Cahier Technique: Directional Protection Equipment
Cahier Technique: Directional Protection Equipment
Cahier Technique: Directional Protection Equipment
Cahier technique
no. 181
P. Bertrand
Cahiers Techniques are a collection of documents intended for engineers and technicians people in the industry who are looking for information in greater depth in order to complement that given in display product catalogues. These Cahiers Techniques go beyond this stage and constitute pratical training tools. They contain data allowing to design and implement electrical equipement, industrial electronics and electrical transmission and distribution. Each Cahier Technique provides an in-depth study of a precise subject in the fields of electrical networks, protection devices, monitoring and control and industrial automation systems. The latest publications can be downloaded on Internet from the Schneider server. code: http://www.schneiderelectric.com section: mastering electrical power Please contact your Schneider representative if you want either a Cahier Technique or the list of available titles. The Cahiers Techniques collection is part of the Groupe Schneiders Collection Technique .
Foreword The author disclaims all responsibility further to incorrect use of information or diagrams reproduced in this document, and cannot be held responsible for any errors or oversights, or for the consequences of using information and diagrams contained in this document. Reproduction of all or part of a Cahier Technique is authorised with the prior consent of the Scientific and Technical Division. The statement Extracted from Schneider Cahier Technique no..... (please specify) is compulsory.
n 181
Directional protection equipment
Pierre BERTRAND An INPG Engineer (Institute National Polytechnique de Grenoble) graduating in 1979, he joined Merlin Gerin in 1983 and was involved in research on the operation and disturbances on electrical networks up to 1986. He then joined the Protection and Control activity in which he held various marketing and technical positions. He is currently leading an electrotechnical excellence group within this activity's technical department.
Lexicon
ANSI code: digital code assigned to a protection function, defined in the ANSI C37-2 standard. Characteristic angle (in a directional protection equipment): angle between the polarisation quantity of relay and the normal to the tripping zone boundary line (see fig. 10 ). Differential protection: zone protection which detects a fault by measuring and comparing currents at the input and output of the protected zone or equipment. Directional protection: protection equipment capable of detecting a fault upstream or downstream (in a given direction) of its position. Earth fault (e/f) protection: protection in which the residual variable (current and/or voltage) is monitored to detect phase-to-earth fault. Phase protection: protection in which the phase current and/or voltage variables are monitored. Phase-to phase-voltage (annotation): U32 = V2-V3. Polarisation quantity (in a directional protection equipment): the variable used as the phase reference. Protection plan: the protection equipment incorporated in an electrical network in order to detect faults and to disconnect the smallest possible part of the faulty network. (protection) Relay: equipment used to monitor one or more electrical variable (current or voltage), generally to detect a fault and to control the opening of a circuit breaker. Relay connection angle (in a phase directional protection equipment): the angle between the chosen polarisation variable and the phase to earth voltage of the monitored phase qualifies the polarisation variable. Residual: (current or voltage in a three phase network) : the vectorial sum of the values of all three phases. Zero sequence (current or voltage, in a three phase network): 1/3 of the residual variable.
Contents
1. Introduction 1.1 The role of directional protection equipment 1.2 Applications 1.3 The codes and symbols of the various relay types 2. Description of directional relays 2.1 Earth fault directional protection 2.2 Phase directional protection 2.3 Power protection 3. Applications of directional protection equipment 3.1 Protection of radial networks 3.2 Protection of closed rings 3.3 Protection of alternators 4.1 Sizing of current and voltage transformers 4.2 Selection between two or three phase protection 4.3 Protecting parallel connected transformers 5. Developments and outlook 5.1 Developments in protection equipment technology 5.2 Developments in sensors 5.3 In conclusion p. 4 p. 4 p. 5 p. 6 p. 9 p. 11 p. 12 p. 16 p. 19 p. 21 p. 22 p. 22 p. 23 p. 24 p. 24
4. Use
1 Introduction
Power protection equipment measures either the active or the reactive power flowing through the connection in which the current sensors are placed. The protection equipment operates if the power is greater than a set threshold and if it is flowing in a given direction. Directional power and current protection requires the current and the voltage to be measured.
