Compressor Service Procedure
Compressor Service Procedure
Compressor Service Procedure
All You Ever Wanted To Know About Servicing Compressors, But Did Not Know Where To Find.
American Standard 1998 1
Compressors
Subject Page Compressor Fails to Start Control Circuit All ................................................................................................ 3 Single Phase Compressors Fails to Start Motor Hums All ....................................................................... 3 Single Phase Compressors Fails to Start Motor Doesnt Hum All ........................................................... 3 3 Phase Compressor Fails to Start Motor Hums All ............................................................................. ......4 3 Phase Compressor Fails to Start Motor Doesnt Hum ...............................................................................4 Compressor Cycles on Internal Overload (I.O.L.) after Starting ........................................................................... 5 Compressor Runs Little or No Pumping ............................................................................................................6 Noisy compressor Running .............................................................................................................................................................6 Starting And/Or Stopping .................................................................................................................................6 Scroll Functional Check ...........................................................................................................................................6 Compressor Power Supply All ............................................................................................................................6 Scroll Power Interruptions ......................................................................................................................................7 Three Phase Power Supplies ..................................................................................................................................7 Run Capacitor(s) Ohmmeter Test ..................................................................................................................................................7 Power Test .........................................................................................................................................................7 Metal-Cased Round Dual Capacitors ......................................................................................................................8 Start Capacitor Checking a Start Capacitor Using the Ohmmeter .....................................................................8 Start Capacitor Relay ...............................................................................................................................................8 Motor Windings Continuity Test Reciprocating Ground Test .......................................................................................................................................................9 Single Phase with Internal Overload Protectors (I.O.L.) ............................................................................... 10 3 Phase with Internal Overload Protectors (I.O.L.) ........................................................................................ 10 Single Phase with Internal Pilot Duty Thermostats (T.M.) ............................................................................11 3 Phase with Internal Pilot Duty Thermostats (T.M.) ..................................................................................... 11 Hi Pot Testing (Scrolls) ...........................................................................................................................................12 Motor Windings Continuity Test Reciprocating 3 Phase Compressors with Solid State Motor Protection System (M.P.M.) ....................................................................................................12 Motor Protection Module Test Robert Shaw Reciprocating ....................................................................... 12 Motor Protection Module Test Texas Instruments Reciprocating ..............................................................13 Terminal Location Protection Module ..............................................................................................................13 Checking Electrical Circuits All .........................................................................................................................13 Important Start Up Procedure Reciprocating .................................................................................................. 14 Crankcase Heat Reciprocating ..........................................................................................................................14
Compressor Serv 1
Crankcase Heat Scroll ........................................................................................................................................14 Trickle Circuit Test Used on Reciprocating Only .............................................................................................. 14 Trickle Circuit Test ..................................................................................................................................................15 Compressor Replacement Procedure ...................................................................................................................15 Acid Formation in Compressors ........................................................................................................................... 16 Acid Test Kits ..........................................................................................................................................................16 Liquid Line Driers ...................................................................................................................................................16
continued
10664 9/21/98
Compressors
Subject continued Page
Suction Line Driers ................................................................................................................................................. 17 Discharging Refrigerant Systems ......................................................................................................................... 17 Recovering the Charge .......................................................................................................................................... 17 Evacuation Reason and Procedure ................................................................................................................... 17 Refrigerant System Leaks Equipment Necessary for Leak Testing ......................................................................................................... 18 To Check for Leaks .......................................................................................................................................... 18 System Checkout After Leak Repair or Compressor Replacement .................................................................... 19 Notes of Interest ..................................................................................................................................................... 19 Compressor Servicing Notes to Remember ........................................................................................................ 19 Quick Troubleshooting List .................................................................................................................................... 20
10664 9/21/98
Compressor Serv 2
Compressors
Compressor Fails to Start
Control Circuit All
Check compressor contactor for energized position. If compressor contactor is not energized, check voltage across contactor coil. If voltage is present, check contactor. If no coil voltage is present, check control transformer and control fuse. If transformer and fuse check good, jumper R to Y low voltage terminals or wires in the outdoor unit. If the contactor energizes, the problem is in the room thermostat or connecting wiring. If the contactor fails to energize when R to Y is jumpered, check all components connected in series with the compressor contactor coil. Identify components from the schematic diagram. If the equipment does not use a start capacitor and relay, temporarily connect a start capacitor (CPT0091) in parallel with the run capacitor. Manually engage the compressor contactor momentarily.
