Introduction
A Grounding Transformer is used to provide a physical neutral for a power transformer with a delta connected downside. The Grounding Transformers neutral point has low impedance and is suitable for different grounding systems such as solid earthing, NER earthing (resistor) and resonance earthing (Arc Suppression Coil). The Grounding Transformer can also be equipped with a low voltage auxiliary winding to be used as local power supply to the substation. Swedish Neutral has together with SGB Germany delivered Grounding Transformers since 1991.

www.swedishneutral.se

Grounding Transformer
A Grounding Transformer provides a physical neutral where one is needed. A Grounding Transformer with built in local power supply can be used as a local transformer. Swedish Neutral also offers five limb YNd (open) connected Grounding Transformers, suitable for neutral grounding of smaller industry grids.

Different Grounding Transformers


Vector group ZN High Voltage Neutral
1N

Vector group YNd (open) five limb Low voltage zero sequence connections

1U

1V

1W

Vector group ZNyn 11/5 With local power winding

Vector group ZNyn 11/5 With LV load disconnector

L1

L2

L3

2N

2U

2V

2W
N L1 L2 L3

2N

2U

2V

2W

1U

1V

1W

1N

1U

1V

1W

1N

Swedish Neutral Grounding Transformer


Manufactured by SGB Germany one of Europes biggest transformer manufacturers Hermetically sealed design (oil cooled) Available for both indoor and outdoor duty (oil cooled / cast resin) Can be delivered with integrated Neutral Earthing Resistor Fused load switch for local power supply as option

Delivery of Grounding Transformer (left) and Arc Suppression Coil (right)

Layout
Grounding Transformer - outdoor

Legend
1. 2. 3. 4. 5. 6. Mounting holes (16mm) for fitting of the Grounding Transformer to the foundation (optional wheels) High voltage bushing Elastimold: Load break/Dead break, DIN, Pfisterer Neutral bushing Elastimold: Load break/Dead break, DIN, Pfisterer Rating plate (movable) Lifting lugs Protective earth

Grounding Transformer with local power supply - outdoor

Legend
1. 2. 3. 4. 5. 6. 7. 8. 9. Mounting holes (16mm) for fixation of the Grounding Transformer to the foundation (optional wheels) High voltage bushing Elastimold: Load break/Dead break, DIN, Pfisterer Neutral bushing Elastimold: Load break/Dead break, DIN, Pfisterer Low voltage bushing DIN Rating plate (movable) Lifting lugs Protective earth Cabinet low voltage bushings Fused load switch (optional)

Grounding Transformer YNd (open) - outdoor

Legend
1. 2. 3. 4. 5. 6. 7. Mounting holes (16mm) for fitting of the Grounding Transformer to the foundation (optional wheels) High voltage bushing Elastimold: Load break/Dead break, DIN, Pfisterer Neutral bushing Elastimold: Load break/Dead break, DIN, Pfisterer Low voltage bushing DIN Rating plate (movable) Lifting lugs Protective earth

Grounding Transformer with auxiliary power supply YNd (open) - indoor

Legend
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Mounting holes (16mm) for fitting of the Grounding Transformer to the foundation (optional wheels) High voltage bushing - M12 Neutral bushing - M12 Low voltage bushing terminals Rating plate (movable) Lifting lugs Enclosure Service hatch Air in Air out Cable bushing for HV cable from bottom Protective earth

Technical specification
Voltage Current Duty Cooling methods for Hermetically sealed Indoor: Frequency Installation Secondary winding voltage Insulation level Ambient temperature Insulation oil in hermetically sealed ONAN (ANSI/IEE C57.12.00) Class AA or Class AFA (ANSI/IEE C57.12.01) 50 or 60 Hz Indoor or Outdoor 400/420 V According to the rated voltage (IEC70076-3) -40 to +40 C, other temperatures on request Nynas: Nytro Taurus Starke & Sohn: Transformer Oil U M&I Materials Ltd: Midel 7131 Other oils on request Up to 130 kV Up to 1000A Continuous or short time (2 hours)

Routine Tests
Visual inspection (SS-EN 60439) Protective earth continuity test (SS-EN 60439) Verification of correct wiring (SS-EN 60439) Verification of correct function (SN routine test) Rated voltage / current test (IEC 60076-6) HV insulation test (IEC 60076-6) LV winding insulation test (3kV ~ 60s) (IEC 60076-6) Measurement of losses (IEC 60076-1)

Type tests
According to IEC 60076-1 Measurement of current at rated voltage Temperature rise test Dielectric test

Special tests
On request, as per agreement

Swedish Neutral AB Vstra Rydsvgen 128 19631 Kungsngen Sweden