Eaton Fire Pump Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

LMR PLUS Electric Fire Pump Controllers

Features
1-1
For more information visit: www.chfire.com
FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition
Product Description
LMR
P
L
U
S

P
L
U
S

BR05805052K/G
The FD80 LMR Plus Controllers use a method
of connecting the pump motor windings into
wye configuration to start, then switching to a
delta configuration to run.
This reduces the starting current of the motor
significantly.
Wye-Delta starting is the only method that has a
starting torque efficiency of 100%. The FD80
can be programmed for either fully automatic or
semi-automatic operations.
The use of an embedded web page for
retrieving diagnostics and history reports, along
with USB and Ethernet communication ports for
downloading data, make the LMR Plus Series of
controllers easy to troubleshoot and maintain.
As well, critical information can be easily
accessed and used for report generation and
analysis, which aids in providing effective,
reliable fire protection.

Product Features Product Features
Alarm LEDs Status LEDs
Phase Reversal
Phase Failure
Fail To Start
Undervoltage
Overvoltage
Low Room Temperature
Locked Rotor Trip
Low Suction Pressure
Source 2 Disconnected
Programmable LED # 2
Power On
Pump Running
Local Start
Remote Start
Deluge Valve
Emergency Start
Interlock On
Low Pressure
Auto Shutdown Enabled
Programmable LED # 1
Membrane Keypad
Door Mount
The membrane keypad is accessible from the
front door of the controller.
NEMA Rating
The standard membrane keypad is rated for
NEMA 2, 3R, 4, 4X and 12.
Alarm & Status LEDs
A total of 20, ( 10 Status - 10 Alarm ) LEDs
provide indication on the membrane keypad.

Logic Controller Board
Communication
The controller can be ordered with the option to
display and output current values and status, on
command, from various software protocols
through the appropriate port(s).
Embedded Web Page
The web page is a multifunction tool that allows
the user to view the controllers current status,
data values, programmed set points and history.
It is accessed using the optional ethernet port.
Ethernet Port
An optional Ethernet port can be used for direct
connection to a computer for data transfer.
RS485 Serial Port
An optional RS485 serial port can be provided
for communication to various external software
programs.
USB Port / USB Drive
The logic controller board is equipped with a
USB port that can be used to transfer data to
and from a portable USB Drive device (memory
stick).
Buzzer
A buzzer is mounted on the logic board which
will operate if Fail to Start, Hardware
Malfunction or any Common Alarm condition
exists.
Power I/O Board
Transformers
Incoming line voltage is run directly to the I/O
board from the incoming lines. The I/O board
will accept voltage inputs between 100 and
600V.
1-1
July 2011
Customer Connection Terminals
Connection terminals for external customer
connections, are located at the top of the Power
I/O board.

Output Relays
Five, 8 Amp, 2 Form - C (DPDT) output relays
are provided standard on each power I/O board.
They are designated for: Common Alarm,
Phase Failure, Phase Reversal, Pump Run and
Future #1. Each socket has an LED mounted on
the I/O board which indicates each relays coil
status.

Optional Output Relay Boards
There is provision to add up to eight additional
relay outputs, via optional relay output boards.
Each board contains a maximum of 2 additional
relays. The Power I/O Board will accept a
maximum of 4 optional boards which mount in a
snap-on configuration.
Each board provides an area for the user to
label the terminal number and relay name.
Drain Valve Solenoid
All LMR Plus electric controllers are equipped
with a drain valve solenoid used for weekly test
purposes.
Silence Button
A silence pushbutton on the membrane can be
used to silence the buzzer. When an alarm
condition exists, the alarm buzzer will sound. If
the Silence Alarm button is pressed, the alarm
buzzer will turn off. If a subsequent alarm
condition occurs after the silence button is
pressed, the buzzer will re-sound. Pressing the
Silence Alarm button again, will silence the
buzzer.
Motor Test Button
The motor test button on the membrane can be
used to simulate an automatic start.
Automatic Shutdown Enabled
When the Automatic Shutdown function is
enabled, a Green LED will indicate on the
controller membrane.
USB External Drive
General
When using an external USB Drive, the drive
should conform to the following specifications:
Min: 128mb
Max: 2 Gig FAT16 protocol
USB 1.0 or 2.0
Standards & Certification
The LMR Plus Electric Fire Pump Controllers
meet or exceed the requirements of
Underwriters Laboratories, Underwriters
Laboratories Canada, Factory Mutual, the
Canadian Standards Association, New York City
building code, CE mark and U.B.C / C.B.C.
Seismic requirements, and are built to NFPA 20
standards.
NEMA 2 Enclosures
All LMR controllers come standard with NEMA 2
enclosures unless otherwise ordered. Available
options include: NEMA 3R, 4, 4X, 12.
Emergency Start Operator
A mechanically operated
emergency start handle
activates the motor
contactor independent of
any electrical control
circuits or pressure
switch input.
N. Y. C.
APPROVED

