Distributed by Mueller Streamline Co. 8285 Tournament Drive, Memphis, TN 38125 800-846-9750 www.muellerindustries.com
Product Description:
Streamline

Service Coils, ACR/Nitrogenized straight-length or line set copper tube for use in refrigeration applications.
Available sizes ranging from 1/8 to 8-1/8 in outside diameter. All tube should be manufactured in the United States.
Material:
Streamline

Copper Tube shall be made from material in compliance with ASTM B75 and of UNS C12200 grade of copper.
Key Specications:
Streamline

Copper Refrigeration Service Coils, ACR/Nitrogenized straight lengths and line sets are made to meet the chemical,
mechanical, cleanness, and eddy current testing requirements of the applicable specication of ASTM B280. Streamline

copper
tube is third party veried in select sizes
1
through Underwriters Laboratories (UL) for operating pressure of 700psi at 250F.
Installation:
Installations shall comply with the latest applicable building codes for the local jurisdiction. For detailed installation instructions,
consult the Copper Developement Association at copper.org.
References:
Product Line Product Type Diameter
Copper Tube
Streamline

Refrigeration Service Coils


Streamline

Line Sets & Mini-Splits


Streamline

ACR - Type L (Hard Lengths)


Streamline

ACR - Type K (Hard Lengths)


1/8 1-1/8
1/8 1-1/8
1/8 1-3/8
1/8 2-5/8
ASTM B75 Seamless Copper Tube
C12200 99.9% Pure Copper
ASTM B280 Seamless Copper Tube for Air Conditioning and Refrigeration
COPPER TUBE FOR HVACR APPLICATIONS
Job Name Contractor
Job Location Wholesaler
Engineer Streamline

Rep
1
MADE IN USA
page 2 of 4
Distributed by Mueller Streamline Co. 8285 Tournament Drive, Memphis, TN 38125 800-846-9750 www.muellerindustries.com
COPPER TUBE DATA
Mueller Industries cleaning, purging and pressurizing process assures the high level of tube cleanliness in conformance to
ASTM B280, the refrigeration industry standard. The tube is sealed with plugs which maintain the standard of cleanliness
from the factory to the job site.
STREAMLINE

COPPER TUBE PRESSURIZED WITH NITROGEN provides maximum protection against the
formation of harmful oxides normally formed during brazing operations. Reduction of these oxides greatly reduces system
contamination. Plugs are reusable. When less than a 20 length of tube is required for an installation the unused length of
tube may be re-plugged to prevent atmospheric contamination during storage.
STREAMLINE

NITROGENIZED seamless copper tube is available in sizes 3/8 OD through 3-1/8 OD. Larger
sizes from 3-5/8 OD through 8-1/8 OD are cleaned and capped. Manufactured and cleaned in accordance with ASTM
B280. 20-ft. lengths hard drawn - cleaned and capped - color coded - Marked ACR/MED
TYPE K NITROGENIZED ACR / MED RATED WORKING PRESSURE (PSIG)
O.D. DIA. WT/FT FT/BNDL WALL 150F 200F 300F 400F
3/8 0.145 500 0.035 913 860 842 537
1/2 0.269 500 0.049 960 904 885 565
5/8 0.344 500 0.049 758 713 698 446
3/4 0.418 200 0.049 700 700 577 368
7/8 0.641 200 0.065 700 700 668 426
1 1/8 0.839 100 0.065 700 700 513 327
1 3/8 1.04 100 0.065 700 700 416 266
1 5/8 1.36 100 0.072 700 700 387 247
2 1/8 2.06 0.083 700 700 341 217
2 5/8 2.93 0.095 700 700 312 199
3 1/8 4.00 0.109 328 308 302 193
3 5/8 5.12 0.120 311 293 286 183
4 1/8 6.51 0.134 306 288 282 180
5 1/8 9.67 0.160 293 276 270 172
6 1/8 13.90 0.192 295 277 271 173
8 1/8 25.90 0.271 314 295 289 184
TYPE L NITROGENIZED ACR / MED
3/8 0.126 500 0.030 775 729 714 456
1/2 0.198 500 0.035 700 700 610 389
5/8 0.285 500 0.040 700 700 565 361
3/4 0.362 200 0.042 700 700 495 316
7/8 0.455 200 0.045 700 700 456 291
1 1/8 0.655 100 0.050 700 700 387 247
1 3/8 0.884 100 0.055 700 700 344 219
1 5/8 1.14 100 0.060 347 327 320 204
2 1/8 1.75 0.070 309 291 285 182
2 5/8 2.48 0.080 285 269 263 168
3 1/8 3.33 0.090 270 254 248 159
3 5/8 4.29 0.100 258 243 238 152
4 1/8 5.38 0.110 249 235 230 147
5 1/8 7.61 0.125 229 215 211 135
6 1/8 10.2 0.140 213 201 196 125
8 1/8 19.3 0.200 230 216 212 135
Tables give computed allowable stress for annealed
copper tube at indicated temperature.
UL Recognized to 700 PSI (select sizes)
page 3 of 4
Distributed by Mueller Streamline Co. 8285 Tournament Drive, Memphis, TN 38125 800-846-9750 www.muellerindustries.com
REFRIGERATION SERVICE TUBE
STREAMLINE

