Water Softeners Residential 9100SXT Valve Softeners US Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

9100SXT Valve

Meter Initiated Water Softener Operation Manual

Read all instructions carefully before operation.

#54745 2/09

Performance

Item Number 7627 7628 7629


(1)

Model Number 9100SXT-30 TMI 9100SXT-45 TMI 9100SXT-60 TMI

Capacity at regeneration salt levels (kilograins as CaCO3) @15lb/cf 30 45 60 @10lb/cf(1) 27 41 55 @6lb/cf 20 30 40

Service Flow Rate(2) USGPM (LPM) 10 (37.9) 11 (41.6) 15 (56.8)

Maximum Flow To Drain USGPM (LPM) 1.5 (5.7) 2.0 (7.6) 3.0 (11.4)

Resin Volume per tank cu.ft. (litres) 1.00 (28) 1.50 (43) 2.00 (57)

Mineral Tank Size Width x Height inches (mm) 9 x 48 (229 x 1219) 10 x 54 (254 x 1372) 12 x 52 (305 x 1321)

Brine Tank Size Width x Height inches (mm) 21 x 36 (533 x 914) 21 x 36 (533 x 914) 21 x 36 (533 x 914)

Salt Capacity Lbs. (kg) 308 (140) 308 (140) 308 (140)

Shipping Weight Lbs. (kg) 185 (84) 248 (113) 340 (154)

10lb/cu.ft. salt dosage is the standard factory setting.


Operating Temperature Range: 34 to 110F (1 to 43C)
Operating Pressure Range: 20 to 120 psi (137 to 827 kPa)
Electrical: 24V/60Hz with a supplied 120V/60Hz Wall Mount Approved Class 2 Transformer
Capacities are based on two tanks of resin. Eg: 9100SXT-30 set at 10lb/cf salt setting would provide 27,000 grains of hardness removal for one tank.

These products are not intended to be used to treat water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system. The manufacturer reserves the right to make product improvements which deviate from the specifications and descriptions stated herein without obligation to change previously manufactured products or to note the change. Peak flow rates are intended for intermittent use only and are for residential application only. 1 kilograin is equal to 1000 grains.

How Your 9100SXT Downflow Water Conditioner Works

Hard water enters your home through the main supply line, enters the softener and passes down through a resin mineral bed which softens the water. An ion exchange process takes place in which the resin beads capture and hold calcium and magnesium, the hardness minerals, while the water takes on sodium ions. The soft water then flows into your household water line. In normal operation, the Time of Day display will alternate being viewed with the Volume Remaining display then the Tank in Service. This display will be in gallons, liters or cubic meters. The tank in service will be shown as U-I or U-2. As treated water is used, the Volume Remaining display will count down from a maximum value to zero or (---).Once this occurs, a regeneration cycle will be initiated at the Set Regeneration Time. Water flow through the valve is indicated by the Flow Indicator that will flash in direct relationship to flow rate. Example 833 Gallons of Treated Water Remaining
PM Indicator Flow Indicator
(Flashing with water flow)

Tank In Service

0 Gallons of Treated Water Remaining

PM Indicator Flow Indicator


(Flashing with water flow)

Control Operation During Regeneration


In regeneration, the control will display a special regeneration display. In this display, the control will show the current regeneration step number the valve is advancing to or has reached and the time remaining in that step. The step number displayed will flash until the valve has completed driving into this regeneration step position. Once all regeneration steps have been completed, the valve will return to Service and resume normal operation. Example Less than 6 minutes remaining in Regen Step Rapid Rinse

Pushing the Extra Cycle Button during a regeneration cycle will immediately advance the valve to the next cycle step position and resume normal step timing.

Control Operation During Programming


The control will only enter the Program Mode with the valve in Service. While in the Program Mode, the control will continue to operate normally, monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently, eliminating the need for battery back-up power.

Meter Immediate Control


A meter immediate control measures water usage and regenerates the system as soon as the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity (typically expressed in grains/unit volume) by the feed water hardness and subtracting the reserve. Meter Immediate systems generally do not use a reserve volume. However, in twin tank systems with soft-water regeneration, the reserve capacity should be set to the volume of water used during regeneration to prevent hard water break-through. A Meter Immediate control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.