1.2 Applications
Directional protection equipment is useful for all network components in which the direction of flow of power is likely to change, notably in the instance of a short circuit between phases or of an earthing fault (single phase fault). c phase directional protection is installed to protect two connections operated in parallel, a loop or a network component connected to two power sources (see fig 2 ). c earth fault (e/f) directional protection is sensitive to the direction of flow of the current to earth. It is necessary to install this type of protection equipment whenever the phase to earth fault current is divided between several earthing systems. However, this current flow is not only due to the earthing of the network's neutral, but also due to the phase to earth capacitance of the lines and cables (1 km of 20 kV cable causes a capacitive current flow of around 3 to 4 amps). Residual directional overcurrent protection, as well as zero sequence active power protection
1 2
fig. 2: The directional protection equipment (1) is tripped since the direction of current flow is abnormal.
are used to protect feeders with a capacitive current of the same order of magnitude as the earthing fault current. On these feeders, the phase to earth capacitance is sufficiently high for a zero sequence current to be detected by a nondirectional e/f protection as soon as a phase to earth short circuit occurs, wherever it may be on the network (see fig. 3 ). Directional protection is therefore complementary to overcurrent protection, enabling good discrimination of the faulty network section to be achieved in the above mentioned situations. Active or reactive power protection equipment is used to detect abnormal power flow other than the one due to a short circuit; e.g.: in the event of the failure of the prime mover, a generator will continue to run as a synchronous motor, drawing power from the system.
fig. 3: The directional residual current protection equipment (2) does not trip since the current is flowing in the opposite direction.
Graphical symbol
Usual names c directional overcurrent, c phase directional c directional residual overcurrent c directional earth fault c zero sequence active power c active overpower c active reverse power
I >
67 N
Ir >
32 P P> 32 Q Q> 32 P P< 32 Q Q<
c active underpower
c reactive underpower
In order to measure a value of power or to localise a fault upstream or downstream of the point at which the current is measured, the phase displacement of the current must be determined relative to a reference variable: the
phase to phase voltage for directional phase protection and the residual voltage for directional earthing protection. This reference variable is called the polarisation quantity.
i1 i2 i3
I1 I2 I3
ir = i1 + i2 + i3
ir
I1 I2 I3
Fr = F1 + F2 + F3 is three times greater than the zero sequence variable. c The residual current is either measured by three current transformers, one per phase, or by a coil (ring CT) around the three phases. v The use of three current transformers (see fig. 5 ) has certain advantages: - CT's are generally dependable, - it is possible to measure high currents. But it also has certain disadvantages: - saturation of the CT's in the instance of a short circuit or when a transformer is switched on produces a false residual current - in practice, the threshold cannot be set to under 10% of the CT's rated current. v Measuring using a ring CT (see fig. 6 ) - has the advantage of being very sensitive, - and the disadvantage of the coil (low voltage insulated) being installed around a non-clad cable to insulate it. c Residual voltage is measured by three voltage transformers (VT); often VT's with two secondary windings are used (see fig. 7 ): one is star connected and enables both phase to neutral and phase to phase voltages to be measured; the other is open delta connected enabling the residual voltage to be measured. If the main VT's only have one secondary winding are star connected, and grounded, a set of auxiliary VT's can be used to measure the residual voltage (see fig 8 ). This situation is often encountered when the protection plan for existing installations is upgraded. It should be noted that certain protection equipment does not require auxiliary VT's, the equipment itself providing the residual voltage value from the three phase to earth voltages. c The residual voltage is most often used as the polarisation variable for an earth fault directional relay; however, it may also be taken as the current in the installation's neutral earthing arrangement (see fig. 9 ).