U.B.C and C.B.C
Must Be Installed Per Applicable Code and Manufacturers Recommendations
SEISMIC QUALIFIED
For more information visit: www.chfire.com
BR05805052K/G
LMR PLUS Electric Fire Pump Controllers
Features
1-2
FD80 Reduced Voltage - Wye Delta (Star-Delta) Closed Transition
Product Features
Main Display
General
The main display will show the current system
pressure, time and date, voltage and amps
reading for all three phases, the system
frequency and any custom messages, alarms
or timers.
Programmed Set-Point
The set-point display will show programmed
pressure start point, pressure stop point and
weekly test timer setting.
Statistics
The statistics display will allow the user to
scroll through all of the measured statistics
stored in memory. Refer to LMR Plus operation
manual IM05805020K for specific details.
Diagnostics
The diagnostics display allows the user to
scroll through various diagnostic points to
assist with troubleshooting the system.
Message History
The user will be able to scroll through all of the
messages stored in the memory of the
controller with the most recent message being
displayed first.
PRINT Menu
Description
All fault and alarm information is sent to the
USB and optional printer on demand, as well as
the status of each output. The LMR Plus will
store up to 10K events which are time and date
stamped. All information can also be retrieved
and displayed on the LCD display.
Saving to USB Drive
The controller will save four separate text files,
one CSV file and the embedded webpage to the
USB external drive. The files, at maximum size,
can be saved multiple times on one 128MB
USB drive.
Files to be saved are: Status Report,
Diagnostics Report, Statistics Report,
Configuration File and Last 10K Messages.
Print Menu
The optional printer menu is accessed in order
to select the desired print function.
Functions include: Print Messages, Last XX
Messages, Date & Time, Status Report,
Diagnostics Report and Statistics Report.
Custom Messages
When this item is selected, custom messages
can be cleared from memory or downloaded
from the USB external drive.
Embedded Web Page
General
The embedded web page is a multifunction tool
that will allow the user to view the current status
of the controller as well as display all current
readings, set points,
and history. An external
computer can be
connected via the
optional Ethernet
port to access the
page. When
connected, the
controller set
points can be
programmed
via the webpage.
Multiple Pages
There are 5 viewable pages that show the Main
Display, Statistics, Diagnostics, History and
Programmed Set Points.
Pressure Points
The pressure reports recorded in memory can
be graphed and/or sorted based on date and
time.
Programmed Set Points
All of the programmed set points and their
current status can be viewed via the webpage.
Custom Messages
Trigger Points
The message can be programmed to appear at
specific trigger points such as specific date and
time, specific number of operations, specific
number of hours run or at any individual alarm
point.
All of the trigger points can be selected as
And/Or values.
Users can create custom messages on a
computer and upload to the controller using a
USB Drive (memory stick). Up to 10 custom
messages of up to 100 characters each, will
continuously scroll across the fourth line of the
LCD display once triggered.
Firmware Update
Firmware revisions are updated from an
external USB drive. All previously programmed
settings will remain intact when updating is
completed. Should there be an update failure,
the controller will automatically revert back to
the previous version of firmware.
July 2011
Programming Menu
General
The LMR Plus programming menu is divided
into 8 different sub-menus. Each sub-menu
contains information relative to its particular
function. Following is a brief description of each
sub-menu.
Language
The language sub-menu allows the user to select
English, French, Spanish or Other languages to
be viewed on the LCD Display. Several other
languages can be uploaded into the controller.
Contact the factory for details.
Regional
Regional settings include the ability to program
the date by adjusting the Month, Day, Year and
Day of Week. As well, the Current Time can be
adjusted on the 24 hour clock.
Pressure
A variety of pressure settings can be
programmed in the pressure sub-menu. These
settings include disabling the pressure
transmitter; setting of the start point, stop point,
low pressure alarm, high pressure alarm, stop
mode, proof pressure switch (for foam units), low
suction shutdown (low foam shutdown), pressure
deviation and hourly pressure recording. Refer to
the LMR Plus operation manual IM05805020K
for details.
Timers
Timers in the LMR Plus that can be programmed
include: Run Period Timer (RPT), RPT Start
Mode, Acceleration Timer (AT), Weekly Test
Timer, Fail to Start Timer (FST) and Sequential
Start Timer (SST). Refer to the LMR Plus
operation manual IM05805020K for details.
Alarm Set Points
There are five settable alarm points that can be
programmed by the user. They include: Phase
Rotation, Over Voltage (OV), Under Voltage
(UV), Over Frequency (OF) and Under
Frequency (UF). Refer to the LMR Plus operation
manual IM05805020K for details.
Custom Inputs / Outputs
There is provision on the Power I/O Board to
accept up to 9 additional inputs and 9 additional
outputs. Each of the inputs can be labeled using
m conditions.
All optional inputs, outputs and LEDs can be
linked, as required.
Inputs can be programmed to energize the
common alarm output, link to relays and optional
LEDs and latch until reset by the user.
Outputs can be programmed for fail safe and
latch until reset by the user.
Optional inputs and outputs can be programmed
with time delay functions.
one of 11 pre-set input descriptions or assigned a
custom description that is programmed by the
user. The optional outputs can be programmed to
indicate up to 25 output conditions. As well, two
optional alarm LEDs can be programmed for up
to 12 alar
System Configuration Menu
The system configuration menu section is
password protected and contains settings such
as system voltage, frequency, CT ratio etc. Refer
to Technical Bulletin PU05805035K/D
for details.
Main Menu Password
A password can be programmed by the user to
protect access to the Main Menu. Refer to the
LMR Plus Operation Manual IM05805020K for
details.
For more information visit: www.chfire.com
Pump and Plumbing
LMR
P
L
U
S

