000 Sanyo Scroll CSBN303H8A
000 Sanyo Scroll CSBN303H8A
000 Sanyo Scroll CSBN303H8A
Discharge Tube
Check valve
Prevents reverse-rotation at shutdown.
Fixed scroll
Discharge Baffle
Reduces discharge volume improving
Orbiting scroll
Rigid
Suction Tube
Main Frame
Internal linebreak
operation.
Crankshaft
Motor
Bearing Plate
PTFE Bearings
Bronze with Teflon impregnation.
Oil
Oil Pump
SAY-56T(R22)
FV-68S
(R407/R410A/R134a)
Refrigerant
R22/R407C/R410A/R134A
Magnet
809 940 88
C-SBN303H8A R407C
A B C D E
Voltage
Phase
Design
Output
Series
Type
Compressor Model
C-XXX AA B C D E
Design
Voltage
Application
Phase
Output
Type
A~
3: 50Hz 200V/60HZ 200,220V
5: 50Hz 220,230,240V
6: 60Hz 208,230V
8: 50Hz 380,415V/60Hz,440,460V
9: 60Hz 380V
H: High Back Pressure
1: 1Phase
3: 3Phase
AA100W
C-SB: C-SB Series Compressor (R-22)
C-SBN: C-SB Series Compressor (R-407C/410A)
C-SC: C-SC Series Compressor (R-22)
C-SCN: C-SC Series Compressor (R-407C/410A)
Compressor
Model
Displac
ement
cm3/rev in3/rev
Capacity
W
Btu/h
Power
W
COP/EER
W/W
Electrical Components
Electrical Data
Btu/Wh
RLA
A
MCC LRA
A
Weight (with
oil)
Run
Capacitor
Start
Capacitor
MFD/V
MFD/V
kg
lb
Oil
Oil
Type
ml
fl.oz
Oil
Balance
Port for
Tandem
Initial Charge
55.7
3.40
9600
32,800
3350
2.87
9.8
7.3
10.2
48
n/a
n/a
36.5
80.5
PVE
1,700
58
n/a
C-SBN303H8A
66.8
4.08
11600
39,600
3800
3.05
10.4
7.9
11.1
48
n/a
n/a
37.5
82.7
PVE
1,700
58
n/a
C-SBN303H8G
66.8
4.08
11600
39,600
3800
3.05
10.4
7.9
11.1
48
n/a
n/a
37.5
82.7
PVE
1,700
58
C-SBN353H8A
77.4
4.72
13400
45,700
4600
2.91
9.9
9.6
13.4
48
n/a
n/a
38.0
83.8
PVE
1,700
58
n/a
n/a
C-SBN373H8A
83.2
5.08
14500
49,500
4950
2.93
10.0
10.1
14.1
48
n/a
n/a
38.0
83.8
PVE
1,700
58
C-SBN373H8G
83.2
5.08
14500
49,500
4950
2.93
10.0
10.1
14.1
48
n/a
n/a
38.0
83.8
PVE
1,700
58
C-SBN453H8A
100.0
6.10
17600
60,100
5800
3.03
10.4
10.4
14.5
66
n/a
n/a
39.5
87.1
PVE
1,700
58
n/a
C-SBN453H8G
100.0
6.10
17600
60,100
5800
3.03
10.4
10.4
14.5
66
n/a
n/a
39.5
87.1
PVE
1,700
58
C-SCN603H8H
137.0
8.36
24500
83,600
7750
3.16
10.8
15.9
22.2
80
n/a
n/a
66.5
146.6
PVE
2,800
95
n/a
C-SCN603H8K
137.0
8.36
24500
83,600
7750
3.16
10.8
15.9
22.2
80
n/a
n/a
66.5
146.6
PVE
2,800
95
C-SCN753H8H
171.2
10.45
29900
102,000
9350
3.20
10.9
19.1
26.7
96
n/a
n/a
69.5
153.2
PVE
2,800
95
n/a
C-SCN753H8K
171.2
10.45
29900
102,000
9350
3.20
10.9
19.1
26.7
96
n/a
n/a
69.5
153.2
PVE
2,800
95
C-SCN903H8H
205.4
12.53
34900
119,100
11300
3.09
10.5
21.6
30.2
96
n/a
n/a
70.5
155.5
PVE
2,800
95
n/a
C-SCN903H8K
205.4
12.53
34900
119,100
11300
3.09
10.5
21.6
30.2
96
n/a
n/a
70.5
155.5
PVE
2,800
95
60/440
100~140/330 38.5
84.9
PVE
1,700
58
n/a
100~140/330 39.0
55.7
3.40
9700
33,100
3400
2.85
9.7
19.0
26.6
100