In theory, both these ways of polarising the protection equipment are equivalent. If Zh is the transformer's zero sequence impedance and Zn the impedance of the neutral point, the residual voltage, Vr, and the current of the neutral point, In, are related by the following equation (written in complex numbers!): Vr = (Zh + 3Zn) In. In practice, polarisation by the neutral point current is only used in networks with an earthing
fault current that is both large (several hundreds of Amps) and at the same time much greater than the current due to parasite capacitance on the network. In this instance the current measurement is more accurate than that of residual voltage, which has a very small value. It can only be used in substations that are near to the neutral earthing connection.
Main VT's
vr = v1+ v2 + v3
vr = v1 + v2 + v3
Auxiliary VT's
Ih >
Polarisation using the residual voltage
Ih >
Polarisation using the neutral point current
Characteristic angle To determine the direction of the fault, the protection equipment measures the phase displacement between the current and the polarisation variable. If the polarisation variable is not in the axis of symmetry of the wished relay's action (the characteristic axis, see fig 10 ), it is necessary to re-phase it; this is done by adjusting the characteristic angle. When designing the protection coordination, the characteristic angle of directional protection equipment must be determined so that any fault in the chosen direction causes a current that falls in the tripping zone and that any current in the other direction causes a current falling outside of this zone. The characteristic angle depends on the chosen polarisation variable and on the network's neutral point arrangement (for residual current directional protection equipment). Therefore, the characteristic angle is often adjustable. The main applications and the corresponding settings are looked at in chapter 3. To be able to measure the phase displacement between the current and the polarisation variable, it is essential for the latter to be sufficiently large (generally u 0.5 to 2% of the rated value of the variable). If the polarisation variable is less than this threshold then the protection equipment does not operate, whatever the measured current value. Principles of detection Three principles of detection exist concurrently; they correspond to various requirements and sometimes to various practices: v directionalized overcurrent, v measurement of the projection of the current,
v measurement of the residual active power. The first two are used for phase and earth fault detection, the last one is specific to earth fault detection with a special neutral point arrangement. c Directionalized overcurrent (see fig. 10 ) This type of directional relay is made by combining overcurrent protection equipment with an equipment to measure the phase displacement between the current and the polarisation variable. Tripping is subject to the two following conditions: v the current is greater than the threshold, and v the phase displacement between the current and the polarisation variable, defined by the characteristic angle, is in the zone between +90 and -90. c Measurement of the projection of the current (see fig. 11 ) This type of protection equipment calculates the projection of the current along the characteristic axis. The value obtained is then compared with a threshold in order to determine whether or not to trip. c Measurement of the residual active power This type of protection equipment actually measures the residual active power and the threshold is expressed in Watts. It must be designed to avoid any spurious tripping caused by measurement inaccuracy in the instance of a strong capacitive residual current (strong residual reactive power); the operating zone is limited as shown in figure 12. To detect earthing faults, the most universal principle is that of measuring the projection of the current.
Non-tripping zone
Ih >
Direction of detection of the protection equipment Tripping zone
Characteristic angle
fig. 10: Operating characteristics of earth fault directional overcurrent protection equipment.
Ih >
Direction of detection of the protection equipment Tripping zone Treshold
Characteristic angle
Polarisation variable
Ih >
Direction of detection of the protection equipment Tripping zone Vh P
fig. 12: Operating characteristics of protection equipment measuring the zero sequence active power.
The use of directionalized overcurrent relays is not suited to all neutral point arrangements (chapter 3 shows that this principle cannot be used with compensated neutral point arrangements).
