GOVERNMENT OF INDIA MINISTRY OF RAILWAYS

SPECFICATIONS FOR OUTDOOR 22/25 KV SP/DP/POLE MOUNTED VACUUM CIRCUIT BREAKER & INTERRUPTER FOR RAILWAY ac TRACTION SUB-STATIONS /SPs /SSPs/ 2x25KV AT FEEDING SYSTEM SPECIFICATION No. TI//SPC/PSI/LVCBIN/0120 ISSUED BY Traction Installation Directorate RESEARCH DESIGNS AND STANDARDS ORGANIZATION Manak Nagar, Lucknow-226011(India) (R.D.S.O.) GOVERNMENT OF INDIA MINISTRY OF RAILWAYS LUCKNOW 226 011

Page 2 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

ANNEXURES & APPENDIX ANNEXURE-A ANNEXURE-B ANNEXURE-I ANNEXURE-II ANNEXURE-III ANNEXURE-IV ANNEXURE-V ANNEXURE-VI SCHEDULE OF GUARANTEED PERFORMANCE TECHNICAL AND OTHER PARTICULARS. INFORMATION TO BE FURNISHED BY MANUFACTURER / SUPPLIER. DRAWING FOR GENERAL SCHEME OF POWER SUPPLY FOR TRACTION SUB-STATIONS. DRAWING NO.ETI/PSI/702 (MOD. B) TERMINAL CONNECTOR DRAWING NO. ETI/PSI/11060.(MOD. E) TERMINAL CONNECTOR DRAWING NO. ETI/PSI/11030.(MOD. C) DRAWING NO. ETI/PSI/SK/5214 INTERLOCKING SCHEME FOR 25kV CB. DRAWING NO. ETI/PSI/ 5212 (MOD. B) (FOR 132Kv INTERLOCKING SCHEME). DRAWING NO. ETI/PSI/SK/334 LOCK & KEY FOR 25kV CB.

Page 3 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

22/25 KV OUTDOOR VACUUM CIRCUIT BREAKER & INTERRUPTER For RAILWAY ac TRACTION SUB-STATION/SPs /SSPs/ 2x25KV AT FEEDING SYSTEM 1. 1.1 Scope This specification applies to Outdoor Type Single Pole, Double Pole & Pole Mounted Vacuum Circuit Breakers and Interrupters for use in Unattended / attended Railway Traction Sub- Stations / SPs / SSPs in any part of India for controlling Power Supply to the 25kV ac 50 Hz Single Phase/ 2 X 25kV AT Feeding System for Traction Overhead Equipment (OHE).The following Specification supersedes:Sl.No. (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) ETI /PSI /139 (12/89)with A&C Slip No.1-4 ETI / PSI /159 ( 10 / 94 TI /PSI/93(5/94) ETI/PSI/46(9/94 ETI PSI 131(8/89) ETI/PSI/132 (8/ 89) Specification No ETI / PSI /167 ( 9/ 97 ) with A&C Slip 1-2 TI/SPC/PSI /CB/0000 with A&C Slip 1-5 TI /SPC / PSI/ ACINT/0040 Description 25kV, SP Outdoor Interrupter Outdoor Circuit Breakers 25KV,SP Outdoor Vacuum Interrupter with Magnetic Actuated Operating Mechanism 25kV, SP SF6 Circuit Breaker 25kV, SP Vacuum Circuit Breaker 25KV,DP, Outdoor SF6 Circuit Breaker for 2x25 KV AT Feeding System 25KV, DP Outdoor Vacuum Interrupter for 2x25 KV AT Feeding System 25KV,DP, Outdoor SF6 Interrupter for 2x25 KV AT Feeding System 25KV, SP Outdoor Pole Mounted Vacuum Interrupter

Page 4 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

This specification shall also apply for 2 X 22 kV two poles VCB for Mumbai Area of Central and Western Railway ac Traction System. 1.2 The Circuit Breaker / Interrupter shall be complete with all parts, fittings, Vacuum Bottle and accessories necessary for its efficient operation, including Mounting Frame work of steel. All such parts, fittings and accessories shall be deemed to be within the scope of this specification, whether specifically Mentioned or not. The CB /Interrupter shall be proven design. The Circuit Breaker / Interrupter shall be erected by the Purchaser / Indian Railways. However, in case a defect / deficiency are noticed, the manufacturer / successful tenderer will have to depute his Engineer for necessary remedial action without any cost to the Railways. In all the cases in which an order is placed either on new Manufacturer or for a new type/ design of the Circuit Breaker / Interrupter , the services of Manufactures Engineer shall be made available free of cost during the erection and proving / pre-commissioning test for the first order of their Circuit Breaker / Interrupter. For this purpose, prior intimation regarding the date and the location shall be given by the purchaser to the successful tenderer / manufacturer. Governing Specification The CB / Interrupter shall unless otherwise specified herein, conform to the IEC 62271-100, IEC600694, IEC 600265-II High Voltage ac Circuit Breaker / Interrupter and the Indian Electricity Rules, wherever applicable. In the preparation of this specification, assistance has been derived from the following Standards: SL.No. (1) (2) (3) (4) (5) (6) IS/IEC/RDSO Specification IEC: 62271-100 IEC: 60694(1980) IS: 456(1978) IS: 996(1979 IS: 2099(1973) IS: 2544(1979) Description High voltage alternating current circuit breakers Common clauses for high voltage Switchgear and Control gear Standards. Code of Practice for plain and reinforced Concrete. Specification for single phase small ac and Universal Electric Motors. Specification for bushing for alternating Voltages above 1000V Specification for Porcelain Post Insulators for System with nominal voltages greater

1.3

2.0 2.1

2.1.1

Page 5 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

(7) (8) (9)

IS: 5561(1978) IS: 5621(1980) IS:6875(Pt.I-1973)

(10) (11) (12) (13) 14)

IS: 7906(Pt. I-1976) IS: 7907(Pt. I-1976) IS: 13118(1991) IS: 1554(Pt. V-1988 IS: 808(1989)

Than 1000V. Specification for Electric Power Connectors. Specification for hollow insulators for Use In Electric equipment. Specification for Control Switches (Switching Device Control and Auxiliary Circuits including contactor Relay) for Voltages up to and including 1000V ac and 1200dc-General requirements and Tests Specification for Helical Extension Springs Specification for Helical Extension springs Specification for high voltage alternating Current Circuit Breakers. Specification for PVC Insulated (heavy duty)Electrical Cables for working Voltage Up to including 1100V. Dimension for hot rolled steel beam, Column Channel and angle sections. Degree of protection provided by Enclosures for low voltage switchgear For Hot Dip Galvanization For Steel and Stainless Steel Bolts,Nuts and Washers For Epoxy Bases Zinc Phosphate Primer (Two Pack) For Aluminum paints based on Polyurethane High Voltage Switches for rated voltage of 52 kV and above Specification for alternating current Switches above 1000 V Method of Testing uniformity of Zinc Coated articles (Issued in 1994)

(15) (16) (17) (18) (19) (20) (21)

IS: 2147(1962) RDSO Specification NO.ETI/OHE/13(4/84) RDSO Specification No.ETI/OHE/18(4/84) RDSO Specification No. M&C/PCN-102/86 RDSO Specification No. M&C/PCN-110/88 IEC:265-II IS 9920

(22) (23)

IS 2633 (1972 AC Traction manual

Page 6 of 67
2.2

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Any deviation from this specification as proposed by the tenderer to improve upon the performance, utility and efficiency of the Equipment will be given due consideration, provided full particulars of the deviation with justification thereof are furnished; subject to approval of RDSO. In case of any contradiction between the provision of the Indian Standards Specification/ IEC standards and this specification, the latter shall prevail. This Specification is framed merging the four RDSO Specification are as under: Sl.No. Specification No. (i) ETI / PSI /167 ( 9/ 97 ) A&C Slip 1-2 (ii) TI/SPC/PSI /CB/0000 with Slip 1-5 (iii) ETI/PSI/ 132 (8/89) with Slip 1-4 (iv) ETI/PSI/ 159 (10 /94) A&C Slip No.1 Description with 25kV, SP Outdoor Interrupter A&C Outdoor Circuit Breakers ( only 25kV, SP /DP portion ) A&C 25 kV, DP Vacuum Interrupter with 25 kV Single Pole Outdoor Pole Mounted Vacuum Interrupter

2.3

Hence the firms approved as per any of the above specifications (four), shall be considered as approved as per this specification also. The changes are with respect to merging of the above mentioned four specifications, elimination of SF6 CBs and Interrupters in 25 kV class, updation of certain clauses as required in line with the relevant RDSO specifications, A&C slips of the above specification, relevant clauses of IS and IEC and modifications wherever required for standardising the specification of Low Voltage Switchgear, viz. Outdoor Type 25kV Vacuum SP /DP / Pole Mounted versions of CBs and Interrupters. 3.0 3.1 3.1.1 Traction Power Supply General Scheme The Single Phase 50Hz Power Supply for Railway Traction at 25kV is obtained from 220/132/110/100/66/22kV three phase grid system through a step down/ step up single phase Power Transformer, the primary winding of which is connected to two of the phase of the three phase effectively earthed transmission line network of the State Electricity Board. The primary voltage of the Traction Transformer being 220kV or 132kV or 110kV or 100kV or 66kV or 22kV and no load secondary voltage being 27kV. In order to reduce the imbalance on the three-phase grid system, the two phases of the three phase transmission line are tapped in a cyclic order for feeding the successive traction sub-

Page 7 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

stations (TSS). The distance between adjacent TSS is normally between 50km and 80km depending upon density of traffic, gradients in the sections and other factors. 3.1.2 One terminal of the 25 kV secondary winding of the traction transformer is connected to the OHE through circuit breaker/interrupters and the other terminal is solidly earthed and connected to the appropriate traction rail(s).The current flows through the OHE, to the locomotives and returns through the rails and earth to the TSS .In sections where booster transformers and return conductors are provided the current returns through Booster Transformers; the Traction Rail(s)and partly through earth in the vicinity of TSS. Approximately midway between two TSS a dead zone known as Neutral Section or Phase break is provided t separate the two sections of OHE fed by different phases. The power fed to the OHE on one side of the TSS is controlled by feeder circuit breakers while the power fed to the OHE of each track is controlled by an interrupter. Incase of a fault on the OHE, the feeder circuit breaker trips to isolate the faulty OHE.A schematic diagram No.ETI/PSI/702 (Mod. B) Showing the general arrangement at a TSS is at appendix 1. TRACTION POWER SUPPLY SYSTEMS (2x25kV AT Feeding System) General Scheme The electric power for railway traction is supplied in ac 50Hz, single phase through 2x25kV AT feeding system, which has a feeding voltage form the substation two times as high (2x25kV) as catenary voltage (25kV) this high voltage power supply from the traction substation through catenary wire and feeder wire is step down to the catenary voltage by use of autotransformers installed about every 13 to 17 km along the tract and then fed to the locomotives. In other words both the catenary voltage and feeder voltage are 25kV against the rail, although the substation feeding voltage between the catenary voltage and feeder is 50kV. Therefore the catenary voltage is same is that of the conventional 25kV system. Since the power is supplied in two times higher voltage, 2x25kV AT feeding system is suitable for a large power supply, and it has the following advantages compared with conventional feeding systems: a) Less voltage drops in feeder circuit. b) Large spacing of traction substation.