P
L
U
S

MD05805005K/B
Pump and Plumbing
Pump and Plumbing for Fire Pump Controllers
March 2010
For more information visit: www.chfire.com
Main Display - LMR Plus Fire Pump Controllers
LMR
P
L
U
S

P
L
U
S

MD05805096K/C
Main Display
LMR PLUS Electric Fire Pump Controllers
Main Display
NOTES:
1. Refer to the LMR Plus technical manual for detail and setup
information, as well as programming and custom labelling for
Programmable LED # 1 and Programmable LED # 2.
NOTE: As of January 1, 2009 - All Limited Service Controllers will not carry FM Approval.
March 2010
N. Y. C.
APPROVED

POWER ON
PUMP RUNNING
LOCAL START
REMOTE START
DELUGE VALVE
EMERGENCY START
INTERLOCK ON
LOW PRESSURE
AUTO SHUTDOWN ENABLED
PHASE REVERSAL
PHASE FAILURE
FAIL TO START
UNDERVOLTAGE
OVERVOLTAGE
LOW ROOM TEMPERATURE
LOCKED ROTOR TRIP
LOW SUCTION PRESSURE
SOURCE 2 DISCONNECTED
LMR
P
L
U
S

ACK.
MENU
SAVE/EXIT
DATA
PRINT
LAMP
TEST
RESET
MOTOR
TEST
SILENCE
ALARM
99-5816-01
LMR PLUS Electric Fire Pump Controllers
Dimensions
For more information visit: www.chfire.com
FD80 Wye-Delta (Star Delta) Closed
LMR
P
L
U
S

