Evolution S
Evolution S
Evolution S
UPS
Eaton Evolution S
1250/1750/2500/3000 VA
Line interactive
High density protection for network devices
Maximum availability
Powershare: the Eaton Evolution S output sockets are individually controlled to provide load-shedding to maximise the backup time and provide remote reboot and sequential start-up as standard ontinuous power supply: Hot swappable batteries. C The optional HotSwap MBP (Maintenance By-Pass) module allows the UPS to be replaced without interrupting the power supply ong backup times: 1 to 4 EXB battery units can be added to L the Evolution S ure sinewave output: when operating in batterie mode the P Eaton Evolution still provides high quality output signal for sensitive connected equipment
Eaton Evolution S
Line-interactive HF technology: the best price/performance ratio o additional cost: all models are provided with tower stands N and rail kits emote supervision: a wide range of options using the Eaton R Software suite, including point-to-point power management, SNMP , relay outputs, etc...
Totally flexibility
Evolution has unmatched Flexibility.
Advanced protection for: Rack servers Tower servers Network devices Storage systems
ormat: Evolution S is available in RT2U convertible rack/tower F version (optimised for rack mounting) or RT3U (for tower or short-depth racks) onnections: with FlexPDU and HotSwap MBP the Evolution S C can be connected by sockets or terminal blocks. They can be installed as required behind, on the side or on top of the unit ompatible with high power factor loads: the Evolution S C are rated for 0.9 total power factor (1250 VA/1150 W, 1750 VA/1600 W, 2500 VA/2250 W and 3000 VA/2700 W) ommunication: the Evolution S includes both serial and USB C ports, plus remote On/Off connector and an extra slot for optional communication cards. The UPS comes with a complete Eaton software suite.
1250/1750/2500/3000 VA
Full user interface: - ON/OFF button for UPS and outlets - Load protected/ not protected LED - Utilised power level/Battery charge level - Status of switchable outlets Panel for batteries replacement (Hot swappable) 1 USB port + 1 serial port + remote ON/OFF Eaton Evolution S 3000 RT2U Netpack EXB battery unit connector EXB units recognised automatically 8 IEC 10A sockets, including 4 programmable sockets Communication card slot
Technical Specifications
Rating (VA/W) Format
Electrical characteristics
Technology Input voltage and frequency ranges without using batteries Output voltage and frequency Line-Interactive High Frequency (Booster + Fader) 160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system), up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software. 230 V (+6/-10 %) (Adjustable to 200 V (10 % derating of output power) / 208 V / 220 V / 230 V / 240 V), 50/60 Hz +/- 0.1 % 1 IEC C14 (10 A) socket 8 IEC C13 (10 A) 1 IEC C14 (10 A) socket 8 IEC C13 (10 A) 1 IEC C20 (16 A) socket 8 IEC C13 (10 A) sockets 1 IEC C19 (16 A) socket 1 IEC C20 (16 A) socket 8 IEC C13 (10 A) sockets 1 IEC C19 (16 A) socket
Connections
Input Outputs Remotely controlled sockets Additional outputs with HS MBP Additional outputs with FlexPDU
2 groups of 2 x IEC C13 (10 A) 4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10 A sockets or terminal blocks (HW version) 8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10 A sockets
Batteries
Typical backup times for 50 and 70% load* Evolution S Evolution S + 1 EXB Evolution S + 4 EXB Battery management 20/14 mn 14/9 mn 17/11 mn 15/10 mn 105/60 mn 60/36 mn 85/55 mn 60/42 mn 300/200 mn 180/115 mn 290/200 mn 210/135 mn Automaticweeklytest(periodadjustable),automaticrecognitionofexternalbatteryunits=>continuousmaximisationofbackuptime + deep discharge protection 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously) + 1 mini terminal block for remote ON/OFF and Remote Power Off 1 slot for NMC Minislot card (included in Netpack versions) or NMC ModBus/JBus or MC Contacts/Serial 0 to 40C < 45 dBA < 45 dBA < 50 dBA < 50 dBA IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 EN 50091-2 class B (EMC), IEC/EN 62040-3 (Performance), IEC/EN 61000-4-2, 61000-4-3, 61000-4-4; 61000-4-5, 61000-4-6, 61000-4-8 (EMI) CE, CB report, TV 440 x 509 x 86.2 (2U) mm 24.3 kg 30.4 kg 440 x 509 x 86.2 (2U) mm 26.6 kg See UPS 30.4 kg 41.7 kg 41.7 kg 440 x 634 x 86.2 (RT2U) mm 440 x 634 x 86.2 (RT2U) mm 440 x 484 x 130.7 (RT3U) mm 440 x 484 x 130.7 (RT3U) mm 33.8 kg 33.8 kg (RT2U) - 34.3 kg (RT3U)
Interfaces
Communication ports Communications card slots
Dimensions W x H x D / Weight
Dimensions Weight of the Tower/Rack Dimensions of EXB Weight of the EXB
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers
Convertible Tower/Rack EXB Models
* NMC card included in Netpack versions.
S 3000 RT3U
In the interests of continuous product improvement all specifications are subject to change without notice. 2009 Eaton Corporation, All Rights Reserved, April 2009.