3.2 3.2.1

Page 8 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

c) Less telecommunication interference by use of AT Installed with adequate spacing. The power is obtained from 220/2x25 kV Scott connected traction transformer or 132/2x25kv single phase transformers. The primary windings of the single phase transformers are connected to 2 or 3 phases of 132kv three phase effectively earthed transmission network of the electricity board, in case of a single phase transformer or in case of the single phase transformers connected in V, respectively. On the other hand, the primary windings of the Scott connected transformers are connected to the three phases of 220kv Three phase, effectively earthed transmission network of the electricity board .The Scott-connected transformer and V-connected single phase Transformers are effective in reducing voltage unbalance on the transmission network of the electricity board. The spacing between the adjacent substations is normally between 70-100kms. One outer side terminal of the secondary windings of traction transformer is connected to the catenary, the other outer side terminal being connected to the feeder. Two inner side terminals are, via series capacitors or directly, connected to each other, and their joint is solidly earthed and connected to the running rails. The load current from the substations flows through the catenary and returns to the substation through the feeder. Between two adjacent ATs, the load current fed from catenary to the locomotive flows in the rail and is boosted up to the feeder through the neutral tap of ATs at left and right sides of the locomotive. At the points of the substations and sectioning posts, a dead zone known as neutral section is provided in OHE to avoid a wrong phase coupling. The power to the catenary and feeder on one side of the substation is fed by one feeder circuit breaker, even if there exists two breakers for one side, and each track is controlled by an interrupter. The two breakers are used as a standby for each other. For maintenance work and keeping the voltage drop within limits, one or more sub sectioning or paralleling posts(known as SSP) are introduced between the traction substations and a sectioning and paralleling post(Known as SP).A SSP on a double track section normally has four sectioning interrupters for each feeder circuit

Page 9 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

and one paralleling interrupter. In case of fault , feeder circuit breaker of the substation isolates it. A figure showing the principle of AT feeding system and a typical power supply diagram showing the general feeding arrangement at a traction substation and sections of the OHE are given in the sketch at the appendix-1and appendix-11. 3.3 3.3.1 Nature of Faults on the OHE OHE is prone to frequent earth faults caused by failure of insulation or by snapping and touching the rail/earth or by a piece of wire dropped by birds which connects the OHE to earth at over line structures/supports or by miscreant activities. The sections of OHE fed by different phases are sometimes in inadvertently bridged causing wrong phase coupling. Protection Scheme The faults in the OHE are isolated by the feeder circuit beaker which operates through either one or more of the following relays: (i) (ii) (iii) (iv) 3.4.2 Distance mho relay Instantaneous over- current relay Wrong phase coupling relay and High speed inter tripping relay

3.3.2 3.4 3.4.1

The faults in the traction transformer are isolated by one of the Following relays: (i) (ii) . (iii) (iv) Differential relay IDMT over current relays for the primary (HV) as well as for the secondary (LV) side Instantaneous earth leakage relays on the primary (HV) as well as for the secondary (LV) side. Auxiliary relays for transformer faults ie.Buchholz,excessive winding and oil temperature trip and alarm and low oil level alarm

Page 10 of 67
3.4.3

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The faults in the shunt capacitor bank are isolated by one of the following Relays: (i) Over current relay

(ii) Over voltage relay (ii) Under voltage relay (iv) Neutral current relay 3.4.4 In the event of the 25kV feeder as well as Transformer Circuit Breakers Failing to operate under fault conditions, the Circuit Breakers on the Primary side of the Transformer operates to Isolate the fault. Short circuit level The fault level for different grid Supply Voltages based on a three Phase symmetrical short circuit fault is between 1000 MVA and 10,000 MVA Depending upon the proximity of the Traction Sub- Station to the Generating Station. The fault level is 550 MVA at 25kV & 1000 MVA at 22KV at the Vicinity of Traction Sub- Station. Nature of load on 25 kV systems The traction load is of frequent and rapidly varying nature and fluctuates between no load and over loads. The load cycle varies from day to day due to non-uniform pattern of traffic. An AC electric locomotive is fitted with single phase bridge connected silicon Rectifier with smoothening reactor for conversion of ac to dc for feeding the dc traction motors. The ripple content is in the region of 25 to 40% which introduces harmonics in the 25kV power supply. The typical percentages of harmonics present in the traction current are as follows: Sl. No (i) (ii) (iii) (iv) (v) Detail With Rectifier With Thyristor 23 % 14 % 10 % 4% 3% With GTOs 3% 2% 0.5% 0.35% 0.40%

3.5 3.5.1

3.6 3.6.1

3.6.2

3rd harmonic (150 Hz) 15 % th 5 harmonic (250Hz) 6% 7th harmonic (350 Hz) 4% 9th harmonic (450 Hz) --11th harmonic (550 --Hz)

Page 11 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Total distortion 3.6.3 3.6.4

harmonic

16.64%

29.15%

3.68%

The average power factor of electric locomotive and multiple units Trains generally vary between 0.7 and 0.8 lagging without Compensation. In big yards and loco sheds large number of locomotives / Electrical Multiple units (Emus) stand idle with only the load of their auxiliaries Drawing higher reactive power. Therefore these are drawing power at Low Power Factor. For improving power factor fixed shunt capacitor bank with 13% Series Reactor is also installed at some traction sub-stations, the Net KVAR Rating of which is generally in the range of 2000- 3500kVAR. Electrical parameters OHE is made up of a stranded cadmium copper catenary of 65 Sq.mm Cross section or stranded aluminum alloy catenary of 116sq mm cross Section and a grooved copper contact wire of 107sq.mm cross section, Making up a total of 150sq.mm copper equivalent. For 2 x 25 AT feeding systems, as a feeder wire, a stranded aluminum alloy catenary of 240 sq.mm is used. The calculated OHE impedance value of AT Feeding circuit (OHE: Al 116 or Cu 107 sq.mm & feeder wire: Al 240sq.mm) for single Track line is 0.0601 + J 0.1419 ohm/km (at 25kV system impedance). The OHE impedance values for conventional 25kV system are generally taken as under: Sl.No Description . (i) Single track OHE without BT and Return Conductor (ii) (iii) (iv) Double Track OHE without BT and Return Conductor Single Track OHE with BT and Return Conductor Double Track OHE with BT and return conductor Impedance values 0.41 < 70 ohm/km 0.24 < ohm/km 0.70 < ohm/km 0.70 < ohm/km 70 70 70

3.6.5

3.7 3.7.1

Page 12 of 67
(v)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Add Booster Transformer impedance

(vi)

Percentage Transformer

impedance

of

@ 0.15 ohms per Booster Transformer where these are Provided. Traction (12+/ -0.5)% for 21.6 MVA at 27kV.

3.8 3.8.1 (i) (ii)

Duties of the Circuit breaker The Circuit Breaker is used at the following locations in the 25kV AC, 50Hz single phase traction system. As transformer circuit breaker on the secondary side of traction Transformer for voltage of 25kV. As feeder circuit breaker for controlling power supply to OHE through Interrupters for voltage of 25kV.

(iii) As Shunt Capacitor Bank circuit breaker for controlling power Supply to shunt capacitor bank for voltage of 25kV. (iv) 3.8.2 3.8.2.1 For controlling Power Supply to major yard or loco sheds for voltage of 25kV. Special Duty to be performed by 25kV CIRCUIT BREAKER The 25kV Circuit Breaker shall be called upon to trip under short- circuit Conditions. On an average, the number of fault tripping seen by the Feeder Circuit Breaker per month is about 40 Nos, but in exceptional Cases the number of fault trappings per month may go as high as 120 Numbers. The magnitude of short circuit current interrupted generally Ranges from 2kA to 8kA. The Circuit Breaker shall also be called upon to Clear wrong phase coupling on the OHE when two sections of the OHE fed By different phases from adjacent Sub-Stations are accidentally shorted. The design and construction of the 25kV Circuit Breaker shall be such That it is capable of a cumulative duty (nI where n is the number Of CO Operations at a current of I kA rms) of 20,000 kA in service without Adjustment/ change of any part/ contacts of vacuum Bottle. Lubrications and tightening of moving parts in the Operating mechanism and cleaning of Porcelain Insulators can However be done as per Manufacturers recommendations.

3.8.2.2

Page 13 of 67
3.8.2.3

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The Manufacturer shall supply graphs in support of suitability of offered Circuit Breaker to perform above duties at the tender stage, Indicating the cumulative duty which can be performed by offered CB Without any maintenance/ replacement of any components. The 25kV circuit breaker is also required to interrupt the line charging and magnetizing current of locomotive transformers without restrike. Values of line charging current are of the order of 10A and values of Magnetizing current for locomotive/ EMU are likely to be as under: (a) (b) Locomotive EMU 6.38 A 6.0 A

3.8.2.4

3.8.2.5

The 25kV Circuit Breakers are normally operated through Remote Control. A single shot auto re-closing scheme provided the Remote Control System to facilitate the re-closing of the circuit breaker Automatically once within the preset dead time after the tripping of the Circuit Breaker on an OHE faults. This feature helps in quick Restoration of Power Supply to the OHE if the fault is of a transient Nature. The dead time is the periods taken by the Auto re-close Mechanism to close the Circuit Breaker after the same has tripped on fault is set at 0.5sec. Duties of Interrupter The Interrupter is used at the following locations in the 25kV AC 50 Hz, Single Phase Traction Systems (i) (ii) (iii) (iv) (v) (vi) As sectioning Interrupter at Sub Sectioning and Paralleling Posts (SSP) As Paralleling Interrupter at Sectioning Post (SP) and Sub Sectioning and Paralleling Post (SSP) As Bridging Interrupter at Sectioning Post (SP) and As feeding Interrupter at Feeding post (FP) As Bus Coupler Interrupter at TSS For controlling Power Supply to Major Yards / Loco Sheds

3.9 3.9.1

3.9.2

The Interrupter is called up on to perform the following duties: (i) (ii) (iii) Making short circuit current Making and Breaking Traction load currents from very low Capacitive or Inductive Current to Rated Normal Current. Carrying normal rated current continuously and

Page 14 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

(iv) 3.10

Carrying short circuit current until the fault is cleared by the Circuit Breaker up- stream

The design and construction of the Circuit Breaker/ Interrupter shall be such that it is capable of performing 20000 Close-Open operations for Spring-Spring Mechanism and Magnetically Actuated Mechanism in service without adjustment/change of any part/contacts or vacuum bottle. Lubrication and tightening of moving parts in the operating mechanism and cleaning of porcelain insulators can be done as per manufacturers recommendation. Environmental Conditions The CB shall be suitable for outdoor use in moist tropical climate and in areas subject to heavy rainfall, pollution due to industry and saline atmosphere and severe lightening. The limited weather conditions for which the equipment has to withstand in service are indicated below: SL.NO. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Description Maximum ambient air temperature Minimum ambient air temperature Average ambient temperature of 24 h Maximum relative humidity Annual rainfall Ranging Number of thunderstorm days per annum Number of dust storm days per annum Number of rainy days per annum Maximum basic wind pressure Altitude Requirements 50 C 0 C

4.0 4.1

over a period 40 C 100% Ranging between1750mm & 6250mm 85(Max) 35(Max) 120 days (Max) 200kgf/m Not Exceeding1000 meters Heavily polluted

11

Pollution Level

Page 15 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

4.2

The CB/Interrupter would be subjected to vibrations on account of trains running on nearby Railway Tracks. The amplitude of these vibrations which occur with rapidly varying time periods in the range of 15ms to 70ms lie in the range of 30 to150 microns at present, with the instantaneous peak going up to 350 microns. Technical specification The rating and other particulars The circuit breakers shall be designed for the following rating and other particulars: RATED SYSTEM VOLTAGE (kV) Circuit Breaker Interrupter 25kV 25kV 25 DP & Single 25kV SP 25kV DP SP 22 kV DP Pole Mounted 3 4 5 6 7 25kV subject to variatio n from 19kV to 27.5kV occasio nally touchin g 30kV 25kV subject to variation from 19kV to 27.5kV occasion ally touching 30kV 52 25kV subject to variation from 19kV to 27.5kV occasion ally touching 30kV 52 25kV subject to variation from 19kV to 27.5kV occasion ally touching 30kV 52 25kV subject to variatio n from 19kV to 27.5kV occasion ally touching 30kV 52

5.0 5.1

S. No.

Particulars

2 Nominal system voltage(kV)

25kV Pole Mounte d 8 25kV subject to variatio n from 19kV to 27.5kV occasio nally touchin g 30kV 52

(i)

(ii)

(iii)

Rated 52 voltage(kV) Rated insulation level (a)Rated1min 95kV wet power (rms) frequency withstand voltage (b)Rated impulse (1.2/50s) 250 kV

95kV (rms)

95kV (rms)

95kV (rms)

95kV (rms)

95kV (rms)

250 kV

250 kV

250 kV

250 kV

250 kV

Page 16 of 67
withstand voltage

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

(peak)

(peak)

(peak)

(peak)

(peak)

(peak)

(v)

Rated frequency

------------------------50Hz 3%---------------------3 4 5 6 7 8

2 Rated breaking capacity (symmetrical) (i) Single pole (ii) Two pole Out of phase breaking current Rated single capacitor bank breaking current Rated line charging breaking current Rated small inductive breaking current Rated making current Rated operating sequence Total beak Time Rated short time current First pole to

(vi)

550 MVA 550 MVA 5 kA (rms)

550 MVA 550/600 MVA 5 kA (rms)

550 MVA 550 MVA 5 kA (rms)

NA NA

NA 344 MVA 3.125k A NA

NA NA

(vii)

NA

NA

(vii)

150A

150A

150A

NA

NA

(ix)

