same as Bumpless = Off.
If Bumpless is set to any value other than Off when the actuator is switched
to Auto and the current deviation between the incoming control signal and
the actuators current position is GREATER than ten times the dead band
parameter, the operation of the actuator is to:
Divide the Bumpless time parameter by 100 to define the time interval
between actuator steps. These steps are how the actuator will track to
its new control position.
Divide the deviation between the current actuators position and the new
control signal position by 100. This defines the size of each step.
Once the actuator reaches the control signal set point the actuator will resume
normal operation.
Only in menu if Signal Type=Analog and Accumulator=No, and Booster Pump=
No.
See INPUTS and DRIVES menus.
Units: Seconds
Range: Off or, from 10 to 990 seconds
80
Seat Ld Cyl {Seat Load Cylinder}: Specifies whether or not the actuator employs
a seat load cylinder. This yes or no option is set at the factory.
Refer to Appendix B, Stem Connection & Seat Loading Methods, for additional
information.
Seat Load {Seat Load Switching}: Specifies that the actuator does not employ
a seat load cylinder (Off) or that a seat load cylinder is employed and the value
entered is the transition point at which the seat load cylinder is engaged/
disengaged via solenoid action.
Sol. Seat {Solenoid Seating}: Uses software to allow the stored energy of
a failsafe actuator to provide the seating force. Can only be used on linear
failsafe actuators where the fail direction is the same as the seating direction.
Replaces the elastic coupling and seat load cylinder for these applications.
Cal. Stroke {Calibrated Stroke}: When Sol. Seat = On, Cal. Stroke can be set
from .3" to 99.9" in one inch increments.
Flow Char {Flow Characterization}: The actuator is designed to have a linear
relationship between Control Signal and stroke (10% CS, 10% stroke, etc.) The
ability to modify this characteristic can assist in loop tuning or linearization of
a control scheme. Changing this actuator characteristic can have a profound
effect on the behavior of the control loop and should only be undertaken wtih
a thorough understanding of the effect. The stroke position can be modified
at 10% control signal intervals. The only restriction is that each stroke position
must be at least 2.5% from its neighbors.
CS 10% Pt thru CS 90% Pt {Control Signal 10% Point thru Control Signal
90% Point): When Flow Char= On, parameters CS 10% Pt thru CS 90% Pt
are added to the CONTROL menu. Each of these 9 parameters specifies
the desired actuator position when the Analog control signal is equal to the
corresponding point. Operation between Setpoints is linear.
Units: % of calibrated stroke
Range: CS 10% Pt: 2.5 to CS 90% Pt 97.5
Each calibrated stroke must be at elast 2.5% distant from the adjacent position.
Ex.; If CS 10% Pt= 2.5 when a 10% Control Signal is applied, the actuator will
travel 2.5% of calibrated stroke.
Max Hi Spd {Maximum High Speed} specifies the maximum motor speed when
operating in the Auto mode when 2-Speed is set to Off or to Bkpt. This speed
parameter will go above 100%, but the output of a stepper module will be
reduced if setting it beyond this value. The motor may run into stall conditions.
Conversely, turning the speed down below 100% will allow the motor to make
more torque if a stalling condition exists. When running a stepper module near
the low temperature specification the speed may need to be lowered to avoid
occasional stalls
Max Up Spd {Maximum Up Speed} is in the menu when operating in Auto mode
when 2-Speed is set to Up/Dn. Max Up Spd specifies the maximum motor
speed when moving from Position Lo toward Position Hi.
Range: 5 to 125 % of actual motor speed, but no greater than Max Hi Spd.
Gain: In the Auto mode Gain is used to determine how motor speed is adjusted
as the actuator approaches the target position. The higher the Gain setting, the
closer the actuator will get to the target position before decelerating. The lower
the Gain setting, the further away the actuator will be from the target position
when it begins to decelerate. This value is typically factory set; however, it may
be changed should the application warrant it.
Range: 1 to 250
82
84
Max Man Spd {Maximum Manual Speed} defines the maximum motor speed
when operating in Setup. Sets the maximum motor speed when operating in
Local Man or RemoteMan only if 2-speed = Off.
Range: 5 to 125 (but no greater than Max Hi Spd)
Default: 80
Signal Type: Selects the main control signal(s) for the Auto mode. Allows
the user to define the type of control signal being sent to the actuator.
Select Analog, 1 Cont, 2 Cont, Pulse, or Commun.
Note: 1 Cont, 2 Cont and Pulse are only included in the Inputs menu if Contact/
Pulse Inputs Board is installed. Refer to Appendix E, Pulse Operating System, and
Appendix Q, Contact Input Options, for additional information.
When Signal Type = Analog, the main control signal is the 4-20 mA
analog input. This selection provides the full modulating capability of the
actuator.
When Signal Type = 1 Cont (one contact), two position operation
open/closed positionis selected. The applied signal defines actuator position.
If the Open input is active (powered), the actuator goes to Position Hi. If the
Open input is not active (un-powered), the actuator goes to Position Lo.
When Signal Type = 2 Cont (two contacts), manual modulation
operation is selected. The main input signals are the Main contacts Open and
Close inputs of the Contact Input Board. If both inputs are active or inactive,
the actuator remains in its current position. If only the Open input is active, the
actuator travels towards Position Hi. If only input Close is active, the actuator
travels towards Position Lo.
Note: Actuator will continue to move in desired direction as long as a signal is
present or until target is reached.
Pulse Dur {Pulse Duration} sets the minimum time that the Pulse Input must
remain active in order to be recognized as a valid signal. A continuous signal
may be measured as multiple pulses.
86
Ex.; With pulse Duration set at 50 milliseconds, a 100 millisecond pulse equals
two pulses.
Units: ms (milliseconds)
Range: 10 to 999 milliseconds
Pulse Inc {Pulse Increment} sets the amount of actuator travel for each valid
pulse received. It only appears in menu if Signal Type= Pulse
Range: 0.1 to 5.0 % of calibrated stroke
The input signals are the Main Contacts Open and Close inputs of the Contact
Input Board. If only input Open is active and meets the requirements of Pulse
Dur, the value set in Pulse Inc is added to (direct acting) or subtracted from
(reverse acting) the current position to become the new target position. The
actuator then seeks this new position. If only input Close is active and meets
the requirements of Pulse Dur, the value set in Pulse Inc is subtracted from
(direct acting) or added to (reverse acting) the current position to become the
new target position. The actuator then seeks this new position. If both inputs
are active or inactive, the actuator holds its current position.
Pulse input has the ability to control the actuator by an Open or Close pulse
signal. Each Input signal must meet the minimum pulse duration. For a period of
time it will be recorded as a number of pulses based on defined pulse duration.
Target position can be adjusted based on the number of pulses and defined
pulse increments. The motor will then move in desired direction until new target
position has been reached.
When Signal Type = Commun, the full modulating capability of the actuator is
also provided. However, the controlling signal is the Setpoint Parameter which
may be written via one of the communication interfaces( HART or Foundation
Field Bus ).
Note: When set to Commun, parameters Failsafe and Shed Time are
added to this menu.
Failsafe defines the position the actuator moves to via the motor if the Analog
control signal falls below 2.5 mA.
Only in menu if Signal Type = Analog.
Select:
Shed Time specifies the maximum amount of time allowed between writes to
parameter Setpoint before the action specified in parameter Failsafe is taken.
When set to OFF, no action is taken.
Only in menu if Signal Type = Commun
Trip parameter defines the active state of the AUX CLOSE input on the
Contacts Inputs Board. This secondary input is used to override the main input
to cause actuator movement with the aid of a solenoid/spring package or with
an accumulator. This Failsafe position is factory configured to either calibrated
end, but not to both, and is not field reversible.
When Trip = Off, trip function is not used
When Trip = Unpwrd, and AUX CLOSE input is not powered, go to end point
(Trip = Logic )
When Trip = Pwrd, and AUX CLOSE input is powered, go to end point (Trip =
Logic I)
Note: Trip = Unpwrd/Trip = Pwrd is only selectable if Contact Inputs Board is installed.
88
Power On parameter defines the mode the Control Enclosure will be in when
Main Power is applied.
When Power On = Last, (the default), on power up or reset, the actuator will
return to its previous operating mode (Auto, Local or Setup).
When Power On = Local, on power up or reset, if the previous mode was Auto,
the actuator will enter Local mode instead.
Drive Type defines the type of motor, stepper or servo, provided with the power
module(s) and is factory set to Step or Servo.
Stall Time defines the maximum time, 1 to 50 Sec (seconds), allowed for the
actuator to travel 1% of calibrated stroke before a stall is assumed. If 1% travel
is not detected in the time set, the motor drive is stopped, the drive is reset
and a restart attempted. A maximum of five retries are allowed before a stall
error (alarmed) is declared.
Note: Stall Time also sets the point at which the Booster Pump will turn off.
Note: If Stall Time = 1-5 seconds, the Booster Pump will turn off 2.5% away
from the target position.
Note: If Stall Time = 6 -10 seconds, the Booster Pump will turn off 1.0%
away from the target position.
Note: If Stall Time > 10 seconds, the Booster Pump will turn off 0.5% away
from the target position.
Main Valves sets the maximum deviation allowed before the main valves are
opened. This is a special parameter; used only with actuators which use an
accumulator for all motive force (no power module).
90
Note: The main valve off point is set by parameter Stall Time.
Note: Main Valves is only visible in the Drives menu if Foundation field bus
is installed. Requires special construction.
Surge Offpt{Surge Offpoint} will only appear in the DRIVES manu when the
Surge Bkpt has a value other than off. Surge Offpt is defined in percentage
of calibrated stroke. This percentage will define a distance the actuator will
be away from its new target position when it changes the state of the surge
solenoid during a surge event. On system with high speed trips this will allow
the controller to change states of the solenoid to anticipate hitting the new
target position and eliminate overshoot during a surge event. With Surge Offpt
set to off the actuator will command the surge solenoid to change state when
it reaches its new target position during a surge event. This will result in some
overshoot of the new position as the actuator will continue to travel while the
solenoid changes states. Surge Offpt has a settable range of 0.1% up to 5%
less than the current Surge Break point value.
Warn Pres.
Rechrg Time {Recharge Time} adjusts the maximum time allowed for a recharge
cycle to complete. A recharge cycle ends when either the Rechrg Pres setting
is reached or the Rechrg Time expires. In either case, the actuator resumes
tracking the control signal. Recharge Time is factory set.