Protection equipment measuring the residual active power is restricted to use with compensated neutral point arrangements in competition with current projection type relays.
to the displacement effect of the neutral point (residual voltage). c When the relay measures the current in phase 1, the polarisation voltage most often used is V2-V3. The protection equipment's angle of connection is then said to be 90 (see fig. 13 ). c Similarly to a directional earthing relay, the characteristic angle of a directional phase relay defines the position of the angular tripping zone. It is the angle between the normal to the tripping plane and the polarisation variable. c In order to be able to measure the fault direction, the polarisation variable (the voltage) must have a sufficiently high value. In particular, a three-phase fault very close to a directional relay is not detected because all of the phase to phase voltages are zero.
To obtain the direction of this type of fault, the protection system must use a memory voltage . Principles of detection Phase directional relays function either as directionalized (see fig. 14 ) overcurrent element, or by measuring the projection of the current on the characteristic axis. Although relays functioning on both principles exist on the market, the directional overcurrent relay should be preferred. Co-ordinating overcurrent protection equipment is much easier since the detection threshold is independent of the current's phase. The power measurement is not used to detect short circuits. Power is not a good fault detection criteria because in the instance of a fault between phases the nearer the fault is the lower its value.
I >
V3
V2
Non-tripping zone
fig. 13: A relay mesuring the current I1 and the voltage V2-V3 has a 90 relay connection.
I >
Treshold Characteristic angle
Polarisation variable
Non-tripping zone
Core
Insulator
Incomer transformer
Capacitive current
Id
Neutral point current
In order to incorporate protection equipment, it is necessary to calculate, for a given feeder, the maximum value of the residual capacitive current. This is the current that would be measured by a coil placed on this feeder when one phase is earthed upstream of it whilst the two others are at the network's rated phase to phase voltage. It is generally called the feeder's capacitive current. The value of this current is : Ic = 3 C V in which : v C is the capacitance of each phase relative to the earth v V is the phase to neutral voltage v is the angular frequency (2 f). c The neutral point arrangement The choice of the neutral earthing connection arrangement is an important stage in designing an electrical network. It is always a result of a compromise between several factors. A factor that is frequently favoured is the desire to reduce the fault current in order to improve the human safety (by limiting the increase in potential of the fault earthing points), and of equipment (by limiting the energy released through electrical short circuit arcing). We will see that by limiting the fault current we make it more difficult to detect the fault and consequently it becomes essential to use an earth fault directional protection system. If the fault current is sufficiently weak, we no longer need to instantly cut off the supply, and this in turn enables a considerable improvement to be achieved in continuity of service. During a fault, the capacitive current superposes itself on the current limited by the neutral earthing impedance. Consequently, in networks with large capacitive currents, the only way of obtaining a low fault
current is to choose an inductive earthing impedance whose current compensates for the capacitive current. When this neutral point inductance is constantly adjusted to retain this balance (3 L C 2 = 1), it is called a Petersen coil ; in this case the fault current is theoretically zero. Earthing fault protection Directional earthing protections are used on radial networks in two situations: v when a feeder's capacitive current is of the same order of magnitude as the protection equipment's threshold current (which must be quite low in order to detect resistive faults), v when the neutral is earthed in several places. c Networks with long feeders When a feeder has a high capacitive current normally one greater than 10 % of the current limited by the neutral earthing impedance - a simple residual overcurrent relay is no longer enough to give sensitive and selective protection. If its threshold is set to a value below the capacitive current of the protected feeder, it will be subject to spurious tripping for all phase to earth faults on the network. In this case, a satisfactory protection system for the feeder will consist of a directional earthing relay whose threshold can be set to below the capacitive current. The characteristic angle will be set according to the neutral point arrangement of the installation; v Isolated neutral network: Operation - The general protection of the network is performed by a continuous insulation level monitor or by residual overvoltage protection equipment (displacement of the neutral point), - Directional earthing protection equipment detects the faulty feeder, - The characteristic angle is chosen: = 90 (see fig. 18 ).
