HTW-1260 T5 (Open Skid) EN
HTW-1260 T5 (Open Skid) EN
HTW-1260 T5 (Open Skid) EN
OPEN SKID
WATER-COOLED
THREE PHASE
50 HZ
DIESEL
Generating Rates
SERVICE
Power Power Rated Speed Standard Voltage Available Voltages Rated at power factor kVA kW r.p.m. V V Cos Phi PRP 1260 1008 1.500 400 400/230 - 415/240 - 380/220 V 0,8 STANDBY 1350 1080
QR Code
HIMOINSA Company with quality certification ISO 9001 HIMOINSA gensets are compliant with EC mark which includes the following directives: EN ISO 13857:2008 Machinery safety. 2006/95/EC Low voltage. 89/336/EEC Electromagnetic compatibility. 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by 2005/88/EC) 97/68/EC Emissions of gaseous and particulate pollutants. (amended by 2002/88/EC & 2004/26/EC)
Ambient conditions of reference: 1000 mbar, 25C, 30% relative humidity. Power according to ISO 3046 normative.
P.R.P. Prime Power - ISO 8528 : prime power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year, between stated maintenance intervals. The permissible average power output during a 24 hours period shall not exceed 80% of the prime power. 10% overload available for governing purposes only. Standby Power (ISO 3046 Fuel Stop power): power available for use at variable loads for limited annual time (500h), within the following limits of maximum operating time: 100% load 25h per year 90% load 200h per year. No overload available. Applicable in case of failure of the main in areas of reliable electrical network. HIMOINSA HEADQUARTERS: Fbrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 [email protected] www.himoinsa.com Manufacture facilities: SPAIN FRANCE INDIA CHINA USA Subsidiaries:
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Generator
Generator
Poles Winding Conections (standard) Frame Mounting Insulation Enclosure (according IEC-34-5) Exciter System Voltage Regulator Steady Voltage Precision Bearing Coupling Coating type Class Num 4 Star S-0 21" H class IP23 self-excited, brushless A.V.R. (Electronic) 1% Single bearing Flexible disc Standar (Vacuum impregnation)
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
CEM7
CEC7
CEA7
FUNCIONALITY Auto-start Automatic Control Panel Without Mains Control Automatic Control Panel With Mains Control (customer change over contactors) Automatic Control Panel With Mains Control (Himoinsa change over contactor with display) Automatic Mains Failure (wall mounted panel)
(**) Pre-heating resistance in the Genset and Battery charger in the control panel included. Option available: Auto-start control panel without circuit breaker
General Description
CEM 7
The CEM7 controller unit is a device able to control de operation, monitoring and protection of a generating set. The controller unit consists of 2 different modules: 1. The VISUALIZATION module 2. The MEASUREMENTS module VISUALIZATION MODULE Provides information about the status of the device and, at the same time, allows the user to interact with it. It consists on a backlit display and various LEDs for monitoring the status of the controller and buttons that allow the user to control, program and configure the functions of the unit. MEASUREMENTS MODULE Controls and monitors the control board. It is located in the rear part of the panel, in order to reduce the wiring and to avoid electromagnetic disturbances. Every signal, sensor and actuator is connected to this module. The connexion between the visualization module and the measurements module is made with a CAN communication bus. This feature allows the intercommunion of other modules to the main controller with a scalability warranty.
CEC 7
The CEC7 controller unit is a net sings supervision equipment, and control and supply supplier through generating set. The controller unit consists of 2 different modules: 1. The VISUALIZATION module 2. The MEASUREMENTS module VISUALIZATION MODULE The visualization module provides information about the status of the device and, at the same time, allows the user to interact with it. With this visualization module the user is able to control, program and configure the functions of the unit. It consists on a backlight display and various LEDs for monitoring the status of the controller and buttons that allow the user to control, program and configure the functions of the unit. MEASUREMENTS MODULE The measurements module controls and monitors the control board. It is located in the rear part of the panel, in order to reduce the wiring and to avoid electromagnetic disturbances. Every signal, sensor and actuator is connected to this module The connection between the measure module and visualization mode is made by means of a CAN BUS (Communication Bus). This produces an interconnection between additional modules which guarantees the proper working of the controller.
CEA 7
CEA7 controller is a supervision equipment for mains signal and also a supervision and electrical supply through the genset. This controller is composed by 2 different modules: 1. VISUALIZATION module 2.MEASUREMENTS module VISUALIZATION MODULE The visualization module provides information about the status of the device and, at the same time, allows the user to interact with it. With this visualization module the user is able to control, program and configure the functions of the unit. MEASUREMENTS MODULE The measurements module controls and monitors the control board. It is located inthe rear part of the panel, in order to reduce the wiring and to avoid electromagnetic disturbances. Every signal, sensor and actuator is connected to this module. Connection between the measure module and visualization mode is made by means of a CAN BUS (Communication Bus). This produces an interconnection between additional modules which guarantees the proper working of the controller.
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Engine Alarms
1. High coolant temperature. 2. Low oil pressure. 3. Battery charge alternator 4. Start failure. 5. Low water level. 6. Fuel storage. 7. Overspeed. 8. Underspeed. 9. Low battery voltage. 10. High coolant temperature by sensor. 11. Low oil pressure by sensor. 12. Low fuel level by sensor. 13. Unexpected shutdown. 14. Stop failure. 15. Low engine temperature. 16. Genset voltage drops. 17. Emergency stop.