P
L
U
S

MD05805091K/C
Dimensions
Standard Enclosure - Type NEMA 2, 3R, 4, 4X, 12
* Coils Available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz
Withstand Rating
Standard Intermediate High
Line Voltage Motor Hp Approx. Weight
Lbs. (Kg)
5 - 40
5 - 50
5 - 75
5 - 100
5 - 100
200 - 208V
220 - 240V
380 - 415V *
440 - 480V
550 - 600V 25,000 100,000
150,000 200,000 100,000 375
(170)
Dimensions in inches and [millimeters].
NOTES:
1. All enclosures finished in FirePump red.
2. Cable Entrance bottom only.
3. Standard Enclosure type NEMA 2.
N. Y. C.
APPROVED

July 2011
U.B.C and C.B.C
Must Be Installed Per Applicable Code
and Manufacturers Recommendations
SEISMIC QUALIFIED
34.57 [878]
12.50 [317]
2.63 [67]
5.25 [133]
6.00 [152]
10.50 [267]
74.00
[1880]
5.00 [127]
12.00 [305]
62.00 [1575]
28.36 [720]
16.00 [406]
64.00
[1626]
1.19 [30]
2.09 [53]
8.42
[214]
3.32 [84]
19.28 [490] 1.22 [31]
4.24 [108]
6
STOP
START
1 - START PUSHBUTTON
2 - STOP PUSHBUTTON
3 - MAIN POWER SWITCH
4 - MSH (EMERGENCY START HANDLE)
5 - MAIN LMR PLUS DISPLAY
6 - RECOMMENDED CABLE ACCESS (BOTTOM ONLY)
1.75 [44]
3A13357H01 3A13357H01
PIPING ENTRANCE
1/2" NPT - FEMALE
PIPING ENTRANCE
1/4" NPT - FEMALE
LMR PLUS Electric Fire Pump Controllers
Electrical Wiring Schematic
For more information visit: www.chfire.com
FD80 Wye Delta (Star-Delta) Closed
LMR
P
L
U
S

P
L
U
S

ES05805098K/D
Electrical Wiring Schematic
May 2011
N. Y. C.
APPROVED

I
N
P
U
T
#
2
L
O
W
R
O
O
M
T
E
M
P
E
R
A
T
U
R
E
I
N
T
E
R
L
O
C
K
O
N
D
E
L
U
G
E
V
A
L
V
E
(
R
E
M
O
V
E
J
U
M
P
E
R
I
F
U
S
E
D
)
I
N
P
U
T
#
5
I
N
P
U
T
#
4
I
N
P
U
T
#
3
I
N
P
U
T
#
7
I
N
P
U
T
#
6
I
N
P
U
T
#
8
I
N
P
U
T
#
9
COMMON ALARM
COMMON ALARM
PHASE FAILURE
(NORMALLY ENERGIZED)
PHASE FAILURE
PHASE REVERSAL
PHASE REVERSAL
FUTURE #1
FUTURE #1
PUMP RUN
PUMP RUN
(NORMALLY ENERGIZED)
(NORMALLY ENERGIZED)
OPTION RELAY #1
(2 SETS FORM-C)
OPTION RELAY #2
(2 SETS FORM-C)
OPTION RELAY #4
(2 SETS FORM-C)
(2 SETS FORM-C)
OPTION RELAY #7
OPTION RELAY #8
(2 SETS FORM-C)
(2 SETS FORM-C)
OPTION RELAY #6
(2 SETS FORM-C)
OPTION RELAY #5
(2 SETS FORM-C)
(NORMALLY ENERGIZED)
R
E
M
O
T
E
S
T
A
R
T
L
O
W
S
U
C
T
I
O
N
P
U
M
P
S
T
A
R
T
I
N
P
U
T
#
1
OPTION RELAY #3
I
N
P
U
T
#
2
A
L
A
R
M
C
O
N
T
A
C
T
S
I
N
T
E
R
N
A
L
C
O
N
N
E
C
T
I
O
N
S
CUSTOMER INPUTS
LMR PLUS Electric Fire Pump Controllers
Field Connections
For more information visit: www.chfire.com
LMR
P
L
U
S

