Chapter 4: Modeling Periodic Flow and Heat Transfer
Chapter 4: Modeling Periodic Flow and Heat Transfer
Chapter 4: Modeling Periodic Flow and Heat Transfer
This tutorial is divided into the following sections: 4.1. Introduction 4.2. Prerequisites 4.3. Problem Description 4.4. Setup and Solution 4.5. Summary 4.6. Further Improvements
4.1. Introduction
Many industrial applications, such as steam generation in a boiler or air cooling in the coil of an air conditioner, can be modeled as two-dimensional periodic heat flow. This tutorial illustrates how to set up and solve a periodic heat transfer problem, given a pregenerated mesh. The system that is modeled is a bank of tubes containing a flowing fluid at one temperature that is immersed in a second fluid in cross flow at a different temperature. Both fluids are water, and the flow is classified as laminar and steady, with a Reynolds number of approximately 100. The mass flow rate of the cross flow is known and the model is used to predict the flow and temperature fields that result from convective heat transfer. Due to symmetry of the tube bank and the periodicity of the flow inherent in the tube bank geometry, only a portion of the geometry will be modeled in ANSYS FLUENT, with symmetry applied to the outer boundaries. The resulting mesh consists of a periodic module with symmetry. In the tutorial, the inlet boundary will be redefined as a periodic zone, and the outflow boundary defined as its shadow. This tutorial demonstrates how to do the following: Create periodic zones. Define a specified periodic mass flow rate. Model periodic heat transfer with specified temperature boundary conditions. Calculate a solution using the pressure-based solver. Plot temperature profiles on specified isosurfaces.
4.2. Prerequisites
This tutorial assumes that you are familiar with the menu structure in ANSYS FLUENT and that you have completed Introduction to Using ANSYS FLUENT: Fluid Flow and Heat Transfer in a Mixing Elbow (p. 111). Some steps in the setup and solution procedure will not be shown explicitly.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
177
Chapter 4: Modeling Periodic Flow and Heat Transfer fluid flow. Their centers are separated by a distance of 2 cm in the The bank has a depth of 1 m.
Because of the symmetry of the tube bank geometry, only a portion of the domain needs to be modeled. The computational domain is shown in outline in Figure 4.1 (p. 178). A mass flow rate of 0.05 kg/s is applied to the inlet boundary of the periodic module. The temperature of the tube wall ( ) is 400 K and the bulk temperature of the cross flow water ( ) is 300 K. The properties of water that are used in the model are shown in Figure 4.1 (p. 178).
4.4.1. Preparation
1. Download periodic_flow_heat.zip from the ANSYS Customer Portal or the User Services Center to your working folder (as described in Preparation (p. 4) of Introduction to Using ANSYS FLUENT in ANSYS Workbench: Fluid Flow and Heat Transfer in a Mixing Elbow (p. 1)).
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
178
4.4.2. Step 1: Mesh 2. Unzip periodic_flow_heat.zip. The file tubebank.msh can be found in the periodic_flow_heat folder created after unzipping the file. 3. Use FLUENT Launcher to start the 2D version of ANSYS FLUENT. For more information about FLUENT Launcher, see Starting ANSYS FLUENT Using FLUENT Launcher in the Users Guide.
Note
The Display Options are enabled by default. Therefore, once you read in the mesh, it will be displayed in the embedded graphics windows.
a. b.
Select cm (centimeters) from the Mesh Was Created In drop-down list in the Scaling group box. Click Scale to scale the mesh.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
179
Chapter 4: Modeling Periodic Flow and Heat Transfer c. 4. Close the Scale Mesh dialog box.
Note
It is a good idea to check the mesh after you manipulate it (i.e., scale, convert to polyhedra, merge, separate, fuse, add zones, or smooth and swap.) This will ensure that the quality of the mesh has not been compromised. 5. Examine the mesh (Figure 4.2 (p. 180)).
Quadrilateral cells are used in the regions surrounding the tube walls and triangular cells are used for the rest of the domain, resulting in a hybrid mesh (see Figure 4.2 (p. 180)). The quadrilateral cells provide better resolution of the viscous gradients near the tube walls. The remainder of the computational domain is filled with triangular cells for the sake of convenience.
