WS0-GCC1 - User's Manual (CC-Link Interface Module) SH (NA) - 080909-A (03.10)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 72

MELSEC WS series

Safety Controller
User's Manual
WS0-GCC1
CC-Link Interface Module
MITSUBISHI ELECTRIC
Art. no.: SH(NA)-080909
01032010
Version A
INDUSTRIAL AUTOMATION
MITSUBISHI ELECTRIC


This document is protected by the law of copyright, whereby all rights established
therein remain with the company Mitsubishi Electric Corporation. Reproduction of
this document or parts of this document is only permissible within the limits of the
legal determination of Copyright Law. Alteration or abridgement of the document is
not permitted without the explicit written approval of the company Mitsubishi Electric
Corporation.

Precautions regarding warranty and specifications

MELSEC-WS series products are jointly developed and manufactured by Mitsubishi
and SICK AG, Industrial Safety Systems, in Germany.
Note that there are some precautions regarding warranty and specifications of
MELSEC-WS series products.

<Warranty>
The gratis warranty term of the product shall be for one (1) year after the date of
delivery or for eighteen (18) months after manufacturing, whichever is less.
The onerous repair term after discontinuation of production shall be for four (4)
years.
Mitsubishi shall mainly replace the product that needs a repair.
It may take some time to respond to the problem or repair the product depending
on the condition and timing.

<Specifications>
General specifications of the products differ.
MELSEC-WS
MELSEC-Q,
MELSEC-QS
Operating ambient
temperature
-25 to 55C
*1
0 to 55C
Operating ambient humidity 10 to 95%RH 5 to 95%RH
Storage ambient temperature -25 to 70C -25 to 75C
*2

Storage ambient humidity 10 to 95%RH 5 to 95%RH
*1 When the WS0-GCC100202 is included in the system, operating ambient
temperature will be 0 to 55 C.
*2 For the MELSEC-QS series programmable controller, storage ambient
temperature will be -40 to 75C.

EMC standards that are applicable to the products differ.
MELSEC-WS
MELSEC-Q,
MELSEC-QS
EMC standards EN61000-6-2, EN55011 EN61131-2



1

SAFETY PRECAUTIONS
(Read these precautions before using this product.)

Before using this product, please read this manual, the relevant manuals, and the safety standards carefully
and pay full attention to safety to handle the product correctly.
The precautions given in this manual are concerned with installation of this product and wiring with the
external application only.
For the safety precautions of the MELSEC-WS safety controller system, refer to the users manual for the
CPU module used.
In this manual, the safety precautions are classified into two levels: WARNING and CAUTION.

Indicates that incorrect handling may cause hazardous conditions, resulting
in death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting
in minor or moderate injury or property damage.

Under some circumstances, failure to observe the precautions given under CAUTION may lead to
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future
reference.

[Design Precautions]
WARNING
The CC-Link interface module is not suitable for operation on a safety fieldbus.
The CC-Link interface module only generates non-safety-related fieldbus data (status bytes) for control
and diagnostics purposes.
Do not use non-safe data from a CC-Link interface module for safety related applications.
With the CC-Link interface module it is possible to integrate non-safe data into the logic editor such that
the safety function of the MELSEC-WS safety controller is compromised. Never implement the CC-Link
interface module into a MELSEC-WS safety controller without having this danger checked by a safety
specialist.

WARNING
CAUTION

2

CAUTION
Do not install the control lines or communication cables together with the main circuit lines or power
cables. Keep a distance of 100 mm or more between them.
Failure to do so may result in malfunction due to noise.
The MELSEC-WS safety controller fulfils the requirements of Class A (industrial applications) in
accordance with the Interference emission basic specifications.
The MELSEC-WS safety controller is therefore only suitable for use in an industrial environment and not
for private use.

[Installation Precautions]
CAUTION
Use the MELSEC-WS safety controller in an environment that meets the general specifications in the
users manual for the CPU module used. Failure to do so may result in electric shock, fire, malfunction,
or damage to or deterioration of the product.
Latch the module onto the DIN rail. Incorrect mounting may cause malfunction, failure or drop of the
module.
To ensure full electromagnetic compatibility (EMC), the DIN mounting rail has to be connected to
functional earth (FE).
Ensure that the earthling contact is positioned correctly. The earthling spring contact of the module
must contact the DIN rail securely to allow electrical conductivity.
Additionally connect all network cable shields directly at the control cabinet entrance to a common FE
ground line.
Tighten the screw within the specified torque range.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
Shut off the external power supply for the system in all phases before mounting or removing the
module.
Failure to do so may result in damage to the product.
Do not directly touch any conductive part of the module.
Doing so can cause malfunction or failure of the module.
The MELSEC-WS safety controller is only suitable for mounting in a control cabinet with at least IP 54
degree of protection.
Failure to meet the installation method may cause the module to fail or malfunction due to the
deposition of dust or the adhesion of water.

3

CAUTION
Make sure that the connection of the CC-Link interface module cannot lead to hazardous
situations during installation.
Ensure that the connection of the CC-Link dedicated cables and power cables cannot lead to a
hazardous situation when implementing the unit on to the MELSEC-WS safety controller and CC-Link
network. Prevent unintended start-up of equipment during connection of a CC-Link interface module.
Failure to do so may cause the system to malfunction.

[Wiring Precautions]
CAUTION
Switch the entire machine/system off line.
The system could start up unexpectedly while you are connecting the devices.
Connectors for external devices must be crimped or pressed with the tool specified by the
manufacturer, or must be correctly soldered. Incomplete connections could result in short circuit, fire,
or malfunction.
Connect the connectors to the module securely.
Failure to do so may cause malfunction due to poor contact.
Place the cables in a duct or clamp them.
If not, dangling cable may swing or inadvertently be pulled, resulting in damage to the module or cables
or malfunction due to poor contact.
Tighten the terminal screw within the specified torque range.
Undertightening can cause short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction.
When disconnecting the cable from the module, do not pull the cable by the cable part.
When disconnecting the cable with connector from the module, hold the connector part.
When disconnecting the cable connected to a terminal block, loosen the terminal screws first.
Failure to do so may result in damage to the module or cable or malfunction.
Prevent foreign matter such as dust or wire chips from entering the module.
Such foreign matter can cause a fire, failure, or malfunction.
Use dedicated cables as specified by the manufacturer for the CC-Link system. If a cable other than the
one specified by the manufacturer is used, the performance of the CC-Link system is not guaranteed.
Also, follow the specifications shown in the Cable Wiring Manual from CC-Link Partner Association for
the overall cable distance and the station-to-station cable length. If the wiring does not meet the
specifications, accurate data transmission is not guaranteed.
Do not install the control lines or communication cables together with the main circuit lines or power
cables. Failure to do so may result in malfunction due to noise.


4

CONDITIONS OF USE FOR THE PRODUCT

(1) Although MELCO has obtained the certification for Product's compliance to the international safety
standards IEC61508, EN954-1/ISO13849-1 from TUV Rheinland, this fact does not guarantee that
Product will be free from any malfunction or failure. The user of this Product shall comply with any and all
applicable safety standard, regulation or law and take appropriate safety measures for the system in
which the Product is installed or used and shall take the second or third safety measures other than the
Product. MELCO is not liable for damages that could have been prevented by compliance with any
applicable safety standard, regulation or law.
(2) MELCO prohibits the use of Products with or in any application involving, and MELCO shall not be liable
for a default, a liability for defect warranty, a quality assurance, negligence or other tort and a product
liability in these applications.
1) power plants,
2) trains, railway systems, airplanes, airline operations, other transportation systems,
3) hospitals, medical care, dialysis and life support facilities or equipment,
4) amusement equipments,
5) incineration and fuel devices,
6) handling of nuclear or hazardous materials or chemicals,
7) mining and drilling,
8) and other applications where the level of risk to human life, health or property are elevated.


5

*The manual number is given on the bottom left of the back cover.
Print date *Manual number Revision
March, 2010 SH(NA)-080909ENG-A First edition

Japanese manual version SH-080908-A
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
2010 MITSUBISHI ELECTRIC CORPORATION

REVISIONS

6
SAFETY PRECAUTIONS........................................................................................... 1
CONDITIONS OF USE FOR THE PRODUCT........................................................... 4
REVISIONS ................................................................................................................ 5
CONTENTS................................................................................................................ 6
GENERIC TERMS AND ABBREVIATIONS................................................................ 9
1. About this document................................................................................11
1.1 Function of this document....................................................................... 11
1.2 MELSEC-WS manuals ........................................................................... 11
1.3 Target group............................................................................................ 12
1.4 Depth of information ............................................................................... 12
1.5 Scope...................................................................................................... 13
1.6 Abbreviations used ................................................................................. 13
1.7 Symbols used ......................................................................................... 13
2. On safety ................................................................................................ 14
2.1 Qualified safety personnel ...................................................................... 14
2.2 Correct use ............................................................................................. 14
2.3 Environmental protection........................................................................ 16
2.3.1 Disposal .............................................................................................. 16
2.3.2 Material separation ............................................................................. 16
3. System configuration.............................................................................. 17
3.1 Overall system configuration .................................................................. 17
3.2 Applicable system................................................................................... 17
4. CC-Link interface module....................................................................... 18
4.1 Overview................................................................................................. 18
4.1.1 Interfaces and operation..................................................................... 18
4.2 Mounting/Dismantling ............................................................................. 21
4.2.1 Steps for mounting the modules ......................................................... 21
4.2.2 Steps for dismantling the modules...................................................... 23
4.3 Electrical installation ............................................................................... 24
4.4 Connecting CC-Link dedicated cables ................................................... 25
4.5 First configuration steps.......................................................................... 26
4.5.1 Station number configuration.............................................................. 26
4.5.2 Establishing a connection between MELSEC-WS safety controller and
PC....................................................................................................... 26
4.5.3 Configuration of the number of occupied stations .............................. 28
4.5.4 Parameter configuration...................................................................... 29
4.5.5 Transfer of a configuration.................................................................. 30
CONTENTS

7
4.5.6 Verification of a configuration.............................................................. 31
4.5.7 Upload of a configuration.................................................................... 31
5. Data sets................................................................................................. 32
5.1 Data transmitted into the network (network input data sets (RX, RWr))
................................................................................................................ 33
5.1.1 Logic results........................................................................................ 33
5.1.2 Module and EFI input and output values ............................................ 34
5.1.3 Routing of data from a second network.............................................. 34
5.2 Data received from the network (network output data sets) (RY, RWw))
................................................................................................................ 35
5.3 Default settings for the input data set ..................................................... 36
5.4 Customizing the input data set (MELSEC-WS to CC-Link) ................ 37
5.4.1 The toolbar .......................................................................................... 38
5.4.2 Available data area ............................................................................. 39
5.4.3 Network Module Data area ................................................................. 40
5.4.4 Tag names area .................................................................................. 40
5.5 Default settings for the output data set ................................................... 41
5.6 Tag names for incoming data (CC-Link to MELSEC-WS)................... 43
5.6.1 Saving and loading a configuration..................................................... 44
5.6.2 Importing and exporting a configuration ............................................. 44
5.7 Monitoring the data set online................................................................. 45
5.8 Accessible range .................................................................................... 46
6. Troubleshooting...................................................................................... 47
6.1 When data cannot be normally exchanged ............................................ 47
6.2 When the L RUN/L ERR. LED does not turn on (green) ........................ 48
6.3 When an error occurs in remote input (RX) or remote register (RWr)
................................................................................................................ 49
6.4 When an error occurs in remote output (RY) or remote register (RWw)
................................................................................................................ 49
7. Technical specifications.......................................................................... 50
7.1 Technical specifications, supply circuit ................................................... 50
7.2 Technical specifications of CC-Link interface module ............................ 50
7.3 General technical specifications ............................................................. 51
7.4 Technical specifications of cables........................................................... 52
7.5 Transmission delay time......................................................................... 52
7.6 Dimensional drawings............................................................................. 53
8. Connecting to a Q series programmable controller................................ 54
8.1 Features achieved by the connection..................................................... 54
8.2 Applicable system................................................................................... 55

8
9. Preparing for operation........................................................................... 56
9.1 System configuration and start-up procedure......................................... 56
9.2 Wiring...................................................................................................... 57
9.3 Sample program..................................................................................... 58
9.3.1 Parameter configuration example....................................................... 59
9.3.2 Sample program ................................................................................. 63
10. Troubleshooting when CC-Link interface module is connected to Q series
programmable controller......................................................................... 64