Genset Alarms
1. Over-load 2. Unbalanced voltage 3. Over voltage 4. Under voltage 5. Over frequency 6. Under frequency 7. Over load 8. Short-circuit 9. Inverse Power 10. Asymmetry among phases 11. Genset contactor Failure
Mains Alarms
1. Maximum Mains Voltage. 2. Minimum Mains Voltage. 3. Maximum Mains Frequency. 4. Minimum Mains Frequency. 5. Mains phase sequence failure. 6. Mains power failure. 7. Mains contactor switching failure.
Programmable Alarms: There are 5 programmable alarms on text and action that could be associated to any engine alarms and showed on the auxiliary led 1 and 2 of the display
Model: HTW-1260 T5
Controllers Features
CEM 7 GENERATOR READINGS Voltage among phases Voltage among phases and neutral Amperage Frequency Apparent power (kVA) Active power (kW) Reactive power (kVAr) Power factor MAINS READINGS Voltage among phases Voltage among phase and neutral Amperage Frequency Aparent power Active power Reactive power Power factor ENGINE READINGS Coolant temperature Oil pressure Fuel level (%) Battery voltage R.P.M. Battery charge alternator voltage ENGINE PROTECTIONS High water temperature High coolant temperature by sensor Low engine temperature by sensor Low oil pressure Low oil pressure by sensor Low coolent level Unexpected shutdown Fuel storage Fuel storage by sensor Stop failure Battery voltage failure Battery charge alternator failure Overspeed Underspeed Start failure Emergency Stop ALTERNATOR PROTECTIONS High frequency Low frequency High voltage Low voltage Short-circuit Asymmetry among phases Incorrect phase sequence Inverse power Overload Genset signal droop
Standard
x x x x x x x x
x x x x
x x x x x x
x x x x x x x x x x x x x x x
x x x
x Not included
Optional
NOTE: All protections are programmable to make warning or stop with cooling time or without
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Controllers Features
CEM 7
COUNTERS Total hour counter Partial hour counter Kilowatimeter Starts valid counters Starts failure counters Maintenance COMUNICATIONS RS232 RS485 Modbus IP Modbus CCLAN Software for PC Analogic modem GSM/GPRS modem Remote screen Telesignal J1939 FEATURES Alarms history External start Start inhibition Mains failure start Start under normative EJP Genset contactor activation Main & Genset contactor activation Fuel transfer control Engine temperature control Manual override Programmable alarms Genset start function in test mode Programmable outputs Multilingual SPECIAL FUNCTIONS Positioning GPS Synchronization with mains Mains Synchronism Second Cero suppression RAM 7 Remote screen Timer
CEC 7
CEA 7
CEM7 + CEC7
(8+4)
x x x
(8+4)
(8+4)
-10 x x x x x x x x
(10) / (+100) x
(10) / (+100)
CEC7: available when the controller CEC7 is incorparted to the installation MPS 5.0: available application when the module MPS 5. has been incorporated to the panel. Note: AS5 + CC2 configuration, will have all CEM7 funcionality plus CEC7 mains readings.
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Alternator
Self-excited and Self-regulated IP23 protection degree Insulation H class
Electrical system
Control and power electric panel, with measurements devices and controller (according to necessity and configuration) Connection panel wired to the safety protection (open thermalmagnetic protection and alarm) Maintenance-free and anti-explosion battery Battery disconnector 4 poles circuit breaker Battery charger (standard on automatic control panels) Pre-heating resistance (standard on automatic control panels) / water jacket heater Battery charge alternator with ground connection Starting battery/ies installed and connected to the engine (supports included) Ground connection electrical installation with connection ready for ground pike (not supplied)
Model: HTW-1260 T5
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Application Data
Exhaust System
Maximum exhaust temperature Exhaust Gas Flow Maximum allowed back pressure Heat evacuated through exhaut pipe C m3/min mm H2o KCal/Kwh 520 258 600 587,17
Starting System
Starting Motor Starting Motor Recommended Battery Capacity Auxiliary Voltage Starting current Starting current Kw CV Ah Vcc Peak Intensity 7,5 x 2 10,2 x 2 400 24 1250 400
Fuel System
Fuel Oil Specifications Maximum power suction pump Maximum return feed pump Fuel Tank mm Hg mm Hg L Diesel 75 150 400
Model: HTW-1260 T5
Dimensions
HEAVY RANGE Open Skid
Powered by MITSUBISHI
Length Height Width Shipping Volume seaworthy (standard suplier) Wet weight Dry weight Fuel tank capacity Autonomy
(*) (with standard accesories)
mm mm mm m3 Kg Kg L. Hours
(*) (*)
Himoinsa reserves the right to modify any characteristic without prior notice. Weights and dimensions based on products standar. Illustrations may include optional equipment. Technical data described here correspond with the available information at the moment of printing. Industrial design under patent.
(32626)
Model: HTW-1260 T5
HEAVY RANGE Open Skid
PDF Summary
Created : 10/10/2011 10:41 Author : Himoinsa Number of pages : 11 Report Type: Data Sheet - Heavy range Generated by: HIMOINSA Engineering Dept. Page 1. Genset data Page 2. Engine Specifications Page 3. Generator Specifications Page 4. Control Panels models + General Description Page 5. Control box and power, CE7 Panel, Alarms Page 6. Controller features (I) Page 7. Controller features (II) Page 8. Generator Features & Options Page 9. Installation Data Page 10. Dimensions Page 11. PDF Summary (ID454E32333531303530) http://www.himoinsa.com/ProductDetail/ficha.aspx?id=235
Powered by MITSUBISHI