10A

10A

10A

10A

10A

10A

(x) (xi) (xii) (xiii)

------------------------ 10A 50A (peak 50A (peak) 50A (peak

--------------------------20 kA 31.25 kA 20 kA

O - 0.3s CO 15 sec CO Not more than 60ms 20kA for 3sec NA

CO 15 sec- CO Not more than 80ms 8kA for 3 sec NA

Not more Not more Not more Not than than than more 60ms 60ms 80ms than 80ms 20kA for 3sec ---1.5 20kA for 3sec NA 8kA for 3 sec NA 12.5kA for3sec -----1.5

(xiv) (xv)

Page 17 of 67
clear factor Corona Extinction Voltage Rating of auxiliary switch contacts

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

for 2 paramet ers------NA NA NA NA

for 2 parame ters---NA NA

(xvi)

(a) Rated voltage (xvii)

(b) Rated current (continuous) ----------------------------10A ---------------------------(c)Rated breaking current --------- 2A at 220V dc with 20ms circuit time constant ----Clearances The design of the CB shall be such that when it is erected on the Supporting Structure, the following clearances / distance of lowest live Part of the circuit breaker from the ground level or earth is achieved: S. No. 1 2 Clearance/distance Minimum height of lowest live part of the CB from ground level From a point where a man may be required to stand for operation or for attending the breaker (sectional clearance). Minimum height of the bottom most part of any insulator from the ground level. Minimum clearance between live part and earth part. Distance between pole centers for 2 poles 22/25KV 3800 mm 3000 mm 2500 mm 500 mm 1500 mm

---------------------------- 110V dc -

----------------------------

5.2

3 4 5

Page 18 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

6.0 6.1

Type and General Construction The design and construction of the Circuit Breaker/ Interrupter shall be such that it is capable of performing 20000 Close-Open operations for Spring-Spring Mechanism and Magnetically Actuated Mechanism in service without adjustment/change of any part/contacts or vacuum bottle. Lubrication and tightening of moving parts in the operating mechanism and cleaning of porcelain insulators can be done as per manufacturers recommendation. The CB / Interrupter shall be of outdoor type suitable for mounting on steel structure / Pole. The 25kV CB shall be of single pole or double pole identical to single pole unit operated through common / two operating mechanisms electrically paralleled. The CB shall comprise ofThe pole (interrupting chamber and support insulators) Operating mechanism cubicle / cubicles and Mounting steel frame suitable for mounting on foundation / pole Interrupting chamber Vacuum Circuit Breaker / Vacuum Interrupter The operating mechanism ( spring-spring and magnetic actuator ), the pole assembly and supporting structure of vacuum CB shall be separate and capable of being packed and handled individually and erected in sequence. The pole shall comprise the interrupting chamber and the support insulator. The interrupting chamber shall consist of vacuum bottle contained in porcelain hollow insulator. The vacuum bottle shall comprise a vessel sealed for life time with insulating side walls and metal ends containing the fixed and moving contacts. The movement of the moving contact in the vacuum enclosure shall be guided by means of metal bellows. Suitable metallic shields shall be provided for preventing heat and metal vapor from arcing zone affecting the insulating envelope. These shields will also control the electric field when contacts are open and voltage is appearing across the CB contacts. This will mask high internal stress points and produce an almost linear axial grading of the external insulating surfaces. A shield shall also be provided to protect the bellows. The design and construction of vacuum bottle of the CB shall be such that the current chopping level is kept to the minimum and shall not produce any appreciable switching over voltages.

6.2

(i) (ii) (iii) 6.2.1 6.2.1.1

Page 19 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

6.2.2 6.2.2.1

Porcelain hollow insulator and terminal connector Porcelain hollow insulator The porcelain hollow insulators used as the support insulators and interrupting chamber insulator for the CB shall be outdoor type conforming to IS: 5621 (1980). The porcelain hollow insulator shall be of single piece construction ie, there shall be no joint with in the porcelain.. The shed profile shall have a lip at the extremity but free from ribs on the under side so as to avoid accumulation of dust and pollutants and permit easy cleaning. These insulators shall be procured from RDSOs approved sources only. Both the porcelain insulators for the support and interrupting chamber shall have a minimum creepage distance of not less than 1300mm.

6.2.3 6.2.3.1

Terminal Connectors The CB/ Interrupter shall have aluminum terminal pads and shall be Supplied with the flexible terminal connectors as per RDSO Drawing No.ETI/PSI/11060 (Appendix-II) and ETI / PSI / P / 6570 Mod F (Appendix II ) suitable for connection to 50 mm / 36 mm outside Diameter aluminum tubular bus bars for 25kV CB / Interrupter Respectively. The connectors shall conform to IS:5561 (1978) and design shall be such, so as to be connected to the equipment terminal pads with minimum four 12mm diameter bolts, nuts,lock-nuts of stainless steel conforming to IS:1570 (Pt.V) (1978) grade 04Cr,17Ni and Mo2 each of these bolts shall have two flat washers. Contacts for both Vacuum CB / Interrupter Main contacts The main, fixed and moving contacts of the CB shall have ample crosssection and contact pressure for carrying the rated current and short time current without excessive temperature rise, pitting and welding. Internal arcing contacts of vacuum bottle shall be made up of suitable material. Indication for contact wear condition shall be provided.

6.2.3.2

6.2.4 6.2.4.1

6.2.4.2

Auxiliary Switch Contacts Apart from the auxiliary switch contacts required exclusively by the manufacturer for the functioning of the CB at least 6 pairs of normally

Page 20 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

open (NO) contacts and 6 pairs of normally closed (NC) contacts shall be provided additionally for the exclusive use of the purchaser. The auxiliary contacts which are operated in conjunction with the main contacts shall be positively driven in both the directions. 6.2.5 6.2.5.1 Operating Mechanism for spring The CB shall be operated by a motor charged spring stored energy mechanism. Both opening and closing operations shall be done by the stored energy of spring (S). The motor shall be so rated that the time required for fully charging the closing spring is not more than 15 seconds. The closing action of the CB shall charge the opening spring so that the CB is ready for opening any time thereafter. The spring shall be of robust design. Using tested steel as per IS: 7906 or IS: 7907 (1976). the ends of the compression springs if used, shall be flattened to enable proper fixing and shall minimize the possibility of misalignment. The motor for spring charging shall be suitable for operation from a 110V dc power from a battery. The voltage at motor terminals is likely to vary between 110% and 85% of the normal value. The carbon brushes provided shall have copper pigtails for carrying motor current. A miniature circuit breaker of adequate ratings and of reputed make shall be provided in the motor circuit for protection of the motor against over current and earth faults. Operating Mechanism (Magnetic Actuator) The magnetic actuator mechanism shall be provided with two well designed magnetic coils /solenoids; one for closing and other for the tripping operations. The latching of mechanism in its two end positions shall be ensured by specially designed, permanent magnets designed to operate with minimum hysteresis loss. The tenderer shall indicate the maximum service temperature ie, the max.temperature to which the magnet may be exposed with no significant long range instability or structural changes and Curie temperature ie, the transition temperature above which material losses its magnetic properties. The temperature rises expected to be attained by the magnets during service shall be indicating by the tenderer. Suppliers catalogs / test certificate for this have to be furnished. The Circuit breaker shall be provided with arrangement s for trip and close circuits to be compatible with either 110 Volt DC potential or potential free contacts from control and relay panel. This feature shall enable use of this circuit breaker in place of existing circuit breaker Interrupter, where potential free contact do not exists.

6.2.5.2

6.2.5.3

Page 21 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

6.2.5.4

The operating mechanism shall be designed so that the CB can be operated from the operating mechanism cubicle itself as well as remotely from the control panel in the TSS and also from the remote control Centre (RCC) which is situated away from the CB. For his purpose LOCAL/REMOTE Two way selector switches which shall be provided in the operating Mechanism cubicle. When the Switch is in the LOCAL position, the CB can be operated locally and when it is in the REMOE position the CB can be operated from the control panel or from the RCC. The selector switch shall be spring loaded in order that it automatically returns to the LOCAL/ REMOTE Position. For closing and opening the CB from the Operating Mechanism cubicle itself, the switch shall be of the push Button type or Knob type. The operating mechanism shall also be provided with a suitable emergency device to manually open the CB in the failure of any part of DC control circuit including the opening coil in the operating Mechanism. The operating mechanism, shall also be provided with a suitable device to manually close the CB (mainly for maintenance Purposes). In addition, a detachable handle/ crank shall be provided for manually charging the closing spring. The height from ground/ platform level at which the handle / crank is to be inserted in the operating mechanism shall be between 1500mm and 2000mm so as to enable its operation conveniently by the operator standing on the round/Platform. The height of other devices like interlock, ON-OF switches, selector switches etc. to be operated from ground/ Platform Platform shall also be at a height between 1500mm and 2000mm. In addition to the manually operated local mechanical opening and Closing devices as indicated in clause 6.1.44 & 6.1.45 above, Provision shall also be made by means of a suitable crank or handle for slow closing and slow opening of the circuit breaker for Maintenance purposes. The closing coil and opening coil in the operating mechanism Shall be suitable for operation from 110V dc power supply From a battery. The closing coil shall be suitable for operating at a voltage variation of +10% to -15%, while the opening coil shall be suitable for operating at a voltage variation of +10% to -30%. The circuit breaker shall be fitted with an electrical anti-Pumping device, to give priority to tripping command in case of a persisting losing command being simultaneously present.

6.2.5.5

6.2.5.6

6.2.5.7

6.2.5.8

6.2.5.9

Page 22 of 67
6.2.5.10 6.2.5.11 6.2.5.12

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The circuit breaker shall be trip-free. Facility for trip circuit supervision shall be provided in Circuit Breaker. An operation counter having five digit recording mechanism for the number of tripping operation shall be provided at a suitable as to be conveniently read by the operator standing on the Ground. The operation counter shall be of lock type and shall not be of resettable type. Mechanical indicators clearly visible from ground, shall be provided for CLOSED and OPEN conditions of the CB /VI. All working parts of the operating mechanism shall be of corrosion existing material, bearings, if any, shall be sealed type. Bearing pins, bolts, nuts and other parts shall be adequately locked to prevent loosening. In case operation of closing device when CB is already in CLOSED condition shall not cause damage to any part of the CB or endanger the operator standing near the CB. The average Power requirement for tripping coil or closing coil shall not Exceed 200W and power requirement at any time including Spring Charging shall not exceed 1000W. In the event of 110V battery supply voltage dropping below 85V which is the minimum voltage prescribed for operation of Tripping coil to trip the circuit breaker, the circuit breaker should Trip automatically by means of a suitable arrangement/ Device (CTD). Shock absorbers used (if any) shall not require any maintenance during the entire life of the CB / Interrupter The operating mechanism and associated accessories shall be enclosed in weather, dust and vermin proof cabinet or cubicle. The cubicle made of at least 2mm thick sheet steel (of tested quality) with provision for pad locking. The cubicle shall be tested for dust and water proofing as per IP55 as per IS: 2147(1962) Suitable heaters(s) shall be provided in operating mechanism cubicle to operate at 240V ac, 50Hz single phase supply to prevent condensation of moisture during monsoon / winter. A 240V ac, 5A, 3 pin socket outlet for an inspection lamp shall also be provided. Miniature circuit breaker / Switch with thermostat of reputed make & of adequate rating shall be used for protection of heater circuit for overload and earth fault.