Accum Dir {Accumulator Direction} defines the direction the accumulator will
cause the actuator to travel during a Trip. This parameter is factory set based
on information provided. This parameter is necessary to inform the CPU as to
which direction, Pos Lo (Position lo) or Pos Hi (Position Hi), to operate the motor
during a recharge cycle after a Trip.
92
Relay #1
Relay #2
Pos Xmitter
Xmitter Low
Xmitter Hi
Password
Version
Relay #1 defines the point in % of calibrated stroke at which relay output 1 is
active. The relay will be active when the actuator position is = or < the value set
in Relay #1
Pos Xmitter {Position Transmitter} defines the action of the position transmitter
output as being direct acting, Dir or reverse acting, Rev.
When set to direct acting, a 4 mA output corresponds to Position Lo.
When set to reverse acting, a 4 mA output corresponds to Position Hi.
Xmitter Low {Transmitter Low} is the parameter to calibrate the Output zero of
the 4-20 mA Position Transmitter.
To calibrate the 4mA Zero, Set a digital multi-meter,
DMM, to read milliamps (mA) DC. Connect the
DMM to the Position Transmitter Output on the CPU.
Connect the Red lead of the DMM to the LOOP OUT
terminal. Connect the black lead of the DMM to LOOP
INT RTN terminal. Press Enter to access this setting.
Xmitter Hi {Transmitter Hi} is the parameter to calibrate the Output span of the
4-20 mA Position Transmitter.
To calibrate the 20 mA Span, Set a digital multi-meter,
DMM, to read milliamps (mA) DC. Connect the
DMM to the Position Transmitter Output on the CPU.
Connect the Red lead of the DMM to the LOOP OUT
terminal. Connect the black lead of the DMM to LOOP
INT RTN terminal. Press Enter to access this setting.
The Value displayed on the REXA display corresponds
to Digital bits. Each increment or decrement is steps
of 4 bits and will increment or decrement the current
output by one micro-amp (1 mA).
Note: The Position Transmitter will output the mA
signal that corresponds to the actuators current
position until the Enter button is pressed and the =
sign is flashing. When the = sign is flashing, the
output will change to the Span or Hi Calibration
value.
Note: Xmitter Hi and Xmitter Lo values are not
transmitted over the bus in Foundation Fieldbus
units.
94
Once the position transmitter calibration is complete, there is no need to recalibrate the transmitter for changes in actuator span. Changing the actuator
span will cause the transmitter span to automatically re-calibrate its output.
Version X01_0_AA_xxxx
The error counters generally operate in the Auto mode (inclusive of Local
Man/RemoteMan) only. Errors detected in Setup are not recorded. If the Auto
mode is entered from Setup with an existing error, the error is not counted. The
only exception to the Auto mode only rule is the Mem Fail counter which
operates only in Setup mode.
Usage indicators only record in Auto mode.
The CURRENT STATS error counters and usage indicators may be reset to zero
by the following;
While in Setup and the counter/indicator to be reset is on display:
Press (E)nter the equals sign begins blinking
Press (D)own the value field resets to zero
Press (E)nter the new count is now zero
Note: If the (U)p key is pressed prior to step 3, the old count is returned to the
display and will be retained if the (E)nter key is then pressed.
96
Mem fail indicates the number of times that the Setup parameter memory failed
to erase/write a parameter value properly.
A/D fail indicates the number of times the A/D converter failed to respond to a
command.
Drive fault indicates the number of times a drive fault was detected.
Pressure bd {Accumulator pressure bad} indicates the number of times that the
Accumulator pressure transducer was detected out of range. The transducer is
considered out of range if the 4-20 mA signal is less than 3 mA or greater than
21 mA.
Shed Time indicates the number of times that a Setpoint update did not occur
within the time set in parameter Shed Time.
SLC Fb bad {Seat Load Cylinder Feedback bad} indicates the number of times
that the feedback from the seat load cylinder (4-20mA) was below 2 mA.
Fb bad {Actuator feedback} indicates the number of times that the actuators
feedback was below 2 mA.
Cs Bad {Analog control signal bad} indicates the number of times the analog
control signal was below 2.5 mA
Direction {Direction error} indicates the number of times the motor was stopped
because the actuator was detected moving in the wrong direction.
SLC stop {Seat Load Cylinder stop} indicates the number of times the actuator
stopped at the Seated position of the seat load cylinder but the control signal
did not require the valve to be seated (control signal was > 0.2%)
Stall indicates the number of times the motor was stopped because the Stall
Time was reached prior to achieving 1% of travel.
Note: For units with a Seat Load Cylinder, Stall will indicate the number
of times the Seated position was reached while position of the main
cylinder was greater than 1% above Position Lo.
Op Pres bad indicates the number of times that the open side pressure
transducer was detected out of range. The transducer is considered out of
range if the 4-20 mA signal is less than 3 mA.
Cl Pres bad indicates the number of times that the close side pressure
transducer was detected out of range. The transducer is considered out of
range if the 4-20 mA signal is less than 3 mA.
Low Oil indicates the number of times the reservoir level switch detected a low
oil condition.
Over Temp indicates the number of times the oil temperature switch detected
an over temperature condition.
The following two parameters are usage counters; each indicates the number of
times an event counter reached a count of 1000. Event counters are located
in volatile memory. Each power-on/reset causes the loss of any partial 1000
counts. Entry into Setup followed by a return to Auto mode preserves partial
1000 counts.
Starts x1K indicates the number of times the motor was started while in Auto.
e.g., Starts x1K=2 is 2000 starts.
Strokes x1K indicates the number of times the actuator traveled a distance
equal to its calibrated stroke divided, by 1000.
e.g., Strokes x1K=2 is 2000 strokes.
98
Last Error is not a counter; it indicates the last error detected. May be manually
reset to None in Setup {press (E)nter while Last Error is on display}. It is
automatically reset to None from reset/power on. The following may appear in
the value field (field 6) if a Last Error occurs:
Fb bad
Cs bad
Dir er
Stall
DrvFlt
Pwr 15
PresBd
Shed
Op bad
Cl bad
Lo Oil
HiTemp
SLC Fb
SLCstp
ADfail
MemBad
Field 1
Au t o
Po s i t i o n =
St a t u s : OK
Field 3
0.0%
Field 4
Field 5
Field 6
100
AutoTrip (Field 1) indicates the unit is in Auto mode with the Trip input active.
Refer to the INPUTS menu.
Control Sig {Live Control Signal} (Field 4) identifies the value of the analog
control signal. The display is 0 -100 % for easy comparison with
the position display.
Value (Field 6): None when parameter Signal does not equal Analog.
Low when current signal is more than 0.5% below Signal Lo.
High when current signal is more than 0.5% above Signal Hi.
102
target position. The value is prefixed with - if the current position is less than
the target and with + if above the target position.
Value (Field 6): 0.0 to 99.9% of calibrated stroke
and
keys may be
A-1
The mechanical limit switches are independent devices installed on the yoke
of the linear units and in the feedback housing area of rotary or drive units.
Electrical connections are made directly to the switches independent of REXA
electronics. Position will be indicated regardless of actuator power status.
A.1 LINEAR
A.1.1 General Specifications
Quantity: 2 or 4
Type: Single Pole, Double Throw (SPDT), Form C.
Rating: 5 amp @ 24 Vdc, 0.5 amp @ 125 Vdc,
GRP. A, B, C & D.
Appendix A
A-2
GRP. A, B, C & D.
Appendix A
A-3
Appendix A
A-4
A.2 ROTARY
A.2.1 General Specifications
Quantity: 2 or 4
Type: Single Pole, Double Throw (SPDT)
Rating: 10 amp @ 24 Vdc, 0.5 amp @ 125 Vdc,
Appendix A
A-5
Appendix A
A-6
Appendix A
Switch Cam
Set Screw
B-1
Appendix B
B-2
Appendix B
of the actuator. Lower rated couplings are available for applications that require
reduced seat load.
The force indicator on the elastic coupling is a pin captured in a slot on the
side of the coupling. As the coupling compresses, the pin slides in the slot. A
scribed line marks the rated output position.
Enclosed spring couplings (not shown) have a small telltale pin protruding
from the top or bottom. As the coupling compresses, the pin is drawn into the
coupling. When the pin is flush with the coupling, it is at its rated output.
Note: The output of each coupling may be verified through the pressure gauges.
Note: To translate pressure gauge readings into actuator output, use the following
formula:
B-3
pumps hydraulic fluid into the actuator cylinder, the output shaft will begin to
extend. Once the force on the extension shaft reached the preset 80% of the
actuators rated output, the pressure in the top of the actuator cylinder will reach
the limit that begins to compress the spring on the seat load cylinder. This will
occur when the driven device reaches its end of stroke. As the pressure builds
within the actuator cylinder, oil flows into the SLC, designated by the high
pressure flow arrow and retracts the SLC shaft. When the spring is compressed
to the full nominal working pressure, the position feedback of the SLC will trigger
the power module to shut off. The rated actuator output is now applied to the
driven device and retained within the cylinders by the Flow Matching Valves.
Appendix B
B-4
Appendix B
Wire colors
Terminal
+15 Vdc
Red
15V
Feedback (+)
White
4-20
Feedback (-)
Black
GND
B-6
B.5 CALIBRATION
Operation of the actuator is the same as a unit with an elastic coupling. The
only difference is at the seated position. Instead of compressing a coupling,
the spring on the SLC is compressed until the indicator on the SLC leg is at the
seated point. See Figure B.5-1.
Appendix B
B-7
Appendix B
B-8
Appendix B
Reset Switch
C-1
C. Accumulator Fail
Appendix C
Accumulator
C-2
Accumulator
Appendix C
Actuator Cylinder
Isolation Valve
Trip Solenoid
Power Module
Trip Speed
Control Valve
Trip Solenoid
Accumulator
Pressure Gauge
Accumulator Bottle
Auxiliary
Reservoir
C-3
Actuator Cylinder
Isolation Valve
Trip Solenoid
Port A (Unit will
trip on power loss)
Power Module
Trip Speed
Control Valve
Optional Plumbing
B
Port B (Unit will not
trip on power loss)
Trip Solenoid
Accumulator
Pressure Gauge
Accumulator Bottle
Pressure Transducer
Appendix C
Accumulator
C-4
Accumulator
DRIVES Menu
The DRIVES menu provides the following:
Drive Type
Stall Time
Boost Pump
Accumulator
Rechrg Pres
Warn Pres
Rechrg Time
Accum Dir
Accum Pres
Reference the DRIVES Menu in Modes of Operation & Control Parameters.
