6MD663 64 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 224
At a glance
Powered by AI
The manual provides information about the functions, operation, installation and start-up of the High Voltage Bay Control Unit 6MD66.

The manual describes the functions, operation, installation and start-up of the High Voltage Bay Control Unit 6MD66.

The manual contains descriptions of device functions and settings, instructions for installation and commissioning, compilation of technical specifications, and data for experienced users in the appendix.

3UHIDFH ,QWURGXFWLRQ )XQFWLRQV ,QVWDOODWLRQ DQG &RPPLVVLRQLQJ

SIPROTEC High Voltage Bay Control Unit 6MD66


V 4.2

7HFKQLFDO 'DWD $SSHQGL[ /LWHUDWXUH *ORVVDU\ ,QGH[

1 2 3 4 A

Manual

C53000-G1876-C102-3

Disclaimer of liability We have checked the text of this manual against the hardware and software described. Exclusions and deviations cannot be ruled out; we accept no liability for lack of total agreement. The information in this manual is checked periodically, and necessary corrections will be included in future editions. We appreciate any suggested improvements. We reserve the right to make technical improvements without notice. Copyright Copyright Siemens AG 2002. All rights reserved. Dissemination or reproduction of this document, or evaluation and communication of its contents, is not authorized except where expressly permitted. All rights reserved, particularly for the purposes of patent application or trademark registration.

Registered Trademarks SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks of SIEMENS AG. Other designations in this manual may be trademarks that if used by third parties for their own purposes may violate the rights of the owner. 4.20.03

6MD66 Manual C53000-G1876-C102-3

Preface
Purpose of this Manual This manual describes the functions, operation, installation and start-up of the High Voltage Bay Control Unit 6MD66. In particular it contains: 1. Descriptions of device functions and settings; 2. Instructions for Installation and Commissioning; 3. Compilation of the technical specifications; 4. As well as a compilation of the most significant data for experienced users in the Appendix. General information about design, configuration, and operation of SIPROTEC 4 devices are laid down in the SIPROTEC 4 system manual. Target Audience Engineers, commissioning engineers, personnel concerned with adjustment, checking, and service of selective protective equipment, automatic and control facilities and personnel of electrical facilities and power plants. This manual is valid for SIPROTEC 4 High Voltage Bay Control Unit 6MD66; Firmware version V 4.2.

Scope of Validity of the Manual Indication of Conformity

This product complies with the directive of the Council of the European Communities on the approximation of the laws of the member states relating to electromagnetic compatibility (EMC Council Directive 89/336/EEC) and concerning electrical equipment for use within certain voltage limits (Lowvoltage Directive 73/23/EEC). This conformity is proved by tests conducted by Siemens AG in accordance with Article 10 of the Council Directive in agreement with the generic standards EN 50 081 and EN 50 082 for EMC directive, and with the standard EN 60 2556 for the low-voltage directive. This device was designed and produced for industrial use according to the EMC standard. The product conforms with the international standard of the series IEC 60 255 and the German standard DIN 57 435/ Part 303 (corresponds to VDE 0435/Part 303).

Additional Support

Should further information on the System SIPROTEC 4 be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens representative. Individual course offerings may be found in our Training Catalogue, or questions may be directed to our training centre in Nuremberg.

Training Courses

6MD66 Manual C53000-G1876-C102-3

Preface

Instructions and Warnings

The warnings and notes contained in this manual serve for your own safety and for an appropriate lifetime of the device. Please observe them! The following warning terms and standard definitions are used: DANGER! indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. indicates that minor personal injury or property damage can result if proper precautions are not taken. This particularly applies to damage on or in the device itself and consequential damage thereof. indicates information about the device or respective part of the instruction manual which is essential to highlight.

Warning

Caution

Note

WARNING!
Hazardous voltages are present in this electrical equipment during operation. Nonobservance can result in death, personal injury or substantial property damage. Only qualified personnel shall work on and around this equipment. It must be thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. The successful and safe operation of this device is dependent on proper handling, installation, operation, and maintenance by qualified personnel under observance of all warnings and hints contained in this manual. In particular the general erection and safety regulations (e.g. IEC, DIN, VDE, EN or other national and international standards) regarding the correct use of hoisting gear must be observed.

Definition

QUALIFIED PERSONNEL

For the purpose of this instruction manual and product labels, a qualified person is one who is familiar with the installation, construction and operation of the equipment and the hazards involved. In addition, he has the following qualifications: Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. Is trained in the proper care and use of protective equipment in accordance with established safety practices. Is trained in rendering first aid.

ii

6MD66 Manual C53000-G1876-C102-3

Preface

Typographic and Symbol Conventions

To designate terms which refer in the text to information of the device or for the device, the following fonts are used: 3DUDPHWHU 1DPHV, i.e. designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with DIGSI), are marked in bold letters of a monospace type style. The same goes for the titles of menus. i.e. possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with DIGSI), are written in italic style, additionally. The same goes for the options of the menus. i.e. designators for information, which may be output by the relay or required from other devices or from the switch gear, are marked in a monospace type style in quotation marks.

