Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor

Supplement to Hilti North American Product Technical Guide Volume 2: Anchor Fastening Technical Guide

2011 Edition

Mechanical Anchoring Systems

3.3.5 KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor


3.3.5.1 3.3.5.2 Product Description Material Specifications

3.3.5.1 Product Description


Hilti KWIK HUS-EZ I (KH-EZ I) anchors are comprised of a body with an internally threaded hex washer head. The anchor is manufactured from carbon steel and is heat treated. It has a minimum 0.0003 inch (8 m) zinc coating in accordance with DIN EN ISO 4042. The internally threaded head is larger than the diameter of the anchor and is formed with serrations on the underside. The anchor body is formed with threads running most of the length of the anchor body. The anchor is installed in a predrilled hole with a powered impact wrench or torque wrench. The anchor threads cut into the concrete on the sides of the hole and interlock with the base material during installation. Applicable base materials include normal-weight concrete, structural lightweight concrete and lightweight concrete over metal deck. Guide Specifications Screw anchors shall be KWIK HUS-EZ I as supplied by Hilti, Inc. Anchors shall be manufactured from heat treated carbon steel material, zinc plated to a minimum thickness of 8m. Anchors shall be installed using a drill bit of same nominal diameter as anchor. Product Features Thread design enables quality setting and exceptional load values in wide variety of base material strengths. Anchor is fully removable Anchor size is same as drill bit size and uses standard ANSI B212.15 1994 drill bits. Suitable for reduced edge distances and spacing.

3.3.5.3 Technical Data 3.3.5.4 Installation Instructions 3.3.5.5 Ordering Information

3.3.5.2 Material Specifications


Hilti KWIK HUS-EZ I anchors are manufactured from carbon steel. The anchors are bright zinc plated to a minimum thickness of 8m.

3.3.5.3 Technical Data


The data contained in Tables 1-4 of this section have been evaluated in accordance with AC 193. For more detail, see ICC-ES ESR 3027. Figure 1 KWIK HUS-EZ I anchor installation details

Listings/Approvals
ICC-ES (International Code Council) ESR-3027 (Cracked & Uncracked Concrete) FM Approved

Independent Code Evaluation


IBC / IRC 2009 (AC 193 / ACI 355.2) IBC / IRC 2006 (AC 193 / ACI 355.2) IBC / IRC 2003 (AC 193 / ACI 355.2)

Suitable for cracked and uncracked normal weight and lightweight concrete, and lightweight concrete over metal deck. Suitable for seismic and nonseismic loads. Quick and easy to install.

2 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en espaol 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I Anchor Fastening Technical Guide 2011