C.3 RECHARGING
The recharge cycle will only occur if:
1. The CPU is in the Auto mode when power is restored after a loss of
power or removal of trip signal,
And
2. The pressure transducer output is less than Rechrg Pres
If CPU is NOT in Auto mode when power is restored or trip signal removed, the
unit MUST be placed in Auto and the reset button pushed.
Appendix C
C-5
IMPORTANT!
Appendix C
Accumulator
C-6
Accumulator
WARNING!
Appendix C
C-7
C.5 DISCHARGING
There will be times that it is necessary to fully discharge the oil-side of the
accumulator system; such as when maintenance is being performed. To
perform this task, do the following:
1. Remove power to the actuator.
2. If the unit is fail in place during power loss, place both solenoid valves in
position B as shown in Figure C.4-2.
3. Open the manual bypass located on the front face of the module. Refer
to Figure C.5.
4. Check to ensure that all the pressure gauges read 0 psi.
Gauge
Gauge
CW Off
CCW On
CW Off
CCW On
Bypass
CW Off
CCW On
Appendix C
Accumulator
D-1
Appendix D
Booster Pump
Appendix D
! Important !
Motor power and motor resolver cables for the power module and booster
pump motors must be shielded! The shield of each is connected to the
green ground screw on the back panel of the control enclosure only.
Failure to follow the above may inhibit the proper operation of the
actuator.
E-1
E.2 INSTALLATION
Wiring for pulse input is performed at the contact inputs board located on top of
the CPU. Terminal block TB3 provides six terminals to connect the HIGH signal
and the LOW signal. Refer to Figure E.2-1, -2, for wiring options.
Appendix E
E-2
Appendix E
E-3
ON state:
Most AC and many DC solid state switching devices require a minimum current
flow in order to remain in the closed state. If this minimum current exceeds the
input signal current at the activation voltage, the current flow may be increased
by adding a shunt resistor across the input signal terminals of the pulse auxiliary
board.
OFF state:
The OFF state leakage current must be less than 1 mA. Diode clamps or RC
snubber networks placed across mechanical relays and the semiconductor
junctions of solid state switches will pass some current in the OFF state. If this
leakage exceeds 1 mA, a resistor added across the input signal terminals will
bypass the current.
Appendix E
E-4
E.5 TUNING
On systems that utilize position feedback to control the pulse train, it is usually
necessary to tune the Pulse Increment to replicate the actuator speed. The ideal
Pulse Increment is determined by dividing the Pulse Duration (in seconds) by the
total stroking time and multiplying by 100%.
Duration
Pulse Increment
= Pulse
Stroke Time 100%
To allow for motor acceleration, round this value up to the next highest tenth of a
percent.
Appendix E
F-1
The following are the error messages which appear on line 1 in place of
Status:OK when one or more errors are detected. If more than one error
is active, each is displayed at 1 second intervals in a repeating fashion. All
errors are cleared by: 1. Cycling the main power; 2. Pushing the reset switch;
3. Entering the Setup mode; or 4. By means identified in the Cleared by
sections which follow. To fix some of these alarm code errors it may be
necessary to refer to the Trouble Shooting and Repair manual.
FB bad
Cause: The actuators main Feedback is below 2 mA; either (+) or (-) 15
fail is set, or A/D fail is set.
Indicators: Alarm and Warning opens.
FB bad is displayed.
Actuator will not move.
Cleared by: Self clearing when Feedback >2 mA, or when 15 fail or
A/D fail clears.
Appendix F
F-2
CS bad
Cause: The analog Control Signal is below 2.5 mA; either the (+) or (-) 15
fail is set, or A/D fail is set.
Indicators: Alarm and Warning relays open.
CS bad is displayed.
Actuator will move to Failsafe position.
Cleared by: Self clearing when Control Signal >2.5 mA, or when 15 fail
or A/D fail clears.
Stall
Cause: After five attempts the actuator was unable to move 1% of stroke
within the defined Stall Time.
The Seated position was reached on the Seat Load Cylinder while the
position of the main cylinder was greater than 1% above Position Lo.
Indicators: Alarm and Warning relays open.
Stall is displayed.
Actuator will not move.
Cleared by: Any control signal change which effects movement in the
opposite direction of the stall will clear the stall error.
Dir error
Cause: The actuator was detected moving in the wrong direction.
Indicators: Alarm and Warning relays open.
Dir error is displayed.
Actuator will not move.
Cleared by: Cleared by cycling main power on, by pushing the reset switch,
or entering the Setup mode.
Appendix F
F-3
Drv fault
Cause: At least one motor drive has detected a problem.
Indicators: Warning relay opens.
Drv fault is displayed.
The actuator may or may not continue normal operation
depending on actuator construction.
Cleared by: CPU will attempt to clear Drv fault error until fault condition is
corrected.
+15 fail or
-15 fail
Cause: The (+) or (-) 15 volt power supply is out of range if it exceeds a (+)
or (-) 10% error band.
Indicators: Alarm and Warning relays open.
(+/-)15 fail is displayed.
Actuator will not move.
Cleared by: CPU will attempt to clear fail error until fault condition is corrected.
Pres bad
Cause: The accumulators pressure transducer {Accum Pres} is out of
range if the 4-20 mA signal is less than 3 mA or greater than 21
mA.
Indicators: Warning relay opens.
Pres bad is displayed.
Actuator continues to operate normally.
Cleared by: Cleared when transducer signal is greater than 3 mA or less
than 21 mA.
Appendix F
F-4
Pres low
Cause: The accumulator pressure {Accum Pres} is below the value set in
parameter Warn Pres.
Indicators: Warning relay opens.
Pres low is displayed.
Actuator continues to operate normally.
Cleared by: Successful Accumulator recharge cycle.
Op Pres bad or
Cl Pres bad
Cause: The open or close pressure transducer is out of range. The transducer is considered out of range if the 4-20 mA signal is less than 3 mA..
Indicators: Warning relay opens.
Op or Cl Pres bad is displayed.
Actuator continues to operate normally in Auto mode..
Cleared by: Transducer signal being greater than 3 mA.
Low Oil*
Cause: The reservoir oil level switch indicates that the oil level is low.
Indicators: Alarm and Warning relays open.
Low Oil is displayed.
Actuator continues to operate normally but will not attempt a
recharge cycle.
Appendix F
F-5
Over Temp*
Cause: The oil temperature switch indicates an over temperature condition
exists.
Indicators: Warning relay opens.
Over Temp is displayed.
Actuator attempts to continue to operate normally.
Cleared by: Temperature returning to normal range.
Slc Fb bad
Cause: The Feedback signal from the Seat Load Cylinder is less than 2 mA.
Indicators: Alarm and Warning relays open.
Slc Fb bad is displayed.
Actuator will not move.
Cleared by: Self clearing when Feedback >2 mA.
Slc stop
Cause: The actuator has detected a Seated position from the seat load
cylinder feedback, but the main cylinder is more than 0.2% from its
Seated position.
Indicators: Warning relay opens.
Slc stop is displayed.
The actuator continues with normal operation; however, the
main cylinder may not seat properly.
Cleared by: Any control signal change which effects movement in the
opposite direction in which the stop occurred will clear the error.
Appendix F
F-6
Key bad
Cause: A bad reading of the key pad has occurred.
Indicators: Warning relay opens.
Key bad is displayed.
Actuator continues to operate normally.
Cleared by: Self clearing with a valid keypad reading.
Mem fail
Cause: A memory location containing a Setup parameter value has failed to
erase/write.
Indicators: Alarm and Warning relays open.
Mem fail is displayed.
Actuator will not move.
Cleared by: Only cleared by cycling main power or pushing the reset
switch.
No inp bd
Cause: 1. Signal Type is set to 1 Cont, 2 Cont, or Pulse when a contact
input board is not installed or is faulty.
2. Trip is not Off.
Indicators:
Cleared by: Changing the Signals menu parameter(s), or (with power off)
installing the required board.
Appendix F
F-7
A/D fail
Cause: The A/D converter on the CPU Board has failed to respond.
Indicators: Alarm and Warning relays open.
A/D fail is displayed.
Actuator will not move.
Cleared by: Self clears if/when A/D responds.
Appendix F
G-1
Appendix G
G-2
If the change in control signal is less than the Surge Breakpoint, the actuator
operates normally. If the change in control signal is greater than the Surge
Breakpoint (and in the surge motion direction), then the solenoid opens and the
actuator is driven by the spring to the new position.
If the actuator is overshooting during a surge event, the Surge Offpt parameter
can be used to eliminate this overshoot. Reference the Drive Menu section in
Modes of Operation & Control Parameters in the IOM for additional information
regarding setting the Surge Offpt parameter. Increasing this Surge Offpt
parameter will reduce the overshoot until the unit begins to slow down too much
prior to hitting its target position. Figure G.1-1 illustrates the overshoot from
a surge event. Increasing the Surge Offpt would be required to eliminate this
issue. Figure G.1-2 shows the expected results when the Surge Offpt parameter
is tuned properly. Figure G.1-3 shows an undershoot condition. Decreasing the
Surge Offpt percentage will reduce the undershoot.
Various configurations of the spring package may have been provided. The
spring may be installed to open or close the driven device. Fail-safe position
can either be lock in place or in the surge direction.
Appendix G
G-3
Appendix G
G-4
G.2 INSTALLATION
The fast response solenoid is a 3-way configuration and piped external to the
hydraulic cylinder. An adjustable needle valve is in line with the solenoid to allow
custom adjustment of the surge speed to meet a particular installation.
The wires used for the surge solenoid are a pair of blue wires in the module
cable. Connection for the solenoid within the control enclosure is made to TB4
of the power supply assembly as shown in G.2-1.
Refer to Figures G.2-1,-2,-3.
G.3 CALIBRATION
Refer to the CONTROL menu for additional information.