Meter Delayed Control


A Meter Delayed Control measures water usage and regenerates the system at the programmed regeneration time after the calculated system capacity is depleted. As with Meter Immediate systems, the control calculates the system capacity by dividing the unit capacity by the feed water hardness and subtracting the reserve. The reserve should be set to insure that the system delivers treated water between the time the system capacity is depleted and the actual regeneration time. A Meter Delayed control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.

Time Clock Delayed Control


A Time Clock Delayed Control regenerates the system on a timed interval. The control will initiate a regeneration cycle at the programmed regeneration time when the number of days since the last regeneration equals the regeneration day override value.

Day of the Week Control


This control regenerates the system on a weekly schedule. The schedule is defined in Master Programming by setting each day to either off or on. The control will initiates a regeneration cycle on days that have been set to on at the specified regeneration time.

Control Operation During a Power Failure


The SXT includes integral power backup. In the event of power failure, the control shifts into a power-saving mode. The control stops monitoring water usage, and the display and motor shut down, but it continues to keep track of the time and day for a minimum of 48 hours. The system configuration settings are stored in a non-volatile memory and are stored indefinitely with or without line power. The Time of Day flashes when there has been a power failure. Press any button to stop the Time of Day from flashing. If power fails while the unit is in regeneration, the control will save the current valve position before it shuts down. When power is restored, the control will resume the regeneration cycle from the point where power failed. Note that if power fails during a regeneration cycle, the valve will remain in its current position until power is restored. The valve system should include all required safety components to prevent overflows resulting from a power failure during regeneration. The control will not start a new regeneration cycle without line power. If the valve misses a scheduled regeneration due to a power failure, it will queue a regeneration. Once power is restored, the control will initiate a regeneration cycle the next time that the Time of Day equals the programmed regeneration time. Typically, this means that the valve will regenerate one day after it was originally scheduled. If the treated water output is important and power interruptions are expected, the system should be setup with a sufficient reserve capacity to compensate for regeneration delays.

Installation Instructions

All government codes and regulations governing the installation of these devices must be observed. CAUTION:If the ground from the electrical panel or breaker box to the water meter or underground copper pipe is tied to the copper water lines and these lines are cut during installation of the Noryl bypass valve and/or poly pipe, an approved grounding strap must be used between the two lines that have been cut in order to maintain continuity. The length of the grounding strap will depend upon the number of units being installed and/or the amount of copper pipe being replaced with poly. See Figure 1. In all cases where metal pipe was originally used and is later interrupted by poly pipe or the Noryl bypass valve as in Figure 1 or by physical separation as in Figure 2, An approved ground clamp with no less than #6 copper conductor must be used for continuity, to maintain proper metallic pipe bonding. Check your local electrical code for the correct clamp and cable size. Check your local electrical code for the correct clamp and cable size. 1. Determine the best location for your water softener, bearing in mind the location of your water supply lines,
drain line and 120 volt AC electrical outlet. Subjecting the
softener to freezing or temperatures above 110F
(43C)will void the warranty.