P
L
U
S

ES05805099K/D
Field Connections
FD80 Wye Delta (Star-Delta) Closed
Line Terminals (Incoming Cables)
Load Terminals (To Motor)
Typical Controller Connection
NOTE:
1. MOTOR CONNECTIONS VARY, PLEASE
REFER TO SPECIFIC MOTOR CONNECTION
DIAGRAM.
2. PLEASE OBSERVE PROPER PHASE
ROTATION, A,B,C-L1,L2,L3 AS CONTROLLER
IS PHASE SENSITIVE.
3. CABLE SIZE TO BE 125% OF FULL LOAD
CURRENT. REFER TO WIRE SIZE TABLE IN
NFPA 70.
Alarm / Relay Outputs External Inputs
Qty. & Cable Sizes
200 - 208 220 - 240 380 - 415 440 - 480 550 - 600
Max HP 20 25 30 40 40 (1)#14-#3 PER (CU)
40 50 75 100 100 (1)#14-1/0 PER (CU/AL)
60 75 100 150 150
(1)#6-250MCM PER (CU/AL)
150 150 250 300 300
(2)1/0-250MCM PER (CU/AL)
250 300 500 600 700
(2)2/0-500MCM PER (CU/AL)
* For Proper Cable Size Refer to National Electrical Code NFPA-70
LINE VOLTAGE
Load Terminals (To Motor)
Qty. & Cable Sizes
200 - 208 220 - 240 *380 - 415 440 - 480 550 - 600
Max HP 25 30 40 60 75 (1)#14-1/0 PER (CU/AL) (1)#14-2/0 (CU/AL)
40 50 75 100 100 (1)#4-4/0 PER (CU)
(1)#4-350MCM (CU/AL)
75 75 150 200 200
(1)#3-350MCM PER (CU/AL) (1)#4-350MCM (CU/AL)
100 125 200 250 300
(2)3/0-250MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
150 200 300 400 400
(2)250-350MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
200 - 350 450 550
(2)#1-500MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
250 300 500 600 700
(3)3/0-400MCM PER (CU/AL) (2)1/0-750MCM (CU/AL)
* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.
Line Terminals on Main Isolation Switch (Incoming Cables)
LINE VOLTAGE Service Entrance GND. LUG
Qty. & Cable Sizes
March 2010
N. Y. C.
APPROVED

COMMON ALARM
COMMON ALARM
PHASE FAILURE
(NORMALLY ENERGIZED)
PHASE FAILURE
PHASE REVERSAL
PHASE REVERSAL
FUTURE #1
FUTURE #1
PUMP RUN
PUMP RUN
(NORMALLY ENERGIZED)
(NORMALLY ENERGIZED)
(NORMALLY ENERGIZED)
A
L
A
R
M
C
O
N
T
A
C
T
S
1. MOTOR CONNECTIONS VARY PLEASE REFER TO SPECIFIC
MOTOR MANUFACTURER'S CONNECTION DIAGRAM.
2. FOR SINGLE VOLTAGE 12 LEAD MOTORS
USE LOWER VOLTAGE CONNECTION DIAGRAM
1. MOTOR CONNECTIONS VARY PLEASE REFER TO SPECIFIC
MOTOR MANUFACTURER'S CONNECTION DIAGRAM.
2. FOR SINGLE VOLTAGE 12 LEAD MOTORS
USE LOWER VOLTAGE CONNECTION DIAGRAM
Wye-Delta Lower Nameplate Voltage
Wye-Delta Higher Nameplate Voltage
NOTE:
NOTE:
LMR PLUS Electric Fire Pump Controllers
Electric Motor Connections
For more information visit: www.chfire.com
FD70 Wye Delta (Star-Delta) Open / FD80 Wye Delta (Star-Delta) Closed
FT70 Wye Delta (Star-Delta) Open / FT80 Wye Delta (Star-Delta) Closed
LMR
P
L
U
S