Appendix G
G-5
Appendix G
G-6
Appendix G
G-7
Appendix G
H. Build Numbers
Appendix H
Build Numbers
H-2
Build Numbers
Appendix H
A
Actuator Type
L=REXA Block Cylinder
C=Commercial Cylinder
Output
C=2000 lbf (8896 N)
D=4000 lbf (17793 N)
E=5000 lbf (22241 N)
F=10000 lbf (44482 N)
G=15000 lbf (66723 N)
H=20000 lbf (88964 N)
I=30000 lbf (133447 N)
J=40000 lbf (177929 N)
M=60000 lbf (266893 N)
K=80000 lbf (355858 N)
L=120000 lbf (533787 N)
Z=Special
Actuator Stroke
A=.75" (.02 m)
B=2" (.05 m)
C=4" (.10 m)
D=6" (.15 m)
E=8" (.20 m)
F=11" (.28 m)
G=16" (.40 m)
H=22" (.56 m)
I=28" (.71 m)
J=36" (.91 m)
K=42" (1.07 m)
L=48" (1.22 m)
Z=Special
15
1
14
Output Limit/Protection
C=37%-73% Total Output
D=74%-99% Total Output
E=100%-140% Total Output (Std)
Z=Special
13
12
11
10
Heater/Solenoid Voltage
A=120 Vac
B=240 Vac
C=125 Vdc
F= 48 Vdc
E=24 Vdc
G=12 Vdc
N=No Heater
Z=Special
Design
X2-A
X2-B
Z=Special
Construction
S=NEMA 4X, (Std)
T=NEMA 4X, TNEMEC Paint
C=NEMA 4X Class1/Div2
D=NEMA 4X, Class1/Div2, TNEMEC Paint
N=CE, IP66, ATEX Zone 2
Z=Special
Mechanical Switches
N=No Switches (Std)
A=2 SwitchesSPDT 4X Hi Temp
C=2 SwitchesSPDT Class1/Div2
E=4 SwitchesSPDT Class1/Div2
G=2 SwitchesDPDT Class1/Div2
J=4 SwitchesDPDT Class1/Div2
O=Oil Level
D=Oil Level & 2 SwitchesSPDT Cl1/Div2
F=Oil Level & 4 SwitchesSPDT Cl1/Div2
H=Oil Level & 2 SwitchesDPDT Cl1/Div2
K=Oil Level & 4 SwitchesDPDT Cl1/Div2
Z=Special
Cable Connections
S=Terminal Strip (Std)
Q=Quick Disconnect
Z=Special
Manual Override
H=Handwheel/Drill Drive
P=Manual Hydraulic Pump
N=None (Std)
Z=Special
The most common codes are shown above. However, the Xpac 2 is an engineered product and REXA practices a policy of continuous improvement. As
such, additional codes may be available or may be added without notice. Please contact the factory for information on any code not shown above.
H-3
A
Actuator Type
R=Rotary Cylinder
D=Drive Unit
Output
C=2500 lbfin (282 Nm)
D=5000 lbfin (565 Nm)
E=10000 lbfin (1130 Nm)
F=20000 lbfin (2260 Nm)
G=50000 lbfin (5650 Nm)
H=100000 lbfin (11300 Nm)
I=200000 lbfin (22597 Nm)
J=400000 lbfin (45194 Nm)
Z=Special
14
13
2
12
Actuator Rotation
A=90 degree (Std)
B=180 degree
C=270 degree
D=280 degree
E=120 degree
Z=Special
3
11
10
6
7
15
Design
X2-A
Z=Special
Output Limit/Protection
C=37%-73% Total Output
D=74%-99% Total Output
E=100%-140% Total Output (Std)
Z=Special
Construction
S=MEMA 4X, (Std)
T=NEMA 4X, TNEMEC Paint
C=NEMA 4X, Class1/Div2
D=NEMA 4X, Class1/Div2, TNEMEC Paint
N=CE, IP66, ATEX Zone 2
Z=Special
Mechanical Switches
N=No Switches (Std)
C=2 SwitchesSPDT
E=4 SwitchesSPDT
G=2 SwitchesDPDT
O=Oil Level
D=Oil Level & 2 SwitchesSPDT
F=Oil Level & 4 SwitchesSPDT
H=Oil Level & 2 SwitchesDPDT
Z=Special
Cable Connections
S=Terminal Strip (Std)
Q=Quick Disconnect
Z=Special
Manual Override
H=Handwheel/Drill Drive
P=Manual Hydraulic Pump
N=None (Std)
Z=Special
Temperature Rating
S=Standard 200F (93C) Temp Rating
H=High 250F (121C) Temp Rating
R=Remote Feedback Std. Temp
Z=Special
Heater/Solenoid Voltage
A=120 Vac
B=240 Vac
C=125 Vdc
F=48 Vdc
E=24 Vdc
G=12 Vdc
N=No Heater
Z=Special
The most common codes are shown above. However, the Xpac 2 is an engineered product and REXA practices a policy of continuous improvement. As
such, additional codes may be available or may be added without notice. Please contact the factory for information on any code not shown above.
Appendix H
Build Numbers
H-4
Build Numbers
Appendix H
A
Power Module Size
B=B Module
C=C Module
D=D Module
F=D Module
G=2D Module
H=D-P9 Module
I=D-P40 Module
M=2C Xpac Module
Z=Special
15
Design
A=X2
B=X2, Design 2
C=X2, Design 3
D=X2, Design 4
Z=Special
Power Supply
A=120 Vac
B=240/208 Vac
C=480 Vac
D=12 Vdc
E=24 Vdc Std 14to185F (-10to+85C)
F=48 Vdc
G=125 Vdc
I=240 Vac 3Phase
J=480 Vac 3Phase
K=380 Vac 3Phase
L=600 Vac 3Phase
Z=Special
14
13
2
Control Signal
G=Analog 4-20mA w/ Surge Sup. (Std)
P=Pulse Operating System
T=Two Position - 1 Signal
M=Manual - 2 Signal
J=Hart 420 mA w/ Surge Sup.
F=Foundation fieldbus
Z=Special
11, 12
10
3
Area Approvals
S=General Locations (Std)
C=CSA C1/D2 (B,C,D)
N=CE, IP66, ATEX Zone 2
9
4
Enclosure Material
P=Painted Steel, NEMA 4 (Std)
S=304 Stainless Steel, NEMA 4X
F=Fiberglass, NEMA 4X
Z=Special
Controls
E=External (Std)
I=Internal
C=Int Controls
with Ext Buttons/Window
D=Int Controls
with Ext Buttons/No Window
Z=Special
Variations
N=None (Std)
T=Quick Release Connectors
U=Quick Release/Conform Coat
Electronics Supplied
Y=Yes
Z=Special
Software
AA=Standard Software (Std)
FA=Foundation Fieldbus
LA-Standard w/Auto Mode Ind.
Options
N=No Options (Std)
A=Accumulator System
S=Hydraulic Surge Option
L=Seat Load Cylinder
D=Accum. & Seat Load Cylinder
H=Surge & Seat Load Cylinder
Z=Special
Position Transmitter
A=Active 420mA
P=Passive 420mA (Std)
L=Active 4-20mA, Local Mode Ind.
M=Passive 4-20mA, Local Mode Ind.
Z=Special
The most common codes are shown above. However, the Xpac 2 is an engineered product and REXA practices a policy of continuous improvement. As
such, additional codes may be available or may be added without notice. Please contact the factory for information on any code not shown above.
H-5
MOUNTING SYSTEMS
Linear Series Actuator
1 2 3 4 5 6 7 8 9
Actuator Type
N=No Mounting Hardware
L=REXA Block Cylinder
C=Commercial Linear Cylinder
Output
C=2000 lbf (8896 N)
D=4000 lbf (17793 N)
E=5000 lbf (22241 N)
F=10000 lbf (44482 N)
G=15000 lbf (66723 N)
H=20000 lbf (88964 N)
I=30000 lbf (133447 N)
J=40000 lbf (177929 N)
M=60000 lbf (266893 N)
K=80000 lbf (355858 N)
L=120000 lbf (533787 N)
Z=Special
1
9
2
Actuator Stroke
A=.75" (.02 m)
B=2" (.05 m)
C=4" (.10 m)
D=6" (.15 m)
E=8" (.20 m)
F=11" (.28 m)
G=16" (.40 m)
H=22" (.56 m)
I=28" (.71 m)
J=36" (.91 m)
K=42" (1.07 m)
L=48" (1.22 m)
Z=Special
Valve Attachment
S=Down Seat Split Clamp
B=Up Seat Split Clamp
N=No Clamp
4
7
3
Certified Drawings
A= Actuator Outline
C=Control Enclosure Outline
E=Electrical Interconnect Schematic
O=Actuator & Interconnect
D=Actuator & Enclosure & Interconnect
N=No Certified Drawings
5
6
Packaging
D=Domestic (Std)
E=Export
Inspection Level
S=Standard Inspection
A=Advanced Inspection (Level II)
P=Premium Inspection (Level I)
Variations
N=No Factory Mount & Calibrate
A=L2000 Mount & Calibrate
B=L4K-L10K Mount & Calibrate
C=L15K & Up, Mount & Calibrate
Other Documentation
B=Bill of Materials
C=Certificate of Conformance
F=Final Inspection Report
A=All (BOM, COC & FIR)
N=No Other Documentation
8
2
7
3
Valve Attachment
N=No Mounting Hardware
A=4" or less
B=6" to 10"
C=12" to 14"
D=16" to 20"
E=20" and up
4
5
Packaging
D=Domestic (Std)
E=Export
Inspection Level
S=Standard Inspection
A=Advanced Inspection (Level II)
P=Premium Inspection (Level I)
Variations
N=No Factory Mount & Calibrate
A=Factory Mount & Cal 4" or Less
B=Factory Mount & Cal 6" to 10"
C=Factory Mount & Cal 12" to 14"
D=Factory Mount & Cal Over 16"
Other Documentation
B=Bill of Materials
C=Certificate of Conformance
F=Final Inspection Report
A=All (BOM, COC & FIR)
N=No Other Documentation
Certified Drawings
A= Actuator Outline
C=Control Enclosure Outline
E=Electrical Interconnect Schematic
O=Actuator & Interconnect
D=Actuator & Enclosure & Interconnect
N=No Certified Drawings
The most common codes are shown above. However, the Xpac 2 is an engineered product and REXA practices a policy of continuous improvement. As
such, additional codes may be available or may be added without notice. Please contact the factory for information on any code not shown above.