Scroll
Due to the inherent nature of the Alliance Scroll, the internal pressures are always equalized even if system pressures are not. This allows excellent low voltage startability. Start component may be required for special situations. CAUTION Do not apply power for more than 5 seconds. Start capacitors are designed for intermittent duty only and could rupture if power is applied for extended time periods. If the compressor starts, remove power immediately. Disconnect the start capacitor. Try to restart the compressor. If the compressor starts, restore equipment to operating condition. Operate the equipment until normal operating pressures are reached. Measure the compressor current draw in the compressor common line. If the current draw is equal to or less than equipment nameplate amps, the servicer must use his experience and judgment to determine whether the equipment will continue to start or a start kit is required. If the compressor draws excessive current at operating conditions, condemn the compressor. If the compressor failed to start with the start capacitor connected, condemn the compressor.
Reciprocating
If the equipment does not use a start capacitor and relay, be sure head and suction pressures are equalized. Equipment utilizing expansion valves may require a long time period to equalize. Single-phase compressors without start capacitors will not start against a pressure differential.
10664 9/21/98
Compressors
If the compressor utilizes an internal line break protector, it will be identified on the wiring diagram as I.O.L. Check I.O.L. If the compressor utilizes and internal pilot duty protector, it will be identified on the wiring diagram as T.M. Check T.M. If the compressor utilizes external line break protector(s), they will be identified on the wiring diagram as XOL and XOLS. Check XOL and XOLS. Compressors utilizing T.M. also utilize XOL and XOLS. If protectors check good, measure compressor resistance at the compressor terminals.
3 Phase Compressors
Fails to Start Motor Hums All
Turn room thermostat to off position. Disconnect outdoor fan motor(s). Measure phase to phase voltage at the line side of the compressor contactor. Supply voltage should be within 10% of equipment nameplate rating. Connect a voltmeter across 1 phase on the load side of the contactor. Observe the voltmeter. Manually engage the contactor momentarily. Voltage should not drop more than 10% below no-load voltage. If the voltage drops more than 10% below no-load voltage, check circuit wire size and length and check terminals for loose connections. Check each phase. Determine from the wiring diagram what type overload protection system is used. If the compressor utilizes external protectors, they will be identified on the wiring diagram as XOL. Check XOL. If the compressor motor hums when power is applied, line voltage on all 3 phases check good, all XOL protectors check good and voltage is present at all 3 compressor winding terminals, then condemn the compressor.
Reciprocating
If compressor has 5 terminals, check for continuity between the 3 top terminals. An open reading between any of these terminals indicates an open winding. Condemn the compressor. The 2 lower terminals are connected to the internal pilot duty overload (TM) and will not measure continuity to the top 3 terminals. Check all top 3 terminals to the suction line or discharge line for grounds. If the ohmmeter indicates less than 50,000 ohms, condemn the compressor.
3 Phase Compressors
Fails to Start Motor Doesnt Hum
Turn room thermostat to off position. Disconnect outdoor fan(s). Manually engage the compressor contactor and measure phase to phase voltage at the load side of the compressor contactor. Phase to phase voltage should be within 10% of equipment nameplate rating. If the supply voltage checks good and the compressor does not hum when power is applied, determine from the wiring diagram what type overload protection system is used.
10664 9/21/98
Compressor Serv 4
Compressors
Reciprocating
If the compressor has 5 terminals and the protectors are identified as XOL, check the XOL protectors. If the XOL protectors check good, phase to phase voltage checks good, supply voltage is present at the top 3 compressor terminals and the compressor fails to hum, an open winding is indicated. Disconnect power and remove wiring from compressor terminals. Verify open winding by measuring continuity between the top 3 compressor terminals. If an open circuit is measured between any of the top 3 compressor terminals, condemn the compressor. The lower 2 terminals are connected to the internal pilot duty protector and will not measure continuity to the top 3 terminals.
Reciprocating
If the compressor has 3 power terminals and 3 protector terminals, the compressor is protected by a solid state protection system. When power is applied by manually engaging the contactor, and the compressor fails to hum, an open winding is indicated. Remove the leads from the upper 3 compressor terminals and verify open windings. An open circuit measured with an ohmmeter between any 2 of the 3 upper terminals verifies an open winding. Condemn the compressor.