9
Generic
term/abbreviation
Description
WS0-MPL Abbreviation for the WS0-MPL00201 MELSEC-WS safety
controller memory plug
WS0-CPU0 Abbreviation for the WS0-CPU000200 MELSEC-WS safety
controller CPU module
WS0-CPU1 Abbreviation for the WS0-CPU130202 MELSEC-WS safety
controller CPU module
WS0-CPU Generic term for the WS0-CPU000200 and WS0-CPU130202
MELSEC-WS safety controller CPU modules
WS0-XTIO Abbreviation for the WS0-XTIO84202 MELSEC-WS safety
controller safety I/O combined module
WS0-XTDI Abbreviation for the WS0-XTDI80202 MELSEC-WS safety
controller safety input module
WS0-4RO Abbreviation for the WS0-4RO4002 MELSEC-WS safety controller
safety relay output module
WS0-GETH Abbreviation for the WS0-GETH00200 MELSEC-WS safety
controller Ethernet interface module
WS0-GCC1 Abbreviation for the WS0-GCC100202 MELSEC-WS safety
controller CC-Link interface module
CPU module Generic term for the WS0-CPU0 and WS0-CPU1
Safety I/O module Generic term for the WS0-XTIO and WS0-XTDI
Network module Generic term for the WS0-GETH and WS0-GCC1
CC-Link interface
module
Another name for the WS0-GCC1
Q series
programmable
controller
Abbreviation for the Mitsubishi MELSEC-Q series programmable
controller
QJ61BT11N Abbreviation for the QJ61BT11N CC-Link system master/local
module
QS0J61BT12 Abbreviation for the QS0J61BT12 CC-Link Safety system
master/local module
QCPU Generic term for the Q00JCPU, Q00CPU, Q01CPU, Q02CPU,
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU, Q02PHCPU,
Q06PHCPU, Q12PHCPU, Q25PHCPU, Q12PRHCPU,
Q25PRHCPU, Q00UJCPU, Q00UCPU, Q01UCPU, Q02UCPU,
Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q10UDHCPU,
Q13UDHCPU, Q20UDHCPU, Q26UDHCPU, Q03UDECPU,
Q04UDEHCPU, Q06UDEHCPU, Q10UDEHCPU, Q13UDEHCPU,
Q20UDEHCPU and Q26UDEHCPU
QSCPU Abbreviation for the QS001CPU
GX Developer Generic product name for the SWnD5C-GPPW-E,
SWnD5C-GPPW-EA, SWnD5C-GPPW-EV, and
SWnD5C-GPPW-EVA
(n indicates version 4 or later.)
-A and V indicate volume license product and version upgrade
product, respectively.

GENERIC TERMS AND ABBREVIATIONS

10

Terms
Generic
term/abbreviation
Description
Cyclic transmission Transmission method to periodically communicate the remote I/O
data and remote register data
Master station Station that controls the data link system (One master station is
required in each system.)
Local station Station that has a CPU module and communicates data with the
master and other local stations
Remote device
station
Remote station that handles bit data and word data
Remote station Generic term for remote I/O station and remote device station (The
remote station is controlled by the master station.)
Intelligent device
station
Station (including local stations) that can perform transient
transmission (example: AJ65BT-R2(N))
Slave station Generic term for remote I/O station, remote device station, local
station, intelligent device station, and standby master station
RX Remote input (area for data to be read)
Bit data that is input from the slave station to the master station
RY Remote output (area for data to be written)
Bit data that is output from the master station to the slave station
RWw Remote register (area for data to be written)
16-bit data that is output from the master station to the slave station
RWr Remote register (area for data to be read)
16-bit data that is input from the slave station to the master station
Terminating resistor Resistor that is connected to the terminal of the stations at both
ends of a CC-Link dedicated cable
Network input Data sent from the WS0-GCC1 to the master station (RX, RWr)
Network output Data sent from the master station to the WS0-GCC1 (RY, RWw)
Input data status Signal that is output from the WS0-GCC1 to the CPU module.
This signal turns on when the WS0-GCC1 receives data from the
master station.
Output data status Signal that is output from the WS0-GCC1 to the CPU module.
This signal turns on when data to be sent from the WS0-GCC1 to
the master station is ready.

Accessories
The following table shows accessories for the WS0-GCC1.

No. Item Amount Remarks
1
Safety Controller CC-Link Interface
Module Users Manual (Hardware)
1
The Japanese manual
is included.
2
Terminating resistor 110 1/2W
(brown-brown-brown)
1 Bar terminal
Screw terminals (for replacement) (WS0-TBS4) are not available for the CC-Link
interface module.

MELSEC-WS About this document

11

Please read the SAFETY PRECAUTIONS, Chapter 1 and Chapter 2 carefully
before working with this documentation and the MELSEC-WS safety controller
CC-Link interface module.
1.1 Function of this document
This manual only applies in conjunction with the other MELSEC-WS manuals (see
Section 1.2) and instructs the technical staff of the machine manufacturer and/or of
the machine operator on safe mounting, adjustment, electrical installation,
commissioning as well as operation and maintenance of the CC-Link interface
module.
The manual does not provide instructions for operating the machine in which the
MELSEC-WS safety controller and CC-Link interface module are, or will be,
integrated. Information of this kind will be found in the manuals for the machine.
1.2 MELSEC-WS manuals
For the MELSEC-WS safety controller there are four manuals with clearly
distinguished fields of application as well as Users Manuals (Hardware) for each
module.
This manual describes the CC-Link interface modules and their functions in
detail.
The Users Manuals (Hardware) are enclosed with each MELSEC-WS module.
They inform on the basic technical specifications of the modules and contain
simple mounting instructions. Use the Users Manuals (Hardware) when mounting
MELSEC-WS safety controllers.
The Safety Controller Users Manual describes all the MELSEC-WS modules
(except for network modules) and their functions in detail. Use the manual in
particular to configure MELSEC-WS safety controllers.
The Safety Controller Setting and Monitoring Tool Operating Manual describes the
software-supported configuration and parameterization of the MELSEC-WS
safety controllers. In addition, the manual contains the description of the
diagnostics functions that are important for operation and detailed information for
the identification and elimination of errors. Use the manual in particular for the
configuration, commissioning and operation of MELSEC-WS safety controllers.

1. About this document
About this document MELSEC-WS

12

The following shows the relevant manuals.
Title Number
Safety Controller Users Manual
WS-CPU-U-E
(13JZ32)
Safety Controller Ethernet Interface Module User's Manual
WS-ET-U-E
(13JZ33)
Safety Controller CC-Link Interface Users Manual
WS-CC-U-E
(13JZ45)
Safety Controller Setting and Monitoring Tool Operating
Manual
SW1DNN-WS0ADR-B-O-E
(13JU67)
Safety Controller CPU Module User's Manual (Hardware)
WS-CPU-U-HW
(13J200)
Safety Controller Safety I/O Module User's Manual
(Hardware)
WS-IO-U-HW
(13J201)
Safety Controller Safety Relay Output Module User's
Manual (Hardware)
WS-SR-U-HW
(13J202)
Safety Controller Ethernet Interface Module User's Manual
(Hardware)
WS-ET-U-HW
(13J203)
Safety Controller CC-Link Interface Module Users Manual
(Hardware)
WS-CC-U-HW
(13J209)
1.3 Target group
This manual is addressed to planning engineers, machine designers and the
operators of systems in which a MELSEC-WS safety controller is integrated and
who want to exchange data with a fieldbus (a controller) via a network module.
It also addresses people who integrate the network module into a machine,
commission it initially or who are in charge of servicing and maintaining the unit.
1.4 Depth of information
This manual contains information on the CC-Link interface module in the following
subjects:
mounting
implementation into a network
configuration via Setting and Monitoring Tool
data transfer to and from the network
status information, planning and related mapping

Warning!
Pay attention to the safety notes and safety measures on the CC-Link interface
module!

For the acquisition of Setting and Monitoring Tool, please contact your local
Mitsubishi representative.

ATTENTION
Note
MELSEC-WS About this document

13

1.5 Scope
This manual applies to the WS0-GCC1 CC-Link interface module.
This document is the original manual.
1.6 Abbreviations used
Enhanced Function Interface
1.7 Symbols used
Notes provide special information on the device.
LED symbols describe the state of a diagnostics LED. Examples:

Red The red LED is illuminated constantly.
Red The red LED is flashing.
Green The green LED is off.
Instructions for taking action are shown by an arrow. Read carefully and follow the
instructions for action.

Warning!
An ATTENTION indicates an actual or potential risk or health hazard. They are
designed to help you to prevent accidents.
Read carefully and follow the attention notices!


EFI
Note
Red, Red,
Green
Action

ATTENTION
On safety MELSEC-WS

14

This chapter deals with your own safety and the safety of the equipment operators.
Please read this chapter carefully before working with a CC-Link interface
module.
2.1 Qualified safety personnel
The CC-Link interface module may only be installed, commissioned and serviced
by qualified safety personnel.
Qualified safety personnel are defined as persons who
have undergone the appropriate technical training
and
have been instructed by the responsible machine operator in the operation of the
machine and the current valid safety guidelines
and
have access to the manuals of the CC-Link interface module and safety controller
and have read and familiarised themselves with them.
2.2 Correct use
The CC-Link interface module can only be operated with a MELSEC-WS safety
controller.
The CC-Link interface module does not have a dedicated voltage supply.
The CC-Link interface module is not suitable for operation on a safety
fieldbus!
The CC-Link interface module only generates non-safety-related fieldbus data
(status bytes) for control and diagnostics purposes.
Do not use non-safe data from a CC-Link interface module for safety related
applications!
With the CC-Link interface module it is possible to integrate non-safe data into the
logic editor such that the safety function of the MELSEC-WS safety controller is
compromised. Never implement the CC-Link interface module into a MELSEC-WS
safety controller without having this danger checked by a safety specialist.

The CC-Link interface module may only be used by qualified safety personnel and
only on the machine where they have been installed and initialized by qualified
safety personnel in accordance with the manual.

2. On safety

ATTENTION
MELSEC-WS On safety

15

Pay attention to the safety notes and safety measures on the CC-Link
interface module!
If the device is used for any other purposes or modified in any way - also during
mounting and installation - any warranty claim against Mitsubishi Electric
Corporation shall become void.

When mounting, installing and using the CC-Link interface module, observe the
standards and directives applicable in your country.
The national/international rules and regulations apply to the installation,
commissioning, use and periodic technical inspection of the MELSEC-WS safety
controller, in particular:
EMC directive 2004/108/EC,
Provision and Use of Work Equipment Directive 89/655/EC,
the work safety regulations/safety rules.
This manual must be made available to the operator of the machine where the
MELSEC-WS safety controller is used. The machine operator is to be instructed in
the use of the device by qualified safety personnel and must be instructed to read
the manual.

The MELSEC-WS safety controller fulfils the requirements of Class A (industrial
applications) in accordance with the Interference emission basic specifications.
The MELSEC-WS safety controller is therefore only suitable for use in an industrial
environment and not for private use.


ATTENTION
Note

ATTENTION
On safety MELSEC-WS

16

2.3 Environmental protection
The CC-Link interface module has been designed to minimise environmental
impact. It uses only a minimum of power and natural resources.
At work, always act in an environmentally responsible manner.
2.3.1 Disposal
Disposal of unusable or irreparable devices should always occur in accordance with
the applicable country-specific waste-disposal regulations (e.g. European Waste
Code 16 02 14).
2.3.2 Material separation
Material separation may only be performed by qualified safety personnel!
Exercise care when disassembling the devices. The danger of injury is present.
Before you can turn over the devices for environmental-friendly recycling, you must
separate the different materials of the CC-Link interface module from one another.
Separate the housing from the remaining components (especially the PCB).
Send the separated components to the corresponding recycling centers (see the
following table).

Component Disposal
Product
Housing
PCBs, cables, plugs and electrical
connection pieces
Plastic recycling
Electronics recycling
Packaging
Cardboard, paper
Paper/cardboard recycling


ATTENTION
Table 1:
Overview of disposal by
components
MELSEC-WS System configuration

17

3.1 Overall system configuration
The following shows the overall system configuration.

MELSEC-WS safety controller
WS0-GCC1
Q61BT11N/QS0J61BT12


Although the WS0-GCC1 can communicate data with the QS0J61BT12 over
CC-Link Safety as well, safety communication cannot be performed.
3.2 Applicable system
(1) Applicable modules and the number of connectable modules
The following table shows the applicable CPU modules and the number of
connectable WS0-GCC1s.