Figure 1

Electrical Panel Ground Strap Copper Pipe

Ground From Panel

Poly Pipe

Poly Pipe

Softener c/w Plastic Bypass

Water Meter

Figure 2
Outside Water Line For Outside & 3rd Tap Comes From Meter

Media Installation (When Necessary) Remove the valve from the mineral tank. Unfiltered Water Bypass Ground Strap Required Loop Cut & Capped Because of Break in Continuity Temporarily plug the open end of the riser tube to ensure that no resin or gravel falls down into the distribution. Filtered Water Line in Home Fill mineral tank one quarter full of water to protect distribution during gravel installation. Slowly and carefully add the gravel support bed and the softener or filtration media leveling each layer as it is placed into the tank. Unplug the riser tube, carefully position the valve over it and turn the valve into the threads in the fiberglass tank, tightening securely into tank. Note: Ensure that the internal O-ring in the valve fits securely over the riser tube. Silicone grease (#13691) or other food grade lubricant may be applied to the O-ring to ease installation of the riser tube. DO NOT use petroleum based lubricants as they will cause swelling of O-ring seals. The softener or filter is now charged with softening resin. It is recommended that the softener or filter tank now be completely filled with water (SLOWLY) to soak the resin or filtration media before startup. This will allow the media to absorb water as well as help displace any trapped air. This will reduce the chance of backwashing resin or filter media out of the tank during the initial backwash on startup. 2. Outside faucets used to water lawns and gardens should not supply softened water. A new water line is often required to be connected to supply hard water to the inlet of the water softener and to the outside faucets. Cut the water line between where it enters the house and before any lines that branch off to feed the hot water heater or other fixtures in the house and as near the desired location of the water softener as possible. Install a tee fitting on the feed end of the cut pipe, and an elbow fitting on the other end. Install piping from the tee to the inlet of the water softener and from the elbow to the outlet of the softener. To sever the water lines which branch off to feed any outside faucets, cut the branch lines approximately two inches from the fitting on the main water line. Install an elbow on the end of the pipe nearest the outside faucet and a cap on the end connected to the existing water line. Install piping from the tee installed on the inlet line to the water softener to the elbow installed on the pipe to the outside faucet. Following this procedure will result in all lines in the house, with the exception of the outside faucets, but including the water heater and therefore the hot water lines, being supplied with soft water. 3. Familiarize yourself with the location of the inlet, outlet and drain on the control valve. Be very careful not to get the controls wet.

Figure 3

4. Attach the bypass valve to the control valve. Connect the inlet and outlet of the water softener to the plumbing in the house. The control valve must not be submitted to temperatures above 71C (110F). When sweat fittings are used, to avoid damaging the control valve, solder the threaded copper adapters to the copper pipe and then, using Teflon tape, screw the assembly into the bypass valve. CAUTION - do not use pipe thread compound as it may attack the material in the valve body. 5. Using Teflon tape, screw the 1/2" hose barb into the drain port in the valve. Attach 1/2" drain hose to the hose barb and tighten securely with a hose clamp. Run the drain line to a floor drain or a laundry drain. Complete any necessary plumbing. 6. On twin tank units, pull the 3/8" brine line through the hole in the back of the brine tank. Connect the brine line to the fitting on the side of the valve using the nut and ferrule. Tighten snugly. 7. Make sure the bypass valve is in the service position. 8. Plug the 24-volt transformer into a 120 VAC 60 Hz outlet. This valve has four positions: 1) Backwash 2) Brine/Rinse 3) Rapid Rinse and 4) Brine Refill. When the valve is in the Service position, the extra cycle button(far left button as shown on Figure 4) must be pressed and held for 5 seconds before it activates. Press and hold the extra cycle button for 5 seconds to advance the valve into the 1 Backwash position. Slowly turn on the water supply and allow the unit to backwash until the air purges out of the tank and clears the system. 9. Press the extra cycle button to advance the valve to the 2 position. Press once more to advance to the 3 position. Press once more to advance to the 4 Brine refill position. Wait until the water level reaches 6" in the brine tank. Water can be added to the tank to speed up the filling but the valve should be in the Brine Refill position for a minimum of two minutes to purge the air out of the injector set. 10. Press the extra cycle button to advance the valve from the Brine Fill position through service to the 2 position Brine/Rinse position. Verify that water is being drawn from the tank. If not, repeat step 9. 11. Press the extra cycle button to advance the valve to the 3 Rapid Rinse position and allow water to run to drain for 2 minutes. 12. Press the extra cycle button to advance the valve to the 4 Brine Fill position until there is 6 of water in the brine tank. Press the extra cycle button to advance the valve back into the service position indicated by the red dot in upper left corner of the display. 13. Put 40 kgs of crystal water softener salt in the brine tank. The unit will automatically fill to the correct level when it regenerates. Optional Sanitization Procedure: We recommend that all new water conditioners be disinfected as part of the startup. Sanitization is achieved by the application of chlorine in the regeneration cycle of the conditioner. A liquid solution of 5.25% sodium hypochlorite (commonly referred to as household bleach) is recommended as a suitable disinfectant. Use only unscented products. For every cubic foot of resin in the softener, pour approximately two (2) tablespoons of sodium hypochlorite into the brine well tube. The brine tank refill in Step 12 should add the correct amount of water to the brine tank. If not, the water can be added manually now. Press and hold the EXTRA CYCLE button to begin a manual regeneration. Press the EXTRA CYCLE button again to advance the valve to the Brine/Rinse position. Allow softener to complete the Brine/Rinse cycle, then let the manual regeneration continue until the brine tank is refilled again with the correct amount of water.
ALL STATE AND LOCAL GOVERNMENT CODES GOVERNING INSTALLATION OF THESE DEVICES MUST BE OBSERVED. 4