3DUDPHWHU 2SWLRQV,

,QGLFDWLRQV,

Deviations may be permitted in drawings when the type of designator can be obviously derived from the illustration. The following symbols are used in drawings: device-internal logical input signal device-internal logical output signal internal input signal of an analogue quantity

external binary input signal with number No. (binary input, input indication) external binary output signal with number No. (device indication)

Example of a parameter switch designated with the address and the possible settings Besides these, graphical symbols are used according to IEC 60 61712 and IEC 60 61713 or similar. Some of the most frequently used are listed below:

Input signal of an analogue quantity

6MD66 Manual C53000-G1876-C102-3

iii

Preface

OR gate

AND gate

ExclusiveOR gate (antivalence): output is active, if only one of the inputs is active

Coincidence gate (equivalence): output is active, if both inputs are active or inactive at the same time

Dynamic inputs (edgetriggered) above with positive, below with negative edge

Formation of one analogue output signal from a number of analogue input signals

Limit stage with setting address and parameter designator (name)

Timer (pickup delay T, example adjustable) with setting address and parameter designator (name)

Timer (dropout delay T, example non-adjustable)

Dynamic triggered pulse timer T (monoflop)

iv

6MD66 Manual C53000-G1876-C102-3

Preface

Static memory (RS-flipflop) with setting input (S), resetting input (R), output (Q) and inverted output (Q)

6MD66 Manual C53000-G1876-C102-3

Preface

vi

6MD66 Manual C53000-G1876-C102-3

Contents
1 1.1 1.2 1.3 2 2.1 2.1.1 2.1.1.1 2.1.1.2 2.1.1.3 2.1.2 2.1.2.1 2.1.2.2 2.1.2.3 2.1.3 2.1.3.1 2.1.3.2 2.1.3.3 2.1.3.4 2.1.4 2.1.4.1 2.1.4.2 2.2 2.2.1 2.2.1.1 2.2.2 2.2.2.1 2.2.2.2 2.2.3 2.2.3.1 2.2.3.2 2.2.4 2.2.4.1 2.3 2.3.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Overall Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 General functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Functional scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 10 10

Power System Data 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Configuration Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Device, General Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 12 15 15 15

Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Command processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Control Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Control Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Process Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Indication processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

6MD66 Manual C53000-G1876-C102-3

Contents

2.4 2.4.1 2.4.1.1 2.4.1.2 2.4.2 2.4.2.1 2.4.3 2.4.3.1 2.4.4 2.4.4.1 2.4.4.2 2.4.4.3 2.4.4.4 2.4.5 2.4.5.1 2.4.5.2 2.4.5.3 2.4.5.4 2.4.6 2.4.6.1 2.4.6.2 2.4.6.3 2.4.6.4 2.4.7 2.4.7.1 2.4.7.2 2.4.7.3 2.4.7.4 2.4.8 2.4.8.1 2.4.8.2 2.4.8.3 2.4.8.4 2.5 2.5.1 2.6 2.6.1 2.6.2 2.7 2.7.1 2.7.1.1 2.7.1.2 2.7.1.3 2.7.1.4 2.7.2 2.7.2.1 2.7.3 2.7.3.1

Measured value processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 General transducer blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Parameterizing transducer blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Measurement U 1.packet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measurement I 1.packet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measurement 1phase 1.packet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measurement 3phase 1.packet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measurement Aron 1.packet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 36 36 37 37 37 37 37 37 38 38 38 38 39 39 39 39 40 40 40 41 41 41 42 42

Metered value processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Threshold-Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Circuit breaker synchronisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 SYNC Function group 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 50 60 62 63

SYNC function group 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Parameterizing SYNC function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

vi

6MD66 Handbuch C53000-G1840-C102-3

Contents

2.8 2.8.1 3 3.1 3.1.1 3.1.2 3.1.2.1 3.1.2.2 3.1.2.3 3.1.2.4 3.1.2.5 3.1.3 3.1.3.1 3.1.3.2 3.1.3.3 3.1.3.4 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.4

Inter relay communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Installation and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Installation and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Hardware Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Switching elements on the PCBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Reassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Flush Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rack Mounting and Cubicle Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting with detached operator panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting without operator panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 102 102 104 104

Checking Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Checking the data connections of the serial interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Operator interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Service / function interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 System interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Time Synchronization Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Optical Fibers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Checking system connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112 Test Mode and Transmission Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113 Testing System Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113 Checking the Binary Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115 Testing User-Defined Functions (CFC logic) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118 Trip/Close Tests for the Configured Operating Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . .118 Final Preparation of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119

6MD66 Handbuch C53000-G1840-C102-3

vii

Contents

4 4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 4.1.8 4.1.9 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.8.1 4.8.2 4.8.3 4.8.4 A A.1

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 General Device Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Analogue inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Auxiliary voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Binary inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Communications interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Electrical Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 Mechanical Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Climatic stress tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Service Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Switchgear control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Circuit breaker synchronisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 User defined functions (CFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Operating measured values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Inter relay communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Auxiliary functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 Flush-mount and cabinet installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 Mounting with detached operator panel or without operator panel . . . . . . . . . . . . . . . . . . 143 Detached Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 D-SUB miniature Connector of Dongle Cable (Panel Flush or Cubicle Door Cutout) . . . . 145 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 Ordering Information and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Panel Flush Mounting or Cabinet Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Housing with Detached Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156 Housing for installation without operator panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Binary Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168 Default display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 Pre-defined CFC-charts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169

A.1.1 A.1.1.1 A.1.2 A.2 A.2.1 A.2.2 A.2.3 A.3 A.4 A.4.1 A.4.2 A.4.3 A.4.4 A.4.5 A.4.6

viii

6MD66 Handbuch C53000-G1840-C102-3

Contents

A.5 A.6 A.7 A.8 A.9 A.10

Protocol-Dependent Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171 Functional Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 Information Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176 Group Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207

6MD66 Handbuch C53000-G1840-C102-3

ix

Contents

6MD66 Handbuch C53000-G1840-C102-3

Introduction

1
The SIPROTEC 6MD66 devices are introduced in this section. An overview of the devices is presented in their application, characteristics, and scope of functions.