Irs
Vr
= 90
Vr
Irs
Ird Ird
Comment This only operates if the capacitive current is sufficiently high. In practice the minimum value is: 1A. v Resistance earthed neutral network (see fig 19 ): In the faulty feeder, the neutral point current, which is active, is added to the capacitive current in the non-faulty feeders. If the resistance of the neutral point is chosen such that the active current is greater than twice the installation's capacitive current, directional protection is not necessary. The following characteristic angle is chosen: - A: = 0 for current projection type relays (set in this way, the relay is sensitive to the active residual current and insensitive to the capacitive current), - B: = 45, for directionalized overcurrent relays. It should be noted that with a characteristic angle of 45, the residual current in the nonfaulty feeder is clearly in the protection system's
non-tripping zone, and therefore all principles of protection are appropriate. With a characteristic angle of 0, the residual current of the non-faulty feeder is at the border of the tripping zone ; it is therefore essential to use a current projection type relay. This solution then offers the advantages of being totally insensitive to the capacitive current. v Compensated neutral network (see fig. 20 ): Operation - The current in the faulty feeder arises from the superposing of: . the capacitive currents in the non-faulty feeders, . the current in the coil that compensates for the total capacitive current in the network, . the current in the neutral point resistance, generally less than 10% of the current in the coil (there exists networks in which this neutral point resistance is not installed however this possibility is not examined here). - The characteristic angle is chosen as: = 0.
Irs
Vr
Irs = 0
Vr
= 45
Vr
Irs
Ird Ird
Ird
B - Recurrent fault: voltage of the faulty phase and residual current kV Extinction of fault Re-ignition
Irs
Vr
20
Ird = 0
Vr 0 A
Irs
Ird
- 20
250 0 - 250
70
150
230
310
390
470
ms
Comment It is essential to use current projection type protection equipment ; directional overcurrent protection equipment risks causing spurious tripping. On this type of network, insulation faults are often recurrent in nature : the fault arc will be extinguished after several milliseconds and reignite several periods later as part b of figure 20 shows. Protection equipment must be specially designed to function in the presence of this type of fault. v Directly earthed neutral networks (see fig. 21 ): Operation - The neutral point current is mainly inductive. It is much greater than the network's capacitive current, - The characteristic angle is chosen to be: = -45 to -90. It should be noted that a simple zero sequence overcurrent relay is sufficient to detect a faulty feeder provided its threshold is set to a value that is greater than the capacitive current of the protected feeder. Directional relays are only used in a meshed network or in one having several neutral points.
c Multiple earthing points Certain networks can be operated with the neutral earthed in several places. This is notably the case when the neutral is earthed in each energy source (generator unit or incomer transformer). The parallel connection of sources therefore leads to the parallel connection of the neutral earthing connections. In this case, the selective protection of sources against earthing faults requires directional earthing protection equipment on the incomer of each of the sources. Figure 22 shows the typical arrangement of earthing fault protection equipment. The arrow indicates the direction of fault detection in each directional earthing protection equipment. The time delays on each piece of equipment are also shown. The characteristic angles are chosen according to the neutral point arrangement : that of the protection equipment located on the generator set incomer according to the neutral earthing arrangement of the transformer and that of the protection equipment installed on the transformer incomer according to the neutral earthing arrangement of the alternator.
Ird
Vr
0.4 s or more
0.4 s or more
Ih >
Ih >
a
Direction of detection
Ih >
0.1 s
Ih >
0.1 s
Phase to phase fault protection Directional phase protection equipment is used on a radial network for substations supplied simultaneously by several sources. In order to obtain good continuity of service, it is important that a fault affecting one of the sources does not cause all the sources to trip. The required selectivity is achieved by installing phase directional protection equipment on the incomer of each of the sources. Figure 23 shows a typical layout for phase to phase fault protection equipment. In this figure, the arrow shows the direction of detection of each directional phase protection equipment.
