CT Sizing
CT Sizing
CT Sizing
Agenda
Current Transformer (CT) introduction Mathematical Modeling Saturated Waveforms CT saturation (Hysteresis Curve) Remnant Flux, High Fault Currents, DC offset Saturation Voltage, CT ratings, Selection and Applications ElectroMagnetic Transients Program (EMTP)/ PSCAD
Introduction CT types
Donut Hall Effect CT Magneto-Optical
Bus Bar
Introduction Application
Current Transformers (CTs) are instrument transformers that are used to supply a reduced value of current to metering, protective relays, and other instruments. CTs provide galvanic isolation from the high voltage primary, permit grounding of the secondary for safety, and step-down the magnitude of the measured current to a value that can be safely handled by the instruments (high fault currents). To achieve the above goals CT contains
1) 2) 3) 4) Iron Core Secondary windings Primary conductor External insulation
CT Symbols
When current flows in the CT from the H1 lead polarity () lead through, the burden (load), and return to the secondary X2 non-polarity lead. The next half cycle the current will reverse.
ANSI
IEC
Electrical Schematic
3D-Representation
CT Connections
Available in Maximum Ratio Error Classes of: 0.3%, 0.6%, 1.2%, 2.4% For Burdens (Loads) of: 0.1, 0.2, 0.5, 0.9, 1.8 Volt-amperes (va) equivalent: 2.5va, 5.0va, 12.5va, 22.5va, 45va Typical Number 0.3 B 0.2
Burden
Ohms (Burden)
Available secondary voltages: 100V, 200V, 400V, 800V Burden support (ZSTD): 1.0, 2.0, 4.0, 8.0
CT Knee point
ANSI Method
CT Knee point
ANSI Method
IEC Method
CT Equivalent Circuit
Is
s
Ip
s
Ie
Hysteresis/Residual Flux
Referring to figure on the left, if H is gradually increased from zero to H1, the magnetization follows path oa. Decreasing H back to zero will leave the material magnetized at a B-value corresponding to point b. Distance ob on the B axis is called the Residual Flux Density. To bring B back to zero requires a negative value of H corresponding to point c on the cure. Distance oc on the H-axis is called the Coercive Force. Decreasing H to H2=-H1 results in the B-value of point d. Finally increasing H back to the original H1 now causes the magnetization to traverse path defa. The latter path is nearly equivalent to path abcd, but flipped about the B and H axes. Path abcdefa is called a hysteresis loop which occurs when an AC voltage is applied to a coil on a ferromagnetic core. As the voltage and current cycle between their max and min values, the core magnetization repeatedly traverses a hysteresis loop.
DC offset
Saturation Occurs
CT Errors impact
Errors to in currents magnitude and angle will have a significant effect on protection relays particularly (directional (67), distance (21), and differentials (87))
vdt !
0
2I F (Z B
RS )(cos [t e
R t L
)dt !
X ! 2 I ( Z RS )1 R X ! 2 I F Z B 1 R X ! I F Z B 1 R
Vgh _ max
Vgh _ max 2
X ! I F Z B 1 R
VSTD ! 20 I N Z STD
X I F Z B 1 e 20 I N Z S R
IF ZB I N Z STD
X 1 e 20 R
To Avoid CT saturation
IF ZB I N Z STD X 1 e 20 R
X 1 I f Z b e 20 R
I F ! Max Fault Current Z B ! Burden from the CTs point of view (CTwdg + Cable Leads + Relays) I N ! CT primary rating if IF is given in primary Amps or ! CT secondary rating if IF is given in secondary Amps
Z STD !
If !
Standard Burden = 1, 2, 4, 8 (at 60) Max Fault in per unit of CT secondary nominal Current Burden in per unit of standard burden
Zb !
X I f Z b e 20 1 R
X I f Z b e 20 1 R
X 1 I f Z b e 20 R
Time to Saturate
s
K s 1 ! 1 ln1 X R
X 1 ! [R
Ts ! time to saturate ln ! Natural log function T1 ! primary system time constant K s ! the saturation factor Vx/Vs, where Vx is the excitation voltage at
10A and, Vs is the saturation voltage IF x ZB
[ ! 2f, where f is the system frequency X ! Reactance of the primary system to the point of the fault R ! Resistance of the primary system to the point of the fault
Waveforms
Waveforms
Multi-Ratio CTs
1200/5, C800 tapped at 600/5 C400 effective rating 4.0 effective standard burden
CT winding Resistance
Typical turn ratio resistance = 2.5m/turn For example a 2000:5 ratio CT; 2000 / 5 !
