Diesel generator set
N14 series
Specification sheet
304 kWe, 380 kVA Prime
Lowest life cycle cost
N14 series design features have made Cummins
diesel, the
standard for comparison of operating economy, reliability and
long life. When all cost factors like initial purchase, fuel, lube oil,
maintenance and overhaul are considered, the bottom line will
show that this Cummins
features:
- Engine electronic governing
- Genset metering parameters like lube oil pressure, coolant
temperature, engine speed (rpm), run hours, DC voltage,
intake manifold temperature (wherever applicable), 3 phase
volts and 3 phase amperes, frequency, kW, kVA, power factor
Technical data
Generator set specifications
Model C 380 D5 P
Prime Power Rating kVA 380
Output Voltage and Frequency 415 Volts, 50 Hz
Power Factor 0.8 (lag)
No. of phases 3 phase
Engine specifications
Make Cummins
Model NTA 14 G3
No. of cylinders 6, in- line
Aspiration Turbocharged-Aftercooled
Bore x Stroke 140 mm x 152 mm
Displacement 14 ltrs
Output - Prime 336 KWm
Fuel consumption @ 75% load with Radiator & Fan 58.2 ltr/hr
Fuel consumption @ 100% load with Radiator & Fan 76 ltr/hr
Typical lube oil consumption @ full load 0.092 ltr/hr
Total wet weight ( engine + radiator) 1620 kg
Length x Width x Height (engine) 1655 x 900 x 1313 mm
Compression Ratio 17:1
Piston Speed 7.6 m/s
Governor /Class Electronic /A1
Lubricating oil sytem capacity 38.6 ltrs
Coolant capacity (engine + radiator) 76.8 ltrs
Combustion air intake @ 100% load (+/- 5%) 223.7 m
3
/min
Fan air flow across radiator 623 m
3
/min
Exhaust Temperature 527
o
C
Battery Capacity /Rating 180 AH, 2 X 12 V
Alternator specifications
Make Stamford
Frame size /Model No. HC4F
Voltage Regulation + 1%
Insulation Class H
Standard Enclosure IP 23
Winding Pitch 2 /3 Pitch
Stator Winding Double layer lap
Rotor Dynamically balanced
Wave form distortion No load < 1.8 %, non distorting
balanced linear load < 5 %
Telephone Interference Factor Better than 50
Total Harmonic Factor Better than 2%
2007 Cummins Power Generation Specifications subject to change without notice
PGBU/CIL/003/N14 380 kVA/CPG/June 2007/1000
Our energy working for you.
TM
www.cumminsindia.com
Conformance standards
IS 4722, BS 5000, IEC 34 / 1, ISO 8528, BS 5514, ISO 3046
Rating definition
- Prime power rating is applicable for supplying continuous
electric power (at variable load) in lieu of commercially
purchased power.
- Prime power is available for an unlimited number of hours
per year in a variable load application.
- 10% overload is available for 1 hour in every 12 hours of
operation.
- Rating definition is as per ISO 3046 / BS 5514.
- Fuel consumption data is based on diesel having specific
gravity of 0.85 and conforming to IS:1460/ Equivalent
- Oil consumption data is based on oil having specific gravity of
0.89 and meeting CH4 API categories
- Fuel consumption tolerance is +5%
Typical diesel genset dimensions
Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Weight (kgs.) (Dry)
C 380 D5 P 380 kVA 5500 2000 2500 7215
Typical enclosed genset dimensions*
Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Weight (kgs.) (Dry)
C 380 D5 P 380 kVA 3387 1576 1988 3215
Cummins India Limited
Power Generation Business Unit
35A/1/2, Erandawana,
Pune 411 038. India
Tel.: (91) 020-6602 7525
Fax: (91) 020-6602 8090
Authorised
Representative
Cummins Power Generation Offices:
Location: Tel: Fax:
Bangalore: (080) 2361 3831/ 2361 1958 (080) 2361 4552
Chandigarh: (0172) 506 3218 (0172) 266 3087
Chennai: (044) 2441 6429/ 2442 3412 (044) 2491 1120
Delhi: Telefax: (011) 4161 8357/ 61
Hyderabad: (040) 2766 3017 (040) 2767 8892
Location: Tel: Fax:
Indore: (0731) 645 1042
Jaipur: (0141) 236 4944 (0141) 236 3746
Kolkota: (033) 2287 8065/ 2247 2481 (033) 2290 3839
Lucknow: (0522) 278 6718/ 278 7514 (0522)278 7880
Mumbai: (022) 2756 6351/ 52/ 53/ 54 (022) 27566355
Vadodara: (0265) 232 4207/ 654 0390 (0265) 234 0623
2007 Cummins Power Generation Specifications subject to change without notice
Cummins and PowerCommand are registered trademarks of Cummins Inc.
*Dimensions of the enclosure are excluding the silencer
Information contained in this publication is typical only and does not form part of any
contractual commitment
PGBU/CIL/003/N14 380 kVA/CPG/June 2007/1000
Our energy working for you.
TM
www.cumminsindia.com