Operating Instructions

Figure 4
The valve has been pre-programmed with factory settings as follows: Regeneration Cycle Step Programming 1. Backwash .....................................10 minutes
2. Brine Rinse ...................................60 minutes
3. Rapid Rinse ..................................10 minutes
4. Brine Refill ....................................08 minutes 9100SXT TMI-30 13 minutes 9100SXT TMI-45 09 minutes 9100SXT TMI 60

Whenever the valve is in Service the current time of day can be set, the control programmed, or an extra regeneration initiated at any time.

Set Time of Day


1. Press and hold either the Up or Down buttons until the programming icon replaces the service icon and the parameter display reads TD. 2. Adjust the displayed time with the Up and Down buttons. 3. When the desired time is set, press the Extra Cycle button to resume normal operation. The unit will also return to normal operation after 5 seconds if no buttons are pressed.

Queueing a Regeneration
1. Press the Extra Cycle button. The service icon will flash to indicate that a regeneration is queued. 2. To cancel a queued regeneration, press the Extra Cycle button.

Regenerating Immediately
Press and hold the Extra Cycle button for five seconds.

User Programming Mode Options


Abbreviation DO Parameter Day Override Description The timers day override setting THIS IS AN OPTION ONLY. PLEASE DO NOT ADJUST BEFORE CONSULTING AN AUTHORIZED DEALER. The hardness of the inlet water - used to calculate system capacity for metered systems The fixed reserve capacity The current day of week

H RC CD

Feed Water Hardness Reserve Capacity Current Day

NOTES:
Some items may not be shown depending on timer configuration.
The timer will discard any changes and exit User Mode if any button is not pressed for sixty seconds.
User Programming Mode Steps
1. Press the Up and Down buttons for five seconds while in service, and the time of day is NOT set to 12:01 PM. 2. Use this display to adjust the Day Override. This option setting is identified by DO in the upper left hand corner of the screen.

THIS IS AN OPTION ONLY. PLEASE DO NOT ADJUST BEFORE CONSULTING AN AUTHORIZED DEALER. 3. Press the Extra Cycle button. Use this display to adjust the Feed Water Hardness. This option setting is identified by FH in the upper left hand corner of the screen.

4. Press the Extra Cycle button. Use this display to adjust the Fixed Reserve Capacity. This option setting is identified by RC in the upper left-hand corner of the screen. 75 gallons X # of people in the house = RC # of People 1 2 3 RC 75 150 225

5. Press the Extra Cycle button to end User Programming Mode.

Error Codes
Note: Error codes appear on the In Service display Error Code [Err 0] [Err 1] Probable Cause Drive motor is stalled Drive motor is running continuously Recover and Resetting Unplug the unit from the power source When power is restored to the unit, the Err _ display code clears. If the condition causing the error has not been resolved the Err _ code reappears in the four digit display. Do not attempt to troubleshoot this problem any further. Regeneration must occur for the unit to recover, the display to clear and the valve to function normally. [ 7 - - 5 ]: To recover from [Err2], the user must initiate a regeneration or set at least one individual day to 1.

[Err 2]

There have been more than 99 days since the last Regeneration. If the Day of the Week mode of regeneration is selected and days since last regeneration exceeds 7 days. [ 7 - - 5 ]: There have been more than 7 days since the last regeneration. All individual settings (d1, d2, d3, d4, d5, d6, d7) are set to 0.

[Err 3]

Control board memory failure.

Perform a Master Reset. If the error returns, do not attempt to troubleshoot this problem any further.

Error Display Example

NOTE: Unit will flash when an error exists.