CPU module type Model
Number of
connectable
WS0-GCC1s
Remarks
MELSEC-WS CPU
module
WS0-CPU000200 2
*1
-
MELSEC-WS CPU
module (with EFI)
WS0-CPU130202 2
*1
-
*1 Up to two network modules can be connected.

(2) Compatible software package
The following table shows the software package compatible with the
WS0-GCC1.

Name Model Version Remarks
Setting and Monitoring
Tool
SW1DNN-WS0ADR-B Version1.2.1.0 -

3. System configuration
Figure 1:
System configuration
Note
Table 2:
Applicable modules and
the number of
connectable modules
Table 3:
Compatible software
package
CC-Link interface module MELSEC-WS

18

This chapter describes the CC-Link interface module (WS0-GCC1).
4.1 Overview
The CC-Link interface module is used to connect a MELSEC-WS safety controller to
a Q series programmable controller.
The module can exchange non-safety related data by connecting an external
application (e.g. Q series programmable controller) over CC-Link.
4.1.1 Interfaces and operation
The CC-Link interface module is equipped with a terminal block for CC-Link
network connection.

SLD
DG
DA
DB
Terminal block
L RUN/L ERR. LED
Station number setting switch 1
Station number setting switch 10
MS LED


4. CC-Link interface module
Figure 2:
Interfaces and display
elements of the
WS0-GCC1
MELSEC-WS CC-Link interface module

19

LED Meaning
No power supply, immediately after the module start or hardware
failure
Green Executing (live process data from/to CPU)
Green Idle (CPU STOP)
Green/Red Executing, but data link stopped or faulty
Red 1 Hz: Configuring/configuration required
2 Hz: Critical fault on CC-Link interface module
MS
Red Critical fault on another module
No power supply or data link stopped
Green Data link active
Green/Red One of the following has been detected when data link is active.
Configuration change of the station number setting switches
Terminating resistor not connected
Module or CC-Link dedicated cable affected by noise
Red One of the following has been detected when data link is
stopped.
Configuration change of the station number setting switches
Terminating resistor not connected
Module or CC-Link dedicated cable affected by noise
L RUN/
L ERR.
Red Station number setting switches out-of-range

Power-up sequence
On power up, the following LED test sequence is performed:
LED MS Off for 6 s.
LED MS Red for 0.25 s.
LED MS Green for 0.25 s.
LED MS Off

Table 4:
Meaning of the LED
displays
CC-Link interface module MELSEC-WS

20

Name Meaning
Station number
setting switches





A switch for configuring a station number for the module (factory
default: 0)
1 to 64: Station number
When the number other than 1 to 64 is configured, the MS LED
flashes in red and the L RUN/L ERR. LED lights up in red.
Example: Setting the station number 11

Terminal block
SLD, DG, DB, DA
CC-Link dedicated cables are connected for data link.
For wiring, see Section 4.3 and Section 4.4.
The SLD terminal is internally connected to the earthing spring
contact. (the connecting part to the DIN rail).
This two-piece terminal block allows replacement of a failed module
without disconnecting from the CC-Link network.
(Before replacement, power off the module to be replaced.)
For the crimp tools, see Section 7.4.

Table 5:
Station number setting
switches and terminal
block
MELSEC-WS CC-Link interface module

21

4.2 Mounting/Dismantling
This chapter describes the mounting of the CC-Link interface module.
Make sure that the connection of the CC-Link interface module cannot lead to
hazardous situations during installation!
Ensure that the connection of the CC-Link dedicated cables and power cables
cannot lead to a hazardous situation when implementing the unit on to the
MELSEC-WS safety controller and CC-Link network. Prevent unintended start-up of
equipment during connection of a CC-Link interface module. Failure to do so may
cause the system to malfunction.
4.2.1 Steps for mounting the modules
The MELSEC-WS safety controller is only suitable for mounting in a control
cabinet with at least IP 54 degree of protection.
Failure to meet the installation method may cause the module to fail or
malfunction due to the deposition of dust or the adhesion of water.
While supply voltage is applied, modules must not be plugged to nor be
removed from the MELSEC-WS safety controller.
To ensure full electromagnetic compatibility (EMC), the DIN mounting rail
must be connected to functional earth (FE). Additionally connect all network
cable shields directly at the control cabinet entrance to a common FE ground
line.

In a MELSEC-WS safety controller, the WS0-CPU0 or WS0-CPU1 module is
positioned at the extreme left.
The two optional network modules follow directly to the right of the CPU module.
Connect further MELSEC-WS safety I/O modules (e.g. WS0-XTIO or WS0-XTDI)
onto the right side of the network modules and any additional safety relay output
modules (WS0-4RO) to the extreme right of the entire MELSEC-WS safety
controller.
Mount the modules in accordance with EN 50274.
The modules are located in a 22.5 mm wide modular system for 35 mm DIN rails
according to EN 60715.
Ensure that suitable ESD protective measures are also taken during mounting.
Otherwise the FLEXBUS+ bus may be damaged.
The connection between the modules is effected by means of the plug connection
integrated in the housing. Take into account that, when replacing a module, the
MELSEC-WS modules have to be pushed approx. 10 mm apart before the
corresponding module can be removed from the DIN rail.
Take suitable measures to ensure that foreign matter does not penetrate the
connector openings, in particular that of the memory plug.


ATTENTION

ATTENTION
CC-Link interface module MELSEC-WS

22

3)
2)
1)


Make sure that the voltage supply of the MELSEC-WS safety controller is
switched off.
Hang the device onto the DIN rail (1)).
Ensure that the earthing spring contact is positioned correctly (2)). The earthing
spring contact of the module must contact the DIN rail securely to allow electrical
conductivity.
Latch the module onto the DIN rail by pressing it lightly in the direction of the
arrow (3)).



If there are several modules, slide the modules together individually in the
direction of the arrow until the side plug connection latches in.
Install the end clips on the right and left.

The following steps are necessary after mounting:
Complete the electrical connections (See Section 4.3.)
Configuration (See Section 4.5 and the Safety Controller Setting and Monitoring
Tool Operating Manual.)
Checking the installation (See the Safety Controller Users Manual.)

Figure 3:
Mounting the module
onto the DIN rail
Figure 4:
Installing the end clips
MELSEC-WS CC-Link interface module

23

4.2.2 Steps for dismantling the modules


Remove the removable terminals with wiring and the end clips.
If there are several modules, slide the modules away from each other individually
in the direction of the arrow until the side plug connection is separated.

1)
2)


Press the module downwards at the rear (1)) and remove it from the DIN rail in the
direction of the arrow while keeping it pressed down (2)).

Figure 5:
Disconnecting the plug
connections
Figure 6:
Removing modules
from the DIN rail
CC-Link interface module MELSEC-WS

24

4.3 Electrical installation
Switch the entire machine/system off line!
The system could start up unexpectedly while you are connecting the devices.

The CC-Link interface module fulfills the EMC requirements in accordance with
the basic specification EN 61000-6-2 for industrial use.
To ensure full electromagnetic compatibility (EMC), the mounting rail has to be
connected to functional earth (FE).
The control cabinet or assembly casing of the MELSEC-WS safety controller must
comply at least with enclosure rating IP 54.
Mount the modules in accordance with EN 50274.
Electrical installation in accordance with EN 60204-1
The voltage supply of the devices must be capable of buffering brief mains voltage
failures of 20 ms as specified in EN 60204-1.
The voltage supply has to fulfill the regulations for extra-low voltages with safe
separation (SELV, PELV) in accordance with EN 60664 and DIN 50178
(equipment of electrical power installation with electronic devices).
Ensure that all the modules of the MELSEC-WS safety controller, the connected
protective devices as well as the voltage supplies are connected with the same
earth (GND). The GND of the RS-232 interface is connected internally to the GND
of the supply of the CPU module (A2).
Connect all fieldbus and CC-Link cable shields directly at the control cabinet
entrance to the functional earth (FE).
Use dedicated cables as specified by the manufacturer for the CC-Link system. If
a cable other than the one specified by the manufacturer is used, the performance
of the CC-Link system is not guaranteed.
Also, follow the specifications shown in the Cable Wiring Manual from CC-Link
Partner Association for the overall cable distance and the station-to-station cable
length. If the wiring does not meet the specifications, accurate data transmission is
not guaranteed.
Do not install the control lines or communication cables together with the main
circuit lines or power cables. Failure to do so may result in malfunction due to
noise.
For other details, see the Cable Wiring Manual from CC-Link Partner Association.
CC-Link Partner Association website: http://www.cc-link.org/


ATTENTION
Note
MELSEC-WS CC-Link interface module

25

4.4 Connecting CC-Link dedicated cables
If the shield of a CC-Link dedicated cable is not properly grounded, the cable does
not meet the specifications of noise immunity.

Ground the shield of a cable connected to the CC-Link interface module which is
the farthest from the input power inside the control cabinet or any of the stations on
the CC-Link network within 30 cm from the module or station.
The CC-Link dedicated cables are shielded cables.
Strip a part of the jacket of the cable as shown in Figure 7 and ground the exposed
shield to the ground as much as possible.

CC-Link dedicated cable
Shield


The following shows the connection between the WS0-GCC1 and the master
station using a CC-Link dedicated cable.

Master station
CC-Link
DA
DB
DG
SLD
DA
DB
DG
SLD
FG
(Blue)
(White)
(Yellow)
CC-Link
Terminating
resistor
Terminating
resistor
interface module
dedicated cable


Use a bar terminal to connect the cable to the CC-Link interface module.
For applicable bar terminals, see Section 7.4.
Two poles of each terminal are internally connected. (See below.)
The SLD terminal is connected to the earthing spring contact at inside of the
CC-Link interface module.



The above figure shows a view from under the module after wiring.

Figure 7:
Grounding a CC-Link
dedicated cable
Figure 8:
Connecting stations to
FG line inside the
control cabinet
Figure 9:
Connecting CC-Link
interface modules
CC-Link interface module MELSEC-WS

26

4.5 First configuration steps
This chapter describes the basic steps you have to perform for the configuration of
the CC-Link interface module:

Station number configuration
Establish a first connection between the MELSEC-WS safety controller and a
PC or laptop.
Configuration of the number of occupied stations
Upload or transfer of a configuration
Verification of a configuration
4.5.1 Station number configuration
Configure the station number of the CC-Link interface module.
Since the configured station number becomes valid when the module is powered
on, power off the module before configuration.
The following is an example when the station number is set to 11.


4.5.2 Establishing a connection between MELSEC-WS safety controller
and PC
Connect a PC or notebook to the RS-232 interface of the CPU module.
Power on the MELSEC-WS safety controller.
Open the Setting and Monitoring Tool installed on the PC.
Click on Com Settings to ensure the correct communication interface has
been selected. The following dialog appears:



To edit the settings click on the pencil icon to the right. The following dialog
appears:
Figure 10:
Station number setting
switches
Figure 11:
Com Settings dialog
MELSEC-WS CC-Link interface module

27



Modify the settings if required.
Click OK. The dialog closes.
Click on Connect. The Setting and Monitoring Tool will search for connected
MELSEC-WS safety controller and load the hardware configuration into the
Hardware configuration dialog. Once all modules have been identified correctly,
the Setting and Monitoring Tool will ask whether the configuration shall be
uploaded.
Click Yes to upload the configuration.

As an example, the following hardware configuration may appear:



Click Disconnect to go into the offline mode if you want to change the
configuration of the MELSEC-WS modules.

Figure 12:
Com Settings dialog
Figure 13:
Hardware configuration
dialog
CC-Link interface module MELSEC-WS

28

4.5.3 Configuration of the number of occupied stations
Click on Network module configuration on the left hand menu.
Configure the number of occupied stations.
The following is an example when 1 station occupied has been selected.