Directional phase protection equipment is generally two phase. Cases requiring three phase protection are described in 4. The time delays of the protection equipment are shown. The characteristic angles are set to take account of the chosen angle of connection. For an angle of connection of 90, the most universally used setting of the characteristic angle is 45. It should be noted that if the generator set's short circuit power is low compared with that of the network, the directional protection equipment installed on the generator set's incomer can be replaced by simple overcurrent protection equipment with a threshold set to be both greater than the generator set's short circuit current and less than that of the network.
I>> I>
0.4 s or more 0.4 s or more
I>
a
I>
0.1 s
I>
0.1 s
Parallel connected lines Two parallel connected lines are the simplest and most frequently encountered example of a closed ring.The protection system must be designed in such a way that a fault on one line does not cause the other line to trip. A typical protection system is shown in figure 25 . In this figure, the arrow shows the direction of detection of each directional protection equipment. Directional phase protection equipment is of two phase type. Its characteristic angle is set to take account of the chosen angle of connection (45 for an angle of connection of 90). The characteristic angle of directional earthing protection equipment is set according to the neutral point arrangement as explained in the previous paragraphs. The protection equipment time delays are shown in the figure. Non directional protection equipment used on upstream substation feeders are time delayed so as to grade with the directional protection equipment of the downstream substation incomers. In the instance of a short circuit on one of the lines, the current is divided according to the impedance in each circuit : part flows directly
from the upstream substation in the faulty line, the rest passes through the downstream substation. The protection equipment is activated in the following order : c A1, D1 and D2 detect the fault, c A1 trips (time delay : 0.1 s), c D2 resets before its time delay has elapsed, c D1 trips (time delay : 0.4 s). When a short circuit occurs near to the upstream substation's busbars, the proportion of current passing through the downstream substation is very low, less than the directional phase protection threshold value. This is the case when the position x of the fault is between 0 and twice the ratio of Is/Isc (between the directional protection relay's threshold and the short circuit current). In this case, the faulty line feeder's overcurrent protection equipment (D1) trips first (time delay: 0.4 s) with A1 tripping next. The total time to elimination of the fault is therefore prolonged. This disadvantage can be overcome by installing a second overcurrent relay on feeders D1 and D2 with a high threshold (tripping for a Isc corresponding to less than 90% of the length of the line) with a time delay of 0.1 s.
0 D1 D2
I>
0.4 s
I>
0.4 s
Ih >
Ih >
x%
I> Ih >
A1 100 % Fault's position 0.1 s A2
I> Ih >
0.1 s
Closed loop Each circuit breaker is equipped with two directional protection systems, each detecting the fault in opposite directions (apart from the circuit breakers at the start of the loop, which are equipped with a single non-directional type protection system). This protection equipment arrangement is shown in figure 26 . Each protection system comprises two phase directional protections and two earth fault directional protection equipments. The direction of detection of each protection system
is shown by an arrow. Two selectivity series are formulated, one for each direction that the fault current can flow in : v A > B > C > D > E, v F > E > D > C > B. If the selectivity is purely time-based, the tripping times rapidly become prohibitive. In practice, this solution is implemented with logical selectivity (see fig. 27 ), which enables very short tripping times (0.1 s) to be obtained by using line links between each substation.
I> Ih >
1.3 s
I> Ih >
1.3 s
Ih > I>
1s
Ih > I>
0.1 s
Ih > I>
1s
Ih > I>
0.1 s
I> Ih >
0.7 s
I> Ih >
0.4 s
I> Ih >
0.7 s
I> Ih >
0.4 s
fig. 26: Protection of a closed loop using directional relays and time-based selectivity.
I> Ih >
Logical wait
I> Ih >
I> Ih >
I> Ih >
I> Ih >
I> Ih >
fig. 27: Protection of a closed loop by directional relays and logical selectivity.
a
P Positive direction of P and Q
fig. 28: Protection against excitation losses by a reactive reverse power relay.
