Swirl Diffuser
Horizontal radial or alternatively vertical compact swirl jet air supply, also suitable for heating applications Also well suited to large and high spaces Supply air pattern can be adjusted either manually or controlled by actuator High induction swirl jet ensures efficient mixing and fast reduction of air velocity Installation using plenum or directly to ductwork
Accessories Balancing plenum with adjustment function (PLC) or also with measurement function (TRI) Actuator (with 24 VAC power supply and proportional 010 VDC control signal or alternatively self actuating wax-bulb) for the direction of airflow pattern
20/TSA/3500/1107/EN
QUICK SELECTION
Pa qv TSA-250(R) l/s m 3/h LpA DPst DPtot Ld Lmin L0.2 TSA-315(R) LpA DPst DPtot Ld Lmin L0.2 TSA-400(R) LpA DPst DPtot Ld Lmin L0.2 TSA-500(R) LpA DPst DPtot Ld Lmin L0.2 TSA-600(R) LpA DPst DPtot Ld Lmin L0.2 LpA values presented with room attenuation 4 dB (red 10m 2 sab). When using room attenuation 8 dB (red 25m 2 - sab): LpA - 4dB. Pa LpA Supply air cooling capacity, W A-weighted sound pressure level, reduced by total equivalent absorption surface of 10m 2, dB(A) red 10m 2 - sab Static pressure drop, Pa DPtot Ld 1200 100 360 23 19 21 2,2 2,6 2,3 1440 120 432 29 27 30 2,4 3,4 2,8 1800 150 540 37 42 47 2,6 4,8 3,4 23 14 16 2,4 3,4 2,8 2160 180 648 45 60 68 3,0 6,2 4,2 28 20 23 2,6 4,4 3,4 2640 220 792 54 90 102 3,4 8,0 5,2 35 30 35 3,2 6,0 4,2 43 46 53 3,4 7,8 5,2 25 16 19 3,0 5,6 5,0 55 77 89 4,2 10,6 6,8 34 27 32 3,6 8,0 6,4 43 45 52 4,2 10,8 8,2 26 17 20 3,2 8,2 6,0 55 79 93 5,0 15,0 11,0 36 30 36 4,0 11,6 8,2 22 11 13 3,0 8,8 6,4 45 47 56 4,8 15,0 10,2 29 17 21 3,6 11,4 8,0 52 68 80 5,4 18,4 12,2 35 25 30 4,2 14,2 9,6 42 37 45 5,0 17,8 11,8 52 60 73 5,8 23,2 15,0 3240 270 972 4200 350 1260 5400 450 1620 7200 600 2160 9000 750 2700 10800 900 3240 13200 1100 3960 16800 1400 5040
DPst
Total pressure drop, Pa Distance from the supply unit, at which air jet detaches from ceiling, m Lmin Minimum distance between central lines of two supply units, m (V3 = 0,25m/s at 1.8m height) L0.2 Isotermal throw length, m when residual velocity of supply air jet 0,2 m/s Room temperature (Tr) = 24 C Supply air temperature (Ta) = 14 C Room height = 2,8 m
20/TSA/3500/1107/EN
QUICK SELECTION
Pa qv TSA-250(C) l/s m 3/h LpA DPst DPtot L0.2 TSA-315(C) LpA DPst DPtot L0.2 TSA-400(C) LpA DPst DPtot L0.2 TSA-500(C) LpA DPst DPtot L0.2 TSA-600(C) LpA DPst DPtot L0.2 LpA values presented with room attenuation 4 dB (red 10m sab). When using room attenuation 8 dB (red 25m 2 - sab): LpA - 4dB.
2
39 48 57 5,6 23 16 19 3,6
44 65 77 6,8 28 22 26 4,2
53 108 128 9,0 37 36 44 5,8 24 13 16 3,2 42 44 54 6,6 28 16 20 3,8 49 64 78 8,2 33 23 28 4,6 22 9 11 2,6 41 35 44 6,2 29 14 17 3,4 48 51 63 7,6 34 20 25 4,2 41 30 37 5,2 47 42 52 6,4
Pa LpA
DPst
Supply air cooling capacity, W A-weighted sound pressure level, reduced by total equivalent absorption surface of 10m 2, dB(A) red 10m 2 - sab Static pressure drop, Pa
Total pressure drop, Pa Distance from the supply unit, at which air jet detaches from ceiling, m L0,2 Isotermal throw length, m when residual velocity of supply air jet 0,2 m/s Room temperature (Tr) = 24 C Supply air temperature (Ta) = 14 C Room height = 2,8 m DPtot Ld
DIMENSIONS
NS 250 315 400 500 630 D 249 314 399 499 629 W 382 475 593 735 917 H 221 233 246 264 286
10
176 H
176
176
273
10
10
20/TSA/3500/1107/EN
Compact jet
Radial Jet
Function The TSA is a high induction swirl diffuser with an adjustable flow pattern. The horizontal radial swirl jet is used mainly in cooling applications that use cool supply air or for ventilation with isothermal supply air. The vertical compact swirl jet with warm supply air is used in heating applications. Adjustment of the supply air pattern is effected by moving the internal adjustment element (cylinder). It is also possible to change from cooling mode to heating mode by adjusting the flow pattern using an electric or wax bulb actuator. The recommended maximum temperature differences between room and supply air temperatures are +15 C for heating and -15 C for cooling applications.