Figure 14:
Configuration of the
number of occupied
stations
MELSEC-WS CC-Link interface module

29

4.5.4 Parameter configuration
The following parameters can be configured with Setting and Monitoring Tool.

No. Option Description
1 Number of occupied stations Select the number of stations
occupied by the CC-Link interface
modules.
2 Input data set
(MELSEC-WS to CC-Link)
Customize the input data sets.
3
Data sets for
cyclic
communication Output data set
(CC-Link to MELSEC-WS)
Define tag names for the output
data sets.

(1) Number of occupied stations
According to data size, the number of stations occupied by the CC-Link
interface module can be configured by the parameter (1 to 4).
Table 7 shows the data size for each device (remote input (RX), remote output
(RY), and remote resisters (RWw and RWr)), depending on the number of
occupied stations.

Device name Number of
occupied
stations
RX RY RWw RWr
1
(default)
2 bytes
(+ 2 bytes used by
the system)
2 bytes
(+ 2 bytes used by
the system)
8 bytes 8 bytes
2 6 bytes
(+ 2 bytes used by
the system)
6 bytes
(+ 2 bytes used by
the system)
16 bytes 16 bytes
3 10 bytes
(+ 2 bytes used by
the system)
10 bytes
(+ 2 bytes used by
the system)
24 bytes 24 bytes
4 14 bytes
(+ 2 bytes used by
the system)
14 bytes
(+ 2 bytes used by
the system)
32 bytes 32 bytes

(2) Customizing network input/output data sets
For customization of network input and output data sets, see Section 5.4 and
Section 5.6.

(3) Transmission speed
Since the transmission speed of the CC-Link interface module is determined
according to that of the master station, it does not need to be configured.
When the transmission speed is determined, Remote READY (RX(m+n)B) turns
on.

Table 6:
Parameter configuration
Table 7:
Device size depending
on the number of
occupied stations
CC-Link interface module MELSEC-WS

30

4.5.5 Transfer of a configuration
Once you have finished the configuration, you have to transfer the configuration to
your MELSEC-WS safety controller. In order to transfer a configuration, perform the
following steps:

Click Connect to go online. The Setting and Monitoring Tool connects to the
MELSEC-WS safety controller.
Click Transfer to transfer the configuration to the MELSEC-WS safety controller.
Depending on your current user level, you will be prompted to log on as
Administrator to be able to transfer a configuration. For details please see the
Safety Controller Setting and Monitoring Tool Operating Manual.
Once the transfer has been completed, you will be asked whether you want to run
the CPU module. Depending on your choice, click Yes or No to leave the dialog.
You can also start and stop the application in the Hardware configuration view
using the Run application or Stop application buttons while the project is online.
More information can be found in the Safety Controller Setting and Monitoring Tool
Operating Manual.
Note
Note
MELSEC-WS CC-Link interface module

31

4.5.6 Verification of a configuration
After the configuration has been transferred successfully, the MELSEC-WS safety
controller can be verified. To this purpose, the downloaded configuration data are
read back out from the safety controller and compared with the project data. If they
match, the data are displayed in a report. If the user confirms that they are correct,
the safety controller is considered to be verified.
In the Hardware configuration view, click the icon Upload and Verify
configuration and compare the configuration. The Upload and Verify Result
window is opened.
Click Yes below at the question Set device to verified? if the displayed
configuration is the expected configuration. The safety controller is then
considered to be verified.
You have to be logged in as an Administrator in order to mark the device as
verified.
If the verification is completed successfully, a Read in and compare report that
provides the most important project information is created subsequently. You
can print out or store this report.
The status verified/not verified is indicated in the lower right-hand corner of the
Setting and Monitoring Tool and by the CV LED of the CPU module turning on.
Only if the device and the corresponding configuration have been marked as
verified, the Auto RUN Mode in the configuration of the CPU module is active. If
the configuration is not set to verified after power up, the safety controller stays in
Idle mode (CV LED on the CPU module flashing) and the safety controller needs
to be set to Run Mode using the Setting and Monitoring Tool.
If differences between the project data and the read-back configuration data are
detected, a corresponding message including information about possible actions
is displayed. Verification of the configuration is not possible then. Observe the
information in the error message for the further procedure. Terminate the dialog
box by clicking Close.
If you change a verified configuration, the status is reset to not verified.
Exception: If you make only non safety-related changes such as modifying the
CC-Link interface module name or the number of occupied stations, the
configuration status remains verified.
More information can be found in the Safety Controller Setting and Monitoring Tool
Operating Manual.
4.5.7 Upload of a configuration
When in online mode, you can upload a configuration from the connected
MELSEC-WS safety controller:
Click on Upload. The current configuration of the safety controller will be
loaded into the Setting and Monitoring Tool and can be edited after going
offline.


Note
Data sets MELSEC-WS

32

The CC-Link interface module allows the MELSEC-WS safety controller to send and
receive non-safety related data to and from the external fieldbus system for control and
diagnostics purposes.

In this manual, the data exchanged between the MELSEC-WS safety controller and
the respective network will be considered always from the network master
(programmable controller) point of view. Therefore data sent from the MELSEC-WS
safety controller into the network (master station) will be referred to as network
input while data received from the network (master station) will be referred to as
network output.
Do not operate a CC-Link interface module on a safety fieldbus!
The CC-Link interface module is not suitable for operation on a safety fieldbus. It
does not support any safety mechanism, which would be mandatory to
communicate within a safety network.
Configuration of the CC-Link interface module is performed using the Setting and
Monitoring Tool on a PC or laptop connected to the CPU module over RS-232
interface. Configuration data can be exported, imported, and saved.
If the MELSEC-WS safety controller has been configured to integrate non-safe
information from the fieldbus into the logic editor, a decoupling of the CC-Link
interface module can result in availability problems.
A CC-Link interface module can only be operated on a MELSEC-WS safety
controller. It does not have a dedicated voltage supply. It is possible to use two
network modules per system.
The CC-Link interface module is fitted in a 22.5 mm wide housing for 35 mm rails in
accordance with EN 60715.

5. Data sets
Note

ATTENTION
MELSEC-WS Data sets

33

5.1 Data transmitted into the network
(network input data sets (RX, RWr))
Available data
The CC-Link interface module can provide the following data:
Operational data
Logic results from the CPU module (see Section 5.1.1.)
Input values (Active/Inactive) for all safety I/O modules in the system and
EFI devices connected (see Section 5.1.2.)
Output values (Active/Inactive) for all safety I/O modules and EFI devices
connected (see Section 5.1.2.)
Output data from another network, i.e. data received by a second network
module in the safety controller (see Section 5.1.3.)
Data sets
Input data sets to be sent from the CC-Link interface module to the network
consist of logic results, I/O state data, and other data.
If a CC-Link network is disconnected, data communication will be disabled.
To hold input data (RX) in the master station, open the Operational settings
window from the CC-Link parameter dialog box of GX Developer and check the
Hold input data checkbox under Data link disorder station setting.
5.1.1 Logic results
Logic results generated by the logic editor of the CPU module can be sent to the
master station. Up to 20 bytes are available where each bit represents one logic
result from the logic editor.
Data set containing the logic results can be customized. For detailed information
see Section 5.4.
Data sets MELSEC-WS

34

5.1.2 Module and EFI input and output values
The CC-Link interface module can transmit all input and output states of all
MELSEC-WS modules and EFI devices connected to the MELSEC-WS safety
controller to the master station. Data set containing the input and output values and
the EFI information can be customized. For detailed information see Section 5.4.
Module input and output states
The input and output states of the modules are transmitted using one byte for each
modules inputs and one byte for each modules outputs where each bit represents
the state of one input or output (on/off).
EFI system information
The WS0-CPU1 module has 2 EFI interfaces. An EFI interface is a safe
communication interface between SICK devices. It allows to
read out information from the safety devices (e.g. SICK C4000, S3000)
transfer commands to the safety devices
The CC-Link interface module allows these EFI devices connected to the
WS0-CPU1 to transmit their data to the master station.
It is only possible to select the EFI data in byte arrays. 4 byte arrays for each
connected EFI device are available. Some of the data contents are reserved and
can not be used at the programmable controller.

Further information about the properties, functions and benefits of the EFI
interfaces can be found in the Safety Controller Users Manual.
5.1.3 Routing of data from a second network
If your MELSEC-WS safety controller contains two network modules, it is possible
to route information received by the first network module from one network (e.g.
from an HMI) into a second network (e.g. to a programmable controller) via the
second network module and vice versa.

Note
MELSEC-WS Data sets

35

5.2 Data received from the network
(network output data sets) (RY, RWw))
The data received from the master station are organized in output data sets (max.
46 bytes (RY is 14 bytes and RWw is 32 bytes)).
The contents of the output data blocks can be used within the Setting and
Monitoring Tool logic editor and can also be made available to another network via
a second network module in the MELSEC-WS safety controller.
In order to make the data from the network available in the logic editor or as
input to another network, you will have to define a tag name for each bit that
shall be used.
Bits without a specific tag name will not be available in the logic editor nor for
routing via another network module. For detailed information on how to define tag
names for the data received please see Section 5.6.
These modules may only be used by qualified safety personnel and only on the
machine where they have been installed and initialized by qualified safety
personnel in accordance with the manual.
The status of the communication to and from the network can be checked by
monitoring the input data status (for data received from the master station) and the
output data status (for data send to the master station) in the logic editor. When the
CC-Link interface module detects a communication error or the STOP status of the
CPU module on the master station, the network output data sets will be set to off and
the corresponding data status will also be set to off.

No. Name Description Remarks
1
Input data status Off: Error
On: Normal
This signal turns on when data is normally
received from the master station.
2
Output data status Off: Error
On: Normal
This signal turns on when data to be sent
from the WS0-GCC1 to the master station
is ready.
Monitor this signal to check if data is ready
for transmission.

Since output data set, input data status, and output data status are non-safety
related data, do not use them for safety related applications.

Note
Table 8:
Data status

ATTENTION
Data sets MELSEC-WS

36

5.3 Default settings for the input data set
In the delivery status, the input data set (RX, RWr) of the CC-Link interface module
are pre-configured. The following table shows the default data assignment.
The default byte assignment can be freely customised as will be described in the
following section. The reserved areas shown in the following table are for system
use; therefore, these areas are not displayed on the editing window.

Data
One station is
occupied.
Two stations
are occupied.
Three stations
are occupied.
Four stations
are occupied.
RX07 - RX00 - - - -
RX0F - RX08 - - - -
RX17 - RX10 - - -
RX1F - RX18
Reserved
- - -
RX27 - RX20 - - -
RX2F - RX28 - - -
RX37 - RX30 - -
RX3F - RX38
Reserved
- -
RX47 - RX40 - -
RX4F - RX48 - -
RX57 - RX50 -
RX5F - RX58
Reserved
-
RX67 - RX60 -
RX6F - RX68 -
RX77 - RX70
RX7F - RX78



Reserved
RWr00 Low Logic result 0 Logic result 0 Logic result 0 Logic result 0
RWr00 High Logic result 1 Logic result 1 Logic result 1 Logic result 1
RWr01 Low Logic result 2 Logic result 2 Logic result 2 Logic result 2
RWr01 High Logic result 3 Logic result 3 Logic result 3 Logic result 3
RWr02 Low Module 1 input Module 1 input Module 1 input Module 1 input
RWr02 High Module 1 output Module 1 output Module 1 output Module 1 output
RWr03 Low Module 2 input Module 2 input Module 2 input Module 2 input
RWr03 High Module 2 output Module 2 output Module 2 output Module 2 output
RWr04 Low Module 3 input Module 3 input Module 3 input
RWr04 High Module 3 output Module 3 output Module 3 output
RWr05 Low Module 4 input Module 4 input Module 4 input
RWr05 High Module 4 output Module 4 output Module 4 output
RWr06 Low Module 5 input Module 5 input Module 5 input
RWr06 High Module 5 output Module 5 output Module 5 output
RWr07 Low Module 6 input Module 6 input Module 6 input
RWr07 High Module 6 output Module 6 output Module 6 output
RWr08 Low Module 7 input Module 7 input
RWr08 High Module 7 output Module 7 output
RWr09 Low Module 8 input Module 8 input
RWr09 High Module 8 output Module 8 output
RWr0A Low Module 9 input Module 9 input
RWr0A High Module 9 output Module 9 output
RWr0B Low Module 10 input Module 10 input
RWr0B High Module 10 output Module 10 output
RWr0C Low Module 11 input
RWr0C High Module 11 output
RWr0D Low Module 12 input
RWr0D High Module 12 output
RWr0E Low -
RWr0E High -
RWr0F Low -
RWr0F High



-
-: Not configured (0 is sent.)
Table 9:
Default configuration for
the input data set
MELSEC-WS Data sets

37

5.4 Customizing the input data set
(MELSEC-WS to CC-Link)
This section outlines briefly how you can customize the input data set that the
CC-Link interface module transmits to the network.
In the delivery status, the data routing configuration of the CC-Link interface module
is shown in the network module configuration dialog.
Click on the GCC1 Network Module [13] button (Network Modules button
when two network modules are used) above the main window and select the
respective CC-Link interface module to open the network module configuration
dialog.
Click on the MELSEC-WS to CC-Link tab on the left hand menu to display the
network module configuration dialog.
The default setting is as follows:

3)
2)
1)
4)

Basically this dialog is divided into three areas: Available data (1)), Network
Module Data (2)) and Tag Names (3)). The upper left corner of the dialog holds the
toolbar (4)).