180
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
Extra
You can use the right mouse button to probe for mesh information in the graphics window. If you click the right mouse button on any node in the mesh, information will be displayed in the ANSYS FLUENT console about the associated zone, including the name of the zone. This feature is especially useful when you have several zones of the same type and you want to distinguish between them quickly. 6. Create the periodic zone. The inlet (wall-9) and outflow ( wall-12) boundaries currently defined as wall zones need to be redefined as periodic using the text user interface. The wall-9 boundary will be redefined as a translationally periodic zone and wall-12 as a periodic shadow of wall-9. a. b. Press < Enter> in the console to get the command prompt (>). Enter the text command and input the responses outlined in boxes as shown:
mesh/modify-zones/make-periodic
Periodic zone [()] 9 Shadow zone [()] 12 Rotational periodic? (if no, translational) [yes] no Create periodic zones? [yes] yes Auto detect translation vector? [yes] yes computed translation deltas: 0.040000 0.000000 all 26 faces matched for zones 9 and 12. zone 12 deleted created periodic zones.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
181
a. b.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
4.4.5. Step 4: Materials a. Click FLUENT Database... in the Create/Edit Materials dialog box to open the FLUENT Database Materials dialog box.
i.
Select water-liquid (h2o l ) in the FLUENT Fluid Materials selection list. Scroll down the list to find water-liquid (h2o l ). Selecting this item will display the default properties in the dialog box.
ii.
Click Copy and close the FLUENT Database Materials dialog box.
The Create/Edit Materials dialog box will now display the copied properties for water-liquid.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
183
b.
184
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
a. b.
Select water-liquid from the Material Name drop-down list. Click OK to close the Fluid dialog box.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
185
Chapter 4: Modeling Periodic Flow and Heat Transfer a. Select Specify Mass Flow in the Type list. This will allow you to specify the Mass Flow Rate. b. c. Enter 0.05 kg/s for Mass Flow Rate. Click OK to close the Periodic Conditions dialog box.
a. b.
Enter wall-bottom for Zone Name. Click the Thermal tab. i. ii. Select Temperaturein the Thermal Conditions list. Enter 400 K for Temperature. These settings will specify a constant wall temperature of 400 K.
c. 2.
Set the boundary conditions for the top wall of the right tube (wall-3). Boundary Conditions a. b. Click the Thermal tab. i. ii. c. Select Temperature from the Thermal Conditions list. Enter 400 K for Temperature. wall-3 Edit...
186
a. b. 2.
Retain the default setting of Least Squares Cell Based for the Gradient in the Spatial Discretization group box. Select Second Order Upwind from the Momentum and Energy drop-down lists.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
187
a. 3.
Enable the plotting of residuals during the calculation. Monitors Residuals Edit...
a. b. 4.
Make sure Plot is enabled in the Options group box. Click OK to close the Residual Monitors dialog box.
188
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
a. b.
Retain the default setting of 300 K for Temperature in the Initial Values group box. Click Initialize. The values shown in the task pane will be used as the initial condition for the solution.
5.
6.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
189
a. b.
Enter 350 for Number of Iterations. Click Calculate. The energy residual curve that is displayed in the graphics window will begin to flatten out as it ap proaches 350 iterations. For the solution to converge to the recommended residual value of , you need to reduce the under-relaxation factor for energy.
7.
8.
Continue the calculation by requesting another 300 iterations. Run Calculation After restarting the calculation, the plot of the energy residual will display an initial dip as a result of the reduction of the under-relaxation factor. The solution will converge in a total of approximately 610 iterations.
9.
Save the case and data files (tubebank.cas.gz and tubebank.dat.gz). File Write Case & Data...
190
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
a. b. c.
Enable Filled in the Options group box. Retain the default selection of Pressure... and Static Pressure from the Contours of drop-down lists. Click Display.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
191
d.
Change the view to mirror the display across the symmetry planes (Figure 4.4 (p. 193)). Graphics and Animations Views...
i.
Select all of the symmetry zones (symmetry-18, symmetry-13, symmetry-11, and symmetry24) in the Mirror Planes selection list by clicking on the shaded icon in the upper right corner.
192
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
Note
There are four symmetry zones in the Mirror Planes selection list because the top and bottom symmetry planes in the domain are each comprised of two symmetry zones, one on each side of the tube centered on the plane. It is also possible to generate the same display shown in Figure 4.4 (p. 193) by selecting just one of the symmetry zones on the top symmetry plane, and one on the bottom. ii. iii. Click Apply and close the Views dialog box. Translate the display of symmetry contours so that it is centered in the graphics window by using the left mouse button (Figure 4.4 (p. 193)).