1.1 1.2 1.3

Overall Operation Applications Characteristics

2 5 7

6MD66 Manual C53000-G1876-C102-3

1 Introduction

1.1

Overall Operation
The digital, high voltage SIPROTEC 6MD66 bay control units are equipped with a powerful microprocessor system. All tasks, from issuing commands to circuit breakers to the acquisition of measured quantities are processed in a completely digital way.

Analogue inputs

The measuring inputs (ILx, Vx) convert the currents and voltages coming from the transformers and adapt them to the level appropriate for the internal processing of the device. The device has 3 current and 4 voltage inputs. The current and voltage inputs can be used separately for measured value acquisition. Within the scope of configuration, one- or three-phase evaluation functions are available for evaluation of the analogue inputs and evaluation after the Aron connection. With voltage inputs, both phase-earth and phase-phase voltages can be applied. In addition to a three-phase system, another reference voltage for synchronisation tasks or a displacement voltage Vn can be measured via the fourth voltage input.

6MD66 Manual C53000-G1876-C102-3

1.1 Overall Operation

Figure 1-1

Hardware structure of the High Voltage Bay Control Unit 6MD66

Furthermore, two measuring transducer inputs are available. The analogue values are transferred further to the IA input amplifier group. The input amplification IA stage provides high-resistance terminations for the analogue input quantities. It consists of filters that are optimised with regard to bandwidth and processing speed. The analogue-to-digital (AD) stage consists of a multiplexor, an analogue-to-digital (A/ D) converter and memory components for the transmission of digital signals to the microcomputer system. Microcomputer system The control functions and the measurement quantities are processed in the microcomputer system C. They especially consist of: Control of command outputs, Processing of indication inputs,

6MD66 Manual C53000-G1876-C102-3

1 Introduction

Recording of indications, Control of signals for logical functions, Filtering and conditioning of the measured signals, Continuous monitoring of the measured quantities Monitoring the communication with other devices, Querying of limit values and time sequences, Management of the operating system and the associated functions such as data recording, real-time clock, communication, interfaces, etc. Binary Inputs and Outputs Binary inputs and outputs from and to the computer system are routed via the I-/O modules (inputs and outputs). The computer system obtains the information from the system (e.g remote resetting) or the external equipment (e.g. blocking commands). Outputs are, in particular, commands to the switchgear units and indications for remote signalling of important events and statuses. With devices with integrated or detached operator panel, information such as messages related to events, states, measured values and the functional status of the device are provided via light-emitting diodes (LEDs) and a display screen (LCD) on the front panel. Integrated control and numerical keys in conjunction with the LC display allow local communication with the device. Via these elements all information of the device such as configuration and setting parameters, operating messages and measured values can be accessed. In addition, control of circuit breakers and other equipment is possible from the front panel of the device. Serial interfaces A serial PC interface is provided for local communications with the device through a personal computer using the operating program DIGSI. This permits convenient operation of all functions of the device. A separate Service Port can be provided for remote communications via a modem, or substation computer using DIGSI 4. This port is especially well suited for the fixed wiring of the devices to the PC or operation via a modem. Via the serial system interface all device data can be transferred to a central evaluation unit or to a control center. This interface may be provided with various protocols and physical transmission schemes to suit the particular application. Communication with other SIPROTEC 4 devices which also have inter relay communication can occur via the serial interface to the (optional) on the device rear. Communication is achieved regardless of the connection to the central device SICAM SAS and a redundancy to the system interface. A further interface is provided for the time synchronization of the internal clock via external synchronization sources. Further communication protocols can be realised via additional interface modules. Power Supply The before-mentioned function elements and their voltage levels are supplied with power by a power supplying unit (Uaux or PS). Voltage dips may occur if the voltage supply system (substation battery) becomes short-circuited. Usually, they are bridged by a capacitor (see also Technical Data).

Front elements

6MD66 Manual C53000-G1876-C102-3

1.2 Applications

1.2

Applications
The high-voltage SIPROTEC 6MD66 bay controllers are integrated components of the SICAM energy automation system. Command outputs and indication inputs are especially adapted to the requirements of high-voltage technology. When connecting the circuit breaker, the High Voltage Bay Control Unit can check if the synchronisation conditions of the two subnetworks to be combined are met (synchrocheck). This makes the use of an additional external synchronisation device unnecessary. The synchronisation conditions can be configured conveniently with the DIGSI operating program. The device distinguishes between synchronous and asynchronous networks and reacts differently on the connection.

Control functions

The device provides a control function which can be accomplished for activating and deactivating switchgears via integrated operator panel, system interface, binary inputs, and the serial port using a personal computer with DIGSI. The status of the primary equipment can be transmitted to the device via auxiliary contacts connected to binary inputs. The present status (or position) of the primary equipment can be displayed on the device, and used for interlocking or plausibility monitoring. The number of the operating equipment to be switched is limited by the binary inputs and outputs available in the device or the binary inputs and outputs allocated for the switch position indications. Depending on the primary equipment being controlled, one binary input (single point indication) or two binary inputs (double point indication) may be used for this process. The capability of switching primary equipment can be restricted by a setting associated with switching authority (Remote or Local), and by the operating mode (interlocked/non-interlocked, with or without password request). Processing of interlocking conditions for switching (e.g. system interlocking) can be established with the aid of integrated, user-configurable logic functions.