Figure 15:
MELSEC-WS to CC-Link
dialog of the WS0-GCC1
Data sets MELSEC-WS

38

5.4.1 The toolbar

The toolbar contains buttons for the following actions (from left to right):
The Load user configuration and Save user configuration buttons allow you
to load and/or save a configuration in XML format. If you load a configuration, all
previously made changes that have not been saved will be lost. You can not
undo this action.
With the Import and Export buttons you can import and export a configuration
including the tag names used as a CSV (comma separated values) file. This
allows you to import and use the assigned tag names in a programmable
controller program. To edit the CSV file, use a text editor.
When importing the exported network module data after editing the data in a text
editor such as Notepad, select CSV Files - Shift-JIS encoded for Files of type in
the Open dialog box if the data is saved in ANSI format. If not, characters in the
data may get garbled.
The Import button is only available for the CC-Link to MELSEC-WS routing
configuration.
Reset to default restores the default routing configuration. You will be prompted
for confirmation. If you click Yes, all previously made changes that have not
been saved will be lost. You can not undo this action.
Clear all clears the configuration, i.e. deletes all assigned bytes in the Network
Module Data area. You will be prompted for confirmation.
Delete Routing deletes the selected byte from the Network Module Data area.
The Undo and Redo buttons allow you to undo or redo changes you made to your
configuration.
Figure 16:
Toolbar for the routing
configuration
Note
Note
MELSEC-WS Data sets

39

5.4.2 Available data area
This area offers all sources from which data may be routed into the network. It is
divided in two views holding the available Input types and Output data. You can
switch between these views using the file cards at the bottom.
The Input types view contains the input values for the connected MELSEC-WS
modules and EFI devices. If your MELSEC-WS safety controller contains a
second network module, the input data of this network module (i.e. data received
from the network the second network module is connected to) will be available
here as well.
The Output view offers the output values for the connected MELSEC-WS
modules and EFI devices as well as the Logic results from the logic editor.
All sources supported by the current configuration are displayed in black:
connected MELSEC-WS modules
connected EFI devices
configured logic results
*1

input data available from another network module in the system

*1 In the default configuration, only the first logic result byte (Logic Result 0) is active and available. You
can activate more logic result output bits in the logic editor.

Sources currently not configured will be displayed in grey. Activating the Show only
available data checkbox in the upper left corner hides the unused sources from the
view.
Sources that offer live data are marked with a little icon next to the text.

How to add a data byte to the routing table:
Drag and drop an element (i.e. byte) from the Available data area to a free slot
in the Network Module Data area. If the desired position is not free, you will
have to clear it first by deleting or moving the byte currently assigned to it.
It is possible to use the same byte several times in the routing table. Note
Data sets MELSEC-WS

40

5.4.3 Network Module Data area
This area contains the routing table. It shows the current content of the CC-Link
interface modules input data modules. Bytes and bits highlighted blue will hold
live data from the system since the hardware configuration does support the
source. Bytes highlighted grey actually do not have data associated with them since
the hardware configuration does not support the sources.

How to delete a data byte from the routing table:
Drag and drop the byte you want to delete to the trashcan icon in the bottom
left corner of the Network Module Data area.
Or:
Select the byte you want to delete by clicking it with the left mouse button. Then,
click on the Delete Routing button in the toolbar.
Or:
Call up the context menu by clicking the respective byte with the right mouse
button. In the context menu, select the Delete Routing command.

How to move a data byte to another place in the routing table:
Drag and drop the byte you want to move to the desired position. If the desired
position is not free, you will have to clear it first by deleting or moving the byte
currently assigned to it.
5.4.4 Tag names area
This area shows the tag names associated with each bit of the byte currently
selected in the Available data or the Network Module Data area. You can enter
these tag names in the logic editor and in the hardware configuration dialog (e.g. for
safety I/O modules).
In the Tag Names area of the MELSEC-WS to CC-Link configuration dialog, it is
not possible to edit the tag names.

MELSEC-WS Data sets

41

5.5 Default settings for the output data set
In the delivery status, the output data set (RY, RWw) of the CC-Link interface
module are pre-configured. The following table shows the default data assignment.
The reserved areas shown in the following table are for system use; therefore,
these areas are not displayed on the editing window.

Data
One station is
occupied.
Two stations
are occupied.
Three stations
are occupied.
Four stations
are occupied.
RY07 - RY00 Byte 0 Byte 0 Byte 0 Byte 0
RY0F - RY08 Byte 1 Byte 1 Byte 1 Byte 1
RY17 - RY10 Reserved Byte 2 Byte 2 Byte 2
RY1F - RY18
RX1B:
Remote READY
Other than RX1B:
Reserved
Byte 3 Byte 3 Byte 3
RY27 - RY20 - - --
RY2F - RY28 - - -
RY37 - RY30 Reserved - -
RY3F - RY38
RX3B:
Remote READY
Other than RX3B:
Reserved
- -
RY47 - RY40 - -
RY4F - RY48 - -
RY57 - RY50 Reserved -
RY5F - RY58
RX5B:
Remote READY
Other than RX5B:
Reserved
-
RY67 - RY60 -
RY6F - RY68 -
RY77 - RY70 Reserved
RY7F - RY78



RX7B:
Remote READY
Other than RX7B:
Reserved
-: Not configured
Table 10:
Default configuration for
the output data set
Data sets MELSEC-WS

42

Data
One station is
occupied.
Two stations
are occupied.
Three stations
are occupied.
Four stations
are occupied.
RWw00 Low - - - -
RWw00 High - - - -
RWw01 Low - - - -
RWw01 High - - - -
RWw02 Low - - - -
RWw02 High - - - -
RWw03 Low - - - -
RWw03 High - - - -
RWw04 Low - - -
RWw04 High - - -
RWw05 Low - - -
RWw05 High - - -
RWw06 Low - - -
RWw06 High - - -
RWw07 Low - - -
RWw07 High - - -
RWw08 Low - -
RWw08 High - -
RWw09 Low - -
RWw09 High - -
RWw0A Low - -
RWw0A High - -
RWw0B Low - -
RWw0B High - -
RWw0C Low -
RWw0C High -
RWw0D Low -
RWw0D High -
RWw0E Low -
RWw0E High -
RWw0F Low -
RWw0F High



-
-: Not configured
Remote READY turns on when a transmission speed is determined by the
autosensing function.
Check that Remote READY is on before configuring the RY and RWw values using
the sequence program.
MELSEC-WS Data sets

43

5.6 Tag names for incoming data
(CC-Link to MELSEC-WS)
In order to enable incoming data bits:
Click on CC-Link to MELSEC-WS on the left hand menu. The following dialog
appears:

2)
1)

Basically this dialog is divided into two areas: Network Module Data (1)) and Tag
Names (2)):
The Network Module Data area shows the current configuration of the output
modules.
The Tag Names area shows the tag names associated to the byte selected in the
Network Module Data area.
Select a byte in the Network Module Data area.
For each bit of the selected byte that you wish to use, enter a tag name in the
Tag Names area.

Figure 17:
CC-Link to
MELSEC-WS dialog of
the WS0-GCC1
Data sets MELSEC-WS

44

Each bit you enter a tag name for here will be available within the logic editor or for
the process image of a second network module:

5.6.1 Saving and loading a configuration
Using the buttons Load user configuration and Save user configuration you can
save and load your configuration in XML format. If you load a configuration, all
previously made changes that have not been saved will be lost. You can not undo
this action.
5.6.2 Importing and exporting a configuration
With the Import and Export buttons you can import and export a configuration
including the tag names used as a CSV (comma separated values) file. This allows
you to import and use tag names you have assigned in the MELSEC-WS safety
controller project in another programmable controller program and vice versa. To
edit the CSV file, use a text editor.
If you import a configuration, all previously made changes that have not been
saved will be lost. You can not undo this action.

The Import button is only available for the CC-Link to MELSEC-WS routing
configuration.
Figure 18:
Tag names of incoming
bits of the WS0-GCC1
in the logic editor dialog
Note
MELSEC-WS Data sets

45

5.7 Monitoring the data set online
When the MELSEC-WS safety controller is online and running, you can monitor the
data set online in the network module configuration dialog.
Click on the GCC1 Network Module [13] button (Network Modules button when
two network modules are used) above the main window and select the respective
CC-Link interface module to open the network module configuration dialog.
Click on the MELSEC-WS to CC-Link or the CC-Link to MELSEC-WS tab on
the left hand menu to display the routing view for the input or output data you
want to monitor.
For both directions, MELSEC-WS to CC-Link as well as CC-Link to MELSEC-WS,
inactive bits are displayed grey while active bits are highlighted green:

In the MELSEC-WS to CC-Link view, bits that are inactive due to an error are
displayed red. This could be the case e.g. for the outputs of a WS0-XTIO module if
the power supply of this module is faulty:

In the CC-Link to MELSEC-WS view, bits that have no tag name assigned (so that
they can not be used in the logic editor) but which are included in the process image
that the CC-Link interface module receives from the programmable controller, are
highlighted yellow:


The CC-Link interface module always reflects the actual physical status of the inputs
and outputs on the connected modules and devices. This means that even when
Force mode is active and inputs that are physically Inactive (Low) are forced Active
(High) (or vice versa) the actual physical status of these inputs will be transmitted to
the programmable controller instead of the (virtual) forced status. If, however, as a
result of forcing of one or several inputs, one or several outputs change their status,
the changed status of these outputs will be transmitted to the programmable
controller since the actual physical status of the outputs on the devices has changed.
Figure 19:
Active and inactive bits
in the online process
image
Figure 20:
Inactive Network input bits
as a result of an error
Figure 21:
Network output bits with
no tag names assigned in
the online process image
Note
Data sets MELSEC-WS

46

5.8 Accessible range
Accessible range of Setting and Monitoring Tool
Setting and Monitoring Tool can access the CPU module that is directly
connected using an RS-232 cable (cannot access the CPU module over
CC-Link).
Accessibility to network input and network output
The following table shows the accessibility from the station on the CC-Link
network to the network input and network output of the WS0-GCC1.
The network input can be read from the master stations, local stations, and
intelligent device stations.
Only the master stations can write the network output.

1
QCPU
2
QCPU
3 4
GT15-J61BT13
RD station: Remote device station
A B
QJ61
QS0J61
BT12
(M
BT11N/
station)
QCPU/
QSCPU
QJ61
(L
BT11N
station)
WS0-
CPU0/
CPU1
WS0-
CPU0/
CPU1
WS0-
GCC1
(RD
station)
WS0-
GCC1
(RD
station)
WS0-
GCC1
(RD
station)
GOT
[GT15/GT16]
(ID station)
M station : Master station
L station : Local station
ID station : Intelligent device station
QJ61
(M
BT11N
station)



Access target
Requesting device
A: WS0-CPU0/CPU1 B: WS0-CPU0/CPU1
1 QCPU/QSCPU -
2 QCPU
3 QCPU
4 GOT (GT15/GT16)

: Can be read/written, : Can be read, -: Cannot be read/written

Figure 22:
Reading/writing network
input and network
output
Table 11:
Accessibility by cyclic
transmission
MELSEC-WS Troubleshooting

47

Check the LEDs of the module during troubleshooting.
6.1 When data cannot be normally exchanged
Refer to the following flowchart when data cannot be normally exchanged.