P
L
U
S

ES05805100K/B
Electric Motor Connections
March 2010
N. Y. C.
APPROVED

Electric Fire Pump Controllers & Transfer Switches
Part Number / Options Selection Guide
FD / FT Electric Fire Pump Controllers
For more information visit: www.chfire.com PA05805025K
Electric Fire Pump Controllers & Transfer Switches
July 2011
N. Y. C.
APPROVED

U.B.C and C.B.C
Must Be Installed Per Applicable Code
and Manufacturers Recommendations
SEISMIC QUALIFIED
Part Number / Options Selection Guide
LMR
P
L
U
S

P
L
U
S

FD/FT
FD = Stand Alone Controller A - Built-in Alarm System
FT = Controller with Transfer Switch B - Alarm Bell
C1 - Extra Contacts "Pump Run" (Two Form-C)
C2 - Extra Contacts "AC Power Failure" (Two Form-C)
20 = Limited Service C3 - Extra Contacts "Phase Rev." (Two Form-C)
30 = Across the Line C4 - Remote Contacts (2 Form C) Low Reservoir
40 = Part Winding C5 - Remote Contacts (2 Form C) High Reservoir
50 = Primary Resistor COM - Communications Option
60 = Autotransformer CX - Extra Contacts (Two Form-C; Specify Function)
70 = Wye Delta (Star-Delta) Open E1 - NEMA 3R - Raintight Enclosure
80 = Wye Delta (Star-Delta) Closed E2 - NEMA 4 - Watertight Enclosure
90 = Soft Start E3 - NEMA 12 - Industrial Dust Tight Enclosure
E5 - NEMA 4X - Stainless Steel Enclosure
E8 - Tropicalization
3 15 40 100 250 450 E9 - NEMA 4X - Painted Steel
5 20 50 125 300 500 E10 - NEMA 4X - 316 Stainless Steel Enclosure
7.5 25 60 150 350 600 EX - Export Crating
10 30 75 200 400 700 F2 - Floor Stand - 2 Inch Height
H - High Withstand Rating (refer to tables)
I - Intermediate Withstand Rating (refer to tables)
LX - Extra Light (Specify Description)
Voltage P7 - Low Suction Pressure Switch
A = 200 - 208V P8 - Low Suction Shutdown (Requires P7)
B = 220 - 240V P10 - Pressure Transducer - Sea Water Rated
C = 380V P13 - Externally Mounted Pressure Transducer
D = 440 - 480V R1 - Space Heater (120 / 220V)
E = 550 - 600V R2 - Space Heater c/w Thermostat
F = 415V R3 - Space Heater c/w Humidistat
R4 - Low Pump Room Temperature Switch
Frequency R5 - Space Heater (Externally powered - 120V)
5 = 50 Hz USB - External Mounted USB Port
6 = 60 Hz X1 - Printer
X2 - 4 Inch Chart Recorder ( 10 - 300 psi fresh water)
2U - Second Utility
L1 = English
L2 = French
L5 = Spanish
NOTE: Other languages available. Consult factory for details.
Language
Horsepower
Starting Type
* Higher Horsepowers not available on all
models. Consult Factory for pricing.
Model Options


LMR Plus Electric Fire Pump Controllers

J uly 2011 For more information visit: www.chfire.com PS05805008K/E
Fire Pump Controllers 1-1
Features
Typical Specifications