Messages and Measured Values

The operating messages provide information about conditions in the power system and the device. Measurement quantities and values that are calculated can be displayed locally and communicated via the serial interfaces. Device indications can be assigned to a number of LEDs, externally processed via output contacts, linked with user-definable logic functions and/or issued via serial interfaces.

Communication

For communication with external operator and control systems and Inter relay communication, serial interfaces are available. A 9-pin DSUB socket on the front panel is used for local communication with a personal computer. By means of the SIPROTEC 4 operating software DIGSI, all operational and evaluation tasks can be executed via this PC interface, such as specifying and modifying configuration parameters and settings, configuring user-specific logic functions, retrieving operational messages and measured values, inquiring device conditions and measured values, issuing control commands. Depending on the individual ordering variant, additional interfaces are located on the rear side of the device. They serve to establish an extensive communication with other digital operating, control and memory components: The service interface can be operated via electrical data lines or fibre optics and also allows communication via modem. For this reason, remote operation is possible via

6MD66 Manual C53000-G1876-C102-3

1 Introduction

personal computer and the DIGSI operating software, e.g. to operate several devices via a central PC. The system interface ensures the central communication between the device and the substation controller. The service interface can be operated through data cables or fibre optic cables. The device has a field bus coupling with PROFIBUS FMS. The PROFIBUS FMS according to DIN 19 245 is an open communication standard with particularly wide acceptance in process control and automation engineering, with especially high performance. A profile has been defined for the PROFIBUS communication that covers all of the information types required for process control engineering. The integration of the devices into the power automation system SICAM can also take place with this profile. Alternatively, the device can be operated via PROFIBUS DP. In addition, standardised protocols in accordance with IEC 60 8705103 are available for data transmission. The integration of the devices into automation systems from other manufacturers can also take place with this profile. Optionally, you can use an additional serial interface for Inter relay communication. It takes over communication with other SIPROTEC 4 devices, regardless if the device is connected to the control center. Note The Appendix contains a list of the functions which can be handled via the respective interfaces.

6MD66 Manual C53000-G1876-C102-3

1.3 Characteristics

1.3

Characteristics
Powerful 32-bit microprocessor system. Complete digital processing and control of measured values, from the sampling of the analogue input quantities to the initiation of outputs for, as an example, tripping or closing circuit breakers or other switchgear devices. Total electrical separation between the internal processing stages of the device and the external transformer, control, and DC supply circuits of the system because of the design of the binary inputs, outputs, and the DC converters. Complete set of functions necessary for the proper control of feeders or busbars. Easy device operation through an integrated operator panel or by means of a connected personal computer running DIGSI. Continuous calculation and display of measured and metered values on the front of the device Constant monitoring of the measurement quantities, as well as continuous selfdiagnostics covering the hardware and software. Communication with central control equipment via serial interfaces is possible through the choice of data cable, modem, or fibre optic cable, as an option. Optional for direct communication between the devices, regardless of their connection to the control center. Battery-buffered clock that can be synchronised with an IRIG-B (via satellite) or DCF77 signal, binary input signal, or system interface command. Commissioning aids such as connection check, status indication of all binary inputs and outputs, easy check of system interface and influencing of information of the system interface during test operation

General features

Synchronisation of the circuit breakers

Checking of the synchronisation conditions of both subnetworks. Differentiation between synchronous and asynchronous networks. Consideration of the circuit breaker operating times with asynchronous networks. Saving of up to eight parameter sets for synchronisation to be able to consider the differing properties of circuit breakers.

Control

High security against incorrect switchings via system and bay related interlocking checks, including the information of neighbouring bays via inter relay communication. High variance with regard to switchgear types and operating modes.

Switching authority and switching mode Measured values

Keylock switches for defining the control authority and the control mode. Logging keylock-switch positions. Connection of measured values in accordance with one- or three-phase system or Aron connection. Flexible measured value processing with configurable measuring packets.

6MD66 Manual C53000-G1876-C102-3

1 Introduction

Metered values

Formation of metered values from measured values Acquisition of pulse metered values via the binary inputs

User-defined functions

Freely programmable links between internal and external signals for the implementation of user-defined logic functions. Logic functions for Boolean and mathematical equations. Switching sequences and interlocks. Time delays and measured value set point interrogation.

Monitoring functions

Increased reliability thanks to monitoring of internal measuring circuits, auxiliary power supply, hardware and software. Monitoring of communication including the evaluation of the number of faulty transmission messages.

Inter relay communication

Direct exchange of information between the SIPROTEC 4 devices, even without a connection to the SICAM control centre. An interlocked control is also possible if the connection to the control centre or the control centre itself is disturbed.

Further functions

Battery-buffered clock which can be synchronised via a synchronisation signal (DCF 77, IRIG B via satellite receiver), binary input or system interface. Indication storage for the last 200 operational indications with real-time assignment.

6MD66 Manual C53000-G1876-C102-3

Functions

2
This chapter describes the numerous functions available on the SIPROTEC 6MD66. It shows the setting possibilities for each function in maximum configuration. There are instructions for reporting setting values and formulae, where required. Additionally it may be defined which functions are to be used.