Compressor Serv 5
10664 9/21/98
Compressors
Scrolls
All of the above conditions apply in addition to: High Discharge temperatures (a) Loss of charge (b) Extremely high compression ratio caused by an evap fan failure. CAUTION During these conditions, compressor dome temperatures can exceed 400F. ent nature of the scroll, excessive noise indicates reverse operation. Compressor damage will occur if operation is continued in reverse rotation.
Noisy Compressor
Starting And/Or Stopping All
Check equipment for level installation. Check compressor for level installation in equipment base pan. Check compressor mounting grommets and bolts. Check refrigerant tubing clearance to equipment cabinet, to adjacent tubing, fan motor(s). Check operating pressures per charts attached to the equipment. Excessive head pressure can cause stopping noise. Be sure the noise is in the compressor. Noise caused by reversing valve operation or rapid pressure balancing expansion valve can appear as compressor noise. If noise level is unacceptable, change the compressor.
Compressor Runs
Little Or No Pumping
High suction pressure and low head pressure are symptoms of a poor pumping compressor, but can also be symptoms of other system component failure. Heat Pump Check Check Valves Heat Pump Check Reversing Valve Check Expansion Valve(s) Check Internal Pressure Relief Valve (IPR) If equipment has service valves, perform pump down test. If system components check good and compressor will not pull suction pressure down, condemn the compressor.
Scroll
All Symptoms above plus: 3 phase compressors, when wired incorrectly, will run in reverse. Due to the inherent nature of the Scroll, no pumping will occur. Compressor damage will occur if operation is continued in reverse rotation.
Scroll
All symptoms above plus 3 phase compressor, when wired incorrectly, will run in reverse. Due to the inher-
Compressors
Supply voltage should be within 10% of the equipment nameplate rating. Equipment is not generally limited to 10% of nameplate rating, but may require special consideration or application limitations. Consult your local Field Service Representative for limits. 2. If capacitor has a discharge resistor connected between terminals, disconnect resistor from one terminal. Set ohmmeter to RX1000 or high scale. Short meter leads and adjust ohmmeter to Zero. Observe meter scale and touch meter leads to capacitor terminals. Good Capacitor Meter pointer will deflect upscale toward zero ohms reading and slowly return downscale to infinity ohms reading. Open Capacitor Meter pointer does not move from infinity ohms reading. Shorted Capacitor Meter pointer will indicate a definite ohm reading less than infinity.
3. 4. 5. 6.
7. 8.
Run Capacitor(s)
Power Test Continuous Duty Oil Filled Capacitors
CAUTION DO NOT PERFORM THIS TEST ON START CAPACITORS
Run Capacitor(s)
Ohmmeter Test Continuous Duty Oil Filled Capacitors
1. 2. 3.
Compressor Serv 7
Connect capacitor to A.C. supply that does not exceed the capacitor voltage rating. Measure and record the applied A.C. voltage. Measure and record amp. Draw of the capacitor. = = Amp. Draw X 2650 Applied A.C. Volts Amp. Draw X 3185 Applied voltage
4. On 60 HZ MFD. On 50 HZ MFD.
10664 9/21/98
1.
5. Example: Capacitor draws 3 amps at 230 volts. (60HZ) Indicated capacitor value is 33 MFD. Calculated value should be within 10% of value stamped on capacitor.
Compressors
Metal-Cased Round Dual Capacitors Start Capacitor
Checking a Start Capacitor Using the Ohmmeter
HER
The round metal-cased dual capacitors with stamped marking of C, HERM and FAN on the top surface are generally used in an air conditioner in a conventional circuit using C to HERM in the compressor circuit with C to FAN in the fan motor circuit. The fan portion of the capacitor is usually not larger than 15 MFD in capacity. Some of these capacitors may have much larger ratings on the terminal labeled FAN and are applied in the Trickle circuit of the compressor to warm the compressor windings during the off cycle. The diagram illustrates this use. The capacitors may be rated 20/20 MFD or 30/30 MFD instead of the more common 20/4 MFD, for example. The presence of a bleed resistor, when used, is an indication of the HERM portion of the capacitor. This resistor is there for your protection. Do not remove it!
BR/RD
OR
BLACK
10664 9/21/98
Start relay (RLY 02227) must be used as a replacement for the Alliance Scroll Compressor.
Compressor Serv 8
FA N
1. 2. 3. 4. 5.