Mechanical Anchoring Systems

KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3.5


Table 1 KWIK HUS-EZ I (KH-EZ I)
Design Guidelines For KWIK HUS-EZ I1 Values for Normal Weight and Lightweight Concrete Characteristic Internal Thread Diameter of Head Wrench Socket Size Nominal Diameter Drill Bit Diameter Maximum Installation Torque4 Maximum Impact Wrench Torque Rating3 Minimum Nominal Embedment Depth Minimum Hole Depth Critical Edge Distance2 Minimum Spacing at Critical Edge Distance Minimum Edge Distance Minimum Spacing at Minimum Edge Distance Minimum Concrete Thickness Anchor Category Tension Resistance of Steel Reduction Factor for Steel Strength Symbol dit ws da dbit Tinst,max Timpact,max hnom hhole cac5 smin,cac5 cmin5 smin5 hmin Steel Strength in Tension (ACI 318 D.5.2) Nsa lb. sa Concrete Breakout Strength in Tension (ACI 318 D.5.2) Effective Embedment Depth hef in. Effectiveness Factor - Uncracked Concrete Kuncr Effectiveness Factor - Cracked Concrete Kcr Modification Factor for cracked and uncracked concrete c,N Reduction Factor for Concrete Breakout Strength cb Pullout Strength in Tension (ACI 318 D.5.3) Characteristic pullout strength, uncracked concrete (2500 psi) Np,uncr lb Characteristic pullout strength, cracked concrete Np,cr lb Reduction Factor for pullout strength p Characteristic Pullout Strength, Seismic (2500 psi) Np,eq lb Reduction Factor for pullout strength eq Values for Installation in the underside of Concrete-Filled Profile Steel Deck Assemblies2 Pullout Resistance, (uncracked concrete) - Lower Flute Np,deck,uncr lb Pullout Resistance, (uncracked concrete) - Upper Flute Np,deck,uncr lb Pullout Resistance, (cracked concrete and seismic loads) - Lower Flute Np,deck,cr lb Pullout Resistance, (cracked concrete and seismic loads) - Upper Flute Np,deck,cr lb
1 The data presented in this table is to be used in conjunction with the design criteria of ACI 318 Appendix D. 2 For installations through the soffit of steel deck into concrete, anchors installed in the lower flute may be installed with a maximum one inch offset in either direction from the center of the flute. See Figure 2. 3 Because of variability in measurement procedures, the published torque of an impact tool may not correlate properly with the above setting torques. Over-torquing can damage the anchor and/or reduce its holding capacity. 4 Tinst,max applies to installations using a calibrated torque wrench. 5 Additional combinations for minimum edge distance, cmin and minimum spacing distance, smin or smin,cac may be derived by linear interpolation between the given boundary values. 6 The characteristic pullout resistance for concrete compressive strengths greater than 2,500 psi may be increased by multiplying the value in the table by (f'c/2,500)0.3 7 The characteristic pullout for concrete compressive strengths greater than 2,500 psi may be increased by multiplying the value in the table by (f'c/2,500)0.5 8 The characteristic pullout resistance for concrete compressive strengths greater than 3,000 psi may be increased by multiplying the value in the table by (f'c/3,000)0.3 9 The characteristic pullout for concrete compressive strengths greater than 2,500 psi may be increased by multiplying the value in the table by (f'c/2,500)0.5

Units in. in. in. in. ft-lbf ft-lbf in. in. in. in. in. in. in.

Value 1/4 or 3/8 3/8 or 1/2 1/4 1/4 18 114 1 5/8 2 2.00 1.50 1.50 3.0 3.25 3 6,070 0.65 1.18 24 17 1 0.45 13056 6676 0.45 5346 0.45 12108 14908 6208 7608 0.65 23587 11667 0.65 11667 0.65 18759 19609 9309 9759 1.92 4.125 1 137 2 1/2 2 7/8 2.78

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en espaol 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I Anchor Fastening Technical Guide 2011 3

Mechanical Anchoring Systems

3.3.5 KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor


Table 2 - Calculated ACI 318-08 Appendix D Strength Design Capacity for Single anchor in Tension3,4,5,6,7
Normal Weight Concrete Anchor Size (in.) 2500 psi1 Internally Nominal Threaded Embedment Head Depth Uncracked Cracked (in.) (in.) Concrete Concrete 1/4 3/8 1/4 3/8 1-5/8 1-5/8 2-1/2 2-1/2 587 587 1533 1533 300 300 758 758 4000 psi Seismic 240 240 758 758 Uncracked Cracked Concrete Concrete 675 675 1940 1940 346 346 958 958 Seismic 277 277 958 958 LWCOMD 3000 psi2 Uncracked Concrete Cracked Concrete

Lower Upper Lower Upper Flute Flute Flute Flute 545 545 1218 1218 670 670 1275 1275 280 280 605 605 342 342 634 634

1/4 x 1-5/8 1/4 x 2-1/2


1 2 3 4 5 6 7

Values for other strengths can be calculated per (f'c/2500)0.3 for 1-5/8" embedment and (f'c/2500)0.5 for 2-1/2" embedment Values for other strength can be calculated per (f'c/3000)0.3 for 1-5/8" embedment and (f'c/3000)0.5 for 2-1/2" embedment Based on single anchor with edge and spacing values greater than those given as critical values in Table 1. Based on lower value of concrete breakout or pullout strength These loads are factored resistance loads in accordance with Chapter 9 of ACI 318-08 (Nn). Interpolation of values for other embedments is not permitted Minimum concrete thickness and edge distance must comply with Table 1.