6.1.5.13 6.1.5.14

6.1.5.15

6.1.5.16

6.1.5.17 . 6.1.5.18

6.1.5.19

Page 23 of 67
6.1.5.20

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The entry of all cables into the operating mechanism cubicle shall be only through suitable cable glands which shall not allow ingress of vermin, insects, etc. into the cubicle. The cable glands shall be supplied with the CB Five cable glands shall be provided of which three shall be of 16.5mm outside diameter while the Balance two glands shall be for cable of 14mm outside diameter. The wiring inside the operating mechanism cubicle shall be with 1100V grade PVC insulated single core cable conforming to IS: 1554 (Pt.I- 1988), with stranded copper conductors of adequate cross-section (with min 2.5 sq.mm strand copper) so proportioned as to reduce voltage drop and IR losses to minimum. The ends of wires shall be terminated with crimped eye type lugs. The wiring of 110V dc control circuit and 240V ac circuit shall be segregated and properly identified. The positive and negative wires of dc circuits shall also be segregated. The length of the cables used shall be kept to the minimum. Wire inside the cubicle shall be properly laid on trays and Anchored to avoid breakage during vibration. The terminal end of all wires shall be provided with numbered interlock type Ferrules which shall be of PVC or other durable material with marking (numbers) either engraved or punched so as to be indelible. The ferrules shall be of white color with lettering thereon black. All wiring shall be properly supported and suitably protected to avoid rubbing against any Metallic part. Terminal blocks of standard type shall be provided in the operating mechanism. There shall be insulating barriers between adjacent terminals. The terminals shall be stud type with spring washers. Suitable dust proof shrouds of unbreakable transparent material shall be provided on each terminal block. The terminal blocks used for DC and AC circuits shall be clearly distinguished and separated from each other. Similarly positive and negative Terminations of the wiring of the dc circuit shall be segregated and Separated by insulating barriers. For earthling of the operating mechanism cubicle, two earthing terminals of adequate capacity to carry the rated short circuit current shall be provided with 17.5 + 1.5/-0. Diameter stud/hole for fixing the Earthling Flat. Steel supporting frame The steel supporting frame for CB / Interrupter shall be designed with a factor of safety not less than 2.5 with respect to the yield point under conditions of maximum loading for a basic wind pressure of 200kg/m on

6.1.5.21

6.1.5.22

6.1.5.23

6.1.5..24

7.0 7.1

Page 24 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

1.5 times the projected area of each member of one face and taking into account to IS:808 (1989) and test certificate shall be furnished to RDSO. The fixing distance for steel supporting frame on the foundation for single pole 25kV CB shall be 650 x 725 mm. 7.2 Typical design calculations for the steel supporting frame shall be furnished by the manufacturer to the RDSO during design approval stage for checking the safety of the supporting frame proposed to be used. For earthling at least 2 legs of the steel supporting frame shall be provided with stud/hole type earthing terminals of adequate capacity to carry the rated short circuit current safely. The earthing shall be provided with 50 x 8 mm MS flat. The terminal shall be provided with 17.5 + 0.5/0.0mm diameter stud/hole for fixing the earthling flat. Foundations Gravity foundation of plain mass concrete to M 10 mix as per IS: 456 (1978) shall be designed considering the normal impact loading in opening/closing operations. The basic wind pressure shall be taken as 200 kgf/m. Two alternative design of foundations one for a normal soil of bearing capacity 5500 kgf/m and other for black-cotton soil of bearing capacity 16500 kgf/m shall be furnished by the manufacturer. The foundation block design shall give complete details of its size and size of pockets provided for grouting the fixing bolts. Detailed design calculation for proposed foundation shall be submitted to DG (TI) RDSO for scrutiny and approval. 9.0 Foot prints and foundation The dimension of steel frame has to match with the sketch no. TI/DRG/PSI/25 kV CB INT/COMFDN/00365/Rev.0. This is to facilitate common foundation and interchangeability of interrupters of different makes. 10. 10.1 Pole (mast) for Pole Mounted VCB/VI The pole (mast) for mounting the Interrupter shall be either steel Mast or a round tapered prestressed spun concrete mast. The detail of pole (mast) for mounting the Interrupter shall be supplied by the purchase/DG(TI) RDSO Lucknow. Typical design calculations shall be furnished by the manufacturer

7.3

8.0

10.2

Page 25 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

for checking the safety of the pole (mast) proposed to be used. The design calculation for steel mast shall be based on a factor of safety of not less than 1.67 with respect to the yield point under conditions of maximum loading allowing for a basic Wind pressure of 200kgf/m2on 1.5 times the projected area of each member of one face and taking into account the dead and impact loads of Interrupter/Circuit Breaker. 11.0 11.1 Corrosion prevention system Galvanizing The operating mechanism cubicle and steel supporting frame shall be hot dip galvanized in accordance with RDSO Specification No. ETI/OHE/13 (4/84) and the weight of zinc coating shall not be less than 1000 gm/m. 11.2 Painting If the successful tenderer/manufacturer is not able to hot dip Galvanize the operating mechanism cubicle and the steel supporting Frame as per Clause 9.1, it shall be painted conforming to RDSOs Specification No. M & C/PCN-110/88. 11.3 Fasteners All fasteners of 12 mm diameter and less exposed to atmosphere Shall be of stainless steel and those above 12 mm diameter shall be of preferably stainless steel or of mild steel hot dip galvanized, to RDSOs specification No. ETI/OHE/18(4/84). 12.0 12.1 Interlocking arrangements The CB Interrupter shall be provided with a suitable interlocking device for electrical and mechanical interlocking with its associated isolator(s), such that (i) the isolator(s) can be operated only when the CB / Interrupter is locked in open condition and (ii) the CB / Interrupter cannot be operated both manually and electrically either on LOCAL or REMOTE unless the isolator(s) is Locked in the CLOSE or OPEN condition. Interlocking Scheme for 25kV CB Three types of isolator interlocking schemes shall be utilized. The details of these schemes are indicated below:

12.2 12.2.1.

Page 26 of 67
a)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Single isolator interlocking (SI) Under this scheme, the circuit breaker shall be interlocked with its single associated isolator. This interlocking scheme shall be provided on the circuit breaker to be installed as transformer breakers and circuit breaker for controlling feed to the shunt capacitor. In this scheme the key shall be trapped in the lock mounted on the circuit breaker mechanism when the circuit breaker is in closed position. The key can be released from the operating mechanism when the circuit breaker is in the open position only. Any attempt to forcibly withdraw the key when the circuit breaker s in the closed position shall result in tripping of the circuit breaker. The key thus released from circuit breaker shall be utilized to operate the lock mounted on the isolator. It shall be possible to release this key from isolator lock only when the isolator is locked in open or closed position. Once the key has been removed from the circuit breaker operating mechanism, it shall not be possible to operate the circuit breaker either manually or electrically by local/remote control.

(b) Double isolator interlocking (DI) The scheme is identical to the SI scheme but in this the circuit breaker shall be interlocked with its two numbers associated isolators. This interlocking shall be provided on circuit breaker to be installed as feeder breakers. (c) Bus Coupler Isolator Interlocking (BCI) Under this scheme the Circuit Breakers of adjacent bay shall be interlocked with the bus coupler /interrupter. The operation of the Bus Coupler Isolator/Interrupter. The operation of the Bus Coupler /Interrupter shall not be possible unless both the circuit breakers of adjacent Circuit are locked in open position. In this scheme the two keys so released from the circuit breakers shall be inserted in a key exchange box (which shall be supplied loose) for releasing a third key which shall be used for operating the Bus Coupler Isolator/ Interrupter. The details of all these schemes indicated above are given I drawing No. ETI/PSI/SK/5124 enclosed as Appendix (IV). 12.2.2 SI Interlocking scheme shall include supply of 2 locks along with the Common interlocking key, out of which one lock shall be duly mounted on the Circuit Breaker Operating Mechanism and the other, shall be supplied loose for mounting by Purchaser on the associated isolator. DI Interlocking scheme shall include supply of 3 locks along with the common interlocking key out of which one lock shall be duly Mounted

12.2.3

Page 27 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

on the Circuit Breaker operating mechanism and 2 locks shall be supplied loose for mounting by Purchaser n the associated Isolators. 12.2.4 BCI Interlocking scheme shall include supply of a Key exchange box which can be operated by the two keys released from the Circuit Breakers of adjacent circuits and one loose lock operated by the key released from the key exchange box. The loose lock shall be Suitable for directly mounting on the bus coupler (Supply of locks fitted on the circuit breakers operating Mechanism shall be covered under SI/DI Interlocking Schemes). The Interlocks provided on the Circuit Breakers installed at a traction Sub- Station shall have non-interchangeable key codes to safeguard against an mal-operation. The lock meant for mounting on the associated isolator(s) and Bus coupler isolator shall be a bolt type lock of approved design. The internal mechanism of the lock shall be made of non-ferrous metal and the outer housing hall be of steel hot dip Galvanized. RDSO drawing No. ETI/PSI/SK/334 showing the Interlocks is attached with this specification as Appendix VI. The key when trapped inside the lock shall remain properly secured so to safeguard against its working loose due to vibrations. One spare duplicate key shall be supplied with each of the three types of Interlocking schemes. In order to facilitate the ordering of Interlocks, the tender shall separately furnish prices for SI, DI, and BCI interlocking schemes. The requirements of interlocks and the key codes to be adopted shall be ascertained by the successful tenderer from the respective Consignee. Interlocking Scheme for 25kV VCB at Sub Station of Mumbai Area under DC-AC conversion Normally, both incoming and lines circuit breakers CB 1& 2 shall Remain closed and 110kV bus coupling circuit breakers CB-3 will be in open position. The power supply to Traction Over Head Equipment shall be fed through any one of the to transformers by closing its respective HV and LV Transformer Circuit Breakers. At a time, only one Transformer will be in service. Other transformer, not on load, can be kept as a) Hot standby, by closing its HV side Transformer Circuit Breaker and

12.2.5

12.2.6

12.2.7 12.2.8

12.3 12.3.1

12.3.2

Page 28 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

b)

keeping LV transformer Circuit Breaker open. OR Dead, by keeping both HV and LV Transformer Circuit Breakers in open position However, each transformer shall Feed load periodically at regular intervals. Bus coupler is provided on 25 kV side with Circuit Breaker CB-8. This shall normally be closed for feeding the OHE in either side of IGL from any of the transformers. In case of outage of one feeder and Transformers on other bay at a Particulars time power supply can be restored through healthy Transformer from other feeder by operation of 110KV bus coupler Circuit Breaker CB-3. Extension of 25KV supply in case of outage of one complete TSS. In the event of failure of any TSS, supply from adjoining TSS may be extended up to the IOL of failed TSS by closing the bridging the SP on either side of failed TSS. Bus coupler CB no.8 at the failed TSS shall be kept in open position along with LV Transformer CB 6&7 at the failed TSS in open position. However, this will necessitate lower panto/raise panto of the trains in front of failed TSS, if it is not provided with neutral sections. Otherwise, supply may be extended over complete zone of failed TSS from any of the adjoining TSS. i.e from SP to SP. Bus coupler CB no.8 at the failed TSS shall be kept in close position along with LV transformer CB 6& 7 at the failed TSS in open position. In this case no lower panto/raise panto is required, however the OHE voltage and load has to be closely monitored. For paralleling of nominated Traction Sub Stations Energize the OHEs of concerned TSS zone up to SP locations and then close the bridging CBs at SP location.Energize the OHE of one TSS zone. Extend the supply by closing bridging CB at SP and feeder CB and bus coupler CB at the next TSS. Then clause LV transformers Circuit Breaker at other Traction Sub-Station to make parallel operation of the Two TSSs. Details of interlocking scheme indicated above are given in the drawing no. TI/DRG/PSI/INTERLOCK/RDSO/00001/06/0 as appendix VII.