2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8

General functions Command processing Indication processing Measured value processing Metered value processing Threshold-Switch Circuit breaker synchronisation Inter relay communication

10 17 29 30 43 49 50 68

6MD66 Manual C53000-G1876-C102-3

2 Functions

2.1

General functions
The function parameters can be changed via the operator or service interface with a personal computer using DIGSI. The procedure is described in detail in the SIPROTEC System Description /1/.

2.1.1
2.1.1.1

Functional scope
Description The High Voltage Bay Control Unit 6MD66 has functions whose scope can be adapted to the system conditions. Some functions (e.g. control authorization and mode) are available by default, whereas other functions must be added within the framework of configuration. The functional scope of the device is specified within the scope of configuration.

Configuring functional scope

In DIGSI, dialog box Functional scope, the functions Measuring transducer (various types) and Synchronization (1 to 8) are configured as Enabled or Disabled. Functions that are configured as Disabled are not processed by the 6MD66: There are no indications, and corresponding settings (functions, limit values) are not displayed. Functions that are not needed can be hidden.

2.1.1.2

Configuration Notes Configuration settings can be entered using a PC and the operating program DIGSI and transferred via the front serial port, or via the service interface. Operation via DIGSI is described in the SIPROTEC System Description /1/. For changing configuration parameters in the device, password no.7 is required (for parameter set). Without the password, the settings may be read, but cannot be modified and transmitted to the device. The functional scope with the available options is set in the Functional Scope dialog box to match plant requirements.

Configuration of Function Scope

2.1.1.3

Settings

Addr. 0 0 0 0

Parameter 08 9B 08 ,B 083B 083B

Setting Options Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled

Default Setting Disabled Disabled Enabled Disabled

Description Measurement V Measurement I Measurement 1phase 1.packet Measurement 1phase 2.packet

10

6MD66 Manual C53000-G1876-C102-3

2.1 General functions

Addr. 0 0 0 0 0 0 0 0 0 0 0

Parameter 083B 083B 08$URQB 6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ 

Setting Options Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled

Default Setting Disabled Enabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled

Description Measurement 1phase 3.packet Measurement 3phase 1.packet Measurement Aron 1.packet Synchronizing Function 1 Synchronizing Function 2 Synchronizing Function 3 Synchronizing Function 4 Synchronizing Function 5 Synchronizing Function 6 Synchronizing Function 7 Synchronizing Function 8

2.1.2
2.1.2.1

Power System Data 1


Description To function, the device requires the 5DWHG )UHTXHQF\ of the network. The default preset value must only be changed if the network of the application field has a different 5DWHG )UHTXHQF\.

2.1.2.2

Configuration Notes The 5DWHG )UHTXHQF\ of the network in which the device is operating is set under the address . A default value is preset.

5DWHG )UHTXHQF\

2.1.2.3
Addr. 214

Settings
Parameter 5DWHG )UHTXHQF\ Setting Options 50 Hz 60 Hz Default Setting 50 Hz Description Rated Frequency

6MD66 Manual C53000-G1876-C102-3

11

2 Functions

2.1.3
2.1.3.1

Device, General Settings


Description The behaviour of 6MD66 devices can be set individually with various settings. The devices are equipped with an illuminated LC display for displaying process and device information. The light for the display is normally off. Illumination is controlled: via an operator action, ON, on actuating any key on the operator control panel or OFF, after 10 minutes if no further operator input follows. via the binary input !/LJKW RQ (if configured correspondingly), ON, if !/LJKW RQ ON or, OFF, after the time set under 7 %DFNOLJKW RQ. The lighting can also be switched on and off with DIGSI via the operator interface or the service interface.

Indications of the device 'HYLFH 2. Indication: The device is ready for operation. The life contact is switched ON and the error LED is switched OFF with this message. Value: ON 5HVHW 'HYLFH Indication: The device has performed a startup. Special communication indication: It is announced on the PROFIBUS that the SIPROTEC-VD has started the PD service (only the logged on partner). Value: ON ,QLWLDO 6WDUW Indication: The device has performed an initial restart. All buffers were cleared (additional information for start-up indication). Value: ON 5HVXPH Indication: The device has performed a restart. All buffers remained intact (additional information for start-up indication). Value: ON 5HVHW /(' Tagging command for acknowledging the LEDs of SICAM or DIGSI. Value: ON !/LJKW RQ Display on/off via binary input. Value: ON/OFF

12

6MD66 Manual C53000-G1876-C102-3

2.1 General functions

&KDWWHU 21

Central chatter suppression message. This message indicates if the chatter suppression responded during a binary message subject to the chatter processing. Value: ON, the chatter suppression responded for at least one object. Value: OFF, chatter suppression did not respond for any objects.

(UURU 3ZU6XS SO\ )DLO %DWWHU\

Indication: The power supply unit is faulty. Value: ON Indication: The battery is faulty. Value: ON

'DWD6WRS

Data transmission blockage for indications, metered and measured values. With data transmission blockage on, all information in the monitoring direction is marked with the transmission blockage bit. The actual transmission blockage is performed in the control center. Value: ON/OFF

!'DWD6WRS

Predefined binary input for tagging 'DWD6WRS Value: ON/OFF

7HVW PRGH

This operating mode is used for device tests during commissioning or maintenance. In test mode, all information in monitoring direction is marked with UBF test bit. This procedure serves to avoid that events caused by the test mode initiate unwanted reactions (horn, derived commands and indications, etc.) in higher-level system components (DIGSI or SICAM). This operating mode can be activated and deactivated by a tagging command in DIGSI. Value: ON/OFF

+:7HVW0RG

Hardware test mode: DIGSI switches ON this operating mode if the user activates the functions Set binary input, Set output relay, Set messages, for example, in startup mode. DIGSI switches OFF the hardware test mode when leaving the start-up area. After the switch-off command, the "Hardware test mode OFF" message is output and an initial device start-up is initiated after a period of 5 seconds. Value: ON/OFF

!7LPH 6\QFK

Input for the external minute pulse. Value (fleeting): ON

6\QFK&ORFN

Acknowledgement of a clock synchronisation. Value (fleeting): ON

&ORFN 6\QF(U URU

Indication: Clock synchronisation error. Value: ON, the synchronizing event is missing after the parametrized tolerance time.