Table 3 KWIK HUS-EZ I (KH-EZ I) Allowable Stress Design Values for Illustrative Purposes1,2,3,4,5,6,7,8,9,10,11
Internal Thread Diameter of Head (in.) 1/4 or 3/8 Nominal Anchor Diameter (in.) 1/4 Embedment Depth, hnom (in.) (mm) 1-5/8 (41) 2-1/2 (64) Effective Embedment Depth, hef (in.) (mm) 1.18 (30) 1.92 (49) Allowable Tension Load lb (kN) 470 (2.1) 1340 (6.0)

For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1 Single anchor with static tension load only. 2 Concrete determined to remain uncracked for the life of the anchorage. 3 Load combinations are taken from ACI 318 Section 9.2 (no seismic loading). 4 40% dead load and 60% live load, controlling load combination 1.2D + 1.6L. 5 Calculation of weighted average for conversion factor = 1.2(0.4) + 1.6(0.6) = 1.44. 6 fc = 4,000 psi (27.6 MPa) (normal weight concrete). 7 ca1 = ca2 cac, see Table 1. 8 h hmin, see Table 1. 9 Values are for Condition B where supplementary reinforcement in accordance with ACI 318 D.4.4 is not provided. 10 Allowable Tension Load = factored Load (Lesser of Np or Concrete Breakout from Table 1) 1.44 11 Values are for single anchors installed without influence of base material edge distance or adjacent anchors.

Figure 2 Installation of KWIK HUS-EZ I (KH-EZ I) in Soffit of Concrete Over Steel Deck Floor and Roof Assemblies

1 A  nchors may be placed in the upper or lower flute of the steel deck profile provided the minimum concrete cover above the drilled hole is satisfied. Anchors in the lower flute may be installed with a maximum 1-inch offset in either direction from the center of the flute. The offset distance may be increased proportionally for profiles with lower flute widths greater than those shown provided the minimum lower flute edge distance is also satisfied.
4 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en espaol 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I Anchor Fastening Technical Guide 2011

Mechanical Anchoring Systems

KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3.5


Table 4 - KWIK HUS EZ I (KH-EZ I) Allowable Stress Design Tension Values for Installations in Soffit of Concrete Over Steel Deck Floor and Roof Assemblies
Internal Thread Diameter of Head (in.) 1/4 or 3/8 Nominal Anchor Diameter (in.) 1/4 Embedment Depth (in.) (mm) 1-5/8 (41) 2-1/2 (64) Effective Embedment Depth (in.) (mm) 1.18 (30) 1.92 (49) Allowable Tension Load lb (kN) Upper Flute Lower Flute 466 (2.1) 885 (3.9) 378 (1.7) 846 (3.7)

For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1 Single anchor with static tension load only. 2 Concrete determined to remain uncracked for the life of the anchorage. 3 Load combinations are taken from ACI 318 Section 9.2 (no seismic loading). 4 40% dead load and 60% live load, controlling load combination 1.2D + 1.6L. 5 Calculation of weighted average for conversion factor = 1.2(0.4) + 1.6(0.6) = 1.44. 6 fc = 3,000 psi (27.6 MPa) (light weight concrete). 7 ca1 = ca2 cac, see Table 1. 8 h hmin, see Table 1. 9 Values are for Condition B where supplementary reinforcement in accordance with ACI 318 D.4.4 is not provided. 10 Allowable Tension Load = factored Load (Lesser of Np or Concrete Breakout from Table 1) 1.44 11 Values are for single anchors installed without influence of base material edge distance or adjacent anchors.

Table 5 - Kwik HUS-EZ I (KH-EZ) Tested Load Values for FM Approval for Automatic Sprinkler Systems
Hanger Rod Size (in.) 3/8 Screw Length (in.) 1 5/8 2 1/2 FM Test Load Tension lb (kN)) 1475 (6.6) FM Maximum Pipe Diameter (in.) 4

1 Tested in accordance with FM Approval Standard for Pipe Hanger Components for Automatic Sprinklers Systems Class Numbers 1951, 1952 and 1953.