Disconnect capacitor from power circuits. Set ohmmeter to RX10 or RX 100 scale. Short meter leads and adjust ohmmeter to Zero. Observe meter scale and touch meter leads to capacitor terminals Good Capacitor Meter pointer will deflect upscale toward zero ohms reading. Pointer will indicate ohm value of the discharge resistor. Open Capacitor Meter pointer will not swing upscale near zero ohms reading. Pointer will indicate ohm value of the discharge resistor. Shorted Capacitor Pointer will indicate a definite ohm reading between zero ohms and less than the ohm value of the discharge resistor.
6.
7.
MS-1
CAPACITOR DFC
This relay may be mounted in any position. However, the relay is calibrated in the position shown. The pick up and drop out voltage will be slightly different when mounted in other positions. Start relay (RLY 1097) should be used as a replacement for all American Standard single-phase reciprocating compressors that require start components. Relays with a different pick up voltage rating should not be used.
Compressors
Reciprocating (Part No. RLY 1097) Relay Contacts Checkout
Disconnect power to unit. Remove wires from terminals #1 and #2. Check for continuity between terminals #1 and #2. If open circuit, replace relay. If closed circuit, check relay visually.
Visual Checkout
MAX. ST WINDING AMPS. @ 230 V 35 A HOT (40C) PICK UP VOLTS 260 280 COLD PICK UP VOLTS 239 268 DROP OUT VOLTS 60 135 CONTINOUS COIL RATING (40C) 502
If coil and contacts check out OK, remove relay cover and visually inspect contacts and coil for signs of pitted or burned contacts and for burned or charred wiring. If any of these are found, replace relay.
1. 2.
Disconnect all electrical leads from compressor terminals. Set an ohmmeter to the highest scale (R X 10,000 or R X 100,000). Short meter leads and adjust ohmmeter to Zero. Check from each compressor terminal to the compressor case or equipment ground. Be sure the ohmmeter probe is touching a bare metal ground. Any definite resistance measurement of less than 50,000 ohms between any compressor terminal and ground indicates a grounded motor. A grounded motor normally has operated at extremely high temperatures prior to failure. It is absolutely necessary to conduct an acid test on the failed compressor oil before the replacement compressor is installed.
3. 4.
5.
Disconnect power to unit. Remove wires from terminals #2 and #5. Check for continuity between terminals #2 and #5. If open circuit, replace relay. If closed circuit, check contacts.
6.
10664 9/21/98
Compressors
Motor Windings Continuity Test
Single Phase Compressors with Internal Overload Protectors (I.O.L.)
1. 2. 3.
Disconnect all electrical leads from the compressor terminals. Set an ohmmeter to the RX1 scale. Short meter leads and adjust ohmmeter to Zero. Measure for continuity between the start and run terminals. (a) A continuity reading indicates that the motor windings are intact. Proceed to step 4. (b) An infinite reading indicates an open winding. The compressor must be replaced.
1. 2. 3.
Disconnect all electrical leads from the compressor terminals. Set an ohmmeter to the RX1 Scale. Short meter leads and adjust ohmmeter to Zero. Measure for continuity between compressor terminals. Resistance should be the same ohm value between all terminals. If continuity is measured between any two terminals and an infinite resistance (open) to the remaining terminal, the motor is open and the compressor must be replaced. If an open circuit is measured between all terminals, the I.O.L. is tripped or open. Allow adequate time for the I.O.L. to reset before condemning the compressor. Up to two hours may be required if the compressor is extremely hot. Internal overload protectors are identified by I.O.L. designation on the equipment wiring diagram.
4.
4.
If continuity is measured between start and run terminals, then measure between start and common, then measure between run and common. An infinite resistance (open) measurement between common and both start and run terminals indicates a tripped or open I.O.L. Allow adequate time for I.O.L. to reset before condemning the compressor. Up to two hours may be required if the compressor is extremely hot. Internal overload protectors are identified by I.O.L. designation on the equipment wiring diagram.
5.
6.
5.
10
10664 9/21/98
Compressor Serv 10
Compressors
Motor Windings Continuity Test Reciprocating
Single Phase Compressors with Internal Pilot Duty Thermostats (T.M.)
1. 2. 3.