6MD66 Manual C53000-G1876-C102-3

13

2 Functions

Value: OFF, a synchronizing event has again arrived. 'D\/LJKW6DY 7LPH Indication: Daylight saving time switchover. Value: ON, a time synchronisation job with summertime was detected by the dateclocktime processing. Value: OFF, a time synchronisation job without daylight saving time was detected. 6HWWLQJV &DOF Annunciation that a parametrization is current. Value: ON, the function is reserved for parametrization. Value: OFF, the function has been enabled again. 6HWWLQJV &KHFN Message that the device operates with new parameters which are not yet saved (online parameterization). Value: ON, the test has begun. Value: OFF, the test is ended, i.e. the device is either operative again, or the new parameters have been saved permanently, or no parameter check is current. /HYHO FKDQJH The indication is issued as ON, as soon as the parameter set loaded via DIGSI was changed by an online parametrisation and the device operates with these new parameters. The indication is OFF as long as the parameter set loaded via DIGSI is not changed or is again issued as OFF, if a parameter set was completely newly loaded and the unit operates with these parameters. The information value of the message (ON/OFF) is preserved during an initial and a resume. Value: ON, parameter changes online at the unit or via parametrisation command. Value: OFF, parameter set completely reloaded. /RFDO FKDQJH Indication that the local operation setting was cancelled. This message is reserved for DIGSI. (UURU %RDUG  Indication: The BG1 module either does not exist or is defective. Value: ON (YHQW /RVW (UURU )06 Fleeting indication Indication lost Fault in the PROFIBUS FMS connection, fibre optic cable 1 with double ring connection Fault in the PROFIBUS FMS connection, fibre optic cable 2 with double ring connection Fault in inter relay communication

(UURU )06

IRC fault

14

6MD66 Manual C53000-G1876-C102-3

2.1 General functions

2.1.3.2

Configuration Notes The hold time of the display lighting (on triggering via a signalling contact) can be set in this range. A default value is preset. This value is always valid for the automatic illumination switch-off after an operator action. The setting is automatically derived from the MLFB number set (item 12, functional interface). The interface should be bypassed only in exceptional cases.

7 %DFNOLJKW RQ

',*6, EDFNSODQH

2.1.3.3
Addr. 401 402

Settings
Parameter 7 %DFNOLJKW RQ ',*6, EDFNSODQH Setting Options 1 .. 60 min Disabled Port C Port D Default Setting 10 min Disabled Description Time Backlight on Serviceport for DIGSI

2.1.3.4

Information

No. >Light on DataStop Test mode

Message IE IE IE

Type of Information EM >Back Light on

Description Stop data transmission Test mode Hardware Test Mode Clock Synchronization Error FMS FO 1 Error FMS FO 2 >Synchronize Internal Real Time Clock >Stop data transmission Device is Operational and Protecting Reset Device Initial Start of Device Reset LED Resume Clock Synchronization Error Daylight Saving Time Setting calculation is running Settings Check Level-2 change Local setting change Event lost Chatter ON Error Power Supply Failure: Battery empty Error Board 1

HWTestMod SynchClock Error FMS1 Error FMS2 3 16 51 55 56 60 67 68 69 70 71 72 73 110 125 147 177 183 >Time Synch >DataStop Device OK Reset Device Initial Start Reset LED Resume Clock SyncError DayLightSavTime Settings Calc. Settings Check Level-2 change Local change Event Lost Chatter ON Error PwrSupply Fail Battery Error Board 1

IE_W AM AM EM_W EM AM AM AM AM_W AM IE AM AM AM AM AM AM_W AM AM AM AM

6MD66 Manual C53000-G1876-C102-3

15

2 Functions

No. 184 185 186 187 188 189

Message Error Board 2 Error Board 3 Error Board 4 Error Board 5 Error Board 6 Error Board 7

Type of Information AM AM AM AM AM AM Error Board 2 Error Board 3 Error Board 4 Error Board 5 Error Board 6 Error Board 7

Description

2.1.4
2.1.4.1

Protocol
Description When detecting an interruption in communication between a SIPROTEC 4 device and the PROFIBUS-DP Master, marking 6\V,QW(UU (fault at system interface) is set to ON in the SIPROTEC 4 device. The message is registered in the event buffer. Following, it can be processed in CFC and allocated to LEDs and output relays. The state of the outputs or switching elements has not changed compared to the state before interruption of the communication. After communication has been reestablished the message is set to OFF and data are taken from the telegrams again received by the PROFIBUS-DP Master.

2.1.4.2

Information

No. SysIntErr.