12.3.3

12.3.4

12.3.5 (a)

(b)

12.3.6

Page 29 of 67
13.0 13.1 (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) (x) (xi) (xii) (xiii) (xiv) (xv) (xvi) (xvii) 13.2

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Parts, fittings and accessories The following parts, fittings and accessories shall be provided for each CB: Contact wear indication. Operating mechanism cubicle door padlocking arrangement with padlock. Local operated mechanical opening and closing device. Spring loaded local/remote selector switch. Local operated electrical closing and opening device (push or knob). Operation counter. Interlocking device (as required) Terminal connectors. Earthing terminals Name/ rating plate. Mechanical ON and OFF position indicators. Handle/crank for slow closing and slow opening of CB. Supporting frame work. Tripping device in case of 82 V D failure (CTD) for VCB Anti-pumping device. Foundation Bolts. Handle/crank for charging the closing spring manually. The name/ rating plate shall contain the following particulars Each CB / Interrupter shall be provided with rating plates (Hindi /English) of weatherproof material fitted in a visible position showing the items indicated below. The letters/numbers on the plate shall be indelibly

Page 30 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

marked by etching/engraving. (i) Manufacturers name and country of origin. (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) (x) (xi) (xii) (xiii) (xiv) Type designation and no: of pole. Serial number Rated voltage Rated normal current Rated frequency Rated short circuit breaking current. Rated short circuit peak making current Rated single capacitor bank breaking current Rated out of phase breaking current. Rated short time withstand current and its duration. Rated insulation level. Rated operating sequence. Control circuit voltage with permissible variation for (a) Closing coil (b) Opening coil (c) Motor voltage Total weight of CB Specification conforming to IEC/RDSO. Vacuum level in Torr (for vacuum CB). Order reference Month/Year of manufacture

(xv) (xvi) (xvii) (xviii) (xiv)

Page 31 of 67
14.0 14.1 14.1.1 Testing General

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

After all the designs and drawings have been approved and clearance Given to this effect by RDSO, the manufacturer shall take up Manufacture of the prototype for inspection/testing by RDSO. It is to be Clearly understood that any changes to be done on the prototype as required by RDSO, the same shall be done expeditiously. Prior to giving a call to the Purchaser/Director General Traction installations, Research Designs and Standards Organization, Lucknow (DG/TI/RDSO,Lucknow) for inspection and testing of the prototype, the successful tenderer/manufacturer shall submit a detailed test schedule consisting of test procedures, schematic circuit diagrams, items/parameters to be checked and values required as per specification for each of the tests and the number of days required to complete all the tests at one stretch. The schedule shall also indicate the venue of each of the test. Once the schedule is approved, the test shall invariably be done accordingly. However, during the process of type testing or even later, the Purchaser /DG/TI/RDSO, Lucknow reserves the right to conduct any additional test(s), besides those specified herein, on any equipment/ item so as to test the equipment/ item to his satisfaction or for gaining additional information and knowledge. Incase any dispute or dis agreement arises between the successful tenderer/ manufacturer and the representative of the Purchaser/DG/TI/RDSO, Lucknow during the process of testing as regards the procedure for type tests and for the interpretation and acceptability of the results of type tests. It shall be brought to the notice of the Purchaser /DG/TI/ RDSO, Lucknow as the case may be whose decision shall be final and binding. Only after the prototype of the equipment is manufactured and ready in all respects, shall the successful tenderer/manufacturer give the actual call for the inspection and testing with at least 15 days notice for the purpose. In the event of the test not being carried through to completion at one stretch for any reason attributable to the successful tenderer /manufacturer and it is required for the representative of the Purchaser /DG/TI/ RDSO to go again or more numbers of times to the works of the successful tenderer/manufacturer or to any reputed testing house/laboratory where tests are being done for continuing and/ or completing the tests on the prototype(s) of the equipment, the successful tenderer/manufacturer shall reimburse to the Purchaser /DG/TI/ RDSO the cost for the representative(s) having to visit the works or other place(s) for the tests more than once. The cost as claimed by the Purchaser /DG/TI/ RDSO ,Lucknow shall be paid thorough a Demand

14.1.2

14.1.3

Page 32 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Draft to the concerned Accounts Officer of the Purchaser/ Purchaser /DG/TI/ RDSO,Lucknow as shall be advised to the successful tenderer/manufacturer. 14.1.4 The tests shall be conducted on the prototype of the CB / Interrupter at the works of the successful tenderer/ manufacturer or at any reputed testing house of laboratory in the presence of Purchaser /DG/TI/ RDSO, Luck bow or his authorized representative. He prototype shall be complete in all respects, including the terminal connectors as would be supplied if it had passed the tests. The tests shall be conducted as per relevant governing specification and as modified or amplified herein. Incase of test being conducted at government test house, the presence of Purchasers representative for witnessing the test may be waived off subject to the discretion of the Purchaser /DG/TI/ RDSO, Luck now. For the tests which are conducted in the laboratories of Central Power Research Institute, Bhopal/Bangalore, Electrical Research Development Association, Vadodara or any such testing house or laboratory a clear certificate to the effect that the equipment has passed the tests as per the specification shall be obtained by the manufacturer and submitted to the Purchaser/DI(TI)/RDSO, Lucknow. Full details of the tests and the test parameters shall be furnished along with the test reports. The type tests comprises of: (i) (ii) (iii) (iv) Mechanical operation test as per clause 13.2.1 for VCB and Interrupter. Mechanical Endurance Test of Operating Mechanism(Magnetic Actuator) Temperature rise tests as per the clause 13.2.2 for VCB and Interrupter Dielectric tests as per the clause 13.2.3 for VCB and Interrupter

14.1.5

(a) Rated lightning impulse voltage withstand test as per clause 13.2.3.1 (b) Rated one minute power frequency wet withstand voltage test (v) (vi) Rated short circuit making and breaking capacity test (basic short circuit test duties) for VCB. Making and breaking test for Interrupter TD-1 Making and breaking test at 100 % of mainly active load.

Page 33 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

TD-2 TD-2a TD-2b TD-3 TD-4b TD-6 (vii)

Closed loop make break test. Transmission circuit closed loop make break operation test. Parallel transformer circuit makes break operation test. Making and breaking test at 5% of mainly active load. Line charging make break operation test and Short circuit making current.

Rated short time withstand current & peak withstand current test as per clause 13.2.5As per clause 13.2.3.2 for VCB and Interrupter

(viii) Line charging breaking current test as per clause 13.2.6 for VCB (ix) (x) (xi) (xii) Test to prove the rated transient recovery voltage (TRV) and rate of recovery Voltage (RRRV) Out of phase making and breaking current as per clause 13.2.9 for VCB, Capacitor current switching test as per clause 13.2.10 for VCB. Special electrical test applicable for 25kV circuit breaker only as per clause 13.2.12

(xiii) Selected EMC(Electro Magnetic Compatibility) preliminary tests as per IEC 61000 and IEC 60694-1996 for Magnetic Actuated VCB and Interrupter (a) (b) (c) (d) (e) (g) EM radiated field immunity test Fast transient immunity test Surge immunity test Radio frequency conducted immunity test HF disturbances: damped oscillatory wave 1 MHz-100 kHz immunity test Radiated emission test

Page 34 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

14.2.1 14.2.1.1

Mechanical Operation test The test shall be conducted in accordance with clause 6.101 of IEC 62271-100 but the number of operations shall be 10,000 in case of 25kV VCB / Interrupter instead of 2000specified therein for 25 kV VCB / Interrupter with spring Spring Mechanism and 20,000 for VCB/ Interrupter with Magnetic Actuator Mechanism. For this purpose, VCB / Interrupter shall be tested in accordance with Table XII of IEC 62271100 However, the sequence shall be repeated 5 times to complete 10, 000 operations in case of 25kV VCB / Interrupter with spring complete 20,000 operations for VCB / Interrupter with Magnetic Actuator Mechanism. Following checks/ tests shall be done before the commencement of

Mechanical operation test. (i) (ii) (iii) General visual inspection of the equipment to check its conformity with the approved drawings. Operation of various circuits and devices of the CB. Measurement of dimensions of components liable to wear, dimension of opening, closing and wipe springs, lift of tripping and closing coil plunger, and clearances of opening and closing coil armatures. Measurement of insulation resistance of auxiliary and motor circuits with 500V meter. Measurement of contact resistance of main circuit by dc voltage drop. Mechanical operation comprising 5 closing and 5 opening operations at the specified, normal, minimum and maximum control voltages. Closing and opening travel characteristics of contacts to record the Following at the specified, normal, minimum and maximum control Voltages. Opening speed & time Closing speed & time Contact bounce & Contact travel

(iv) (v) (vi) (vii)

Page 35 of 67
14.2.1.3

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The measurement of items (v) & (vii) above shall be repeated after every 5000 operations for 22KV/25kV VCB and observations made/ results obtained shall be evaluated by comparing with the figures and the tolerances given by the successful tenderer/manufacturer in the SOGP. After completion of 10,000 operations in case of 25kV CB / Interrupter with spring spring and 20,000 for magnetic VCB / Interrupter before dismantling the CB for internal inspection, the following checks/tests shall be performed. (i) (ii) (iii) (iv) (v) Dielectric tests on control and auxiliary circuit (110Vdc) by applying 2kV (rms) for 1 min. after disconnecting the motor Spring charging motor shall be tested at 1kV (rms) for 1 min. Power frequency dry withstand voltage test on complete CB / Interrupter for 1 minute. Temperature rise test on opening and closing coils as 13.2.2.2 Closing and Opening Travel characteristics of contacts to record the Following at the specified normal , minimum and maximum control voltages Opening speed & time Closing speed & time Contact bounce & Contact travel

14.2.1.4

The above parameters shall be within the specified limits declared by the manufacturer in SOGP. 14.2.2 14.2.2.1 Mechanical Endurance of Operating Mechanism (Magnetic Actuator) Mechanical endurance for operating mechanism without Vacuum bottle shall be tested for 1,00,000 operation for VCB / interrupter with Magnetic Actuator Mechanism. The test shall be performed on the prototype unit in accordance with IEC 62271-100, clause 6.101.1.2 (component tests) & as per 6.101.2.4 (extended mechanical endurance tests) for special service requirements. At the beginning of the design test, the characteristics of the magnetic actuator shall be established as the reference characteristics for the

Page 36 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

actuator. The purpose of this reference is to characterize the behavior of the magnetic actuator. The following characteristics shall be measured and recorded before and after the tests: a. Resistance of the coils (Both closing & opening coils in the case of double coil magnetic actuators) b. Ambient temperature at the time of measurement of resistance of the coil. c. Insulation level of the coils, i.e, 2kV (rms) frequency voltage applied on to the coils across the body of the actuator. Since the parts of auxiliary and control equipments which have been manufactured in accordance with relevant standard and also test along with the operating mechanisms of conformance to these standards, the proper functions of such parts in connection with the functions of the other parts of the magnetic actuator need not be verified separately. 14.2.2.2 Condition of the magnetic actuator during and after the tests during and after the tests, the actuator shall be in such a condition that it is capable of operating at the rated voltage as per clause 5.0 of the specification. In general, these requirements are fulfilled, if During the test, the actuator operates on command and does not operate without command After the test, all parts do not show undue wear. During and after the tests, any distortion of the mechanical part is not such that it adversely affects the operation of the actuator After the tests, the insulating properties of the actuator coils shall be in essentially in same condition as before the tests. Visual inspection of the actuator after the test is usually sufficient for verification of the insulating properties Procedure The mechanical operation tests on magnetic actuator shall be made at the ambient air temperature of the test location. The ambient temperature should be recorded in the test reports. Auxiliary equipments, forming parts of the operating devices are being tested with the equipment, shall be included as a part of evaluation for this test. The actuator for the test shall be mounted on its own support. Any springs mounting arrangement required to simulate the tripping condition of the breaker shall be made part of the mounting arrangement.

(a) (b) (c) (d)

14.2.2.3

Page 37 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The mechanical operation test shall consist of l00000 operating sequence Operating sequence: C ta O - ta Supply voltage / operating pressure Minimum Rated No. of operating sequence 10000 90000

O= Opening, C = Closing ta= Time between two operation which is necessary to re store the initial condition and /or to prevent undue heating of parts of the actuator(this time can be different according to the type of operation and shall not exceed 15 second) Between the test series specified, some maintenance such as lubrication and mechanical adjustment, is allowed, and shall be performed in accordance with the manufacturers instructions. Change of parts is not permitted. The programme of maintenance during the tests shall be defined by the manufacturer before the tests and recorded in the test report. 14.2.3 14.2.3.1 Temperature rise test for VCB / Interrupter On main contact The temperature rise test on the main circuit (contacts) and terminal connectors of VCB / Interrupter shall be carried out as per clause 6.3 IEC 694(1980) or latest. Contact resistance of the main circuit shall be determined by dc voltage drop and recorded before and after this test. 14.2.3.1.1 Procedure Unless otherwise specified, temperature rise on the main circuit shall be made on a new CB in closed position with clean contacts. The test shall be mad with rated normal current. The test shall be done in indoor environment substantially free from air currents, except those generated by heat from the CB being tested. Temporary connections to the CB terminals shall be such that no significant amount of heat is conducted away from, or conveyed to the CB / Interrupter during the test.

Page 38 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The temperature rise at the terminal of main circuit and the temporary connections at a distance of 1m from the terminal shall be measured. The difference of temperature rise shall not exceed 5C. The type and sizes of temporary connections shall be recorded in the test report. 14.2.3.1.2 The maximum temperature rise of contacts, terminals for Connection to external conductors by bolts, material used as Insulation and metal parts in contact with insulation shall Not exceed the values given in Table below when carrying Rated Normal current continuously. These values shall be Conforming to IEC 694(1984) or latest. Table Nature of faults/components Maximum temperature rise at an ambient temperature not exceeding 50C 25C 55C 40C 130C

Sl.No

1.

2. 3. 14.2.3.1.3

CONTACTS i) Bare copper and bare copper alloy in SF6 gas. ii) Silver contacts in SF6 gas. Terminal for external connection by bolts Insulator (Porcelain)

In case a layer of coating of silver over the contact area is not maintained at the end of any tests the contacts shall be regarded as bare for the purpose of temperature rise limits. On Auxiliary equipment (Closing & Opening coils) The temperature rise test on the coils shall be carried out as per clause 6.3 of IEC 694(1980) or latest.