1. Approvals
A. The Fire Pump Controller shall meet the require-
ments of the latest edition of NFPA 20 and shall be
listed by [Underwriters Laboratories (UL)]and ap-
proved by [Factory Mutual Research (FM)] [Cana-
dian Standards Association (CSA)] [New York De-
partment of Buildings (NYSB)] and carry the CE
marking for fire pump service.
2. Starting Type
A. The controller shall be of the combined manual and
automatic type designed for [Full Voltage Starting]
[Part Winding Starting] [Primary Resistor Starting]
[Autotransformer Starting] [Wye-Delta (Star-Delta)
Open Transition Starting] [Wye-Delta (Star-Delta)
Closed Transition Starting] [Solid State Soft Start
Starting]
3. Ratings
A. The Controller shall have a withstand rating of
100,000 RMS symmetrical amperes @ [208V] [240V]
[380V] [400V] [415V] [480V] [25,000 @ 600VAC].
4. Construction
A. The controller shall include a motor rated combina-
tion isolating switch and circuit breaker, mechanically
interlocked and operated with a single externally
mounted handle.
B. The isolating switch shall be rated to disconnect the
motor load.
C. The isolating switch/circuit breaker combination shall
be mechanically interlocked such that the enclosure
door cannot be opened when the handle is in the on
position except by a tool operated defeater mechan-
ism.
D. The controller manufacturer shall manufacture the
contactor, isolating switch, circuit breaker, pushbut-
tons, and enclosures. Brand-labeled components
will not be accepted.
5. Enclosure
A. The controller shall be housed in a NEMA Type 2
(IEC IP11) drip-proof, powder baked finish, frees-
tanding enclosure.
B. Optional Enclosures:
1. NEMA 3R (IEC IP14) rain-tight enclosure.
2. NEMA 4 (IEC IP66) watertight enclosure.
3. NEMA 4X (IEC IP66) watertight 304 stainless
steel enclosure.
4. NEMA 4X (IEC IP66) watertight 316 stainless
steel enclosure.
5. NEMA 4X (IEC IP66) watertight corrosion resis-
tant enclosure.
6. NEMA 12 (IEC IP52) dust-tight enclosure.




6. Microprocessor Control
A. The controller shall come complete with a 4 line by
40 character LCD display mounted on a panel open-
ing in the front door. The LCD display shall indicate
the following:
1. Main screen displaying system pressure, three-
phase voltage and amperage readings, system
frequency, date, and time.
2. Set point review screen displaying the pro-
grammed pressure start and stop points, and
weekly test time.
3. Controller statistics screen, including:
a. Powered Time
b. Motor Run Time
c. Number of Calls to Start
d. Number of Starts
e. Last Motor Start Time
f. Last Motor Run Time
g. Last Low Pressure Start
h. Minimum System Voltage
i. Maximum System Voltage
j. Minimum System Frequency
k. Maximum System Frequency
l. Minimum System Pressure
m. Maximum System Pressure
n. Last System Startup
o. Last Phase Failure
p. Last Phase Reversal
q. Last Locked Rotor Trip
r. Maximum Run Current
s. Last Locked Rotor Current
4. Controller diagnostics screen, including:
a. Date & Time
b. Firmware Version
c. Shop Order Number
d. Customer Order Number
e. Transformer Output Voltage
f. Current Transformer Outputs
g. Pressure Transducer Calibrated Settings
h. Input Status
i. Output Status
5. Display last messages screen that will display
up to 10,000 alarms/messages stored in the
controllers' memory.
6. Display up to ten (10) custom messages of up to
100 characters each, which will continually scroll
across the fourth line of the display.
7. Remaining time left on active timers.
B. The controller shall be supplied with ten (10) green
status LEDs for the following:
1. Power On
2. Pump Running
3. Local Start
4. Remote Start
5. Deluge Valve
6. Emergency Start