Appendix H
Build Numbers
H-6
Build Numbers
Appendix H
Actuator Type
D=Drive Unit
Output
C=2500 lbin (282 Nm)
D=5000 lbin (565 Nm)
E=10000 lbin (1130 Nm)
F=20000 lbin (2260 Nm)
G=50000 lbin (5650 Nm)
H=100000 lbin (11300 Nm)
I=200000 lbin (22597 Nm)
J=400000 lbin (45194 Nm)
Z=Special
9
2
Actuator Rotation
A=90 Degrees (Std)
B=180 Degrees
C=270 Degrees
D=280 Degrees
E=120 Degrees
Z=Special
Valve Attachment
S=Standard Base & Arm
A=Standard Base & Custom Arm
B=Custom Base & Standard Arm
C=Custom Base & Custom Arm
4
5
Packaging
D=Domestic (Std)
E=Export
Inspection Level
S=Standard Inspection
A=Advanced Inspection (Level II)
P=Premium Inspection (Level I)
Variations
N=No Linkage Kit
C=Custom Linkage Kit
Other Documentation
B=Bill of Materials
C=Certificate of Conformance
F=Final Inspection Report
A=All (BOM, COC & FIR)
N=No Other Documentation
Certified Drawings
A= Actuator Outline
C=Control Enclosure Outline
E=Electrical Interconnect Schematic
O=Actuator & Interconnect
D=Actuator & Enclosure & Interconnect
N=No Certified Drawings
The most common codes are shown above. However, the Xpac 2 is an engineered product and REXA practices a policy of continuous improvement. As
such, additional codes may be available or may be added without notice. Please contact the factory for information on any code not shown above.
H-7
Actuator Type
N=No Mounting Hardware
L=REXA Block Cylinder
C=Commercial Linear Cylinder
Output
C=2000 lbf (8896 N)
D=4000 lbf (17793 N)
E=5000 lbf (22241 N)
F=10000 lbf (44482 N)
G=15000 lbf (66723 N)
H=20000 lbf (88964 N)
Z=Special
Actuator
Stroke
A=.75" (.02 m)
B=2" (.05 m)
C=4" (.10 m)
D=6" (.15 m)
E=8" (.20 m)
F=11" (.28 m)
G=16" (.40 m)
Z=Special
1
17
Revision
A=Current Rev
16
Variations
N=None
2
15
14
3
Valve Attachment
S=Down Seat Split Clamp
B=Up Seat Split Clamp
N=No Clamp
13
4
Certified Drawings
A= Actuator Outline
C=Control Enclosure Outline
E=Electrical Interconnect Schematic
O=Actuator & Interconnect
D=Actuator & Enclosure & Interconnect
N=No Certified Drawings
12
5
Other Documentation
B=Bill of Materials
C=Certificate of Conformance
F=Final Inspection Report
A=All (BOM, COC & FIR)
N=No Other Documentation
11
10
6
9
7
8
Valve Stroke
A=" to 1"
B=1-18" to 1-78"
H=2" and up
Z=Special
Stem Height
A=4-"
B=6-316"
C=6-58"
D=8-78"
E=9-58"
Stem Thread
B=38"24
D="20
F="16
H=1"14
I=1-"12
Yoke Boss
A=2-18"
C=2-316"
E=3-916"
G=5"
Packaging
D=Domestic (Std)
E=Export
Inspection Level
S=Standard Inspection
A=Advanced Inspection (Level II)
P=Premium Inspection (Level I)
The most common codes are shown above. However, the Xpac 2 is an engineered product and REXA practices a policy of continuous improvement. As
such, additional codes may be available or may be added without notice. Please contact the factory for information on any code not shown above.
Appendix H
Build Numbers
K-1
K. Fieldbus
The Resource block and the Input/Output blocks are standard Fieldbus blocks
which implement the networking and control capability of a Fieldbus system.
The Transducer block is a custom block which is designed specifically to
connect an Xpac 2 actuator to a Fieldbus network. In a control application,
the Transducer block reads and writes process variables from the actuator and
passes these values to the network via the I/O blocks.
The Transducer block also provides access to all X2 actuator configuration
(Setup) parameters (excluding stroke calibration parameters). Any configuration
parameter which may be viewed or changed at the local Operators Panel may
also be viewed or changed over the Fieldbus network.
Appendix K
Fieldbus
K-2
Fieldbus
Resource block:
The Resource block provides device identification and some basic network
communications parameters.
There are no X2 actuator specific parameters in this block.
Appendix K
- Set the Transducer block parameter CONTROL_CHANNEL {Positioner Control Method} to CH1- Analog Output
Appendix K
Fieldbus
K-4
Fieldbus
- Set the Transducer block parameter CONTROL_CHANNEL {Positioner Control Method} to CH4- Discrete Output
Appendix K
Transducer block
The Transducer block links the XPac X2 actuator to the Input/Output
function blocks. It also provides access to all of the X2 actuators
configuration parameters. Other parameters which provide for control and
observation of the X2 actuator are also included.
All parameters may be viewed at any time. To change any parameter, the
block should be put in OOS (Out Of Service). To change any X2 actuator
configuration parameter, the X2 actuator must also be in Comm Setup
mode. The X2 actuators current mode may be viewed using parameter
MODE_STATUS {Mode\Status Byte}. The X2 actuators current mode
may be changed using parameter OPERATING_MODE {Operating Mode}.
CONTROL Menu
DEADBAND {Deadband}
Deadband
Min Mod
Bumpless
Appendix K
Seat Load
Sol. Seat
Cal. Stroke
Flow Char
CS 10% Pt thru
CS 90% Pt
Fieldbus
K-6
Fieldbus
Appendix K
SPEED/ACCEL Menu
MAX_HI_SPEED {Max Hi Speed}
Max Hi Spd
Max Up Spd
GAIN {Gain}
Gain
Hi Accel
Accel Bkpt
Lo Accel
TWO_SPEED {2 Speed}
2-Speed
Max Lo Spd
Max Dn Spd
Speed Bkpt
INPUTS Menu
SIGNAL_TYPE {Signal Type}
Signal Type
Pulse Dur
Pulse Inc
FAILSAFE {Failsafe}
Failsafe
Shed Time
TRIP {trip}
Trip
Power On
DRIVES Menu
Drive Type
Stall Time
Boost Pump
Main Valves
Surge Bkpt
ACCUMULATOR {Accumulator}
Accumulator
Rechrg Pres
Warn Pres
Rechrg Time
Accum Dir
Accum Pres
OUTPUTS Menu
RELAY_1 {Relay #1}
Relay #1
Relay #2
Pos Xmitter
Password {Password}
Password
Open Pres
Close Pres
Version
Appendix K
Mem fail
A/D fail
Drive fault
Pressure bd
Shed Time
SLC Fb bad
Fb bad
Cs bad
Direction
SLC stop
Fieldbus
K-8
Fieldbus
Appendix K
STALL {Stall}
Stall
Cl Pres bad
Op Pres bad
Low Oil
Over Temp
Starts x1K
Strokes x1K
Auto mode: Switches the X2 actuator to Auto mode for Setpoint tracking.
Panel Setup mode and Panel Local mode: These modes are only
selectable at the X2 actuators local Operators Panel and cannot be
invoked over the Fieldbus network.
The Mode\Status Byte also reports the presence of the Contact Input Board
if it is installed in the X2 actuator, and reports active status of the Trip input
(override signal).
RESPONSE_CODE {Response Code}: When an X2 actuator configuration
parameter is written, a response code is issued as part of the return
message indicating the relative success or failure of the write operation.
Conditional success: the data sent was too large, too small or imprecise. The X2 actuator has corrected the data by rounding down, rounding up, or rounding off the value sent prior to writing.
Failure Not Available: The write attempt was rejected because the
parameter is not used in this version of the X2 actuator or the parameter
is currently not usable due to settings of other parameters. When a
parameter is not available it is displayed with a value of 1.#QNAN.
Failure Wrong Mode: The write attempt was rejected because the X2
actuator was not in Comm Setup Mode.
Appendix K
Fieldbus
K-10 Fieldbus
Appendix K
ERROR_BYTE1:
main feedback failure
FB bad
SlcFb bad
CS bad
Dir error
-15 fail
+15 fail
Slc stop
actuator stall
Stall
ERROR_BYTE2:
motor drive fault
Drv fault
Pres bad
Pres low
bad keypad
Key bad
Mem fail
No inp bd
A/D failure
A/D fail
CPU failure
CPU fail
ERROR_BYTE3:
Op Pres bad
Cl Pres bad
Over Temp
low oil
Low Oil
Shed Time
Appendix K
Fieldbus
K-12 Fieldbus
Appendix K
M-1
M. Manual Operators
Appendix M
Manual Operators
Appendix M
HANDWHEEL REVOLUTIONS
Linear
Rotary
(90 of rotation/1000
lbin of rated torque)
~75
~200
C, D
~25
~65
~13
~33
Power Module
M-3
CAUTION:
Care must be taken to ensure the drill gun is limited to 2000
rpm. Running into a mechanical stop using a drill may
damage the actuator and potentially the equipment it is
attached to. As the actuator nears the end point, decrease
drill speed so damage doesnt occur.
Appendix M
Linear
Rotary
~1
~2.5
Manual Operators
Appendix M
Directional
control knob
WARNING!
M-5
Appendix M
Manual Operators
N-1
N. Digital Communications
Appendix N
Digital Communications
N-3
Appendix N
Digital Communications
Appendix N
TABLE OF CONTENTS
1. INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Who should use this document?. . . . . . . . . . . . . . . . . . . . . . .
1.4 Abbreviations and definitions . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
6
6
6
6
7
2. DEVICE IDENTIFICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. PRODUCT OVERVIEW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4. PRODUCT INTERFACES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Process Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Sensor Input Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Host interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1 Analog Input 1: Actuator Setpoint. . . . . . . . . . . . . . . . . .
4.3 Local Interfaces, Jumpers And Switches. . . . . . . . . . . . . . . .
4.3.1 Local Controls And Displays. . . . . . . . . . . . . . . . . . . . . .
4.3.2 Internal Jumpers And Switches. . . . . . . . . . . . . . . . . . .
8
8
8
8
8
8
8
8
5. DEVICE VARIABLES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6. DYNAMIC VARIABLES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7. STATUS INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.1 Device Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.2 Additional Device Status (Command #48). . . . . . . . . . . . . . . 10
8. UNIVERSAL COMMANDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.1 Supported Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9. COMMON-PRACTICE COMMANDS . . . . . . . . . . . . . . . . . . . . . . . 21
9.1 Supported Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.2 Burst Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10. DEVICE-SPECIFIC COMMANDS . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.1 Supported Device Specific Commands . . . . . . . . . . . . . . . 27
11. TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
12. PERFORMANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
12.1 Sampling Rates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
N-5
12.2 Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.3 Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.4 Self-Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.5 Command Response Times. . . . . . . . . . . . . . . . . . . . . . . . .
