PT 100 Manual
PT 100 Manual
PT 100 Manual
2.0
4.1 Mechanical The TX203P transmitter has been specifically designed to fit inside a DIN standard probe head enclosure (such as the SCH-4 series), which provides adequate protection from moisture, dust, corrosive atmosphere etc. All cable entries must be sealed using the correct size gland. Likewise any probe assembly fitted must be sealed. Care must be taken when locating the transmitter to ensure the working ambient temperature range of (-40 to 85) C is not exceeded. The TX203P enclosure has a centre hole allowing the sensor wired to enter screw terminals from the transmitter centre, this is applicable when the sensor is mounted directly below the transmitter. 4.2 Electrical Electrical connections to the transmitter are made to the screw terminal provided on the top face. The sensor wires must be equal length and type for the lead compensation to work correctly. The screw terminals allow for wires to enter either inner or outer direction. The transmitter is protected against reverse connection and over voltage. If no sensor (input) connection is made the transmitter will go into either up or down scale output current, depending on configuration. Figure 2 gives connection details, the output is shown connected to a 24 V supply. The load symbol represent any other device connected in the loop, such as Monitoring equipment , panel indicators and loop isolators. The load value can range from 0 ohms to the max loop load for given supply, refer to section 3 Max load for more information. The transmitter conforms with EC directive BS EN 61326 : 1998 when correctly installed in a termination head providing at least IP20 protection and with sensor wires less than 3 metres. Screened or twisted pair wires are recommended for output wires. Always ensure the (4 to 20 ) mA loop is grounded at one point, this would normally be at the monitoring equipment or loop power supply. In normal operation the program LED acts as over-range LED. Figure 2
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately. 3.0 SPECIFICATION @ 20 C PT100 100 R @ 0C 2 or 3 Wire (-200 to +850) C (18 to 390) Screw terminal 25 C BS EN 60751(IEC 751) standard / JISC1604 0.1 C0.05% of Reading 0.0025 % / C < 200 uA 0.002 C/ 20 per leg
INPUT Sensor Type Sensor Range Sensor Connection Minimum span (see note 1) Linearisation Accuracy (see note 2) Thermal Drift Excitation current Lead Resistance effect Maximum lead Resistance Note 1
Global Measurement & Control Derwent Street, Long Eaton, NG10 3LP Tel: +44 (0)115 946 7441 Fax: +44 (0)115 946 7442 Email: [email protected] Every effort has been taken to ensure the accuracy of this specification, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice
Note 2 OUTPUT Type Limits Accuracy Loop Effect Thermal Drift Max Load GENERAL Update Time Response Time Start up time Filter Factor Ambient Temperature Connection Approvals Factory Default 4.0
Any span may be selected, full accuracy is only guaranteed for spans greater than the minimum recommended span. Basic measurement accuracy includes the effects of calibration, linearisation and repeatability Two wire (4 to 20) mA sink Low 3.8 mA ; high 21.5 mA (mA out / 2000) or 5 uA which ever greater 0.2 uA / V measured @ 50 Hz 1 V (peak to peak) 1 uA / C typical ; 1.5 uA Max [ (Vsupply 10)/20 ] K 0.5 Seconds 1 Second to reach 90% of final value From power up typically 5 Seconds Adaptive (-40 to 85) C Screw Terminal BS EN 61326 ; 1998 Electrical equipment for measurement and control ANNEX A ; ANNEX F (0 to 100) C upscale burnout (0.0 C user trim)
White
Pt 100 U
Red
Power Supply
-
SIDE VIEW
BASE VIEW
Red
Load
43.0 mm 1.0 DESCRIPTION 33.0 mm CENTRES The TX203P head mounted temperature transmitter connects to any standard pt100 resistance sensor and converts the linearised temperature to a (4 to 20) mA signal. The transmitter is a two wire device, and is fully configurable by the user, over a wide temperature range, with the aid of a simple push button. This new TX203P design incorporates additional configuration menus, allowing the user to push button trim the transmitter output at both zero and span, ideal for trimming out sensor errors. The transmitters advanced circuitry guaranties high stability over the wide operating ambient temperature ranges experienced by head mounted devices. One of the transmitters features is the program LED, which provides visual indication of sensor fault when in normal operation and is also used to guide the operator through the simple menus during configuration.