Disconnect all electrical leads from the compressor terminals. Set an ohmmeter to the RX1 scale. Short meter leads and adjust ohmmeter to Zero. Measure for continuity between the common and start terminals. Measure for continuity between the common and run terminals. An infinite reading (open) between either common and start or common and run indicates an open winding. The compressor must be replaced. Measure for internal thermostat (T.M.) continuity between the two lower compressor terminals. T.M. should read continuity (zero ohms). An infinite reading (open) is measured across T.M.; the thermostat is tripped or open. Allow adequate time for T.M. to reset before condemning the compressor. Up to two hours may be required if the compressor is extremely hot. Internal thermostats are identified by T.M. designation on the equipment wiring diagram.
1. 2. 3.
Disconnect all electrical leads from the compressor terminals. Set an ohmmeter to the RX1 scale. Short meter leads and adjust ohmmeter to Zero. Measure for continuity between the upper three compressor terminals. (a) An infinite (open) reading between any two terminals or all terminals indicated an open winding. Replace the compressor. (b) 3 phase compressors with good windings should measure the same resistance between terminals.
4.
4.
5.
Measure for internal thermostat (T.M.) continuity between the two lower compressor terminals. T.M. should measure continuity (zero ohms). An infinite (open) reading across T.M. indicates that T.M. is tripped or open. Allow adequate time for T.M. to reset. Up to two hours may be required to T.M. to reset if the compressor is extremely hot. Internal thermostats are identified by T.M. designation on the equipment wiring diagram.
5.
10664 9/21/98
Compressor Serv 11
11
Compressors
Hi Pot Testing
Scrolls
Alliance Scrolls are configured with the motor down and the pumping components at the top of the shell. As a result, the motor can be immersed in refrigerant to a greater extent than the reciprocating compressor when liquid refrigerant is in the shell. When the Alliance Scroll compressors are hi pot tested with liquid refrigerant in the shell, higher levels of leaks could be observed. The level of current leakage does not represent any safety issues. Brief operation of the compressor will redistribute the refrigerant and should give normal hi pot readings. (b) If (MS) picks up but compressor does not run, de-energize immediately. 1. Check all terminals in power and control circuits. Repair loose connections and re-energize (5 sec. Max.). If compressor fails to run, de-energize. 2. Remove and isolate power leads at compressor. Energize and check 3 phase voltage. If voltage is correct on all phases, compressor has internal problem and must be replaced. 2. If compressor operates with jumper, check each component of solid state protection system for possible malfunction as follows:
Transformer (MPT)
(a) Primary side must be connected to line side of contactor. (b) Remove secondary leads (S, CT, S) from module and measure voltage between each X and CT. The two voltages should be the same, approximately 12 volts. If not, MT is defective and must be replaced.
Sensors Remove sensor leads (C, Sensor 1, Sensor 2) from module. Measure resistance between C and each sensor using a battery powered volt-ohm meter.*
Compressor Serv 12 10664 9/21/98
MPM
C S CT S
CONTROL
CIRCUIT
SEN 1 SEN 2
*WARNING: DO NOT USE A VOLT-OHM METER WHICH APPLIES MORE THAN 3 V DC TO CHECK SENSORS OR SENSOR FUSES. BOTH ARE EASILY DAMAGED AND NO ATTEMPT SHOULD BE MADE TO CHECK CONTINUITY BY ANY OTHER MEANS. (a) Resistance should measure between 60 and 150 ohms. If resistance is greater than 90 ohms, motor is too hot to permit operation. Allow to cool until sensor resistance is less than 90 ohms.
(a) If contactor (MS) does not pick up, problem is in the controls external to compressor terminal box.
12
Compressors
(b) If sensor resistance is greater than 150 ohms: 1. Check sensor fuses. Spare fuses are taped in terminal box. Use only MKB 1/16 amp fuses. 2. If fuses are okay, remove terminal block from small terminal and check sensors according to diagram below. If either sensor has a resistance greater than 150 ohms, compressor must be replaced. Module (MPM) If sensor fuses, sensors and transformer are not defective, module must be replaced. If the compressor contactor fails to energize, jumper terminals M1 and M2 of the module. Do not jumper for more than 5 seconds. If compressor contactor still fails to energize, the problem is in the controls external to the compressor terminal box. If the compressor contactor energizes when module terminals M1 and M2 are jumpered, check voltage at terminals T1 and T2 on the module. Voltage should be between 21 and 30 volts A.C. If T1 and T2 voltage is present, disconnect the motor sensor leads from module terminals S and S1. Measure resistance of the motor sensors with a battery powered ohmmeter. Sensors will be damaged if exposed to high voltage. Resistance should be between 2,000 and 45,000 ohms. If resistance is above 10,000 ohms the motor is too hot to permit operation. Allow motor to cool until sensor resistance is below 10,500 ohms before operating the compressor. If sensor resistance is above 45,000 ohms sensors are damaged and the compressor must be replaced. If sensor resistance and supply voltage are correct and the motor contactor will not energize, the module is defective. Compressor motor overheating can be caused by: (a) Shorted or grounded motor windings (b) Defective run capacitors (c) Defective start capacitors or start relay (d) Low line voltage (e) Low refrigerant charge (f) Dirty condenser or excessive head pressure due to refrigerant overcharge.