Manual Regeneration Cycle If you run out of softened water because of inadequate regeneration frequency, inadequate reserve capacity, power failure or unusually high water usage, you can initiate a manual regeneration simply by pressing the extra cycle button. The softener will now automatically complete a regeneration cycle and return to service. If possible, avoid water use during the regeneration cycle. Once you have set your softener and you experience frequent loss of water pressure, you may have to increase the frequency of regeneration by resetting the gallons between regeneration. Automatic Bypass The regeneration cycle lasts approximately 2-1/2 hours, after which soft water service will be restored. During regeneration, hard water is automatically bypassed for use in the household. Hot water should be used as little as possible during this time to prevent hard water from filling the water heater. This is why the automatic regeneration is set for sometime during the night and manual regenerations should be performed when little or no water will be used in the household. Safety Float The brine tank is equipped with a safety float which prevents your brine tank from over filling as a result of a malfunction such as a power failure. Water Pressure Your softener is designed to operated under normal water pressures from 20 psi (1.4 atm) to 100 psi (8.2 atm). New Sounds You may notice new sounds as your water softener operates. The regeneration cycle lasts approximately 2-1/2 hours. During this time, you may hear water running intermittently to the drain. Manual Bypass (Figure 5) In case of an emergency such as an overflowing brine tank, you can isolate your water softener from the water supply using the bypass valve located at the back of the control. In normal operation the bypass is open with the ON/OFF knobs in line with the INLET and OUTLET pipes. To isolate the softener, simply rotate the knobs clockwise (as indicated by the word BYPASS and arrow) until they lock. You can use your water related fixtures and appliances as the water supply is bypassing the softener. However, the water you use will be hard. To resume soft water service, open the bypass valve by rotating the knobs counter-clockwise.

Figure 5
OUTLET

INLET

Maintenance Instructions

Checking the Salt Level Check the salt level monthly. Remove the lid from the cabinet or brine tank, make sure salt level is always above the brine level (you should not be able to see water). Adding Salt Use only clean salt labeled for water conditioner use, such as crystal, pellet, nugget, button or solar.
The use of rock salt is discouraged because it contains insoluble silt and sand which build up in the brine tank and can
cause problems with the systems operation.
Add the salt directly to the tank, filling no higher than the top of the brine well.
Caution Liquid brine will irritate eyes, skin and open wounds - gently wash exposed area with fresh water. Keep children away from your water conditioner. Bridging (Figure 6) Humidity or the wrong type of salt may create a cavity between the water and the salt. This action, known as bridging, prevents the brine solution from being made, leading to your water supply being hard. If you suspect salt bridging, carefully pound on the outside of the plastic brine tank or pour some warm water over the salt to break up the bridge. This should always be followed up by allowing the unit to use up any remaining salt and then thoroughly cleaning out the brine tank. Allow four hours to produce a brine solution, then manually regenerate the softener. Care of Your Softener To retain the attractive appearance of your new water softener, clean occasionally with a mild soap solution. Do not use abrasive cleaners, ammonia or solvents. Never subject your softener to freezing or to temperatures above 110F (43C). Cleaning the Injector Assembly (Figure 7) Sediment, salt and silt will restrict or clog the injector. A clean water supply and pure salt will prevent this from happening. The injector assembly is located on the right side of the control valve. This assembly is easy to clean. Shut off the water supply to your softener and reduce the pressure by opening a cold soft water faucet. Using a screwdriver, remove the two screws holding the injector cover to the control valve body. Carefully remove the assembly and disassemble as shown in Figure 7. The injector orifice is removed from the valve body by carefully turning it out with a screwdriver. Remove the injector throat the same way. Carefully flush all parts including the screen. Use a mild acid such as vinegar or Pro-Rust Out to clean the small holes in the orifice and throat. Reassemble using the reverse procedure. Resin Cleaner An approved resin cleaner MUST be used on a regular basis if your water supply contains iron. The amount of resin cleaner and frequency of use is determined by the quantity of iron in your water (consult your local representative or follow the directions on the resin cleaner package).
O RING INJECTOR COVER INJECTOR SCREEN