6. Troubleshooting
Note
Figure 23:
Troubleshooting
flowchart: when data
cannot be normally
exchanged
Troubleshooting MELSEC-WS

48

6.2 When the L RUN/L ERR. LED does not turn on
(green)
Refer to the following flowchart when the L RUN/L ERR. LED does not turn on
(green) at power-on or during RUN of the WS0-GCC1.



Figure 24:
Troubleshooting
flowchart: when the L
RUN/L ERR. does not
turn on (green)
MELSEC-WS Troubleshooting

49

6.3 When an error occurs in remote input (RX) or
remote register (RWr)
Refer to the following flowchart when an error occurs in remote input (RX) or
remote register (RWr) at power-on or during RUN of the WS0-GCC1.


6.4 When an error occurs in remote output (RY) or
remote register (RWw)
Refer to the following flowchart when an error occurs in the remote output (RY) or
remote register (RWw) at power-on or during RUN of the WS0-GCC1.




Figure 25:
Troubleshooting
flowchart: when an
error occurs in remote
input (RX) or remote
register (RWr)
Figure 26:
Troubleshooting
flowchart: when an
error occurs in remote
output (RY) or remote
register (RWw)
Technical specifications MELSEC-WS

50

7.1 Technical specifications, supply circuit

Item Specifications
Supply voltage 24 V DC (16.8 to 30 V DC)
Power consumption Max. 1.4 W
7.2 Technical specifications of CC-Link interface
module

Item Specifications
Fieldbus CC-Link
CC-Link station type Remote device station
CC-Link Version Ver.1.10
Data transmission
speed
156kbps/625kbps/2.5Mbps/5Mbps/10Mbps
(autosensing)
Station number 1 to 64 (factory default: 0)
Number of occupied
stations
1 station (RX/RY 32 points each, RWw/RWr 4points each)/
2 stations (RX/RY 64 points each, RWw/RWr 8points each)/
3 stations (RX/RY 96 points each, RWw/RWr 12 points each)/
4 stations (RX/RY 128 points each, RWw/RWr 16 points each)
(The last 16 points of RX/RY are for system use (reserved).)
CC-Link interface 1 terminal block at the lower part of the module
Cable Ver.1.10-compatible CC-Link dedicated cable
*1

Data interface Backplane bus (FLEXBUS+)
*1 Connect a terminating resistor (110).
7. Technical specifications
Table 12:
Technical specifications,
supply circuit
Table 13:
Technical specifications
of CC-Link interface
module
MELSEC-WS Technical specifications

51

7.3 General technical specifications

Item Specifications
Fieldbus CC-Link
FLEXBUS+ 10-pin connector for internal safety bus (plug)
Ambient operating
temperature
0C to +55C
Storage temperature -25C to +70C
Humidity 10% to 95%, non-condensing
Climatic conditions According to EN 61131-2
Vibration Tested in accordance with IEC 61131-2.
Rigidity Tested in accordance with IEC 61131-2.
Protection class III
Electromagnetic
compatibility
IEC 61000-6-2, EN 55011 Class A
Housing material Polycarbonate
Housing type Device for control cabinet installation
Housing enclosure
rating/terminals
IP 40/IP 20 according to IEC60529
Housing color Light grey
Weight 120g
Mounting rail Mounting rail according to IEC/EN 60715

Table 14:
General technical
specifications
Technical specifications MELSEC-WS

52

7.4 Technical specifications of cables
Technical specifications of cables
Item Specifications
Ver1.10-compatible
CC-Link dedicated
cable
For the specifications and any inquiries on the
CC-Link dedicated cables, refer to the following:
CC-Link Partner Association website:
http://www.cc-link.org/
Cable size 20 AWG
Temperature rating -15C to +75C
Material Conductor: Annealed copper wire (finely stranded)
Core type Finely stranded
Solderless terminal
(bar terminal) and
crimp tool
1) Mitsubishi Electric Engineering Co., Ltd.
Bar terminal model: FA-TVC125T9
Crimp tool : FA-NH65A
2) NICHIFU Co.,Ltd.
Bar terminal model: TE0.5-10 (for CC-Link
dedicated cable (0.5mm
2
)), TE1.5-10 (for SLD)
Crimp tool: NH-79
3) PHOENIX CONTACT
Bar terminal model: AI0.5-10WH (for CC-Link
dedicated cable (0.5mm
2
)), AI1.5-10BK (for SLD)
Crimp tool: CRIMPFOX UD6, CRIMPFOX
UD6-4, CRIMPFOX UD6-6, and CRIMPFOXZA3
*Note: When a shielded cable is excessively crimped
to a bar terminal using a tool, CRIMPFOX
UD6-4 or CRIMPFOX UD6-6, the bar terminal
may not be connected to the terminal block
depending on the cross-sectional shape after
crimping.
Tightening torque
range
No torque range specified since two-tier tension-spring
terminal is used.
7.5 Transmission delay time
For transmission delay time, refer to the CC-Link System Master/Local Module
User's Manual.
For the processing time of the remote device station that is used to calculate the
transmission delay time, see the response time of the MELSEC-WS safety
controller given in the Safety Controller Users Manual.
The following shows the response times of field bus sender and receiver that are
used to calculate the response time of the safety controller.
Response time field bus sender: 1 ms
Response time field bus receiver: 1 ms
Table 15:
Technical specifications
of cables
MELSEC-WS Technical specifications

53

7.6 Dimensional drawings

120.8
9
6
.
5
22.5
Unit: mm

Figure 27:
Dimensional drawings
of WS0-GCC1 (mm)
Connecting to a Q series programmable controller MELSEC-WS

54

This chapter describes the exchange of non-safety related data (transmission data:
RX, RWr, reception data: RY, RWw) between a MELSEC-WS safety controller and
a Q series programmable controller over CC-Link.
The safety controller can also exchange non-safe data with a QS series
programmable controller.
8.1 Features achieved by the connection
The QJ61BT11N or QS0J61BT12 can read the MESLEC-WS safety controller
information (e.g. operation results of the CPU module, safety input/output data) by
cyclic transmission.
This feature allows you to notify the MELSEC-WS safety controller of device state
or other information from a Q series programmable controller.

Do not operate a CC-Link interface module on a safety fieldbus!
The CC-Link interface module is not suitable for operation on a safety fieldbus. It
does not support any safety mechanism, which would be mandatory to
communicate within a safety network.

A1 A2
CPU1
A
B
A
B
1-EFI-2
EFI 2
EFI 1
X 1 X2 A1 A2
Q 1 Q2 Q 3 Q4
I 5 I6 I7 I 8
I 1 I2 I3 I 4
MS MS
CV
XTIO
X1 X2 X3 X4
X5 X6 X7 X8
I 5 I6 I7 I 8
I 1 I2 I3 I 4
MS
XTDI
13 23 33 43
14 24 34 44
Y 14 Y1Y24 Y3
PWR
B1 Y2 B2 Y 4
K1/2
K3/4
+24 V I NT. B2
B1 Y1 13 23 Y 1 4
Y
4
3
4
4
4
Y 2
4
Y
2
1
4
2
4 Y3 33 43
4RO
MITSUBISHI
MS
GCC1
DA DB DG FG
L RUN/L ERR
STATIONNo.
WS0-GCC1
<MELSEC-WS safety controller> <Programmable controller>
<GOT>
POWER
MELSEC
Q61P
MITSUBISHI
MODE
Q25HCPU
RUN
ERR.
USB
RS- 232
USER
BAT.
BOOT
QJ61BT11N
RUN
MST
SD
L RUN
RD
ERR. L ERR.
S MST
CC-Link
QJ61BT11N/QS0J61BT12
MELSEC-WS safety
controller information
Logic results of
the CPU module
Input/output
signal state
Input
Output
x 10
x1
Operation
result

8. Connecting to a Q series programmable controller

ATTENTION
Figure 28:
Obtaining information in
a MELSEC-WS safety
controller
MELSEC-WS Connecting to a Q series programmable controller

55

A1 A2
CPU1
A B A B
1-EFI -2
EFI2
EFI1
X1 X 2 A1 A2
Q1 Q2 Q3 Q4
I 5 I 6 I7 I8
I 1 I 2 I3 I4
MS MS
CV
XTIO
X 1 X 2 X3 X4
X 5 X 6 X7 X8
I5 I6 I7 I 8
I1 I2 I3 I 4
MS
XTDI
13 23 33 43
14 24 34 44
Y14Y1 Y24 Y3
PWR
B1 Y2 B2 Y4
K1/2
K3/4
+24 V I NT . B2
B
1
Y
1
1
3
2
3
Y1
4
Y4 34 44 Y2 4
Y2 14 24 Y3 33 43
4RO
MIT SUBISHI
WS0-GCC1
<MELSEC-WS safety controller> <Programmable controller>
<GOT>
POWER
MELSEC
Q61P
MITSUBISHI
MODE
Q25HCPU
RUN
ERR.
USB
RS- 232
USER
BAT.
BOOT
QJ61BT11N
RUN
MST
SD
L RUN
RD
ERR. L ERR.
S MST
CC-Link
QJ61BT11N/QS0J61BT12
Notification of device state or other information
MS
GCC1
L RUN/L ERR
STATI ON No.
x10
x 1
DA DB DG FG


8.2 Applicable system
For system configuration of the programmable controller, refer to the following.
CC-Link System Master/Local Module User's Manual


Figure 29:
Notifying information to a
MELSEC-WS safety
controller
Preparing for operation MELSEC-WS

56

9.1 System configuration and start-up procedure

This section provides procedures before operation with the following system
configuration example.

PO WER I / O0 I/ O1 I/O 2 I/ O3 I/ O 4 CPU
BASE UNIT
MITSUBISHI
MELSEC
Q61P- A1
POWER

PULL
Q06UDHCPU
MODE
RUN
ERR.
USER
BAT.
BOOT
PULL

RS- 232

USB

QJ71GP21C- SX
PRM
D .LI NK
RD
C ERR .
RUN
MO DE
SD
ERR .
1 0 0 1 0 1
IN
OUT
QJ61BT11
RU N
MST
SD
ERR
L RU N
S MST
RD
L ERR .
9 0
876
5 4 3 2 1
.
1
3
5
7
2
4
6
9
0
87
6
5 4 3 2
1
9 0
87
65
4 3 2 1
10
1
STATI ON
NO
MODE
QJ61BT11N
Master station
Station number: 0
Start I/O number: 0
A1 A2
CPU1
A
B
A
B
1-EFI -2
EFI 2
EFI 1
MS
CV
MITSUBIS
HI
MS
L ERR
GCLL
DA DB DG FG
L RUN
ST No.
WS0-GCC1
Remote device station
(1 station occupied )
Station number: 1
CPU module
WS0-CPU1


Start
Mount modules.
Wire cables.
Configure station numbers.
Configure the parameters of
the WS0-GCC1.
End
Configure the parameters of
the master station.
Power on the WS0-GCC1
again.

9. Preparing for operation
Figure 30:
System configuration
example
Figure 31:
Procedure before
operation
MELSEC-WS Preparing for operation

57

9.2 Wiring
This section describes wiring of the WS0-GCC1 using CC-Link dedicated cables.
For wiring of the QJ61BT11N, refer to the following.
CC-Link System Master/Local Module User's Manual

(1) Cables
Use dedicated cables as specified by the manufacturer for the CC-Link system
(see Section 7.2).
If a cable other than the one specified by the manufacturer is used, the
performance of the CC-Link system is not guaranteed.
For the specifications and any inquiries on the CC-Link dedicated cables, refer
to the following:
CC-Link Partner Association website: http://www.cc-link.org/

Wiring precautions
For wiring precautions, refer to SAFETY PRECAUTIONS.

Preparing for operation MELSEC-WS

58

9.3 Sample program
This section describes examples of parameter configuration and a program for
communication between the WS0-GCC1 and QJ61BT11N.
For system configuration, refer to the example in Section 9.1.

The WS0-GCC1 exchanges data and signals with the QJ61BT11N by cyclic
transmission.
The cyclic transmission automatically exchanges bit data (RX, RY, RWw, and RWr)
between the WS0-GCC1 and the QJ61BT11N.
The CPU module periodically sends/receives those bit data to/from the
WS0-GCC1.