12.6 Delayed-Response. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.7 Non-Volatile Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.8 Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.9 Write Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.10 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
29
29
30
30
30
30
30
30
Appendix N
Digital Communications
1. INTRODUCTION
1.1 Scope
The Xpac Series X2 Rexa Electrohydraulic Actuator complies with HART
Protocol Revision 5.0. This document specifies all the device specific features
and documents HART Protocol implementation details. The HART functionality
of this Field Device is described sufficiently to allow its proper application in a
process and its complete support in HART capable Host Applications.
1.2 Purpose
This specification is designed to compliment other documentation (e.g., the
Xpac Series X2 Rexa Electrohydraulic Actuator Installation Manual) by providing
a complete, unambiguous description of this Field Device from a HART
Communication perspective
CPU
Appendix N
N-7
Definitions
Actuator
1.5 References
Hart Revision 5 specifications: HCF_SPEC-11, HCF_SPEC-54, HCF_SPEC-81,
HCF_SPEC-99, HCF_SPEC-127, HCF_SPEC-151, HCF_SPEC-183, HCF_SPEC307. Available from the HCF.
Xpac Series X2 Rexa Electrohydraulic Actuator Installation Manual, Available
from REXA.
2. DEVICE IDENTIFICATION
Manufacturer Name:
REXA
Model Name(s):
Manufacture ID Code:
5.0
Device Revision:
None
FSK
Actuator
X2
3. PRODUCT OVERVIEW
The X2 is an electrohydraulic actuator that is powered separately from the
primary analog input signal. The actuator and its electronics do not draw
current from the circuit which is used only for HART signaling.
The X2 is configured using the pushbuttons on the front panel of the device.
The analogue input of this device is interpreted by the device as a setpoint. The
setpoint can be treated linearly or characterized according to user input. The
Appendix N
Digital Communications
HART communication over the analog input is used primarily for monitoring of
position, signal, and cylinder differential pressure (may not be available on all
models).
4. PRODUCT INTERFACES
4.1 Process Interface
4.1.1 SENSOR INPUT CHANNELS
The X2 has sensors that measure actuator position, actuator differential
pressure, and analog input signal. The measurements from these sensors are
scaled by the device into engineering units and are available as variables using
HART communication.
Other sensors are available as options but are not available using HART
communication. These are described in the X2 manual.
Appendix N
N-9
5. DEVICE VARIABLES
This Field Device does not expose any Device Variables.
6. DYNAMIC VARIABLES
Two Dynamic Variables are implemented.
Meaning
Units
PV
SV
Pressure differential
psi
7. STATUS INFORMATION
7.1 Device Status
Bit 4 (More Status Available) is set whenever any status bit is detected.
Command #48 gives further detail.
Appendix N
Digital Communications
Appendix N
Bit
0*
Meaning
Class
Error
Error
Error
Not used
Not used
Not used
Not used
Not used
Error
Error
Error
Error
Error
Error
Warning
Actuator stall
Error
Warning
1**
Warning
2**
Warning
Bad keypad
Warning
Error
Error
A/D failure
Error
CPU failure
Error
1**
6**
2
N-11
0**
Error
1**
Error
2**
Warning
3**
Low oil
Warning
Not used
Not used
Not used
Not used
Information
Information
Not used
Not used
Not used
Not used
Not used
Not used
Not used
*Byte 0 refers to the HART interface board. The remaining bytes refer to the
controller board.
**Not available on all models.
Not used bits are always set to 0.
These bits are set or cleared by the self-test executed at power up, or following
a reset command. They are also set (but not cleared) by any failure detected
during continuous background self-testing.
Appendix N
Digital Communications
8. UNIVERSAL COMMANDS
8.1 Supported Commands
Command Number: 0
Command Name: Read Unique Identifier
Command Type: Read
Sets Configuration Changed: no
Description: Returns the manufacturer and device information needed for
other communication with the device. This command can be sent using short
addressing (polling address) and thus can be used before knowing the full
device address.
Request: no data
Response:
Byte 0: u8 - Device code for expansion 254
Byte 1: u8 Manufacturers code 222 for Rexa
Byte 2: u8 Manufacturers device code 128 for this device
Byte 3: u8 Number of preambles required for this device default is 5
Byte 4: u8 Universal command revision 5 for this device
Byte 5: u8 Transmitter revision 1 for this device
Byte 6: u8 Software revision 1 for this device
Byte 7: u8 Hardware revision multiplied by 8 8 for this device (revision of 1)
Byte 8: u8 Flags 0 for this device
Bytes 9 11: u24 Device ID
Command Errors: none
Appendix N
N-13
Command Number: 1
Command Name: Read Primary Variable
Command Type: Read
Sets Configuration Changed: no
Description: Returns the primary variable (position) and its units (%)
Request: no data
Response:
Byte 0: u8 Position units code 57 for this device which is the code for percent
Bytes 1-4: float Primary variable position for this device
Command Errors: none
Command Number: 2
Command Name: Read Current and Percent of Range
Command Type: Read
Sets Configuration Changed: no
Description: Returns the input signal in mA and the signal as a percent of the
signal scale.
Request: no data
Response:
Bytes 0-3: float Input signal in mA
Bytes 4-7: float Input signal as a percent of range in percent
Command Errors: none
Appendix N
Digital Communications
Command Number: 3
Command Name: Read Dynamic Variables
Command Type: Read
Sets Configuration Changed: no
Description: Returns the primary variable (position), the secondary variable
(pressure differential) and the input signal. The units of the PV and SV are also
returned.
Request: no data
Response:
Bytes 0-3: float input signal in mA
Byte 4: u8 Units code of the primary variable 57 (percent) for this device
Bytes 5-8: float The primary variable - position for this device
Byte 9: u8 Units code of the secondary variable 6 (psi) for this device
Bytes 10-13: The secondary variable pressure differential for this device
Command Errors: none
Command Number: 6
Command Name: Write Polling Address
Command Type: Write
Sets Configuration Changed: yes
Description: Sets the polling address for the device.
Request:
Byte 0: u8 Polling address. Can be 0 to 15. Since this device is controlled by the 4-20 signal, only polling address 0 should be used.
Appendix N
N-15
Response:
Byte 0: u8 Polling address
Command Errors:
2 Invalid parameter if the polling address is greater than 15
Command Number: 11
Command Name: Read Unique Identifier Associated with Tag
Command Type: Read
Sets Configuration Changed: no
Description: Returns device identification information if the device tag matches
the tag sent in this command.
Request:
Bytes 0-5: ascii The device tag which can be up to 8 text characters long.
Response: Note: the device only responds if the tag matches the tag saved in
the device. If the tag does not match, the device does not respond at all.
Byte 0: u8 - Device code for expansion 254
Byte 1: u8 Manufacturers code 222 for
Byte 2: u8 Manufacturers device code 128 for this device
Byte 3: u8 Number of preambles required for this device default is 5
Byte 4: u8 Universal command revision 5 for this device
Byte 5: u8 Transmitter revision 1 for this device
Byte 6: u8 Software revision 1 for this device
Byte 7: u8 Hardware revision multiplied by 8 8 for this device (revision of 1)
Appendix N
Digital Communications
Command Number: 12
Command Name: Read Message
Command Type: Read
Sets Configuration Changed: no
Description: Returns the message field saved in the device. The message
field can be up to 32 text characters long.
Request: no data
Response:
Bytes 0-23: ascii The message saved in the device up to 32 text characters long.
Command Errors: none
Command Number: 13
Command Name: Read Tag and Descriptor
Command Type: Read
Sets Configuration Changed: no
Description: Returns the tag field, the descriptor field, and the date field. All of
these fields are user settable. These fields can be used in whatever manner the
user wants.
Request: no data
Appendix N
N-17
Response:
Bytes 0-5: ascii The tag, up to 8 text characters long
Bytes 6-17: ascii The descriptor, up to 16 text characters long
Bytes 18-20: u8 The date as 3 unsigned bytes. The first byte represents
the day of the month (1 to 31), the second byte the month (1 to 12), and
the third byte the year minus 1900 (e.g. 2006 would be 106).
Command Errors: none
Command Number: 14
Command Name: Read Primary Variable Sensor Information
Command Type: Read
Sets Configuration Changed: no
Description: This command is included only for compatibility with certain DCS
systems. The data returned in this command is always constant.
Request: no data
Response:
Bytes 0-2: u24 Sensor serial number always 0 for this device
Byte 3: u8 units code 250 (not used) for this device
Bytes 4-7: float upper limit special code for not-a-number for this device
Bytes 8-11: float lower limit special code for not-a-number for this device
Bytes 12-15: float minimum span special code for not-a-number for this device
Command Errors: none
Appendix N
Digital Communications
Command Number: 15
Command Name: Read Primary Variable Output Information
Command Type: Read
Sets Configuration Changed: no
Description: This command is included only for compatibility with certain DCS
systems. The data returned in this command is always constant.
Request: no data
Response:
Byte 0: u8 - Alarm code 250 (not used) for this device
Byte 1: u8 - Transfer function 250 (not used) for this device
Byte 2: u8 - Primary variable units code 57 (percent) for this device
Bytes 3-6: float - Upper range always 100.0 for this device
Bytes 7-10: float - Lower range always 0.0 for this device
Bytes 11-14: float Damping value always 0.0 for this device
Byte 15: u8 Write protect code 250 (not used) for this device
Byte 16: u8 Private label code 250 (not used) for this device
Command Errors: none
Command Number: 16
Command Name: Read Final Assembly Number
Command Type: Read
Sets Configuration Changed: no
Appendix N
N-19
Description: Returns the final assembly number stored in the device. This
number is user settable and can be used for whatever the user wants.
Request: no data
Response:
Bytes 0-2: u24 The final assembly number. The value can range from 0 to
16777215.
Command Errors: none
Command Number: 17
Command Name: Write Message
Command Type: Write
Sets Configuration Changed: yes
Description: Sets the message field in the device
Request:
Bytes 0-23: ascii The message field, up to 32 text characters.
Response:
Bytes 0-23: ascii The message field, up to 32 text characters.