Table 6 - Kwik HUS-EZ I (KH-EZ I) Allowable Stress Design Values for Installations into Hollow Core Concrete Panels1,2
Hanger Rod Size (in.) 1/4 3/8 Min. Effective Embedment hef (in.) 1 3/8 Allowable Load3 Tension lb (kN) 455 (2.0) Shear lb (kN)4,5 485 (2.2) 755 (3.4) Ultimate Load Tension lb (kN) 1810 (8.1) Shear lb (kN)4,5 1,930 (8.6) 3,025 (13.5)

1 The Admissible Anchor Location must be established to prevent damage to the prestressed cable during the drilling process. Verify the location and height of the cable with the hollow core plank supplier to confirm Admissible Anchor Location. 2 Minimum compressive strength of prestressed concrete is 7,000 psi. Published ultimate loads represent the average results conducted in local base materials. Due to variations in materials and dimensionl configurations, on-site testing is required to determine the actual performance. 3 Allowable loads calculated with a 4:1 factor of safety. 4 The bottom of the shear plane adjacent to the top of the coupler. 5 Shear values controlled by the steel strength of ASTM A193, Grade B7 (min. tensile strength 125 ksi) screws used to fasten the shear fixturing. Shear values should consider the screw or threaded rod strength.

Figure 3 Installation of KWIK HUSEZ I (KH-EZ I) in Hollow Core Concrete

3.3.5.4 Installation Instructions


Use the installation instructions that are including with the Kwik HUS-EZ I packaging box. To obtain a digital copy of the Installation Instructions, visit www.us.hilti.com, www.hilti.ca or contact Hilti Technical Support.
Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en espaol 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I Anchor Fastening Technical Guide 2011 5

Mechanical Anchoring Systems

3.3.5 KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor


The data below is developed from testing performed in accordance with ACI 355.2. It is intended for applications designed according to CSA A23.3-04 Update No. 3 (August 2009) Design Of Concrete Structures Annex D and is generally suitable for the conditions described in the introduction of Annex D. Table 7 KWIK HUS-EZ I (KH-EZ I)
Design Guidelines For KWIK HUS-EZ I Values for Normal Weight and Lightweight Concrete
1

c
Symbol Units Value in. 1/4 or 3/8 in. 3/8 or 1/2 in. 1/4 in. 1/4 ft-lbf (Nm) 18 (24) ft-lbf (Nm) 114 (154) 137 (186) mm 41 64 0.65 0.85 MPa 924 mm2 29.0 mm 51 73 mm 38 mm 38 mm 76 mm 83 105 3 1 kN 30 51 10 7 1.4 0.70 2.66 1.36 0.65 1.16 0.65 2.48 3.08 1.38 1.58 5.49 5.79 2.79 2.89 3.47 1.00 6.87 3.47 15.9 0.70 49 71

Characteristic Internal Thread Diameter of Head Wrench Socket Size Nominal Diameter Drill Bit Diameter Maximum Installation Torque4 Maximum Impact Wrench Torque Rating3 Minimum Nominal Embedment Depth Concrete material resistance factor Steel material resistance factor Ultimate Strength of anchor steel Effective cross-sectional area of anchor Minimum Hole Depth Minimum Spacing at Critical Edge Distance Minimum Edge Distance Minimum Spacing at Minimum Edge Distance Minimum Concrete Thickness Anchor Category Steel Strength in Tension (CSA A23.3 D.6.1) Factored Steel Resistance in Tension Reduction Factor for Steel Strength