Cyclic transmission
WS0-GCC1 CPU module
Internal data
Data
communications
QJ61BT11N
RY, RX, RWw, RWr RY, RX, RWw, RWr

Figure 32:
Data exchange by cyclic
transmission
MELSEC-WS Preparing for operation

59

9.3.1 Parameter configuration example
This section describes parameter configuration to output data from the WS0-GCC1
to the QJ61BT11N and to input data from the QJ61BT11N to the WS0-GCC1.
(1) Configuration required for the WS0-GCC1
The following shows the configuration example using the system configuration
of Figure 30.
1) Creating a hardware configuration
Read the hardware configuration data from the actual CPU module to Setting
and Monitoring Tool or place modules in Setting and Monitoring Tool
according to the actual configuration.



Figure 33:
Hardware configuration
dialog
Preparing for operation MELSEC-WS

60

2) Configuring the number of occupied stations
Configure the number of stations occupied by the WS0-GCC1 in the network
module configuration dialog.
In this example, 1 station occupied has been selected.


When Setting and Monitoring Tool is connected to the CPU module, the station
number, number of occupied stations and transmission speed can be checked in
the network module configuration dialog.

Figure 34:
Configuring the number
of occupied stations
Figure 35:
Monitoring the station
number, number of
occupied stations, and
transmission speed
MELSEC-WS Preparing for operation

61

3) Editing data sets
Editing network input data sets
Open the MELSEC-WS to CC-Link dialog and edit RX and RWr.



Editing network output data sets
Open the CC-Link to MELSEC-WS dialog and configure tag names for each output
data set as required.


Figure 36:
MELSEC-WS to
CC-Link dialog
Figure 37:
CC-Link to
MELSEC-WS dialog
Preparing for operation MELSEC-WS

62

(2) Configuration and program required for the QJ61BT11N
The following shows a network parameter configuration example with GX
Developer.
For precautions for parameter configuration and program creation, refer to the
following.
CC-Link System Master/Local Module Users Manual
1) Configuring network parameters with GX Developer
Select CC-Link to open the network parameter dialog box and configure the
options as follows.



Figure 38:
Network parameter
configuration for
CC-Link
MELSEC-WS Preparing for operation

63

2) Network parameter - Station information setting
Select Station information to open the configuration dialog box and
configure the options as follows.



After configuring the parameters of the master station, power on the WS0-GCC1
again.
9.3.2 Sample program
Create a program so that the communication is interlocked according to the
data-link status.
Also, create an error-handling program.



If a CC-Link dedicated cable is disconnected, the line status may become
unreliable, resulting in a data link communication error at multiple stations.
Configure an interlock circuit in the sequence program to ensure that the entire
system will operate safely even if a data link communication error occurs at
multiple stations.

Figure 39:
Network parameter -
CC-Link station
information setting
dialog

ATTENTION
Figure 40:
Sample program

ATTENTION
Troubleshooting when CC-Link interface module is
connected to Q series programmable controller
MELSEC-WS


64


Check the status of each module after all the modules required in the system have
been connected using CC-Link dedicated cables, and verify that data link can be
performed normally.
For details of GX Developer operations, see the operating manual of GX
Developer. Also, see Chapter 5 in this manual.


10. Troubleshooting when CC-Link interface module is
connected to Q series programmable controller


WARRANTY

1. Limited Warranty and Product Support.
a. Mitsubishi Electric Company ("MELCO") warrants that
for a period of eighteen (18) months after date of
delivery from the point of manufacture or one year from
date of Customer's purchase, whichever is less,
Mitsubishi Safety Controller (the "Products") will be free
from defects in material and workmanship.
b. At MELCO's option, for those Products MELCO
determines are not as warranted, MELCO shall either
repair or replace them or issue a credit or return the
purchase price paid for them.
c. For this warranty to apply:
(1) Customer shall give MELCO (i) notice of a warranty
claim to MELCO and the authorized dealer or
distributor from whom the Products were purchased,
(ii) the notice shall describe in reasonable details the
warranty problem, (iii) the notice shall be provided
promptly and in no event later than thirty (30) days
after the Customer knows or has reason to believe
that Products are not as warranted, and (iv) in any
event, the notice must given within the warranty
period;
(2) Customer shall cooperate with MELCO and
MELCO's representatives in MELCO's investigation
of the warranty claim, including preserving evidence
of the claim and its causes, meaningfully responding
to MELCO's questions and investigation of the
problem, grant MELCO access to witnesses,
personnel, documents, physical evidence and
records concerning the warranty problem, and allow
MELCO to examine and test the Products in
question offsite or at the premises where they are
installed or used; and
(3) If MELCO requests, Customer shall remove
Products it claims are defective and ship them to
MELCO or MELCO's authorized representative for
examination and, if found defective, for repair or
replacement. The costs of removal, shipment to and
from MELCO's designated examination point, and
reinstallation of repaired or replaced Products shall
be at Customer's expense.
(4) If Customer requests and MELCO agrees to effect
repairs onsite at any domestic or overseas location,
the Customer will pay for the costs of sending repair
personnel and shipping parts. MELCO is not
responsible for any re-commissioning, maintenance,
or testing on-site that involves repairs or replacing of
the Products.
d. Repairs of Products located outside of Japan are
accepted by MELCO's local authorized service facility
centers ("FA Centers"). Terms and conditions on which
each FA Center offers repair services for Products that
are out of warranty or not covered by MELCO's limited
warranty may vary.
e. Subject to availability of spare parts, MELCO will offer
Product repair services for (4) years after each Product
model or line is discontinued, at MELCO's or its FA
Centers' rates and charges and standard terms in effect
at the time of repair. MELCO usually produces and
retains sufficient spare parts for repairs of its Products
for a period of four (4) years after production is
discontinued.
f. MELCO generally announces discontinuation of
Products through MELCO's Technical Bulletins.
Products discontinued and repair parts for them may
not be available after their production is discontinued.
2. Limits of Warranties.
a. MELCO does not warrant or guarantee the design,
specify, manufacture, construction or installation of the
materials, construction criteria, functionality, use,
properties or other characteristics of the equipment,
systems, or production lines into which the Products
may be incorporated, including any safety, fail-safe and
shut down systems using the Products.
b. MELCO is not responsible for determining the suitability
of the Products for their intended purpose and use,
including determining if the Products provide
appropriate safety margins and redundancies for the
applications, equipment or systems into which they are
incorporated.
c. Customer acknowledges that qualified and experienced
personnel are required to determine the suitability,
application, design, construction and proper installation
and integration of the Products. MELCO does not
supply such personnel.
d. MELCO is not responsible for designing and conducting
tests to determine that the Product functions
appropriately and meets application standards and
requirements as installed or incorporated into the
end-user's equipment, production lines or systems.
e. MELCO does not warrant any Product:
(1) repaired or altered by persons other than MELCO or
its authorized engineers or FA Centers;
(2) subjected to negligence, carelessness, accident,
misuse, or damage;
(3) improperly stored, handled, installed or maintained;
(4) integrated or used in connection with improperly
designed, incompatible or defective hardware or
software;
(5) that fails because consumable parts such as relay,
batteries, backlights, or fuses were not tested,
serviced or replaced;
(6) operated or used with equipment, production lines or
systems that do not meet applicable and
commensurate legal, safety and industry-accepted
standards;
(7) operated or used in abnormal applications;
(8) installed, operated or used in contravention of
instructions, precautions or warnings contained in
MELCO's user, instruction and/or safety manuals,
technical bulletins and guidelines for the Products;
(9) used with obsolete technologies or technologies not
fully tested and widely accepted and in use at the
time of the Product's manufacture;
(10) subjected to excessive heat or moisture, abnormal
voltages, shock, excessive vibration, physical
damage or other improper environment; or
(11) damaged or malfunctioning due to Acts of God,
fires, acts of vandals, criminals or terrorists,
communication or power failures, or any other
cause or failure that results from circumstances
beyond MELCO's control.
f. All Product information and specifications contained on
MELCO's website and in catalogs, manuals, or
technical information materials provided by MELCO are
subject to change without prior notice.
g. The Product information and statements contained on
MELCO's website and in catalogs, manuals, technical
bulletins or other materials provided by MELCO are
provided as a guide for Customer's use. They do not
constitute warranties and are not incorporated in the
contract of sale for the Products.


h. These terms and conditions constitute the entire
agreement between Customer and MELCO with
respect to warranties, remedies and damages and
supersede any other understandings, whether written
or oral, between the parties. Customer expressly
acknowledges that any representations or statements
made by MELCO or others concerning the Products
outside these terms are not part of the basis of the
bargain between the parties and are not factored into
the pricing of the Products.
i. THE WARRANTIES AND REMEDIES SET FORTH IN
THESE TERMS ARE THE EXCLUSIVE AND ONLY
WARRANTIES AND REMEDIES THAT APPLY TO
THE PRODUCTS.
j. MELCO DISCLAIMS THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
3. Limits on Damages.
a. MELCO'S MAXIMUM CUMULATIVE LIABILITY BASED
ON ANY CLAIMS FOR BREACH OF WARRANTY OR
CONTRACT, NEGLIGENCE, STRICT TORT LIABILITY
OR OTHER THEORIES OF RECOVERY REGARDING
THE SALE, REPAIR, REPLACEMENT, DELIVERY,
PERFORMANCE, CONDITION, SUITABILITY,
COMPLIANCE, OR OTHER ASPECTS OF THE
PRODUCTS OR THEIR SALE, INSTALLATION OR
USE SHALL BE LIMITED TO THE PRICE PAID FOR
PRODUCTS NOT AS WARRANTED.
b. Although MELCO has obtained the certification for
Product's compliance to the international safety
standards IEC61508 and EN954-1/ISO13849-1 from
TUV Rheinland, this fact does not guarantee that
Product will be free from any malfunction or failure. The
user of this Product shall comply with any and all
applicable safety standard, regulation or law and take
appropriate safety measures for the system in which the
Product is installed or used and shall take the second or
third safety measures other than the Product. MELCO is
not liable for damages that could have been prevented
by compliance with any applicable safety standard,
regulation or law.
c. MELCO prohibits the use of Products with or in any
application involving power plants, trains, railway
systems, airplanes, airline operations, other
transportation systems, amusement equipments,
hospitals, medical care, dialysis and life support
facilities or equipment, incineration and fuel devices,
handling of nuclear or hazardous materials or chemicals,
mining and drilling, and other applications where the
level of risk to human life, health or property are
elevated.
d. MELCO SHALL NOT BE LIABLE FOR SPECIAL,
INCIDENTAL, CONSEQUENTIAL, INDIRECT OR
PUNITIVE DAMAGES, FOR LOSS OF PROFITS,
SALES, OR REVENUE, FOR INCREASED LABOR OR
OVERHEAD COSTS, FOR DOWNTIME OR LOSS OF
PRODUCTION, FOR COST OVERRUNS, OR FOR
ENVIRONMENTAL OR POLLUTION DAMAGES OR
CLEAN-UP COSTS, WHETHER THE LOSS IS BASED
ON CLAIMS FOR BREACH OF CONTRACT OR
WARRANTY, VIOLATION OF STATUTE,
NEGLIGENCE OR OTHER TORT, STRICT LIABILITY
OR OTHERWISE.
e. In the event that any damages which are asserted
against MELCO arising out of or relating to the Products
or defects in them, consist of personal injury, wrongful
death and/or physical property damages as well as
damages of a pecuniary nature, the disclaimers and
limitations contained in these terms shall apply to all
three types of damages to the fullest extent permitted by
law. If, however, the personal injury, wrongful death
and/or physical property damages cannot be
disclaimed or limited by law or public policy to the extent
provided by these terms, then in any such event the
disclaimer of and limitations on pecuniary or economic
consequential and incidental damages shall
nevertheless be enforceable to the fullest extent
allowed by law.
f. In no event shall any cause of action arising out of
breach of warranty or otherwise concerning the
Products be brought by Customer more than one year
after the cause of action accrues.
g. Each of the limitations on remedies and damages set
forth in these terms is separate and independently
enforceable, notwithstanding the unenforceability or
failure of essential purpose of any warranty,
undertaking, damage limitation, other provision of these
terms or other terms comprising the contract of sale
between Customer and MELCO.
4. Delivery/Force Majeure.
a. Any delivery date for the Products acknowledged by
MELCO is an estimated and not a promised date.
MELCO will make all reasonable efforts to meet the
delivery schedule set forth in Customer's order or the
purchase contract but shall not be liable for failure to do
so.
b. Products stored at the request of Customer or because
Customer refuses or delays shipment shall be at the risk
and expense of Customer.
c. MELCO shall not be liable for any damage to or loss of
the Products or any delay in or failure to deliver, service,
repair or replace the Products arising from shortage of
raw materials, failure of suppliers to make timely
delivery, labor difficulties of any kind, earthquake, fire,
windstorm, flood, theft, criminal or terrorist acts, war,
embargoes, governmental acts or rulings, loss or
damage or delays in carriage, acts of God, vandals or
any other circumstances reasonably beyond MELCO's
control.
5. Choice of Law/Jurisdiction.
These terms and any agreement or contract between
Customer and MELCO shall be governed by the laws of
the State of New York without regard to conflicts of laws.
To the extent any action or dispute is not arbitrated, the
parties consent to the exclusive jurisdiction and venue of
the federal and state courts located in the Southern
District of the State of New York. Any judgment there
obtained may be enforced in any court of competent
jurisdiction.
6. Arbitration.
Any controversy or claim arising out of, or relating to or in
connection with the Products, their sale or use or these
terms, shall be settled by arbitration conducted in
accordance with the Center for Public Resources (CPR)
Rules for Non-Administered Arbitration of International
Disputes, by a sole arbitrator chosen from the CPR's
panels of distinguished neutrals. Judgment upon the
award rendered by the Arbitrator shall be final and
binding and may be entered by any court having
jurisdiction thereof. The place of the arbitration shall be
New York City, New York. The language of the arbitration
shall be English. The neutral organization designated to
perform the functions specified in Rule 6 and Rules
7.7(b), 7.8 and 7.9 shall be the CPR.






