Command Errors: none
Command Number: 18
Command Name: Write Tag and Descriptor
Command Type: Write
Sets Configuration Changed: yes
Appendix N
Digital Communications
Description: Sets the tag field, the descriptor field and the date field in the device
Request:
Bytes 0-5: ascii The tag, up to 8 text characters long
Bytes 6-17: ascii The descriptor, up to 16 text characters long
Bytes 18-20: u8 The date as 3 unsigned bytes. The first byte represents
the day of the month (1 to 31), the second byte the month (1 to 12), and
the third byte the year minus 1900 (e.g. 2006 would be 106).
Response:
Bytes 0-5: ascii The tag, up to 8 text characters long
Bytes 6-17: ascii The descriptor, up to 16 text characters long
Bytes 18-20: u8 The date as 3 unsigned bytes. The first byte represents
the day of the month (1 to 31), the second byte the month (1 to 12), and
the third byte the year minus 1900 (e.g. 2006 would be 106).
Command Errors: none
Command Number: 19
Command Name: Write Final Assembly Number
Command Type: Write
Sets Configuration Changed: yes
Description: Sets the final assembly number in the device
Request:
Bytes 0-2: u24 The final assembly number. The value can range from 0 to
16777215.
Appendix N
N-21
Response:
Bytes 0-2: u24 The final assembly number. The value can range from 0 to
16777215.
Command Errors: none
9. COMMON-PRACTICE COMMANDS
9.1 Supported Commands
Command Number: 33
Command Name: Read Transmitter Variables
Command Type: Read
Sets Configuration Changed: no
Description: Returns up to 4 variables specified from the list of variables. For
this device, possible variable codes are
0. Input Signal
1. Position
2. Pressure differential
Request: Note: fewer than 4 parameters can be sent and the response will be
correspondingly shortened
Byte 0: u8 the transmitter variable code for slot 0
Byte 1: u8 the transmitter variable code for slot 1
Byte 2: u8 the transmitter variable code for slot 2
Byte 3: u8 the transmitter variable code for slot 3
Appendix N
Digital Communications
Response:
Byte 0: u8 the variable code for slot 0
Byte 1: u8 the units code for the variable in slot 0
Bytes 2-5: float the value of the selected variable in slot 0
Byte 6: u8 the variable code for slot 1
Byte 7: u8 the units code for the variable in slot 1
Bytes 8-11: float the value of the selected variable in slot 1
Byte 12: u8 the variable code for slot 2
Byte 13: u8 the units code for the variable in slot 2
Bytes 14-17: float the value of the selected variable in slot 2
Byte 18: u8 the variable code for slot 3
Byte 91: u8 the units code for the variable in slot 3
Bytes 20-23: float the value of the selected variable in slot 3
Command Errors:
2 Invalid parameter if the variable code is not 0, 1, or 2
Command Number: 38
Command Name: Reset Configuration Changed Flag
Command Type: Process
Sets Configuration Changed: yes (cleared)
Description: Clears the configuration changed flag for the HART master that
sent the command.
Appendix N
N-23
Request: no data
Response: no data
Command Errors: none
Command Number: 48
Command Name: Read Additional Status
Command Type: Read
Sets Configuration Changed: no
Description: Returns the device specific status bytes. These bytes indicate:
Byte 0
Bit 0: Invalid EEPROM state
Bit 1: Invalid EEPROM write
Bit 2: EEPROM write error
Byte 1
Bit 0: Main feedback failure
Bit 1: Seat load cylinder feedback failure
Bit 2: Control signal failure
Bit 3: Actuator direction error
Bit 4: -15v supply failure
Bit 5: 15v supply failure
Bit 6: Seat load cylinder stall
Bit 7: Actuator stall
Appendix N
Digital Communications
Byte 2
Bit 0: Motor drive fault
Bit 1: Bad pressure reading
Bit 2: Accumulator requires recharge
Bit 3: Bad keypad
Bit 4: EEPROM erase failure
Bit 5: Pulse board missing
Bit 6: A/D failure
Bit 7: CPU failure
Byte 3
Bit 0: Open direction pressure bad**
Bit 1: Close direction pressure bad**
Bit 2: Temperature too high**
Bit 3: Low oil**
Byte 4
Bit 0: Local manual control
Bit 1: Remote manual control
Byte 0 of the status codes refer to the HART interface board. The remaining
bytes refer to the controller board. Bits that apply to options that are not in the
delivered model will be set to 0.
**Not available on all models.
Request: no data
Appendix N
N-25
Response:
Bytes 0-4: u8 status data, each bit identifying the condition defined above.
Byte 5: u8 reserved
Byte 6: u8 operating mode 1 0 for this device
Byte 7: u8 operating mode 2 0 for in this device
Bytes 8-10: u24 analog output saturated 0 for this device
Bytes 11-13: u24 analog output fixed 0 for this device
Command Errors: none
Appendix N
Digital Communications
Appendix N
N-27
Appendix N
Digital Communications
Response: no data
Command Errors: none
11. TABLES
Command Types
Read returns data from the device
Write sends data to the device
Process sends a command to the device
Data Types
u8 unsigned byte (8 bit number)
s8 signed byte
u16 unsigned short integer (16 bits)
s16 signed short integer
u24 unsigned 24 bit integer
u32 unsigned long integer (32 bits)
s32 signed long integer
float IEEE floating point number
ascii packed ascii (see Hart foundation documentation for details)
Appendix N
N-29
12. PERFORMANCE
12.1 Sampling Rates
Typical sampling rates for HART are shown in the following table:
Primary position sensor sample
500 ms
Pressure differential
500 ms
500 ms
12.2 Power-Up
On power up, the transmitter goes through a self-test procedure (see section
12.4), which takes approximately 2 seconds. During this period, the device will
not respond to HART commands other than HART command 0.
12.3 Reset
Command 42 (Device Reset) is not implemented. A device reset buttons is
available inside the housing, which resets the main electronics board and the
HART communications board.
12.4 Self-Test
The self-test procedure is executed at power up or after a device reset. The
self-test includes:
Microprocessor
Configuration storage eeprom
Analog-to-digital converter
Digital-to-analog converter
This self-test takes about 2 seconds. During self-test following power-up or
reset, the device will not respond to HART commands.
Appendix N
Digital Communications
5 ms
Typical
20 ms
Maximum
150 ms
12.6 Delayed-Response
Delayed-response is not used.
12.8 Modes
The actuator can be in auto, manual, or setup modes, however these modes are
accessible only from the pushbuttons on the main panel. In setup mode, HART
communication is disabled.
12.10 Damping
Damping is not used.
Appendix N
N-31
Device type
Actuator
HART revision
5.0
No
electrohydraulic
1: 4 - 20mA analog
No
Appendix N
24
Burst mode?
Yes
Write-protection?
No
Digital Communications
Appendix N
O-1
O.2 IDENTIFICATION
Each valve has a pressure label sticker indicating its range of adjustment. The
range corresponds to the spring installed under the adjustment cap as noted in
Table O.2
Appendix O
Spring Color
750-1500
Purple
1500-2250
Orange
2250-3000
Brown (Std)
O-2
Appendix O
Standard springs are 22503000 psi unless specified otherwise. The limiting
cartridge is then factory set to 23002400 psi. To translate pressure into
actuator output, use the following formula:
)(
) [
The pressure gauge reading can be obtained from the corresponding pressure
gauge shown in Figure O.2. This value should be the delta between the two
gauges when calculating actual output.
O-3
O.3 ADJUSTMENT:
Loosen the lock nut while holding the adjustment cap in place.
While running the actuator in a hard stop, read the corresponding gauge
to the valve that is being adjusted.
Turn the adjustment cap CW to increase the relief pressure and CCW to
decrease the relief pressure.
Note: The adjustment cap does not have a hard stop and will unthread.
Tighten lock nut against the cap to 100 lbin (11 Nm) and test set
pressure.
Appendix O
P. Interconnect Diagrams
& Control Enclosure Drawings
D97904 STEPPER WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . P-2
B QUICK CONNECT CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . P-3
C QUICK CONNECT CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . P-4
D97904-.5D D SERVO WIRING DIAGRAM . . . . . . . . . . . . . . . . . P-5
D QUICK CONNECT CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . P-6
D97904-D D SERVO WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . P-7
D QUICK CONNECT CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . P-8
D97904-2D 2D SERVO WIRING DIAGRAM . . . . . . . . . . . . . . . . . . P-9
D97904-P9 D,P9 SERVO WIRING DIAGRAM . . . . . . . . . . . . . . . . . P-10
D97904-P40 D,P40 SERVO WIRING DIAGRAM . . . . . . . . . . . . . . . . P-11
D97904-STEPACCUM STEPPER WITH ACCUMULATOR FAIL OPTION . . . . .P-12
D97904-.5DACCUM D SERVO WITH ACCUMLATOR FAIL OPTION . . . . . P-13
D97904-DACCUM D SERVO WITH ACCUMULATOR FAIL OPTION . . . . . . . P-14
D97904-2DACC 2D SERVO WITH ACCUMULATOR FAIL OPTION . . . . . . . P-15
D97904-P9ACC D,P9 SERVO WITH ACCUMLATOR FAIL OPTION . . . . . . . P-16
D97904-P40ACC D,P40 SERVO WITH ACCUMULATOR FAIL OPTION . . . . . P-17
B AND C-PUMP CONTROL ENCLOSURE DRAWING . . . . . . . . . . . . . . . P-18
B AND C CONTROL ENCLOSURE FOR QUICK CONNECT CABLES . . . . . . . . . P-19
D AND D CONTROL ENCLOSURE FOR QUICK CONNECT CABLES . . . . . . . P-20
D AND D PUMP CONTROL ENCLOSURE DRAWING . . . . . . . . . . . . . . P-21
2D & D,P9 CONTROL ENCLOSURE DRAWING . . . . . . . . . . . . . . . . . . P-22
D,P40 CONTROL ENCLOSURE DRAWING . . . . . . . . . . . . . . . . . . . . . P-23
Appendix P
Interconnect Drawings
P-3
P-4
P-5
P-6
P-7
P-8
P-9
P-10
P-11
P-12
P-13
P-14
P-15
P-16
P-17
P-18
P-19
P-20
P-21
P-22
P-23
Q-1
CONTACT INPUTS
Note: Refer to the INPUTS menu, Signal Type parameter in the Modes of Operation
& Control Parameters section.
Appendix Q
Q-2
ON state:
Most AC and many DC solid state switching devices require a minimum current
flow in order to remain in the closed state. If this minimum current exceeds the
input signal current at the activation voltage, the current flow may be increased
by adding a shunt resistor across the input signal terminals of the pulse auxiliary
board.