Wiring diagrams are attached to control box covers or power panel covers on all equipment. The wiring diagram shows physical location of components, terminal connections, and physical wiring layout. The schematic portion of the diagram shows electrical connections to components necessary to operate each electrical circuit in the system.
10664 9/21/98
13
Compressors
When a component fails to operate, the schematic should be used to identify all other components that complete the circuit. The wiring diagram should be used to physically locate the components. Wire color codes are shown on wiring diagrams and schematics to assist in circuit tracing. The wiring diagram identifies compressor terminals and internal overload protector terminals. Before condemning a compressor for internal electrical failure, measure resistance between all terminals and measure each terminal to ground. ined to determine whether a system fault contributed to the compressor failure, and may cause the replacement compressor to fail.
3. 4.
Replacement capacitors in units utilizing trickle circuits must be the same microfarad rating or circuit malfunction may occur. Nuisance tripping of compressor overload protectors is likely.
14
10664 9/21/98
Compressor Serv 14
Compressors
Only factory supplied start kits should be used with trickle circuit units. Field wired start kits might cause start circuit malfunctions.
3.
4.
Compressor Serv 15
5.
MS-1
CR-A
BR/RD RD
BR/RD
S OR R
C BK/BL
10664 9/21/98
CR-B
F S RD
CPR
IOL
MS-2
BROWN
CF
PURPLE
FAN MOTOR
R BLACK
15
Compressors
manifold valve closed. Permit liquid refrigerant to charge into the high side for 2 to 3 minutes. Close the high side manifold valve. Allow time for high and low side gauges to indicate equalized pressure. Start the equipment and observe pressure readings for proper system operation; balance the refrigerant charge by charging refrigerant vapor into the system low side. Do not charge liquid into the low side compressor damage will result. 6. Use the correct charge balancing method for the type flow control used in the system.
Oil Samples
Oil is a scavenger for acids. If acids are present in the system, they can be detected by testing the compressor oil. CAUTION Highly acid oil can cause chemical burns to eyes and skin. Obtain an oil sample from the suction port of the failed compressor. Use a clean glass or plastic container for the oil sample. If the oil sample is badly discolored or contains solid particles, clean up the system without further tests. Conduct acid test on oil immediately upon removal from the compressor. Acids may be neutralized by chemical reaction with the container (including glass containers).
Liquid line driers are vitally important to the life expectancy of air conditioning equipment. Their purpose is to remove moisture and neutralize acid build-up in the refrigerant system. Liquid line driers should be replaced if the refrigerant charge is lost due to leaks, when a compressor is replaced, or when the refrigerant must be recovered for repairs.
16
Compressors
Liquid line driers should never be oversized, since system refrigerant charge will be increased to accommodate the drier. Excessive refrigerant charge can cause compressor liquid slugging at start-up. Heat pump equipment may contain one or two liquid line driers. A check valve arrangement ensures that liquid flow through the driers is in the same direction regardless of flow direction in the liquid line. Replacement driers in heat pump equipment must be located in the same physical location as the original equipment drier. Do not use commercially available 2-way driers advertised for use in the liquid line outside the heat pump equipment cabinet. Replacement driers in straight cooling equipment may be installed in the liquid line outside the equipment cabinet only if the existing defective drier is removed from the refrigerant circuit and replaced by refrigerant pipe. Note the flow direction arrow or in out marking on the original equipment driers. Replacement drier(s) must be installed in the same flow direction. 2. 3.