21.0 mm
Figure 1
Mounting holes : two holes 5.5 mm diameter, 33 mm centres Centre Hole sensor wire entry : 4 mm
5.0 USER CONFIGURATION IMPORTANT READ COMPLETE SECTION BEFORE ATTEMPTING CONFIGURATION PARTICULAR CARE SHOULD BE TAKEN REGARDING TIMEOUTS IN MENU 2 & 3 Using Menus Menu 1 Range configuration (No Timeout) Menu 3 User trim (Timeout is 20 Seconds) This menu allows the user to trim the output current at 4 mA and 20 mA points, (similar function to trim potentiometers) and is very useful for trimming out sensor errors. The input of the transmitter must be connected to either a calibrator or a temperature sensor held at a known temperature. The (4 to 20) mA loop current will also need to be monitored with a current meter. Refer to figure 3, connect sensor or resistance box to TX203P input terminals using three wire connection. Connect output to a DC supply, observe polarity, connect current meter in series with loop. Turn power on and allow 1 minute warm up period. Set calibrator to the equivalent resistance of the pt100 sensor, at required trim point. Alternatively ensure sensor temperature is at the required calibration point. The transmitter will automatically trim the 4 mA end if the output is within the active band of (3.8 to 6 ) mA, and trim the 20 mA end if the output is within the active band of (18 to 21.5 ) mA . No setting adjustment is performed if the output current is not within these two bands. Ensure your calibration points are within these bands. Press and hold button > 2 seconds to enter menus, menu 1 will then be selected, indicated by one flash every burst. Single press button to advance selection to menu 2, and single press again to select menu 3 indicated by three flashes of the program LED every burst. Whilst menu 3 is selected, press and hold button > 2 seconds to enter menu 3, at which stage the program LED toggle on and off at either a slow rate indicating downward trim direction or fast rate indicating upwards trim direction. To change trim direction double press button. The Program LED toggle rate will toggle to the opposite direction. Repeated double presses will toggle between up and down trim direction To trim output current, single press button to advance current 2 uA in set direction, or press and hold button to auto advance in set direction release button to stop advance. Note after approximately 20 seconds of continuous button press, the auto trim rate will speed up. Monitor the current change on the current meter. To store new setting allow 20 seconds with no button action, the program will then timeout, store new setting then return to normal operation.
+
Program Button Power Supply (10 to 30) VDC
Configuration will require the following tools and equipment : DC Supply (12 to 30) V @ 30 mA Precision resistance decade box to simulate PT100 sensor. Screw driver flat blade 3mm wide PT100 resistance tables Current meter (user trim)
+
Calibrator precision resistance source Burnout / Program LED
To re-range the temperature scale follow the following instructions: Refer to figure 3, connect resistance box to TX203P input terminals using three wire connection. Connect output to a DC supply, observe polarity. Turn power on and allow 1 minute warm up period. Set calibrator to the equivalent resistance of the pt100 sensor, at required low range temperature. If the program LED is on at this stage the input is out of range, check resistance and connection. Press and hold button > 2 seconds to enter menus, menu 1 will then be selected, indicated by one flash every burst. Whilst menu 1 is selected, press and hold button > 2 seconds to enter menu 1, at which stage the program LED toggle on and off at a slow rate. Allow ten seconds then single press button to store low range setting, the program LED will now flash at a fast rate. Set calibrator to the equivalent resistance of the pt100 sensor, at required high range temperature and allow ten seconds. Press button to store high range setting, the program LED will flicker for one second before the transmitter returns to normal operation. The transmitter is now re-ranged.
Figure 3 Configuration circuit User Configuration User configuration uses three menus, each menu sets a different parameter:Menu 1 Menu 2 Menu 3 Set range Set direction of output on sensor burnout User trim at 4 mA and 20 mA. = Advance = Escape or change direction = Enter
The configuration menus are navigated using the push button and program LED, The push button is located under the hole in the keyhole shaped wiring label. To press the button use a 3 mm screw driver (flat blade) inserted into the hole. The button has a slight click action. Three types of button press are used: Single button press Double press within 0.5 seconds Press and hold button > two seconds
Menu 2 Burnout Selection (Timeout is 3 Seconds) Refer to figure 3, Connect output to a DC supply, observe polarity. For this menu the input can be connected or open circuit. Turn power on. Press and hold button > 2 seconds to enter menus, menu 1 will then be selected, indicated by one flash every burst. Single press button to advance selection to menu 2, indicated by two flashes of the program LED every burst. Whilst menu 2 is selected, press and hold button > 2 seconds to enter menu 2, at which stage the program LED will either toggle on and off at a slow indicating low scale burnout or fast rate indicating upscale burnout. To change burnout direction single press button. The Program LED toggle rate will change to the other setting. Repeated single presses will toggle between up and down scale. To store setting allow 3 seconds with no button action, the program will then timeout, store new setting then return to normal operation.
When a menu is selected the Program LED will flash in bursts of one to three flashes, the number of flashes represents the menu number. Navigating the menus To access menus, press and hold button > 2 second, then program LED will start to flash, one flash every burst. This Indicates menu 1 is selected. Use single button press to advance selection to menu 2, the program LED will now show two flashes per burst. The Next single presses will advance the selected menu to menu 3 and the next single press will advance selected menu back to menu 1. Repeated single presses will cycle the selected menu back around menus 1 to 3, in the above sequence. Double press button to escape from menus, and return to normal. Normal operation can also be selected by turning transmitter power off and on. Note the transmitter will not time out and automatically escape from menus.
Reset to factory default settings If required the TX203P can be reset to factory default setting, this procedure also removes any user trim adjustment. Factory default settings are : Range Burnout User trim (0 to 100) C up-scale All user adjustment cleared
To reset to factory setting, hold the button down whilst the TX203P is power up.