LMR Plus Electric Fire Pump Controllers

J uly 2011 For more information visit: www.chfire.com PS05805008K/E
Fire Pump Controllers 1-2
Features
7. Interlock On
8. Low Pressure
9. Auto Shutdown Enabled
10. Programmable LED #1
C. The controller shall be supplied with ten (10) red
alarm LEDs to indicate the following:
1. Phase Reversal
2. Phase Failure
3. Fail to Start
4. Undervoltage
5. Overvoltage
6. Low Room Temperature
7. Locked Rotor Trip
8. Low Suction Pressure
9. Source 2 Disconnected
10. Programmable LED #2
D. The microprocessor logic board shall be available
with:
1. A USB port for transference of message history,
controller status, diagnostics, and statistics and
the ability to update firmware.
2. An optional Ethernet port for direct connection to
a computer for data transfer.
3. An optional RS485 Serial port for communica-
tion to various external software programs.
E. The controller shall be available with an embedded
web page to allow viewing of the controllers' current
status, data values, programmed set points, and his-
tory.
F. A Fail-to-Start alarm shall occur if the motor control-
ler sees less than 20% of the motor full load amps af-
ter an adjustable time delay of 1-90 seconds.
G. Locked rotor protection shall be provided. After a trip
condition and restoration of power, the LCD display
shall indicate LOCKED ROTOR TRIP.
H. A sequential start timer and weekly test timer shall
be provided as standard.
I. A restart time delay of two (2) seconds shall be pro-
vided to allow the residual voltage of the motor to
decay prior to re-starting the motor. In the event that
the pump motor continues to run after a request to
stop, then the controller must display a fail to stop
message to indicate this condition.
J . Overvoltage (5-20%) and undervoltage (5-30%)
sensing and alarming shall be provided as standard.
K. The controller shall be supplied with interlock and
shutdown circuits as standard. A flashing green LED
shall indicate an interlock on condition.
L. Where shutdown of the pump(s) due to low suction
pressure is required, it shall be accomplished without
the addition of a separate panel or enclosure. The
LCD display shall indicate low suction shutdown.
Resetting of the condition shall be automatic or ma-
nual as selected by the user.
M. Means shall be provided to test the operation of all
LEDs to ensure their functionality.

7. Programming Menu
A. The programming menu shall have the ability to ena-
ble an entry password.
B. The programming menu shall be limited to two (2) le-
vels of password protection.
C. The controller shall have three (3) languages as a
standard, English, French, and Spanish, with the
ability to add a fourth language.
D. The programming menu shall be grouped into 6 main
menu headings as follows:
1. Regional Settings
2. Pressure Settings
3. Timer Values
4. Alarm Set points
5. Input/Output Menu
6. System Configuration (password protected)
8. Pressure Sensor
A. A solid-state 4-20mA pressure sensor shall be pro-
vided. The pressure Start and Stop points shall be
adjustable in increments of one (1) PSI. A low pres-
sure pre-alarm, indicated with a flashing green LED,
shall denote a potential pump starting condition and
will remain lit once the pump has started to indicate
the starting cause.
9. Custom Inputs/Outputs
A. The controller shall come standard with nine (9) fu-
ture inputs, two (2) future LED indicators, and one (1)
future output, with the ability to add up to another 8
outputs via optional relay boards.
B. The user shall be able to program the future in-
puts/outputs through the main programming menu.
C. The inputs shall be selectable based on the following
criteria:
1. User selected message or thirteen (13) prede-
termined messages.
2. Energize the common alarm relay when the in-
put is received.
3. Link to a future relay and/or LED indicator.
4. Alarm latched until reset.
5. Normally open or closed input.
6. On-delay timer.
D. The LED indicators shall be selectable based on the
following criteria:
1. Indication based on a minimum of twelve (12)
predetermined alarms or a custom input.
E. The future relays shall be selectable based on the
following criteria:
1. Output based on a minimum of twenty-seven
(27) predetermined alarms, controller status or a
custom input.
2. Latched until reset.
3. Energized under normal conditions.
4. On or off delay timer on the output.




LMR Plus Electric Fire Pump Controllers

J uly 2011 For more information visit: www.chfire.com PS05805008K/E
Fire Pump Controllers 1-3
Features


10. Alarm Relays
A. All relays shall be of the plug-in type. An LED on the
relay panel shall indicate the energized state of the
relay. All relay contacts shall be rated @ 8A,
277VAC/30VDC. Two (2) sets of Form-C contacts
shall be provided for each of the following:
1. Phase Reversal
2. Phase Failure
3. Common Alarm
4. Future #1
5. Pump Run.
B. The Common Alarm and Phase Failure relays shall
be energized under normal conditions.
11. Audible Alarm Buzzer
An audible alarm buzzer, capable of being heard
while the motor is operating, shall operate if Fail to
Start, Hardware Malfunction or any Common Alarm
condition exists.
12. Manufacturer
A. The controller shall be of the LMR Plus type as man-
ufactured by Eaton Corporation.

You might also like