C-SBN301H5A
66.8
4.08
11800
40,300
4000
2.95
10.1
23.2
32.5
122
60/440
86.0
PVE
1,700
58
n/a
C-SBN351H5A
77.4
4.72
13500
46,100
4750
2.84
9.7
27.0
37.8
115
70/440
n/a
39.0
86.0
PVE
1,700
58
n/a
C-SBN371H5A
83.2
5.08
14700
50,200
5050
2.91
9.9
28.4
39.7
115
70/440
n/a
39.5
87.1
PVE
1,700
58
n/a
66.8
4.08
11500
39,200
3850
2.99
10.2
16.7
23.4
85
n/a
n/a
37.5
82.7
PVE
1,700
58
n/a
C-SBN373H5A
83.2
5.08
14700
50,200
5050
2.91
9.9
19.1
26.8
97
n/a
n/a
38.0
83.8
PVE
1,700
58
n/a
C-SBN453H5A
100.0
6.10
17700
60,400
5900
3.00
10.2
23.9
33.5
121
n/a
n/a
39.5
87.1
PVE
1,700
58
n/a
C-SCN603H5H
137.0
8.36
24200
82,600
7700
3.14
10.7
29.9
41.9
152
n/a
n/a
66.5
146.6
PVE
2,800
95
n/a
C-SCN753H5H
171.2
10.45
29900
102,000
9400
3.18
10.9
36.4
50.9
184
n/a
n/a
153.2
PVE
2,800
95
n/a
C-SCN903H5H
205.4
12.53
34800
118,700
11300
3.08
10.5
42.4
59.4
215
n/a
n/a
69.5
70.5
155.5
PVE
2,800
95
n/a
1.2 EER (Energy Efficiency Ratio) Is shown in Btu/W-hr and W/W and may be
interpolated.
1.3 Sound Level Sound levels are in section 3.2 of this application guide.
1.4 Refrigerant Product offerings include R22, R407C,R134a and R410A.
2.0
Physical Requirements
2.1 Mounting Standard 4 foot mounting with 7.5 (190.5 cm) between mounting
holes.
2.2 Height Maximum and mounting height dimensions are in the specifications.
2.3 Weight Compressor weights are shown on the specifications in section 1.0.
2.4 Piping Discharge and suction tube diameters are standard industry sizes and
similar to ALL competitive scroll compressor models.
specifications.
3.0
6. Operational Limits:
Scrolls are one the most reliable compressor type and can yield years of
troublefree operation when correctly applied in an air conditioning system.
However, there are several key considerations in designing and building a
reliable system. The most critical issue is the handling of liquid refrigerant.
Application criteria for usage of crankcase heaters and suction accumulators is
included in the Application Guide in section 7.0. Maintaining suction sump
superheat and discharge gas temperatures within specified limits are also key
factors in system application of scroll compressors. Operation within the
specified envelope of temperatures and pressures will assure excellent
reliability for many years to come. The following temperature limits are
recommended for SANYO scroll compressors with R22/ R407C/R410A/R134a.
R22 Operating Limits
Evaporating Temp
Condensing Temp
Maximum Discharge (C-SB)
Maximum Discharge (C-SC)
Minimum
-13 F
86 F
n/a
n/a
Maximum
59 F
154 F
266 F
275 F
Minimum
-13 F
86 F
n/a
n/a
Maximum
59 F
149 F
266 F
275 F
Minimum
5F
86 F
n/a
n/a
Maximum
59 F
167 F
240 F
240 F
8. Dimensions/Wiring Diagrams