14.2.3.2

14.2.3.2.1

Procedure The temperature rise on auxiliary equipment (Closing and Opening coils) shall be made by the method of measuring Variation of resistance before and after energisation at 110V dc. For this purpose the coil(s) shall be energized 10 times for 1 second, the interval between the instant of each energizing being 2 second. The resistance of the coil shall be measured Immediately before and after such energisation. The value of Temperature rise, over the ambient shall be computed.

Page 39 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

14.2.3.2.2

The maximum temperature rise shall be as per table V of IEC 694(1980) or latest considering the insulating material of the Coil. The temperature rise shall not exceed the value as Guaranteed by the manufacturer in SOGP. Dielectric tests VCB / Interrupter Dielectric tests shall be carried out generally in accordance with Clause 6.1 of IEC 694 (1980) or latest. Humidity and air density Correction factor if less than 1.0 shall not be applied.

14.2.4

14.2.4.1

Rated Impulse withstand voltage test The CB / Interrupter shall withstand its rated impulse voltage 250 kV (peak) of 1.2/50s wave shape.

14.2.4.2

Rated one minute wet power frequency voltage withstand test for VCB / Interrupter The CB / Interrupter shall withstand rated one minute wet power frequency withstand voltage of 95 kV .

14.2.5

Basic short circuit test duties for VCB The basic short circuit test duties 1 to 5 shall being accordance to Clause 6.106 of IEC 62271-100. The Power Frequency Recovery Voltage shall be as per clause 6.104.7 of IEC -62271-100.

14.2.6

Making and breaking test for Vacuum Interrupter These tests shall be conducted in accordance with IEC-265-2 as Modified or amplified here. The test set up shall be for single phase System with earthed neutral. Only the following test duties shall be Performed in any convenient order without any adjustment or Change of part of lubrication or re-conditioning of the interrupter.

14.2.6.1

Making and breaking test at 100% mainly active load (Test duty No.1.0) Five hundred make-break operations shall be conducted at 80A (rms) at a test voltage of not less than 27.5 kV. The supply circuit shall have a power factor not exceeding 0.2 and the load circuit shall have a power factor between 0.65 and 0.75. Prospetive TRV Parameters shall be set in

Page 40 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

accordance with Table III of IEC-265-2 The test may be interrupted after every 10 operations, if necessary, to enable the components to cool down to the ambient temperature 14.2.6.2 Closed loop make break operations (Test Duty No.2a & 2b) If TRV parameters achieved in test duty 1 are equal or more severe then the TRV parameters prescribed in Table IV-A of IEC 265-2 for test duty 2a and 2b then test duty 2a and 2b need not be performed, otherwise tests comprising test duties 2a and 2b described as under shall be performed: i) ii) 14.2.6.3 Transmission circuit closed loop make-break operation test (Test Duty No.2a)-10 make-break operations shall be performed at 800 A. Parallel transformer circuit make-break operation (Test Duty No.2b)-10 make break operation shall be performed at 800 A. Making and breaking test at 5 % of mainly active load (Test Duty No.3). Twenty make break operations shall be performed at 5 % of the rated normal current with a test voltage of not less than 27.5 kV. 14.2.6.4 Line charging make-break operation(Test Duty No.4b) Test shall be made at 100% and from 20% to 40% of rated line charging current. 12 make-break operations at each current shall be performed with contact separation distributed at intervals of approximately 30 electrical degrees. If this is not possible then 30 make break operations shall be performed at random contact separation. The over voltages produced during switching shall not exceed 77.7kV(peak) at single phase test voltage of 27.5 kV(rms) with earthed neutral. 14.2.6.5 Short circuit making current test (Test Duty No.6) Twenty close operations at 20 kA (peak) shall be performed. Opening of the interrupter shall be done with supply disconnected. 14.2.7 All the making and breaking tests shall be done on a single Interrupter and no maintenance or reconditioning of the contacts shall be permitted during the above test series.

Page 41 of 67
14.2.8 14.2.8.1

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Condition of the interrupter during make-break tests and short time withstand current test: During the test the interrupter shall neither show signs of excessive distress nor endanger the operator. No disruptive discharge between energized parts and earth shall occur during the tests. Their shall be no indication of significant leakage current to the interrupter earthed structure or screens whenever fitted during the tests. The earthed parts should be connected to earth through a fuse consisting of a copper wire of 0.1mm diameter and 5 cm length. The fuse wire shall be intact after the tests. Condition of the interrupter after make-break tests and Short time withstand current test: The mechanical functions and the insulation of the interrupter shall be essentially in the same condition as before the tests. The wear of the contacts shall not be disproportional. The interrupter shall be capable of carrying rated normal current and also capable of performing assigned duty provided in the Clause 3.5 and 3.7 of the specification. The interrupter should withstand 95kV (rms) for 1 min in dry conditions

14.2.8.2

14.2.9

Rated short time withstand current & peak current withstand test This test shall be conducted as per clause 6.5 of IEC 694 (1980) or latest. Ie, 20kA (rms) for 3 seconds and 50 kA (peak) for VCB, 8kA (rms) and 20 kA (peak) for interrupter.

14.2.10

Line charging current switching test for VCB This test shall be conducted as per clause 6.111.5.1 of IEC 62271-100 test values shall conform as given in SOGP.

14.2.11

Test to prove rated transient recovery voltage (TRV) for VCB The measurement shall be done 62271 as per clause 6.104.5 of IEC

14.2.12

Out of phase making and breaking test for VCB This test shall be conducted as per clause 6.110 of IEC 62271100) at its rated out of phase breaking current.

Page 42 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

14.2.13

Capacitor bank breaking current test for VCB The test shall be carried out at rated single capacitor bank breaking current generally as per clause 6.111 of IEC 62271-100 . No restrike shall occur during the test. The breaking current shall conform to the guaranteed value.

14.2.14

Special Electrical Test (applicable for 25kV CB only) CB shall be subjected to short circuit making and breaking capacity test at a current of 6.25kA for duty cycle CO-15s-CO for 200 close-open operations. During this test no part of CB shall require any inspection/maintenance, change of SF6 gas or vacuum bottle or any other part. The standard value of prospective TRV shall be taken as 64kV. Other conditions shall be similar to short circuit test duties specified in IEC 56 (1987). The test may be interrupted once after every 10 CO operations if need arises to enable the components to cooled down to ambient temperature.

14.2.15

Condition of CB during the tests conducted as per clause no. 14.2.5, 14.2.9, 14.2.10, 14.2.11, 14.2.12, 14.2.13, and 14.2.14 of this specification shall conform as under: During these tests the CB shall neither show signs of excessive distress nor endanger the operator. No disruptive discharge between energized parts and earth shall occur during the test. There shall be no indication of significant leakage current to the earth structure or screens whenever fitted during the test. The earthed part shall be connected to earth through a fuse consisting of copper wire of 0.11mm diameter and 5cm length. The fuse wire shall be intact after the test. Condition of CB during the tests conducted as per clause No.14.2.5, 14.2.9, 14.2.10, 14.2.11, 14.2.12, 14.2.13,and 14.2.14 of this specification shall conform as under : The mechanical functions and insulation of CB shall be essentially in the same condition as before the test. The wear of the contacts shall not be disproportionate to its original shape and size. The CB shall be capable of carrying its rated normal current and also capable of performing its assigned duty provided in clause 3.7 of the specification The CB shall withstand for 1 minute dry power frequency withstand voltage 95KV rms.

14.2.15.1

14.2.16

14.2.16.1

Page 43 of 67
14.2.17 14.2.17.1

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Selected EMC preliminary test EM radiated field immunity test(80-10000 MHz) according to IEC/EN 61000-4-3 Criteria for successful passing of the test are as follows: (a) (b) No unwanted trip in all frequency range with both open and close position of the circuit breaker Correct trip at stepped frequency 80-100-120-180-240-320-48040-960 MHz for following operation: C/O;C/Auxiliary O; C/Protection Trip O;C/OpenLock;c/Under voltage O; Reclose function.

14.2.17.2

Fast transients immunity tests according to IEC/EN 61000-4-4 test shall be done for severity level 4 for AC main(+/- 4 kV) and Binary Input/Output (+/- 2kV) of different modes. Criteria for successful passing of test are as follows: (a) No unwanted trip during disturbance injection with both open and close position of circuit breaker. (b) Correct trip(absence of anomalies) with open circuit breaker for C/O operations.

14.2.17.3

Surge immunity test according to IEC/EN 61000-4-5 Test shall be done for different severity levels from 1 to 4 for AC Main (+/- 4 kV) and Binary Input/Output(+/- 2 kV) of different modes. No degradation of performance shall occur during the injection of disturbances. Radio frequency conducted immunity tests according to IEC/EN 610004-6 Criteria for successful passing of the tests are as follows: No unwanted trip during disturbance injection with both open and close position of circuit breaker. Correct trip (absence of anomalism)with open Circuit Breaker for C/O operations.

14.2.17.4

14.2.17.5

HF disturbances: damped oscillatory wave 1 MHz 100 kHz immunity tests according to IEC/EN61000-4-10 Criteria for successful passing of the tests are as follows: No unwanted trip during disturbance injection with both open and close position of circuit breaker. Correct trip(absence of anomalism)with open Circuit Breaker for C/O operations.

14.2.17.6

Radiated emission test according to EN 55011/CISPR 11. Test setting shall be as per sub clause.

Page 44 of 67
14.3

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

The tenderer may quote separately the charges for short circuit test duties, short time withstand current and peak current withstand test, line charging breaking current tests, test to prove rated TRV, short line fault tests, out of phase making and breaking tests, capacitor bank breaking current test, measurement of RIV level and special electrical tests as per clause 14.2.4,14.2.5, 14.2.6,14.2.7, 14.2.8, 14.2.9, 14.2.10, 14.2.11, 14.2.12 . No test charge shall be payable for any other test. If the prototype of the CB / Interrupter conforming to the specification has been approved for earlier supplies to Indian Railways, testing of prototype again may be waived provided that no changes in the design and/ or materials used have been made. For this purpose the successful tenderer/manufacturer shall approach Purchaser/DG(TI), RDSO Lucknow with complete documents to ascertain whether the equipment is identical to the prototype approved earlier. Once prototype approval is accorded after conducting all or part of the type tests by RDSO, the prototype approval shall normally be valid for five years subject to the no change of design, material and the process adopted for prototype. Only after clear written approval of the prototype is communicated by Purchaser/DG/TI/, RDSO Lucknow to the successful tenderer/manufacturer, they shall take up bulk manufacture of the CB which shall be strictly with the same design, material and process as adopted for the prototype. In no circumstances the material from sources other than those approved in the design/drawings and / or the prototype shall be used for bulk manufacture. The successful tenderer/manufacturer can furnish copies of type test reports as per relevant IS/IEC for all the important items including items listed at Annexure B. Suitable monogram in the form of engraving/embossing or other similar means shall be provided for each of these items to identify their manufacturer/ source and shall be verified during the prototype inspection. Details of the important parts and sub assemblies listed at Annexure B shall be furnished by the successful tenderer/manufacturer to DG/(TI), RDSO Lucknow for record. Routine tests Every CB / interrupter shall be subjected to the routine tests at the manufacturers works as per Clause 7 of IEC 62271-100 /.Routine test reports of items / components used shall be made available to the testing authority. The routine test comprise -

14.4

14.5

14.6

14.7

14.8

Page 45 of 67
(i) (ii) (v) (vi) (vii)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Rated one minute power frequency dry withstand voltage test on the main circuit as clause no. 13.10.1 Dielectric test on control and auxiliary circuits as per clause no.13.10.2 Measurement of contact resistance of main circuit as per clause no. 13.10.3 Mechanical operation tests as per clause no. 13.10.4 Design and visual checks as per clause no. 13.10.5

14.8.1

Rated one minute Power Frequency Dry withstand Voltage Test The Circuit Breaker/Interrupter Power frequency dry withstand voltage Test on complete CB/ Interrupter for 1 minute.

14.8.2

Dielectric tests on control and auxiliary circuits The control and auxiliary circuits shall withstand 2000V ac for one minute After disconnecting spring charging motor. The spring charging motor Shall Withstand 1500 V ac for one minute.

14.8.3

Measurement of contact resistance of main circuit The resistance shall be measured by dc voltage drop. The measured Value shall not exceed 1.2 times the value of resistance recorded before Temperature rise test during the type tests approved by DG/(TI), RDSO.