Evacuation
1. Proper evacuation of a refrigerant system after compressor replacement, leak repair or any other reason for recovering the refrigerant is absolutely necessary if the system is expected to maintain a long life expectancy with good reliability. Purging a system with refrigerant is not adequate to maintain good reliability and not permitted. Replacement of liquid line driers after compressor replacement or leak repair is imperative for good reliability. The presence of air, moisture or other foreign materials in a refrigerant system will result in poor system performance and reduced life expectancy. High vacuum measurements require the use of a vacuum micron gauge. Manifold pressure gauges are not capable of measuring high vacuum.
4.
5.
Evacuation Procedure
The purpose of evacuating a refrigerant system is to remove moisture and foreign gases from the system. Moisture in an operating refrigerant system chemically combines with refrigerants, forming acids that damage or destroy refrigerant system components, particularly hermetic compressor motors. Foreign gases such as air, hydrogen or nitrogen in the refrigerant system are non-condensable at operating pressures and will cause elevated head pressures and erratic operation of flow controls. To adequately evacuate a system, a high vacuum pump capable of 50 micron pull down is required. (Robinair No. 15001, 15021 or equiv.). To properly measure a high vacuum, a thermocouple vacuum gauge is required. (Robinair No. 14010 or equiv.). Manifold gauges are not adequate for high vacuum measurements.
Refrigerant may contain acids harmful to eyes, skin, clothing, pets, shrubs, and flowers and has been proven harmful to the ozone layer. Always wear protective clothing, glasses or face mask when recovering refrigerant.
10664 9/21/98
17
Compressors
Charging manifold used for evacuation must be in good condition. Hoses must be leak-proof and no longer than 48 inches. Long hoses with small internal diameter will not permit adequate vacuum pull down. CAUTION Close vacuum pump shut-off valve and manifold valves before stopping the vacuum pump, or oil from the pump may flow back into the refrigerant system, unless an oil trap is used. Remove the manifold center hose from the vacuum pump and connect the hose to a refrigerant cylinder. Loosen the center hose fitting at the manifold end and purge the hose with refrigerant. Release only the amount of charge necessary to purge the hose. Charge system with refrigerant.
18
Compressors
Dry nitrogen may be used to pressurize the system in locating small leaks. Do not pressurize the system above 300 psig. Rupture of system components can result. Never pressurize a refrigerant system with compressed oxygen. Oil and oxygen under pressure will explode. 7. After system charging has been completed, check head and suction pressures. Compare pressures to normal operating characteristics charts attached to the equipment. COOLING EQUIPMENT Check thermostat for: (a) Fan only operation (b) Cooling operation 9. HEAT PUMP EQUIPMENT Check thermostat for: (a) Fan only operation (b) Cooling operation (c) Heating first stage (heat pump only) (d) Heating second stage (heat pump plus resistance heat) (e) Emergency Heat Resistance heaters only
8.
Notes of Interest
1. 2. 3. 4. Bleed Resistor is always across CR-A. Normally the Fan Terminal (if it is actually for fan) will not exceed 15 MFD. Normally the Fan Rating will be lowest MFD. There are capacitors rated at 20/20 and 30/30 MFD.
10664 9/21/98
Compressor Serv 19
19
Compressors
1. Open I.O.L. ............................................................................ Check resistance C to S and C to R Allow compr. to cool and re-test 2. Open Windings .................................................................... Check resistance Start to Run 3. Grounded Compressor ........................................................ Check resistance of terminals to ground 4. Locked Rotor (stuck) ............................................................ Voltage Present @ C to S and C to R Locked Rotor Amps on C (Start capacitor may be required for starting) 5. Defective Run Capacitor/St. Cap. ........................................ Check with Ohmmeter 6. Open Start Leg Fuse ............................................................ Check for continuity 7. Shorted Windings ................................................................ Compare winding resistance to valves from Service Manual
1. Insufficient Refrigerant ........................................................ Compare System press to Performance Charge/Restriction Charts 2. Defective Run Cap./St. Cap .................................................. Check with Ohmmeter 3. Defective Start Relay ........................................................... Current on St. Cap should drop off within 5 sec.
1. Compr. Valves Defective ...................................................... Little or no difference between head and suction 2. Internal Mechanical Failure ................................................. Suction press rises sharply during off cycle 3. SOV not seated .................................................................... Check temp rise of suction line across SOV
20
Note: This publication is general in nature and is intended for INSTRUCTIONAL PURPOSES ONLY. It is not to be used for equipment selection, application, installation, or specific service procedures.
P.I. (L)