OFF state:
The OFF state leakage current must be less than 1 mA. Diode clamps or RC
snubber networks placed across mechanical relays and the semiconductor
junctions of solid state switches will pass some current in the OFF state. If this
leakage exceeds 1 mA, a resistor added across the input signal terminals will
bypass the current.
Q.2 1 CONT
The single contact (1 Cont) option of controlling the actuator is for ON/OFF
applications. A single dry contact or live voltage is applied to the Contact Inputs
Board.
The dry contact is biased by 120 Vac available from the Contact input board. A
live voltage, 24 to 120 Vac/Vdc, is supplied by the end user.
When Signal Type = 1 Cont (one contact), two position operation
open/closed positionis selected. The applied signal defines actuator position.
If the Open input is active (powered), the actuator goes to Position Hi. If the
Open input is not active (un-powered), the actuator goes to Position Lo.
Note: Actuator will continue to move in desired direction as long as a signal is
present or until target is reached.
Appendix Q
Q-3
Appendix Q
Q-4
Q.3 2 CONT
The dual contact (2 Cont) option of controlling the actuator is for manual
modulation control, using two signals. Two dry contacts or two live voltages are
applied to the Contact Inputs Board.
The dry contacts are biased by 120 Vac available from the Contact input board
or live voltages, 24 to 120 Vac/Vdc, are supplied by the end user.
Appendix Q
Appendix Q
Q-6
Appendix Q
R-1
Appendix R
R-2
The RemoteMan mode will be entered when the MAN Input of the Remote
Auto/MAN Inputs is activated. The actuator is then controlled by activating the
Open or Close Inputs of the Remote Auto/MAN Input.
Appendix R
R-3
Appendix R
S-1
Appendix S
S-2
Appendix S
either the full open or the full closed position. This function needs to be
controlled directly from the users SIS and not through the Rexa control
box. The ESD is certified for low demand fail safe applications.
3.1 The safety solenoids defined on the hydraulic schematic must be
wired directly into the main safety system. It is possible for the Rexa
controller to control these solenoids but in order to minimize the number of
components in the safety loop they must be wired directly into the safety
system for SIL applications.
3.2 Since the safety solenoids are controlled directly by the safety system
a trip relay must be installed to disable the Rexa electronics during a safety
event. This relay will insure the Rexa electronics cannot react to the safety
system taking control of the actuator.
3.3 This system has been designed to full stroke at rate which is shown
on the actuator data sheet provided to by REXA for this specific order.
3.4 The useful life of this actuator is 10 years based on the duty
cycle provided to REXA for this application. After recommended seal
maintenance the actuators useful product life is 20 years.
3.5 The REXA actuator is available in normally open or normally closed
ESD configurations.
3.6 A 24 hour mean time to repair should be assumed for safety
availability calculations.
Appendix S
S-4
monitored by the safety system through an alarm relay. The only critical
alarmed feature that would indicate the system may not perform its
intended trip function is the stall alarm.
5.1.1 Stall Alarm If the actuator fails to move 1%, within the adjustable
stall time setting, while positioning the alarm relay will open indicating an
alarm event.
5.1.2 Partial stroke testing is performed to verify the actuator is capable
of performing its intended safety function. The actuator shall be designed
to support proof test intervals of 1 year or greater while consuming less
than 40% of the allowable PFDavg for SIL 2 SIF applications when PST is
implemented. The control and design of this test should be in the scope
of the control system. The Rexa actuator will only follow the requested
change in position as defined by the control loop. This PST percentage to
activate needs to be calibrated within the scope of the plants SIS system.
During a partial stroke test the control system must monitor the position
transmitter to insure the actuator actually successfully performed this
function. The control room supervisor needs to review and sign off on the
results of the proof tests. This PST should be sufficient to achieve a greater
than 65% SFF (Safe Failure Fraction). Key points to review during this test:
5.1.3 Verification from the REXA position transmitter that the actuator
followed the change in the control position and performed its PST function.
5.1.4 Redundant verification from an optional PST limit switch can be
provided, this limit switch needs to be wired directly into the SIS system.
5.2 The test results are to be recorded and stored for the life of the
product.
5.3 In order to insure this system can maintain its as designed
functionality the maintenance section of this IOM must be strictly adhered
too.
Appendix S
S-5
6.2 Run the actuator close and verify stroking time meet the specification
sheet.
6.3 Perform an ESD trip and verify stroking time meet the specification
sheet.
6.4 Run the actuator to its PST position to verify position feedback and
the optional PST limit switch is functioning properly.
Appendix S
T-1
T. Position Transmitter
Appendix T
Position Transmitter
T-2
Position Transmitter
Appendix T
Active
<0.1% of full stroke
24 Vdc
(internal supply)
Also included with the transmitter is an Alarm Relay. Whenever the actuator is
unable to follow the applied control signal, the Alarm Relay will change state
(de-energize). See PM14 for additional details.
Alarm Relay:
Response: second of any "fail to operate condition"
Alarm Contacts: SPST
Rating: 1 amp @ 30 Vdc, 0.3 amp @ 120 Vac - resistive
Connection: Terminal strip on the auxiliary board
Figure T.1-1
Appendix T
T-3
Position Transmitter
T-4
Position Transmitter
Figure T.1-2
Appendix T
U-1
U. ELECTRONIC RELAYS
Limit Switch, Alarm and Warning
ELECTRONIC RELAYS
The electronic limit, alarm and warning relays are located on the CPU board. All
wiring connections are made directly to this board at TB1 and TB5. An indicator
LED shows the status (energized-ON) of each relay.
Two of the relays are configured in the Setup Mode to activate upon user
defined stroke limits. The third relay is an alarm indicator and the fourth is a
warning indicator.
Appendix U
Electronic Relays
U-2
Electronic Relays
Appendix U
Once the actuator detects an error, or is put into LOCAL or SETUP mode,
the Alarm and Warning Relays open and LEDs D6 and D7 will turn off.
When the CPU detects an error, which opens the Warning Relay only, LED D7
will turn off. The Warning relay is a signal from the control enclosure that means
the REXA CPU detects a problem but can still operate and follow the Control
Signal.
The Alarm relay is a signal from the control enclosure that means the REXA CPU
detects a problem, or is in LOCAL or SETUP modes, and cannot follow the
Control Signal.
GENERAL SPECIFICATIONS
Quantity:
Type:
Rating:
Turn On time:
<3 mS
Differential Travel
0.1%
(Hysteresis):
Connection:
U-3
CPU
PHOTOMOS
WARNING RELAY
RATING:
200 VAC/VDC, 1.0 AMP
PHOTOMOS
ALARM RELAY
RATING:
200 VAC/VDC, 1.0 AMP
PHOTOMOS
LIMIT SWITCH RELAYS
RATING:
200 VAC/VDC, 1.0 AMP
Appendix U
Electronic Relays
V-1
Appendix V
V-2
Appendix V
Appendix W
Appendix W
Voltage
24VDC max
Relays
Warning
Alarm
Limit Switches
Voltage
36VDC max
36VDC max
24VDC - 120VAC/VDC
1-5VDC
Voltage Amps
24VDC 4-20mA
Amps
4-20mA
Voltage
Amps
200VAC/VDC
1.0A
200VAC/VDC
1.0A
200VAC/VDC
1.0A
Feedback Out
Control Signal
Standard 4-20mA control signal
Optional 10 - 50mA
Pulse control signal ( 1 or 2 contacts)
Low Coltage control
Amps
4-20mA
10-50mA
1A
20mA
Electronic Unit
Heater Power
Volts
Amps
24VDC
8A
48VDC
5A
115VAC
2A
230VAC
1A
24VDC
8A
115VAC
2A
115VAC
2A
115VAC
2A
230VAC
1A
230VAC
1A
230VAC
1A
230VAC
1A
230VAC
1A
W-3
X-1
X. Redundant Construction
INTRODUCTION
The modular construction of the Xpac allows the duplication of the critical
components without a major redesign or sacrificing operational characteristics.
Two Power Modules, two complete control electronics and two feedback
assemblies are used to operate a single hydraulic cylinder. Each module
operates from its own controls and feedback. Wiring and setup are the same as
for any standard REXA Actuator.
One module is designated as main and the other as backup. In this manner, the
operation of the main system is indicated to the backup system via the Main
systems Alarm relay Output. The functional difference between the modules is
strictly in the response to a change in control signal.
For instance, setting the dead band of each module to 0.1% would mean that
the backup module is at 1.6%. A control signal change of less than 1.6% would
result in only the main module taking action to change position. A change
greater than 1.6% would have both modules operating. Regardless of the
Appendix X
Redundant Construction
X-2
Redundant Construction
change, positioning would still be 0.1% resolution. If the main module cannot
respond (indicated by the alarm), then the backup module will automatically
revert to fine control and position to the 0.1% setting.
This configuration has a redundancy of 90%. The only major component not
duplicated is the hydraulic cylinder which is unlikely to suffer a catastrophic
failure. Any size module can be upgraded. An R is added to the model number
to indicate this enhancement (L2000-2-2BR-P).
Appendix X
X-3
X.3 OPERATION
The operation is substantially unchanged from a standard unit. However,
some mention should be made to the interaction of two independent Power
Modules on the same cylinder. Both CPUs are looking at the actual position
and comparing this to the target position set by the control signal. If the target
position for one module is satisfied but not for the other, then one module will
reposition the actuator. If the repositioning causes the first module to move
outside of its target, then it will move the actuator back. This action would occur
with the same signal and low dead band settings (< 0.5%). Such operation is
alleviated by simultaneous calibration and the backup units deadband having
an internal setting sixteen times that of the main unit.
Another extraordinary condition will happen if one module is put into LOCAL
MAN and moved manually. The other unit will continue to track the control
signal and move the actuator back. Placing both CPUs in LOCAL MAN and
moving only one remedies this situation.
Appendix X
RedundantConstruction
X-4
Redundant Construction
Appendix X
X.4 WIRING
CALIBRATE
CONTROL
SPEED /
ACCEL
Function
Deadband
INPUTS
Min Mod
DRIVES
Bumpless
OUTPUTS
Surge
Bkpt
CURRENT
STATS
HISTORIC
STATS
Seat Ld
Cyl
Flow Char
Se t u p
No i n p b d
Fu n c t i o n = Ba c ku p
X-5
Position Lo, Position High, all values in the SETUP Parameters should be
identical.
Appendix X
RedundantConstruction
X-6
Redundant Construction
Appendix X
X-7