P>
a
P Positive direction of P and Q
This protection equipment has two objectives: c ensuring the safety of the production unit's power station, c ensuring the safety of the main network, which can be supplied from the industrial premise's power station. This protection equipment is generally installed on the industrial network incomer circuit breaker, controlling its opening. It can also control the opening of a coupling circuit breaker between two parts of the installation. One of the roles of the decoupling protection equipment is illustrated in figure 30 : it involves detecting a fault situated upstream of the industrial installation, with the dual aim of: c ensuring the safety of the network: cutting the supply to the fault, c ensuring the safety of the alternator : avoiding the reclosing of the feeder to the source substation, performed without taking any account of the conditions of synchronisation, causing a dangerous coupling. Fault detection is ensured by phase directional and earth fault protection equipment: c earth fault directional protection detects the residual current created by phase to earth capacitance in the installation and / or that generated by the earthing of the power station, c directional phase protection detects an upstream fault between phases. Because it is directional, this protection equipment is insensitive to a fault situated within the industrial installation. c Apart from directional protection equipment, a protection for parallel operation often comprises
Source substation
Power station a
I> Ih >
a rate of change of frequency relay (df/dt): the spurious increase in power demand at the power station, in the case of a loss of mains, causes a variation in generator frequency. Voltage and frequency protection equipment can be requested by the supply authority in order to guarantee the quality of energy supplied by the private generation equipement. Lastly, an active overpower protection system can also be installed in order to indicate an abnormal direction of power flow.
4 Use
fig. 31: Angle error calculated under the following conditions: c the fault comprises an aperiodic component of 100% and a time constant of 40 ms; c the CT's saturation current is twice the short circuit current.
The choice of VT's (voltage transformers) does not pose any particular problem. VT's normally installed on distribution networks are either of class 0.5 or 1; they are perfectly suitable for the supply of directional protection equipment as long as the sum of the loads connected to them is neither greater than their rated burden, nor too low, in order to avoid risks of ferro-resonance. CT's (current transformers) are more tricky to design for this purpose. Should they be underdesigned and in the instance of a short circuit current having an aperiodic component with a high time constant, the CT's become saturated. This phenomenon causes an error in the phase current measurement during the transient, as shown in figure 31 . The current measured on the CT's secondary winding always leads the primary current. Incorrect design of CT's can have two consequences: c it may cause spurious tripping - a risk that decreases the longer the protection equipment's time delay, c it may cause delayed tripping - a risk that is independent of the selected time delay. The main factor influencing the protection equipment's behaviour is the phase displacement between the short circuit current and the protection's tripping zone boundary line, as defined in figure 32 .
In practice, if this angle is greater than 45 (which is very often the case with the recommended settings), the design requirements for the CT are not so strict : choose the accuracy limit factor for the CT (as defined in Cahier Technique n 164) to be greater than or equal to 0.3 times the value of the maximum short circuit current observed by the directional protection equipment.
Tripping zone
Characteristic angle
V polarisation
Characteristic axis
Ih > I>
0.2 s 0.1 s
Ih > I>
0.2 s 0.1 s
Ih > I>
0.2 s 0.1 s
Variant
fig. 34: The SEPAM 2000, a multiple function digital relay enabling directional protection equipment to be used combined with logical selectivity.
5.3 In conclusion
Technological advances (digital protection equipment, new sensors, etc.), as well as logical selectivity make directional protection equipment easier to use. Today, this high performance and easy to incorporate protection equipment is proving invaluable in improving the dependability of the electrical power supply. It is increasingly being used to protect networks and machines, whether for phase to phase fault protection or for earthing fault protection. Readers interested in more general information on the various types of protection equipment used in MV can refer to Cahier Technique n 174.
Schneider
Direction Scientifique et Technique, Service Communication Technique F-38050 Grenoble cedex 9 Fax. (33) 04 76 57 98 60
Real.: Sodipe - Valence Edition: SEST Grenoble 03.98 - 1500 - Printing: Clerc Printed in France
88258
03-98
1998 Schneider