dehydrated and nitrogen purged and sealed copper tube is of a consistent annealed temper, bright and
thoroughly dried and packaged in individual cartons. Each carton is clearly labeled showing size and length.
Tube is manufactured in accordance with ASTM B280 and ANSI B9.1, refrigeration industry standards. For special lengths
and sizes not listed please consult your local Mueller Industries representative.
COILS
SIZE RATED INTERNAL WORKING PRESSURE (PSIG) 50 FEET SHIP INFO 100 FOOT
O.D. WALL 150F 200F 350F 400F COIL DIA WT/COIL COIL/MSTR COL DIA WT/COIL
1/8 0.030 2613 2459 2049 1537 10 3/4 1.74 10 17 3.48
3/16 0.030 1645 1548 1290 968 11 3/4 2.88 10 18 5/8 5.76
1/4 0.030 1195 1125 938 703 13 1/2 4.02 10 18 5/8 8.04
5/16 0.032 1017 957 798 598 15 1/2 5.45 10 19 7/8 10.90
3/8 0.032 836 787 656 492 17 6.70 10 21 7/8 13.40
1/2 0.032 700 700 485 363 19 7/8 9.10 5 25 18.20
5/8 0.035 700 700 412 309 21 1/4 12.55 5 25 1/4 25.10
3/4 0.035 700 700 341 256 23 1/4 15.25 3 29 30.50
7/8 0.045 700 700 388 291 27 1/4 22.75 3 32 1/4 45.50
1 1/8 0.050 700 700 330 247 34 1/2 32.75 - 38 1/2 65.50
1 3/8 0.055 373 351 293 219 45 44.20 - 45 88.40
1 5/8 0.060 347 327 272 204 45 57.00 - 49 114.00
TECHNICAL DATA
Values of allowable internal working pressure for copper tube in service are based on the formula from ANSI B31, Standard
Code for Pressure Piping:

P = Allowable Pressure @150F S = 5100 PSIG annealed
S = Allowable stress @ 200F S= 4800PSIG annealed
T = Wall thickness @ 300F S= 4700 PSIG annealed
D Max = Outside Diameter @ 400F S= 3000 PSIG annealed

All ratings listed for types K, L, M, DWV and refrigeration service tube in the preceding charts are calculated
for tube in the annealed condition. These values should be used when soldering, brazing or welding is employed
for joining components in a system. While the ratings for hard drawn tube are substantially higher, they should
only be used for systems using properly designed flare or compression mechanical joints, since joining
by any heating process might anneal (soften) the tube.
In designing a system, careful consideration should also be given to joint ratings as well as those of the components.
COPPER TUBE DATA
UL Recognized to 700 PSI (select sizes)
2 S tm
D max - 0.8 tm
P =
page 4 of 4
Distributed by Mueller Streamline Co. 8285 Tournament Drive, Memphis, TN 38125 800-846-9750 www.muellerindustries.com
COPPER TUBE AND SOLDER TYPE FITTINGS
1. Cut tube to length & remove
burr with le or scraper.
2. Clean outside of tube with
sandpaper or sand cloth.
3. Clean inside of tting with wire
brush, sand cloth or sandpaper.
4. Apply ux thoroughly to
inside of tting.
5. Apply ux thoroughly to
outside of tube - assemble
tube and tting.
6. Apply heat with torch. When
solder melts upon contact with
heated tting, the proper temp
for soldering has been reached.
Remove ame & feed solder to
the joint at one or two points
until a ring of solder appears at
the end of the tting.
1. Cut tube square with the cutter or ne hack
saw (32 tooth blade is recommended).
Remove Burr.
2. Clean outside end of copper tube thoroughly
with sand cloth or sandpaper equal depth of
tting. Leave no dark spots.
3. Clean inside of tting carefully to tube stop with
wire brush. Note: Sand cloth or sandpaper may
also be used.
4. Using a brush, apply light uniform coat of
soldering ux to the outside of the tube
and inside of the tting.
5. Slip tube into tting to tube stop. Turn tube
back and forth once or twice to distribute
ux evenly.
6. Apply heat uniformly around the tting with
torch. When solder melts upon contact with
heated tting, the proper soldering temperature
has been reached. Remove ame and feed
solder slightly off center at the bottom of the
joint. Proceed across the bottom of the tting
and up to the top center position. Return to
the starting point, and then proceed up the
incomplete side to the top, again, overlapping
the solder metal. Wipe off surplus solder with
a piece of cloth.
CAUTION: No not overheat the joint or
direct the ame into the face of the tting
cup. Overheating could burn the ux,
which will destroy its effectiveness and the
solder will not enter the joint properly.