14.8.4

Mechanical operation test The test comprising five opening and five closing operations at each of the rated, maximum and minimum control voltages ie. at 110V dc, +10% and -15% for closing operations and at 110V dc -30% for opening Operations shall be performed. The contact travel characteristics shall be Recorded for each closing and opening operations. The characteristics Shall be within the tolerances specified in SOGP/ type test values Approved by DG/(TI), RDSO.

14.8.5

Design & visual check The CB shall be checked to verify its complaints with this specification.

Page 46 of 67
In (i) (ii) (iii) (iv) (v)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

particular following items shall be checked: Verification of dimension of equipment and assembly as per drawings/datasheet approved by RDSO. Verification of operation under local and remote. Verification of clearances as per approved drawing Quality of painting / galvanizing of cubicles and mounting structure Fasteners used in various assemblies shall be of stainless steel for 12mm dia or below and those above 12mm may be hot dip galvanized or stainless steel. Verification of behavior under local electrical command while on local/ remote selector switch is in remote and vice versa, the CB should not operate. Verification of manual opening and closing operation Verification of emergency device for opening of CB in the event of failure as per clause 6.1.4.4

(vi)

(vi) (vii)

(viii) Verification of rated operating sequence (ix) Verification of Interlocking

The CB should not close either on remote or on local (Mechanical or Electrical) if key of the Interlocking key is removed from the CB operating mechanism. (x) (xi) (xii) Measurement of spring charging time. Verification of contact wears indicator position. Measurement of current drawn by the motor for spring spring mechanism

(xiii) Verification of function of tripping device in the event of 82 V / 110 V dc supply failure (CTD). (xv) Verification of function of anti pumping device for VCB

Page 47 of 67
(xvi) (xvii) (xviii) (xix) (xx) (xxi) (xxii) (xxiii) (xxiv) 15.0

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Measurement of resistance of operating coils. Verification of wiring and numbering of cables. Verification of signal positions for close/ trip and spring charged/ Spring discharged. Verification of make, type designation and rating of parts / components. Verification of name plate details. Verification of type and routine test reports of parts/ components Used. Checking of proper fixing and support of springs, gas pipes, relays, Gauges and tripping/ closing coils. Checking of free movement of armature of opening and closing Coils. Visual check of painting and galvanization.

The tenderer shall specifically indicate in a statement attached with his offer, his compliance with each clause and sub clause of the specification. A separate statement shall be attached either the offer indicating references to the clauses where the tenderer deviate there from together with the detailed remarks/justification. If either the statements of the compliance or statements of deviation is not attached with the offer, t is not likely to be considered. For the reason that it is an incomplete offer which can not be properly evaluated and compare with other offers if any. If there re more deviations, a NIL statement shall be attached. Following drawings/ documents to be furnished along with the tender: (i) (ii) (iii) (iv) Full dimensioned General Arrangement drawing indicating clearances, fixing arrangement of the mounting structure on the foundation. Schematic drawing. QAP for the equipment ISO certification

16.0

Page 48 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

(v) (vi) (vii)

List of essential plant, machinery and testing facilities. Type test report for relevant rating as per RDSO /IEC specification. List of supplies and performance reports for the tendered equipment from user railway/ other customer.

(viii) Information furnished in the schedule of guaranteed technical performance, data and other particulars (Annexure A) shall be complete in all respects. If there is any entry like shall be furnished later or blanks are left against any item, the tender is not likely to be considered as such omissions cause delays in finalizing the tender. 17.0 17.1 Technical data and drawing to be furnished by successful tenderer/ manufacturer Details of the important parts and sub assemblies listed at Annexure B shall be furnished by the successful tenderer/ manufacturer to RDSO after award of contract. The successful tenderer shall submit the following details/ dimensioned drawings as per Indian Railways Standard in sizes of 210mm x 297mm or any integral multiples thereof for approval. (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) Name / rating plate. General assembly showing mounting arrangement and overall dimensions. Schematic and wiring diagram with explanation sheet. Cross-section of interrupting chamber indicating the arcing /main Contacts and nozzle (s) or of the vacuum bottle a the case may be. Details of main, fixed and moving contacts and arcing contacts. Operating and coupling mechanism of complete CB along with schematic diagram showing the mechanical linkages with explanation sheet. Detailed drawings for springs for closing and opening. Full details of all sealing points with details of O rings and gaskets. Details of Terminal Connector.

17.2

Page 49 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

(ix) Details of porcelain hollow insulators for support and interrupting chamber. (xi) Plain mass concrete foundation, drawing and design calculations. (xii) Design calculation for structural safety along with the details of supporting structure. (xiii) Erection, commissioning, operation and maintenance manual. (xiv) Details of main parts/ sub assembly as per Annexure B. (xv) Any other drawing considered necessary by the successful tender/ manufacturer and / or Purchaser. 17.3 Numbering of drawings shall be so structured as to give information about total number of drawings , data sheets/ instructions sheets relating to the contract for example a drawing designated as D307 [4-12] sheet 2 of 5 denotes that : (i) (ii) (iii) 17.4 D 307 is the drawing number the choice of which is left to the successful tenderer. It is the 4th drawing out of a total set of 12 drawings / datasheet for the contract. It is the 2nd sheet out of total 5 sheets and Cross reference of identical drawing if approved for earlier contract shall be given in the drawing information required during commissioning and maintenance of equipment shall be shown in greater detail. After approval, six copies of approved drawings along with 2 set of reproducible prints shall be supplied to each consignee. Drawings shall be made in Auto CAD R14, which is window based for approval to RDSO. Two sets of approved drawings of hard copies, one copy of RTF and one set of floppies in Auto CAD R14 shall be sent to RDSO for record. Space earmarked for assigning RDSOs drawing number shall be available on the right hand top side of each drawing. Numbering shall be allotted by RDSO after approval of drawing. Five copies of the approved erection, commissioning, operation and maintenance manual shall be supplied to each consignee, in case order is

17.5

17.6

17.7

Page 50 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

more than 10 nos. In case order is less than 10 nos two copies of manual shall be supplied. Two copies of manuals shall be supplied to the Purchaser/DG (TI), RDSO, Lucknow (India) for record. 17.8 Drawings approved by RDSO after prototype approval shall be submitted for the future contracts also till the validity of prototype approval with a clear certification on the drawing that design, process and material have not been changed in the design of the subject equipment from the prototype already approved by RDSO. Erection, Testing and commissioning The CB shall be erected and commissioned by the Purchaser / manufacturer. However, incase a defect/ deficiency is noticed, the manufacturer/ successful tenderer will have to depute his engineer foe necessary remedial action without any cost to the Railways. In all the cases in which an order is placed either on new manufacturer or for a new type/ design of the CB, services of manufacturers engineer shall be made available during the erection and proving/ pre commissioning test for the first order of their CB free of cost. For this purpose, prior intimation regarding the date and location shall be given by the purchaser to the successful tenderer/ manufacturer. 19.0 19.1 Spares The tenderer shall furnish along with his offer, a list of spares (with cost) recommended by him for maintenance of CB for a period of 10 years. The list should include gaskets/ O rings, parts which are likely to wear and items requiring replacement/ replenishment, besides other items recommended by the manufacturer. The successful tenderer shall give an undertaking to the effect that he shall supply the required spares for the total life of the equipment (i.e. 25 years approx.) The tenderer shall furnish along with his offer, the cost of gas filling arrangement, evacuation plant for SF6 gas and cost of SF6 in 10kg cylinder. Training of Indian Railways Engineers The offer shall include the training of two engineers of the Indian Railways free of cost at the manufactures works in India or abroad and at the maintenance depots/ workshops on a railway system or other public utility where circuit breakers of similar/ identical design are n operation. The total duration of training for each engineer shall be four weeks of which approximately two weeks will be at manufacturers works

18.0

19.2

20.0

Page 51 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

and two weeks on a railway system or other public utility. If the country of manufacturer is not India, the cost to travel to that country and back will be borne by the Indian Railways. Other details shall be settled at the time of finalizing the contract/ Purchase order. 21.0 21.1 After sales - service The successful tenderer shall make necessary arrangements for closely monitoring the performance of the CB through periodical (preferably once in two months during warranty period) visit to the locations where they are erected for observations and interactions with operating and maintenance personnel of Indian Railways. Arrangements shall also be made by the successful tenderer/ manufacturer for emergency/ stand by spare parts being kept readily available. To meet exigencies warranting replacements so as to keep the CB in service with listed on time. Successful tenderer/ manufacturer shall respond promptly and in a work man like manner to any call given by Indian Railway for any assistance by way of attending to failures, investigations into the causes of failures including the tests, if any, to be done and such other items with a view to seeing that the CB serves for the purpose for which it is procured. Besides, technical guidance to ensure proper operation and maintenance of the CB shall be constantly rendered. Warranty The successful tenderer/ manufacturer shall warrant that all equipments shall be free from defects and faults in design, material, workman ship and manufacture and of the highest grade consistent with the established and the generally accepted standards for the equipment of the type order and in full conformity with the specifications and shall operate properly. This warranty shall cover inspection of, payment for and acceptance of the equipment, but shall expire 30 (thirty) months after the delivery at ultimate destination, or 24 (twenty four) months from the date of commissioning and proving test of the equipment at ultimate destination in India whichever period expires earlier, except in respect of complaints, defects and / or claims notified to the successful tenderer/ manufacturer within 3 (three) months of expiry of such date. Any approval or acceptance by the purchaser of the equipment shall not in any way limit the successful tenderer/ manufacturers liability. The successful tenderer/ manufacturers liability in respect of any complaint, defects and / or claims shall not be limited to the furnishing and installation of replacement of parts of free of any charge or the

21.2

22.0 22.1

Page 52 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

repair of defective parts only to the extend that such replacements or repairs are attributable to or arise from faulty workman ship or material or design in the manufacture of goods, provided that the defects are brought to the notice of the successful tender/ manufacturer with in 3 (three) months of their being first discovered during the warranty period of 3 (three) months from the date of expiry of warranty period, or at the option of the Purchaser, to the payment of the value, expenditure and damage as here after mentioned. The successful tenderer/ manufacturer shall, if required, replace or repair the equipment of such portion there of as is rejected by the purchaser free of cost at the ultimate destination or at the option of the Purchaser. Successful tenderer/ manufacturer shall pay to the Purchaser value there of at the contract price or in the absence of such price at a price decided by the Purchaser and such other expenditure and damages as may arise by reason of the breach of the conditions herein specified. All replacement and repairs that the Purchaser shall upon the successful tenderer/ manufacturer to deliver or perform under this warranty shall be delivered and performed by the successful tenderer/ manufacturer, promptly and satisfactorily and in any case with in 2 (two) months of the date of advice to this effect. If the successful tenderer/ manufacturer so desires, the parts that are removed may be taken over by him or his representative for disposal as he deems fit at the time of replacement with good parts. No claim what so ever shall lie on the Purchaser there after for the parts so removed. The warranty here in contained shall not apply to any material which shall have been repaired or altered by the purchaser or on his behalf in any way without the consent of successful tenderer/ manufacturer, so as to affect the strength, performance or reliability or to any defects to any part due to misuse, negligence or accident. 22.8 The decision of the Purchaser in regard to successful tenderer/ manufacturers liability and the amount, if any, payable under this warranty shall be final and conclusive. Packing and dispatch The various components of each CB shall be securely packed in wooden crates/ boxes. General packing list, together with weight and overall dimensions of each packing case shall be furnished for each CB indicating the following.

23.0 23.1

Page 53 of 67
Crate/ Box No.

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Description of item/ component in the crate/ box

Gross weight in kg

Approximate outside dimensions

23.2 23.3 23.4 23.5

As far as possible, the gross weight of a crate/ box shall be so kept that it shall be possible to manually handle it by two persons. In case of overseas supplies, packing shall be sea worthy. Necessary instructions for handling and storage shall also be furnished for use at receiving end. Porcelain housing/ support insulator shall be supplied securely packed in wooden crates. Not more than two porcelain housing/ support insulators shall be packed in a crate in order to facilitate manual loading and unloading.