Figure 6

Figure 7
INJECTOR BODY INJECTOR THROAT INJECTOR NOZZLE

SCREW

Trouble Shooting Guide

1. CONDITIONER DELIVERS HARD WATER Bypass valve is open No salt in brine tank Injector or screen plugged Insufficient water flowing into brine tank Hot water tank hardness Leak at distributor tube Internal valve leak Flow meter jammed Flow meter cable disconnected or not plugged into meter cap Improper programming CONDITIONER FAILS TO REGENERATE Electrical service to unit has been interrupted Timer is not operating properly Defective valve drive motor Improper programming UNIT USES TOO MUCH SALT Improper salt setting Excessive water in brine tank Improper programming LOSS OF WATER PRESSURE Iron build-up in line to water conditioner Iron build-up in water conditioner Inlet of control plugged due to foreign material broken loose from pipes by recent work done on plumbing system 5. LOSS OF RESIN THROUGH DRAIN LINE Air in water system Drain line flow control is too large 6. IRON IN CONDITIONED WATER Fouled resin bed Iron content exceeds recommended parameters 7. EXCESSIVE WATER IN BRINE TANK Plugged drain line flow control Brine valve failure Improper programming SALT WATER IN SERVICE LINE Plugged injector system Timer not operating properly Foreign material in brine valve Foreign material in brine line flow control Low water pressure Improper programming CONDITIONER FAILS TO DRAW BRINE Drain line flow control is plugged Injector is plugged Injector screen is plugged Line pressure is too low Internal control leak Improper programming Timer not operating properly Close bypass valve Add salt to brine tank and maintain salt level above water level Replace injectors and screen Check brine tank fill time and clean brine line flow tank control if plugged Repeated flushing of the hot water tank is required Make sure distributor tube is not cracked. Check O ring and tube pilot Replace seals and spacers and/or piston Remove obstruction from flow meter Check meter cable connection to timer and meter cap Reprogram the control to the proper regeneration type, inlet water hardness, capacity or flow meter size. Assure permanent electrical service (check fuse, plug, chain or switch) Replace timer Replace drive motor Check programming and reset as needed Check salt usage and salt setting See #7 Check programming and reset as needed Clean line to water conditioner Clean control and add resin cleaner to resin bed. Increase frequency of regeneration Remove piston and clean control

2.

3.

4.

Assure that well system has proper air eliminator control. Check for dry well condition. Ensure drain line flow control is sized Check backwash, brine draw and brine tank fill. Increase frequency of regeneration. Increase backwash time. Add iron removal filter system Clean flow control Replace brine valve Check programming and reset as needed Clean injector and replace screen Replace timer Clean or replace brine valve Clean brine line flow control Raise water pressure Check programming and reset as needed Clean drain line flow control Clean or replace injectors Replace screen Increase line pressure (line pressure must be at least 20 psi at all times) Change seals and spacers and/or piston assembly Check programming and reset as needed Replace timer Replace timer Replace faulty microswitch or harness Replace cycle cam or reinstall

8.

9.

10. CONTROL CYCLES CONTINUOUSLY Timer not operating properly Faulty microswitches and/or harness Faulty cycle cam operation 11. DRAIN FLOWS CONTINUOUSLY Foreign material in control

Remove piston assembly and inspect bore. Remove foreign material and check control in various regeneration positions Internal control leak Replace seals and/or piston assembly Control valve jammed in brine or backwash position Replace piston and seals and spacers Timer motor stopped or jammed teeth Replace timer motor and check all gears for missing teeth Timer not operating properly Replace timer

10

GUARANTEE

HYDROTECH guarantees that your new water conditioner is built of quality material and workmanship. When properly installed and maintained, it will give years of trouble-free service.

FIVE YEAR COMPLETE PARTS GUARANTEE


HYDROTECH will replace any part which fails within 60 months from date of manufacture, provided the failure is due to a defect in material or workmanship. The only exception shall be when proof of purchase or installation is provided and then the warranty period shall be from the date thereof.

TEN YEAR GUARANTEE ON MINERAL AND BRINE TANKS


HYDROTECH will provide a replacement mineral or brine tank to any original equipment purchaser in possession of a tank that fails within 120 months, provided that the water conditioner is at all times operated in accordance with specifications and not subject to freezing or exposure to direct sunlight.

GENERAL PROVISIONS
HYDROTECH assumes no responsibility for consequential damage as a result of escaped water from the water filter; labor or expense incurred as a result of a defect or for failure to meet the terms of these guarantees because of circumstances beyond its control.

WaterGroup Inc. Regina, Saskatchewan Fridley, Minnesota Cambridge, Ontario Durham, North Carolina Calgary, Alberta 1-800-354-7867 1-877-299-5999 www.hydrotechwater.com

You might also like