The document provides technical specifications for Novaris surge filter products. It describes the multi-stage protection design including metal oxide varistors and filters. It lists specifications for voltage, current ratings, response times, dimensions and mounting options for various models rated up to 240V AC and 20 amps.
The document provides technical specifications for Novaris surge filter products. It describes the multi-stage protection design including metal oxide varistors and filters. It lists specifications for voltage, current ratings, response times, dimensions and mounting options for various models rated up to 240V AC and 20 amps.
The document provides technical specifications for Novaris surge filter products. It describes the multi-stage protection design including metal oxide varistors and filters. It lists specifications for voltage, current ratings, response times, dimensions and mounting options for various models rated up to 240V AC and 20 amps.
The document provides technical specifications for Novaris surge filter products. It describes the multi-stage protection design including metal oxide varistors and filters. It lists specifications for voltage, current ratings, response times, dimensions and mounting options for various models rated up to 240V AC and 20 amps.
Novaris Technologies DINsafe power line surge filters are designed for effective protection against induced transient overvoltages caused by lightning and other events on AC and DC power supply circuits.
Versions are available for voltage ratings up to 240V AC and are housed in a rugged metal enclosure with DIN43880 compliant dimensions.
Operation
Multistage transient protection is utilised in every unit. Metal oxide varistors, as the first stage, absorb the majority of the energy. These components are continuously monitored for integrity with full protection indicated by a green LED on the top of the case. A red LED indicates power ON.
The first stage is followed by a low pass LC filter that further attenuates the let through voltage. The filter also attenuates low-level noise and harmonics.
The third stage comprises metal oxide varistors. These provide a final clamping circuit and protect against impulses generated by the connected load. This is particularly important when multiple loads are connected. Do not exceed total filter ratings.
10 amp and 20 amp filters also feature external alarms. These provide a clean changeover contact that may be used to remotely monitor the status of the filter or as a power fail indicator. The relay is normally energised when power is applied.
Specifications
Description Multistage power surge filter No phases: 1 Voltage drop: < 2V at full load Efficiency: 99% Earth leakage: < 0.75mA Protection modes: Transverse and common mode Protection stages: MOV / low pass filter / MOV Surge withstand: IEEE C62.41 cat, A, B, opt. C AS1768-1991 cat. A, B, opt. C Surge rating: 16kA per line for 8/20us pulse 40kA per line for cat. C units Let through voltage for 6kV 1.2/50us, 3kA 8/20us pulse: < 680V Response time: Instantaneous Frequency response: 3dB point at 800Hz Indicators: MOV integrity - green LED Power ON - red LED Alarm relay: Clean contact with 4kV isolation from active circuitry. Dimensions: SF105DIN-xxx/A: 116H x 80D x 54W SF110DIN-xxx/A: 116H x 80D x 120W SF120DIN-xxx/A: 116H x 80D x 120W Mounting: DIN rail mountable. Panel mount brackets are available on request. Terminal capacity: SF105DIN-xxx/A: 4mm 2
SF110DIN-xxx/A: 16mm 2
SF120DIN-xxx/A: 16mm 2
Location: Final subcircuits to AS1768 location categories A and B, category C is optional. Options Cat No. Vmax AC Current Rating SF105DIN-30V/A 30V 5A 2kA SF105DIN-50V/A 50V 5A 6.5kA SF105DIN-150V/A 150V 5A 8kA SF105DIN/A 250V 5A 8kA SF105DIN-16/A 250V 5A 16kA SF105DIN-40/A 250V 5A 40kA