Product models TSA with electric actuator Siemens GDB161.2E/HA actuator with 24 VAC power supply and proportional 010 VDC control signal TSA with wax-bulb actuator TSA can be equipped with a wax-bulb actuator, which work without any power supply. The cylinder position changes according to the temperature of supply air. The temperature range of the wax-bulb actuator is about 20 C to 27 C. The time taken to change from radial to compact jet (or the other way around) is 10 - 20 minutes. When warm air is supplied the piston of the wax bulb actuator keeps moving until the TSA supply air pattern is vertical. When cold air is supplied, the TSA supply air pattern is changed back to horizontal by means of a spring.
20/TSA/3500/1107/EN
Installation The diffuser is connected either directly to the duct by screwing or riveting or alternatively to TRI or PLC balancing plenum. The front vane panel can be reattached Remove the screws through the front vane panel (sizes 250 and 315) or between the cylinder and casing (sizes 400, 500 and 630), turn and hold the front vane panel to remove. Take care during installation to ensure that the cylinder can move freely and that the actuator has adequate installation space. There should be at least 50 mm clearance space above the top of the device when the cylinder is in the lowest position. The connection and fixing rivets or screws may not be located more than 50 mm below the upper edge of the diffuser. A minimum safety distance upstream of the diffuser
TSA with PLC plenum TSA 500 630 D1 500 630 PLC PLC 500 PLC 630 H1 810-950 850-990 W1 620 785
It is recommended that the distance between the PLC plenum and TSA sizes 500 and 630 is at least 1xD to ensure proper diffuser operation.
Ensure that the actuator has adequate installation space when installed in TRI plenum. It is recommended to install the collar outwards. The technical performance for the combination of supply air diffuser and TRI plenum is presented separately for the two different installations. See HIT Design software.
0 10
W1
H1
of 3xD is recommended.
20/TSA/3500/1107/EN
Adjustment CODE 1 2 3 4 DESCRIPTION Control knob Casing Front vane panel Cylinder
qv = k * pm
Pass the tubes and control spindle through the front vane panel. Measure the differential pressure using a manometer. The flow rate is calculated using the formula below.
Throw pattern adjustment The supply air jet is adjusted by changing the position of the cylinder. When you turn the knob clockwise the throw pattern is changes from radial to compact. Airflow adjustment It is not possible to adjust the airflow in TSA itself. In order to enable airflow adjustment and measurement of airflow rate it is recommended that you connect the diffuser TSA 250, 315 and 400 to the TRI balancing plenum. The supply flow rate is determined by using the measurement and adjustment module MSM. Adjust the airflow rate by rotating the control spindle until the desired setting is achieved. Replace the tubes and spindle in the plenum.
20/TSA/3500/1107/EN
TSA-500, TSA-630
TSA-500(R) TSA-630(R)
Selection example : Requirements : qv = 350 l/s LpA < 35 dB(A) L0,2 < 8,0 Horizontal jet Selection : TSA-400 LpA = 34 dB(A) L0,2 = 8,0 DPtot = 32 Pa
Note : For exposed installation horizontal the throw pattern can be reduced by approximately 30 %, of the value given in the diagram. With isothermal air, the throw pattern can be calculated for other terminal velocity by using correction factor : L0.3 = L0.2 x 0.67 L0.4 = L0.2 x 0.5 With non-isothermal air, the throw pattern changes due to air density. Please refer to next page or to the Halton HIT. CD-rom calculation program.
TSA-315(R)
TSA-400(R)
TSA-500(R)
660 2376 13 776 2794 19 896 3226 25 1029 3704 33 LpA values presented with room attenuation 4 NR/NC noise criteria
TSA-630(R)
20/TSA/3500/1107/EN
TSA-500, TSA-630
Selection example : Requirements : qv = 350 l/s LpA < 30 dB(A) L0,2 < 16,0 Selection : TSA-400 LpA = 28 dB(A) L0,2 = 15,0 DPtot = 26 Pa
Note : With non-isothermal air, the throw pattern changes due to air density. Please refer to next page or to the Halton HIT software.
LpA values presented with room attenuation 4 dB (red 10m 2 - sab). When using room attenuation 8 dB (red 25m 2 - sab): LpA - 4dB. NR/NC noise criteria
20/TSA/3500/1107/EN
Servicing Remove the front vane panel and clean the diffuser by wiping it with a damp cloth, instead of immersing it in water. Option with balancing plenum
Product code TSA-D D = Connection size 250, 315, 400, 500, 630
Specifics and accessories Remove the measurement and adjustment module by pulling gently the shaft; (not the control spindle or measurement tubes!). Wipe the parts with a damp cloth, instead of immersing them in water. Remount the measurement and adjustment module by pushing the shaft until the module meets the stopper. MO = Actuator type Suggested specifications The diffuser shall consist of a frame with fixed internal profiled vane rings and a movable deflector ring or cylinder for throw pattern selection. The front vane panel, the movable cylinder and the frame shall be made of powder painted steel, with a white (RAL 9010) as standard colour. The airflow pattern shall be adjustable automatically using an electrical or wax-bulb actuator, (in applications where both heating and cooling are required.) NA M2 M3 No actuator 24 VAC actuator, 0...10 VDC control signal Wax-bulb actuator CO = Colour W X White Special colour
Code example TSA-250, CO=W,MO=NA Sub products PLC Plenum (Ceiling diffusers) TRI Plenum (Diffusers)
20/TSA/3500/1107/EN