Message IE

Type of Information

Description Error Systeminterface

16

6MD66 Manual C53000-G1876-C102-3

2.2 Command processing

2.2
2.2.1
2.2.1.1

Command processing
General
Description The source of command are recorded in the event log at the moment of the command output. The following source of command are possible:
Cause text SC = Local SC = SICAM SC = Remote SC = Auto SC = Auto device SC = DIGSI Command source Local control using the keypad on the local user interface of the device Local control of central device (e.g. SICAM) Remote control of central device Automatic command of central device (e.g. SICAM CFC) Automatic command of device Control using DIGSI

2.2.2
2.2.2.1

Control Device
Description Devices with integrated or detached operator panel can control switchgear via the operator panel of the device.

Requirements

The number of switchgear devices to be controlled is limited by the binary inputs present binary outputs present

Operation using the SIPROTEC 4 device

Commands can be initiated using the keypad on the local user interface of the relay. For this purpose, there are three independent keys located below the graphic display. The key &75/ causes the control display to appear in the LCD. Control of switching devices only is possible within the control display, since the two control keys OPEN and CLOSE only become active as long as the control display is present. The LCD must be changed back to the default display for other, non-control, operational modes. The navigation keys , , t, u are used to select the desired device in the Control Display. The , key or the 2 key is then pressed to convey the intended control command. Consequently, the switch icon in the control display flashes in setpoint direction. At the lower display edge, the user is requested to confirm his switching operation via the (17(5 key. Next a security check takes place. After the security check is completed, the (17(5 key must be pressed again to carry out the command. If this confirmation is not performed within one minute, the setpoint flashing changes again to the corre-

6MD66 Manual C53000-G1876-C102-3

17

2 Functions

sponding actual status. Cancellation via the (6& key is possible at any time before the control command is issued. During normal processing, the control display indicates the new actual status after the control command was executed and the message FRPPDQG HQG at the lower display edge. In case of control commands with feedback, the message )% UHDFKHG is displayed for a short time before this. If the selected control command is not accepted, because an interlocking condition is not met, then an error message appears in the display. The message indicates why the command was not accepted (see also SIPROTEC 4 System Description /1/). This message must be acknowledged with Enter before any further control commands can be issued. Operation using the DIGSI Control devices can be controlled via the operator control interface by means of the DIGSI operating program installed on a PC. The procedure to do so is described in the SIPROTEC System Description /1/ (Control of Switchgear). Operation using the SCADA Interface Control of switching devices can be performed via the serial system interface and a connection to the substation control and protection system. Please check MLFB order number to ensure that your individual relay has a SCADA interface module that supports this. Within the device also specific settings have to be made to the serial interface (see SIPROTEC System Description /1/). Note The switching commands (annunciations) listed in the following Information List are examples preset. As they are only examples they may be deleted or overwritten by the user.

2.2.2.2

Information

No. Q0 Q0 Q1 Q1 Q2 Q2 Q8 Q8 Q9 Q9 ReleaseQ0 ReleaseQ1 ReleaseQ2

Message

Type of Information BR_D2 DM BR_D2 DM BR_D2 DM BR_D2 DM BR_D2 DM IE IE IE

Description circuit breaker Q0 circuit breaker Q0 bus disconnector Q1 bus disconnector Q1 bus disconnector Q2 bus disconnector Q2 earthing isolator Q8 earthing isolator Q8 feeder disconnector Q9 feeder disconnector Q9 Release circuit breaker Q0 Release bus disconnector Q1 Release bus disconnector Q2

18

6MD66 Manual C53000-G1876-C102-3

2.2 Command processing

No. ReleaseQ8 ReleaseQ9

Message IE IE

Type of Information

Description Release earthing isolator Q8 Release feeder disconnector Q9

2.2.3
2.2.3.1

Control Authorization
Description For the control of switchgear there are several types of commands that have to be considered.

Usercases

Operation of circuit breakers, disconnectors and ground electrodes Raising and lowering transformer LTCs Control of Petersen coils Manually overriding/updating information of process-dependent objects Establishing internal settings Setting and resetting internal buffers or data stocks Adding/removing additional information

Requirements Commands to the system

For more information see SIPROTEC System Description These are all commands that are directly output to the switchgear to change their process state: Switching commands for the control of circuit breakers (asynchronous), disconnectors and ground electrodes, Step Commands, e.g. raising and lowering transformer LTCs Setpoint commands with configurable time settings, e.g. to control Petersen coils

Device-internal commands

These commands do not directly operate command outputs. They serve for initiating internal functions, communicating the detection of status changes to the device or for acknowledging them. Manual overriding commands to manually update information on process-dependent objects such as indications and switching states, e.g. if the communication with the process is interrupted. Manually overridden objects are flagged as such in the information status and can be displayed accordingly. Tagging commands are issued to establish internal settings, e.g. deleting / presetting the switching authority (remote vs. local), a parameter set changeover, data transmission block to the SCADA interface, and measured value setpoints. Acknowledgment and resetting commands for setting and resetting internal buffers or data stocks. Information status command to set/reset the additional information "information status" of a process object, such as: Acquisition blocking Output blocking.