==============

Page 54 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Annexure A Schedule of Guaranteed Performance Technical and other particulars for 22KV/ 25 kV, SP/ DP/POLE MOUNTED, Outdoor Type, Vacuum Circuit Breaker/ Interrupter, Guaranteed particulars are to be established by test reports/ actual tests. S.No. 1 2 3 A 4 5 6 7 8 Description Makers Name Country of Manufacture Manufacturers type Designation (i) Circuit breaker pole (ii) Operating mechanism RATING Number of poles Rated voltage Voltage rating class as per standard Rated normal current Rated frequency Rated insulation level of the circuit breaker (i) One minute dry and wet power frequency withstand voltage (ii) Switching surge withstand voltage (iii) Standard lighting impulse withstand voltage 1.2/ 50 s waveform ( full wave) (iv) Corona extension voltage Rated short circuit breaking current (i) Symmetrical at a recovery voltage of not less than the highest system voltage (ii) Asymmetrical at a recovery voltage of not less than the highest system voltage (iii) Breaking capacity (symmetrical) Rated making current Rated line charging breaking current Rated cable charging breaking current Rated small inductive breaking current Unit of measurement Values to be supplied by tenderer

No. kV kV A Hz

kV (rms) kV (p) kV (p) kV (rms) kA

10

kA MVA kA peak A A A

11 12 13 14

Page 55 of 67
15 16 17 18 19 B 20 21 22

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

23 24 25

26 27 28 29 30 31 32 33

Rated capacitor bank breaking current Rated short time current (i) for 1 s (ii) for 3 s Rated operating sequence Rated transient recovery voltage Breaking current on out of phase condition CONSTRUCTIONAL FEATURES Number of breaks per pole Total length of break per pole Contact travel characteristics (i)Length of contact travel (ii)Closing speed(60% contact travel ) (iii)Opening speed (60% contact travel ) (iv)Contact bounce (v)Bounce duration (Please furnish a graph showing contact travel characteristics) Type of main contacts Type of arcing contacts Details of vacuum bottle ( for Vac.CB) Make Type designation Voltage class Total weight Weight of pole assembly per pole per circuit breaker Weight of operating mechanism Total weight of circuit breaker Minimum electrical clearance (i) between poles (ii) between live part and earth Minimum sectional clearance between lowest live part and any part where a person may stand Minimum height of bottom most part of any insulator from ground level Distance between centers of pole for TP & DP CB Overall dimensions of the circuit breaker complete with insulators, operating mechanism cubicle etc. Mounted on the supporting structure. (i) Length

A kA kA kV kA (rms)

Mm mm m/s m/s mm (max) s (max)

kV kg kg Kg Kg mm mm Mm Mm Mm

mm

Page 56 of 67
(ii) (iii)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Width Height

mm mm

C 34 35 36 37

(Please furnish the General Arrangement drawing with overall dimension) OPERATING PARTICULARS Closing time from the instant of closing coil energisation (max) Opening time from the instant of trip coil energisation(max) Make Time (max) Arcing Time (i) At rated normal current (ii) At rated short circuit breaking current (iii) At 60% of short circuit breaking current (iv) At 30% of short circuit breaking current (v) At 10% of short circuit breaking current Critical current Total break time from the instant of trip coil energisation to the final extinction of arc (i) At rated normal current (ii) At short circuit breaking current Rated restriking voltage (i) Amplitude factor (ii) Rate of rise at natural frequency (iii) Type and device used to limit rate of rise of restriking voltage Minimum time interval (t) permissible between successive CO operation after first auto reclosure

Ms Ms Ms ms ms ms ms ms ms ms kA

38 39

40

ms ms kV

41

42

Number of operations (close and open) the circuit breaker can perform with the No available stored energy Number of operations permissible without change of vacuum bottle (i) At 50% of rated current

43

No

Page 57 of 67
(ii) (iii) (iv)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

44

At 100% of rated current At 50% of rated current At 100% of short circuit breaking current Number of operations permissible without replacement/ inspection of contacts ( min ) (i)At 50% of rated current (ii)At 100% of rated current (iii)At 50% of short circuit breaking current (iv)At 100% of short circuit breaking current ( A graph establishing the above two parameters at SN 49 and 50 should be enclosed ) First pole to clear factor (In case of TP and DP CBs) OTHER TECHNICAL PARTICULARS Maximum rise at temperature over an ambient of 50C when carrying its normal rated current continuously (i) Main contacts of vacuum bottle (ii) Terminal when connected with external connectors (iii) Metal parts arcing as springs (iv) Metal parts in contact with insulators (v) Auxiliary contacts (vi) Operating coils Power required for tripping / closing (max) Control circuit voltage with permissible voltage variation (i) Closing coil (ii) Tripping coil (iii) Contactors ( if any) (iv) any other item ( for which the tenderer feels that the voltage is to be maintained within certain limits)

No No No

No No No No

45 D 46

C C C C C C W

47 48

V dc % V dc % V dc % V dc %

+%/+%/+%/+%/-

Page 58 of 67
49 50 51

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

52

Type of tripping / closing mechanism Manual tripping / closing mechanism (lever push button or any other device) Spring charging motor (i) Make and type designation (ii) Rating (iii) Voltage with permissible variation (iv) Power frequency withstand voltage (v) Class of insulation (vi) Time required by the motor to charge the spring(s) fully (vii) Power required at normal controlled voltage to charge the spring (viii) Mode of protection (ix) Specification of design and testing Springs- Closing / Opening No. of springs Type (Compression/tension) Specification of testing and design Porcelain Insulators (i) Makers name and type designation (ii) Minimum creepage distance (i) (ii) (iii)

kW V kV (rms) s W

IS/ IEC

IS/IEC Support Insulator Interrupting Chamber Insulator V

53

54 55 56 57

Insulation grade of PVC control wiring cable Approximate height of close/trip switch and socket for spring charging from ground level. Details of Operation counter: (i) Make and type (ii) No. OF digits Auxiliary Switch (contacts) (i) Make and type (ii) Normally open contacts (iii) Normally close contacts (iv) Continuous ratings of contacts

Total Total A

Spare Spare

Page 59 of 67
(v)

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

58

Breaking capacity of contacts at 220V dc with inductive load (vi) Life (No. of operations) Limit switch ( for spring charging motors) (i) Make and type (ii) Continuous ratings of contacts (iii) Breaking capacity of contacts at 220V dc with inductive load (iv) Life (No. of operations) OTHER DETAILS Is the circuit breaker having a common drive (for TP & DP CB)? Is vacuum bottle easily replaceable Is a device for tripping the circuit breaker, in the event of 82 V / 110V dc supply failure, provided? The Circuit Breaker should TRIP automatically below 82V. (Indicate the type of the device)? Does provision of trip circuit supervision exist? Is electrical anti-pumping device provided? Is mechanical closing device provided? Is local electrical closing & tripping device provided? Is manual closing & tripping device provided? Is terminal connector of CB provided? Is mechanical tripping device provided? Is handle/crank for manual charging of the closing spring provided? Is operating counter visible without opening the mechanism door? Are the mechanical close and open indicator provided? Is two position LOCAL/REMOTE switch provided? Indicate type- (spring loaded) Is the CB trip free? Are electrical and mechanical interlocks with keys provided?

A No.

A A No

E 59

Yes/No

60 61

Yes/No CTD/No volt relay

62 63 64 65 66 67 68 69 70 71 72 73 74

Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No

Page 60 of 67
75

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

76 77 78 79 80 81 82 83

84 85 86 87 88 89 90 91 92 93 94

Is the operating mechanism housed in a dust weather vermin proof cabinet of 2mm thick sheet steel construction? (indicate the protection) Is a heater provided for prevention of condensation of moisture in the operating mechanism box? Is three pin socket and inspection lamp provided? The size and number of cable glands provided What is the insulation grade of PVC cable used? Are the cables terminated with crimped lugs? Is ac and dc +ve & -ve wiring completely segregated? Are the terminal blocks for wiring dust proof and provided with unbreakable transparent shrouds? Are the two distinct earthling terminals provided with indication for earth? (i) Support structure (ii) Operating mechanism cubicle Are fasteners of 12mm dia and less exposed to atmosphere of stainless steel? Are fasteners of more than 12mm dia of stainless steel or mild steel hot dip galvanized? If supervision for erection testing and commissioning is provided? If training of two IR engineers be arranged for a total period of 4 weeks? Is warranty provided as per clauseNo.22? Has list of spares been furnished? Has list of special maintenance tools furnished? Has erection operation and maintenance manual furnished? Does provision of slow opening and slow closing exists? Have closing/tripping springs properly fixed to prevent their misalignment? If any deviations asked? Give number of clauses where deviation has been asked

Yes/No

Yes/No Yes/No Dia Dia V Yes/No Yes/No Yes/No No No

Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Clause No.

Page 61 of 67
95 96 97 98 99

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Is any external indicator for contact wire provided? What are the test certificates attached? Please list out If painting of steel surfaces exposed to weather done to RDSOs specifications? If the support structure and operating mechanism cubicle hot dip galvanized? Quantity of zinc or galvanization

Yes/No

Yes/No Yes/No Kg/m2

Page 62 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Annexure- B The following information shall be furnished by the manufacturer/ supplier. Sl. No. 1. Description Details of Permanent Magnet a) Make b) Type and its Material c) Governing Specification d) Maximum service temperature ie, the max.temperature to which the magnet may be exposed with no significant long range Instability or structural changes. e) Curie Temperature ie, the transition temperature above which material looses its Magnetic properties. Capacitors used for opening and closing a) Make b) Description and Type c) Type designation d) Identification Mark e) Governing Specification. f) Rating i) Capacity in Farad ii) Operating voltage with permissible variation Electronic controller Unit a) Description and Type b) Type Designation c) Identification Mark d) Governing Specification Proximity Switches a) Make b) Description and Type c) Type designation d)Rating Unit of measurement

Page 63 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Vacuum Bottle (i) Description and type Designation (ii) Make (iii)Rating (iv)Identification mark. (v)Item drawing No (vi)Geometry of contact (vii)Governing specification No. (viii)Weight (ix)Level of vacuum adopted (x)Level of current chopping (xi)Shelf life Auxiliary contact (i) Description and type Designation (ii) Make (iii)Identification mark (iv)Item drawing No. (v)Governing specification No. (vi)Rating (a)Voltage (b)Continuous Current (c)Breaking and making Current (d)Electrical & Mechanical life( No. of operations)

Motor limit switch (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No. (vi)Rating (a)Voltage (b)Continuous Current (c)Breaking and making Current (d)Electrical & Mechanical life( No. of operations)

Page 64 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

MCBs (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No. (vi)Rating (a) Voltage (b) Continuous Current (c) Breaking and making Current (d) Electrical & Mechanical life( No. of operations)

Spring charging motor (i) Description and type (ii ) Type designation (iii) Make (iv) Identification mark (v) Governing specification No. (v) Rating (a) Voltage(with permissible variation) (b) Wattage (c) Power frequency voltage withstand (d) Class of insulation (e) Time required by the motor to charge the spring fully(max) (f) Power required at normal control voltage to charge the spring (g) Mode of operation

Page 65 of 67
10

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

Spring- Closing/ Tripping /Other (i) Description and type (ii) Type designation (iii) Make (iv) Identification mark (v) Governing specification No. (vi) Drawing No. (vii) Rating (a) No. of springs (b) Type(compression/ tension/spiral) (c) No. of turns (d) Gauge (e) External diameter (f) Stiffness (g) Material (f ) Force developed in fully charged position Operating coil Closing Tripping (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No. (vi)Rating (a) Operating voltage (with permissible variation) (b) Power (c) Resistance at 20 C (d) Class of insulation

11

12

Operation counter (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No. (vi) No. of digits

Page 66 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

13

Heater (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No (vi)Rating (a) Voltage (b) Power (vii) Make and type designation of thermostat (if used) Interlock (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No (vi)Electrical rating of switch used

V - ac W

14

dc

15

16

O Ring and Gasket(Please furnish details for all the varieties) (i) Description and make (ii) Dimension/Drawing No. (iii) Material and Specification Terminal connector (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No (vi)Rating (a) Voltage (b) Current

ac A

Page 67 of 67

Effective from 01.07.2012

SPEC. No. TI/SPC/PSI/LVCBIN/0120

17

Relays and contactors( please furnish details for all the types of relays/ contactors used) (i)Description and type (ii)Type designation (iii)Make (iv)Identification mark (v)Governing specification No (vi)Rating (a) Operating voltage range (b) Pick up voltage (c) Drop out voltage (d) Burden (e) Auxiliary contact rating (f) Guaranteed life 1. Electrical 2. Mechanical (g) Wiring details (drawing No.) Shock Absorber (i) Description and Type (ii) Type Designation (iii) Identification Mark (iv) Governing Specification (v) Type Brand and Specification of fluid used (if any)

V V V V No. of operations No. of operations

18