2000 2 .5 m ; ! 1 .0 ; 5
CT Application
Type of Fault Connection Wye (connect at CT) Wye (connected at switchhouse) Delta (connected at switchhouse) Delta (connected at CT) 3 ph or ph-to-ph Z = RS + RL + ZR Z = RS + 2RL + ZR Z = RS + 2RL +3 ZR Z = RS + 3RL +3 ZR Ph-to-ground Z = RS + 2RL + ZR Z = RS + 2RL + ZR Z = RS + 2RL +3 ZR Z = RS + 2RL +2 ZR
Z is the effective impedance seen by the CT RS is the CT secondary winding resistance and CT lead resistance; also includes any relay impedance that is inside the delta connection () RL is the circuit one-way lead resistance () ZR is the relay impedance in the CT secondary current path ()
KVAshortcircu it ! 3 240 kV 7316 A ! 3,041,204.09 kVA % Z source ! 50,000kVA / 3,041,204.09kVA x100 ! 1.644%
X 5 ! tan R
1
X ! Sin5 * Z R ! Cos5 * Z
%Zsource ! 1.644
X / R ! 12
5 ! tan 12
! 85.24
1 S
% Z xmfr ! 8 . 0
X / R ! 15
5 ! tan 1 15
! 86.19
X ! Sin(86.19) * (8.0%) ! 7.982% R ! Cos(86.19) * (8.0%) ! 0.531%
Rtotal ! Rsource Rxmfr ! 0.138 % 0.531 % ! 0.669 % X total ! X source X xmfr ! 1.638 % 7.982 % ! 9.62%
Step #5: X/R at138kV
KVAshortcircu it ! 3 240 kV 7316 A ! 3,041,204.09 kVA % Z source ! 50,000kVA / 3,041,204.09kVA x100 ! 1.644%
FLA LV !
kVA xmfr 3 kV LL
FLA LV
SCC LV
SCC LV
Global Example
C200 400/5 (full ratio) IF = 7,316A (HV side) X/R = 15 (HV side faults) One-way RL length = 152m (500) Determine what CT Class and Ratio is valid on the 138kV 240kV 138kV
Global Example
Case #1) From previous slide for X/R and SCC on the 138kV side.
X X 9 . 622 % ! total ! ! 14 . 4 R R total 0 . 669 %
Zb !
1 .3 ; ZB ! ! 0 . 7 pu 2 .0 ; Z STD
Global Example
From previous slide for X/R and SCC on the 138kV side.
SCC LV !
If !
2 ,169 A IF ! ! 5 . 5 pu 400 A IN
X 1 I f Z b e 20 ? R
CT Saturates
Global Example
K s 1 Ts ! T1 ln1 X R
T1 !
Global Example
Case #2 Choosing C400 (2000/5 tapped at 600/5).
600 4 ; ! 1 .2 ; 2000
ZB = 1.4 due to 600/5 ratio CT winding resistance.
Zb !
If !
X 1 I f Z b e 20 ? R
CT Saturates
Global Example
K s 1 Ts ! T1 ln1 X R
T1 !
Vx ! 150V
Ks !
Global Example
Case #3 Choosing C400 (2000/5 full ratio).
If !
X 1 I f Z b e 20 ? R
CT OK
Global Example
Case #4 Choosing C400 (2000/5 full ratio with 80% remenant flux).
X 1 I f Z b e 20 * (1 80 %) ! 4 ? R
CT Saturates
Case #4 Choosing C400 (2000/5 full ratio with 50% remenant flux).
X 1 I f Z b e 20 * (1 50 %) ! 10 ? R
CT OK
Vs
mfgr's data log-log plot, equal decade spacing
slope = 1/S
Ve volts rms
Ie
amps rms
10
Measuring the S
HOW TO MEASURE THE SLOPE Use a ruler to determine the slope. Do NOT read currents or voltages for this purpose. (We assume equal decade spacing of the axes)
10 0 1 2 3 4 5 6 7 8 9
EMTP/PSCAD SIMULATION
The CTs are subject to saturation during DC transient of fault current , hence there is growing interest in simulations like EMTP/PSCAD. The IEEE-PSRC CT calculator is only accurate at high fault currents and burden , hence to get better idea of CT performance at low fault currents/ burden we need to model in PSCAD/EMTP. The primary aim of PSCAD simulation is to obtain digitized records, which can be recognized as secondary analog signal using D/A conversion and amplification, for the purpose of relay testing.
EMTP/PSCAD SIMULATION
QUESTIONS?