Microsoft, Windows, Windows NT, and Windows Vista are registered trademarks of Microsoft Corporation in the United
States and other countries.
Ethernet is a trademark of Xerox Corporation.
All other company names and product names used in this manual are trademarks or registered trademarks of their
respective companies.

SH(NA)-080909ENG-A

HEADQUARTERS
EUROPE MITSUBISHI ELECTRIC EUROPE B.V.
German Branch
Gothaer Strae 8
D-40880 Ratingen
Phone: +49 (0)2102 / 486-0
Fax: +49 (0)2102 / 486-1120
CZECH REPUBLIC MITSUBISHI ELECTRIC EUROPE B.V.
Czech Branch
Avenir Business Park, Radlick 714/113a
CZ-158 00 Praha 5
Phone: +420 - 251 551 470
Fax: +420 - 251-551-471
FRANCE MITSUBISHI ELECTRIC EUROPE B.V.
French Branch
25, Boulevard des Bouvets
F-92741 Nanterre Cedex
Phone: +33 (0)1 / 55 68 55 68
Fax: +33 (0)1 / 55 68 57 57
IRELAND MITSUBISHI ELECTRIC EUROPE B.V.
Irish Branch
Westgate Business Park, Ballymount
IRL-Dublin 24
Phone: +353 (0)1 4198800
Fax: +353 (0)1 4198890
ITALY MITSUBISHI ELECTRIC EUROPE B.V.
Italian Branch
Viale Colleoni 7
I-20041 Agrate Brianza (MB)
Phone: +39 039 / 60 53 1
Fax: +39 039 / 60 53 312
POLAND MITSUBISHI ELECTRIC EUROPE B.V.
Poland Branch
Krakowska 50
PL-32-083 Balice
Phone: +48 (0)12 / 630 47 00
Fax: +48 (0)12 / 630 47 01
SPAIN MITSUBISHI ELECTRIC EUROPE B.V.
Spanish Branch
Carretera de Rub 76-80
E-08190 Sant Cugat del Valls (Barcelona)
Phone: 902 131121 // +34 935653131
Fax: +34 935891579
UK MITSUBISHI ELECTRIC EUROPE B.V.
UK Branch
Travellers Lane
UK-Hatfield, Herts. AL10 8XB
Phone: +44 (0)1707 / 27 61 00
Fax: +44 (0)1707 / 27 86 95
JAPAN MITSUBISHI ELECTRIC CORPORATION
Office Tower Z 14 F
8-12,1 chome, Harumi Chuo-Ku
Tokyo 104-6212
Phone: +81 3 622 160 60
Fax: +81 3 622 160 75
USA MITSUBISHI ELECTRIC AUTOMATION, Inc.
500 Corporate Woods Parkway
Vernon Hills, IL 60061
Phone: +1 847 478 21 00
Fax: +1 847 478 22 53
EUROPEANREPRESENTATIVES
AUSTRIA GEVA
Wiener Strae 89
AT-2500 Baden
Phone: +43 (0)2252 / 85 55 20
Fax: +43 (0)2252 / 488 60
BELARUS TEHNIKON
Oktyabrskaya 16/5, Off. 703-711
BY-220030 Minsk
Phone: +375 (0)17 / 210 46 26
Fax: +375 (0)17 / 210 46 26
BELGIUM ESCO DRIVES & AUTOMATION
Culliganlaan 3
BE-1831 Diegem
Phone: +32 (0)2 / 717 64 30
Fax: +32 (0)2 / 717 64 31
BELGIUM Koning & Hartman b.v.
Woluwelaan 31
BE-1800 Vilvoorde
Phone: +32 (0)2 / 257 02 40
Fax: +32 (0)2 / 257 02 49
BOSNIA AND HERZEGOVINA INEA BH d.o.o.
Aleja Lipa 56
BA-71000 Sarajevo
Phone: +387 (0)33 / 921 164
Fax: +387 (0)33/ 524 539
BULGARIA AKHNATON
4 Andrej Ljapchev Blvd. Pb 21
BG-1756 Sofia
Phone: +359 (0)2 / 817 6004
Fax: +359 (0)2 / 97 44 06 1
CROATIA INEA CR d.o.o.
Losinjska 4 a
HR-10000 Zagreb
Phone: +385 (0)1 / 36 940 - 01/ -02/ -03
Fax: +385 (0)1 / 36 940 - 03
CZECH REPUBLIC AutoCont C.S. s.r.o.
Technologick 374/6
CZ-708 00 Ostrava-Pustkovec
Phone: +420 595 691 150
Fax: +420 595 691 199
CZECH REPUBLIC B:ELECTRIC, s.r.o.
Mladoboleslavsk 812
CZ-197 00 Praha 19 - Kbely
Phone: +420 286 850 848, +420 724 317 975
Fax: +420 286 850 850
DENMARK Beijer Electronics A/S
Lykkegrdsvej 17, 1.
DK-4000 Roskilde
Phone: +45 (0)46/ 75 76 66
Fax: +45 (0)46 / 75 56 26
ESTONIA Beijer Electronics Eesti O
Prnu mnt.160i
EE-11317 Tallinn
Phone: +372 (0)6 / 51 81 40
Fax: +372 (0)6 / 51 81 49
FINLAND Beijer Electronics OY
Jaakonkatu 2
FIN-01620 Vantaa
Phone: +358 (0)207 / 463 500
Fax: +358 (0)207 / 463 501
GREECE UTECO A.B.E.E.
5, Mavrogenous Str.
GR-18542 Piraeus
Phone: +30 211 / 1206 900
Fax: +30 211 / 1206 999
HUNGARY MELTRADE Ltd.
Fert utca 14.
HU-1107 Budapest
Phone: +36 (0)1 / 431-9726
Fax: +36 (0)1 / 431-9727
LATVIA Beijer Electronics SIA
Vestienas iela 2
LV-1035 Riga
Phone: +371 (0)784 / 2280
Fax: +371 (0)784 / 2281
LITHUANIA Beijer Electronics UAB
Savanoriu Pr. 187
LT-02300 Vilnius
Phone: +370 (0)5 / 232 3101
Fax: +370 (0)5 / 232 2980
EUROPEANREPRESENTATIVES
MALTA ALFATRADE Ltd.
99, Paola Hill
Malta- Paola PLA 1702
Phone: +356 (0)21 / 697 816
Fax: +356 (0)21 / 697 817
MOLDOVA INTEHSIS srl
bld. Traian 23/1
MD-2060 Kishinev
Phone: +373 (0)22 / 66 4242
Fax: +373 (0)22 / 66 4280
NETHERLANDS HIFLEX AUTOM.TECHNIEK B.V.
Wolweverstraat 22
NL-2984 CD Ridderkerk
Phone: +31 (0)180 46 60 04
Fax: +31 (0)180 44 23 55
NETHERLANDS Koning & Hartman b.v.
Haarlerbergweg 21-23
NL-1101 CH Amsterdam
Phone: +31 (0)20 / 587 76 00
Fax: +31 (0)20 / 587 76 05
NORWAY Beijer Electronics AS
Postboks 487
NO-3002 Drammen
Phone: +47 (0)32 / 24 30 00
Fax: +47 (0)32 / 84 85 77
ROMANIA Sirius Trading & Services srl
Aleea Lacul Morii Nr. 3
RO-060841 Bucuresti, Sector 6
Phone: +40 (0)21 / 430 40 06
Fax: +40 (0)21 / 430 40 02
SERBIA Craft Con. & Engineering d.o.o.
Bulevar Svetog Cara Konstantina 80-86
SER-18106 Nis
Phone: +381 (0)18 / 292-24-4/5
Fax: +381 (0)18 / 292-24-4/5
SERBIA INEA SR d.o.o.
Izletnicka 10
SER-113000 Smederevo
Phone: +381 (0)26 / 617 163
Fax: +381 (0)26 / 617 163
SLOVAKIA AutoCont Control s.r.o.
Radlinskho 47
SK-02601 Dolny Kubin
Phone: +421 (0)43 / 5868210
Fax: +421 (0)43 / 5868210
SLOVAKIA CS MTrade Slovensko, s.r.o.
Vajanskeho 58
SK-92101 Piestany
Phone: +421 (0)33 / 7742 760
Fax: +421 (0)33 / 7735 144
SLOVENIA INEA d.o.o.
Stegne 11
SI-1000 Ljubljana
Phone: +386 (0)1 / 513 8100
Fax: +386 (0)1 / 513 8170
SWEDEN Beijer Electronics AB
Box 426
SE-20124 Malm
Phone: +46 (0)40 / 35 86 00
Fax: +46 (0)40 / 35 86 02
SWITZERLAND Omni Ray AG
Im Schrli 5
CH-8600 Dbendorf
Phone: +41 (0)44 / 802 28 80
Fax: +41 (0)44 / 802 28 28
TURKEY GTS
Bayraktar Bulvari Nutuk Sok. No:5
TR-34775 Yukar Dudullu-mraniye-STANBUL
Phone: +90 (0)216 526 39 90
Fax: +90 (0)216 526 3995
UKRAINE CSC Automation Ltd.
4-B, M. Raskovoyi St.
UA-02660 Kiev
Phone: +380 (0)44 / 494 33 55
Fax: +380 (0)44 / 494-33-66
EURASIANREPRESENTATIVES
KAZAKHSTAN Kazpromautomatics Ltd.
Mustafina Str. 7/2
KAZ-470046 Karaganda
Phone: +7 7212 / 50 11 50
Fax: +7 7212 / 50 11 50
MIDDLE EAST REPRESENTATIVES
ISRAEL ILAN & GAVISH Ltd.
24 Shenkar St., Kiryat Arie
IL-49001 Petah-Tiqva
Phone: +972 (0)3 / 922 18 24
Fax: +972 (0)3 / 924 0761
ISRAEL TEXEL ELECTRONICS Ltd.
2 Haumanut, P.O.B. 6272
IL-42160 Netanya
Phone: +972 (0)9 / 863 39 80
Fax: +972 (0)9 / 885 24 30
LEBANON CEG INTERNATIONAL
Cebaco Center/Block A Autostrade DORA
Lebanon - Beirut
Phone: +961 (0)1 / 240 430
Fax: +961 (0)1 / 240 438
AFRICANREPRESENTATIVE
SOUTH AFRICA CBI Ltd.
Private Bag 2016
ZA-1600 Isando
Phone: + 27 (0)11 / 977 0770
Fax: + 27 (0)11 / 977 0761
MITSUBISHI
ELECTRIC
FACTORY AUTOMATION
Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Strae 8 /// D-40880 Ratingen /// Germany
Tel.: +49(0)2102-4860/// Fax: +49(0)2102-4861120/// [email protected]/// www.mitsubishi-automation.com
MITSUBISHI ELECTRIC

You might also like