The pressure contours displayed in Figure 4.4 (p. 193)do not include the linear pressure gradient computed by the solver. Thus, the contours are periodic at the inlet and outflow boundaries. 2. Display filled contours of static temperature (Figure 4.5 (p. 195)). Graphics and Animations Contours Set Up...
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
193
a. b.
Select Temperature... and Static Temperature from the Contours of drop-down lists. Click Display and close the Contours dialog box.
194
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
The contours in Figure 4.5 (p. 195) reveal the temperature increase in the fluid due to heat transfer from the tubes. The hotter fluid is confined to the near-wall and wake regions, while a narrow stream of cooler fluid is convected through the tube bank. 3. Display the velocity vectors (Figure 4.6 (p. 197)). Graphics and Animations Vectors Set Up...
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
195
a.
Enter 2 for Scale. This will increase the size of the displayed vectors, making it easier to view the flow patterns.
b. c. d. e.
Retain the default selection of Velocity from the Vectors of drop-down list. Retain the default selection of Velocity... and Velocity Magnitude from the Color by drop-down lists. Click Displayand close the Vectors dialog box. Zoom in on the upper right portion of one of the left tubes to get the display shown in (Figure 4.6 (p. 197)), by using the middle mouse button in the graphics window.
The magnified view of the velocity vector plot in Figure 4.6 (p. 197) clearly shows the recirculating flow behind the tube and the boundary layer development along the tube surface.
196
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
4.
This isosurface and the ones created in the steps that follow will be used for the plotting of temperature profiles. Surface Iso-Surface...
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
197
Chapter 4: Modeling Periodic Flow and Heat Transfer a. b. c. d. 5. 6. 7. Select Mesh... and X-Coordinate from the Surface of Constant drop-down lists. Enter 0.01 for Iso-Values. Enter x=0.01m for New Surface Name. Click Create.
In a similar manner, create an isosurface on the periodic tube bank at the two columns of tubes) named x=0.02m.
In a similar manner, create an isosurface on the periodic tube bank at = 0.03 m (through the middle of the second column of tubes) named x=0.03m, and close the Iso-Surface dialog box.
Create an XY plot of static temperature on the three isosurfaces (Figure 4.7 (p. 200)). Plots XY Plot Set Up...
a.
Enter 0 for X and 1 for Y in the Plot Direction group box. With a Plot Direction vector of (0,1), ANSYS FLUENT will plot the selected variable as a function of . Since you are plotting the temperature profile on cross sections of constant , the temperature varies with the direction.
b. c.
Select Temperature... and Static Temperature from the Y-Axis Function drop-down lists. Select x=0.01m, x=0.02m, and x=0.03m in the Surfaces selection list. Scroll down to find the x=0.01m, x=0.02m, and x=0.03m surfaces.
d.
Click the Curves... button to open the Curves - Solution XY Plot dialog box. This dialog box is used to define plot styles for the different plot curves.
198
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
i.
Select + from the Symbol drop-down list. Scroll up to find the + item.
= 0.01 m curve. Set the Curve # to 1 to define the style for the = 0.02 m curve.
Click Apply to assign the + symbol to the Select x from the Symbol drop-down list. Scroll up to find the x item.
v. vi.
Enter 0.5for Size. Click Apply and close the Curves - Solution XY Plot dialog box. Since you did not change the curve style for the
e.
Release 13.0 - SAS IP, Inc. All rights reserved. - Contains proprietary and confidential information of ANSYS, Inc. and its subsidiaries and affiliates.
199
4.5. Summary
In this tutorial, periodic flow and heat transfer in a staggered tube bank were modeled in ANSYS FLUENT. The model was set up assuming a known mass flow through the tube bank and constant wall temperatures. Due to the periodic nature of the flow and symmetry of the geometry, only a small piece of the full geometry was modeled. In addition, the tube bank configuration lent itself to the use of a hybrid mesh with quadrilateral cells around the tubes and triangles elsewhere. The Periodic Conditions dialog box makes it easy to run this type of model with a variety of operating conditions. For example, different flow rates (and hence different Reynolds numbers) can be studied, or a different inlet bulk temperature can be imposed. The resulting solution can then be examined to extract the pressure drop per tube row and overall Nusselt number for a range of Reynolds numbers.
200