Tinst,max Timpact,max hnom c s fut Ase hhole smin,cac5 cmin5 smin5 hmin

da dbit

Nsr R

Concrete Breakout Strength in Tension (CSA A23.3 D.6.2) Effective Embedment Depth hef mm Critical Edge Distance2 cac5 mm Effectiveness Factor - Uncracked Concrete Kuncr Effectiveness Factor - Cracked Concrete Kcr Modification Factor for cracked and uncracked concrete c,N Reduction Factor for Concrete Breakout Strength R Pullout Strength in Tension - Non Seismic Applications (CSA A23.3 D.6.3} Factored Pullout Resistance, uncracked concrete (17.23 MPa) Npr,uncr kN Factored Pullout Resistance, cracked concrete (17.23 MPa) Npr,cr kN Concrete Resistance Factor for pullout strength c,pull Factored Pullout Strength, Seismic (17.23 MPa) Npr,eq kN Concrete Resistance Factor for pullout strength c,seis Values for Installation in the underside of Concrete-Filled Profile Steel Deck Assemblies2 Factored Pullout Resistance, (uncracked concrete 20.68 MPa) - Lower Flute Npr,deck,uncr kN Factored Pullout Resistance, (uncracked concrete 20.68 MPa) - Upper Flute Npr,deck,uncr kN Factored Pullout Resistance, (cracked concrete and seismic loads 20.68 MPa) - Lower Flute Npr,deck,cr kN Factored Pullout Resistance, (cracked concrete and seismic loads 20.68 MPa) - Upper Flute Npr,deck,cr kN
1 The data presented in this table is to be used in conjunction with the design criteria of CSA A23.3-04.

2 For installations through the soffit of steel deck into concrete, anchors installed in the lower flute may be installed with a maximum one inch offset in either direction from the center of the flute. 3 Because of variability in measurement procedures, the published torque of an impact tool may not correlate properly with the above setting torques. Over-torquing can damage the anchor and/or reduce its holding capacity. 4 Tinst,max applies to installations using a calibrated torque wrench. 5 Additional combinations for minimum edge distance, cmin and minimum spacing distance, smin or smin,cac may be derived by linear interpolation between the given boundary values. 6 The characteristic pullout resistance for concrete compressive strengths greater than 17.23 MPa may be increased by multiplying the value in the table by (f'c/17.23)0.3 7 The characteristic pullout for concrete compressive strengths greater than 17.23MPa may be increased by multiplying the value in the table by (f'c/17.23)0.5 8 The characteristic pullout resistance for concrete compressive strengths greater than 20.68 MPa may be increased by multiplying the value in the table by (f'c/20.68)0.3 9 The characteristic pullout for concrete compressive strengths greater than 20.68 MPa may be increased by multiplying the value in the table by (f'c/20.68)0.5
6 Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en espaol 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I Anchor Fastening Technical Guide 2011

Mechanical Anchoring Systems

KWIK HUS-EZ I (KH-EZ I) Carbon Steel Screw Anchor 3.3.5 3.3.5.6 Ordering Information
Order Information
Description Internal Thread Diameter Internal Thread Length Hole Diameter Minimum Embedment Qty (pcs) / Box

KH-EZ 1/4"x1-5/8" | 1/4" KH-EZ 1/4"x2-1/2" | 1/4" KH-EZ 1/4"x1-5/8" | 3/8" KH-EZ 1/4"x2-1/2" | 3/8"

1/4" 1/4" 3/8" 3/8"

3/8" 3/8" 7/16" 7/16"

1/4" 1/4" 1/4" 1/4"

1-5/8" 2-1/2" 1-5/8" 2-1/2"

100 100 100 100

Hilti, Inc. (US) 1-800-879-8000 | www.us.hilti.com I en espaol 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I Anchor Fastening Technical Guide 2011 7

Hilti. Outperform. Outlast.


P.O. Box 21148, Tulsa, OK 74121 Hilti, Inc. (US) 1-800-879-8000 www.us.hilti.com Servicio al Cliente en espaol 1-800-879-5000 Hilti (Canada) Corporation 1-800-363-4458 www.hilti.ca Hilti is an equal opportunity employer Hilti is a registered trademark of Hilti, Corp. Copyright 2012 by Hilti, Inc. 01/12 BB
The data contained in this literature was current as of the date of publication. Updates and changes may be made based on later testing. If verification is needed that the data is still current, please contact the Hilti Technical Support Specialists at 1-800-879-8000. All published load values contained in this literature represent the results of testing by Hilti or test organizations. Local base materials were used. Because of variations in materials, on-site testing is necessary to determine performance at any specific site. Laser beams represented by red lines in this publication. Printed in the United States