6MD66 Manual C53000-G1876-C102-3

19

2 Functions

Sequence in the command path

Security mechanisms in the command path ensure that a switch command can be carried out only if the test of previously established criteria has been successfully completed. In addition to general fixed prescribed tests, for each resource separately further interlocks can be configured. The actual execution of the command job also is then monitored. The entire sequence of a command is described briefly in the following. Please observe the following: Command entry, e.g. using the keypad on the local user interface of the device Check password access rights Check switching mode (interlocking activated/deactivated) selection of deactivated interlocking status. User configurable Interlocking checks Switching authority Device Position Check (scheduled vs. actual comparison) Interlocking, Zone Control (logic using CFC) Interlocking, System Interlocking (centrally, using SICAM) Double Operation (interlocking against parallel switching operations) Protection Blocking (blocking of switching operations by protective functions) Fixed command checks Internal process time (software watch dog which checks the time for processing the control action between initiation of the control and final close of the relay contact) Configuration in Process (if configuration is in process, commands are denied or delayed) Equipment enabled as output (if an piece of equipment was configured, but not configured to a binary input, the command is denied) Output Blocking (if output blocking has been programmed for the circuit breaker, and is active at the moment the command is processed, then the command is denied) Module hardware error Command in Progress (only one command can be processed at a time for one piece of equipment, object-related Double Operation Block) 1-of-n check (for multiple allocations such as common contact relays it is checked if a command procedure was already ininitiated for the output relays concerned).

Checking a command job

Command execution monitoring

The following is monitored: Interruption of a command because of a Cancel Command Running Time Monitor (feedback monitoring time)

20

6MD66 Manual C53000-G1876-C102-3

2.2 Command processing

Switchgear interlocking

Switchgear interlocking checks in a SICAM/SIPROTEC system are divided in the following groups: System interlocking relies on the system database in the central control system Zone controls, relies on the object image (feedbacks) in the field device and information of the neighbouring fields via IRC. The extent of the interlocking checks is determined by configuration. Switching objects that require system interlocking in a central control system are assigned to a specific parameter inside the bay unit (via configuration matrix). For all commands, operation with interlocking (normal mode) or without interlocking (test mode) can be selected: for Local commands, by activation of "Normal/Test"-key switch, for automatic commands, via command processing by CFC and Deactivated Interlocking Recognition, for local / remote commands, using an additional interlocking disable command, via PROFIBUS.

Interlocked/deinterlocked Switching

The configurable command checks in the SIPROTEC 4 devices are also called "standard interlocking". These checks can be activated via DIGSI (interlocked switching/ tagging) or deactivated (non-interlocked). De-interlocked or non-interlocked switching means that the configured interlock conditions are not tested. Interlocked switching means that all configured interlocking conditions are checked within the command processing. If a condition is not fulfilled, the command is rejected, marked with a minus sign (e.g. "CO"), and a message to that effect is output. The following table shows some types of commands and messages. For the device the messages designated with *) are displayed in the event logs, for DIGSI they appear in spontaneous indications.
Type of Command Control issued Manual tagging (positive / negative) Control Switching Override CO MT Cause Indication CO+/ MT+/ ST+/ *) OB+/ *) CA+/

Output blocking, Acquisition block- Acquisition blocking ST ing Information status command, Output blocking Abort command Output blocking Abort OB CA

The "plus" appearing in the message is a confirmation of the command execution. The command output has a positive result, as expected. The "minus" is a negative confirmation and means that the result was unexpected. The command was rejected. Possible command replies and their causes are dealt with in /1/. Figure 2-1 shows the operational indications relating to command execution and operation response information for a successful operation of the circuit breaker. Interlocking checks can be configured individually for all switching devices and markings. Other internal commands such as overriding or abort are not tested, i.e. are executed independently of the interlockings.

6MD66 Manual C53000-G1876-C102-3

21

2 Functions

Figure 2-1

Example of an operational annunciation for switching circuit breaker 52

Standard Interlocking Defaults (fixed programming)

The standard interlockings contain the following fixed programmed tests for each switching device, which can be individually enabled or disabled using parameters: Device Status Check (setpoint = actual): The switching command is rejected, and an error indication is displayed if the circuit breaker is already in the set position. If this check is enabled, then it applies whether switch interlocking is activated or deactivated. System Interlocking: For checking the system interlocking a locally issued command to the central unit is instigated with switching authority = local. A switching device that is subject to system interlocking cannot be switched by DIGSI. Zone Control: Logic combinations deposited in the device using CFC are scanned and taken into consideration for interlocked switching. Blocked by protection: This interlocking option enabled for devices with integrated protection functions has no significance and no effect on the 6MD66 device version. Double operation locking: Parallel switchings are mutually interlocked; when a switching is being processed a second one cannot be executed. LOCAL switching authority: A switching command from the user interface of the device (command with command source LOCAL) is only allowed if the Key Switch (for devices without key switch via configuration) is set to LOCAL. DIGSI switching authority: Switching commands that are issued locally or remotely via DIGSI (command with command source DIGSI) are only allowed if the Key Switch (for devices without key switch via configuration) is set to REMOTE. If a DIGSI-PC communicates with the device, it deposits here its virtual device number (VD). DIGSI must have the same virtual device number (with REMOTE switching authority). Switch commands of the remote control are rejected. REMOTE switching authority: A remote control command (command with initiator source REMOTE) is only allowed if the Key Switch (for devices without key switch via configuration) is set to REMOTE.

22

6MD66 Manual C53000-G1876-C102-3

2.2 Command processing

Figure 2-2 1)

Standard interlocking arrangements

Initiator source REMOTE also includes LOCAL. (LOCAL command via the power system management in the station, REMOTE command via telecontrol station to power system management and from power system management to the device) Release from testing of interlocking conditions Not relevant for 6MD66

2) 3)

For devices with operator panel the display shows the configured interlocking reasons. They are marked by letters explained in the following table.
Table 2-1 Interlocking Commands Interlocking Commands Switching authority System interlocking Zone Control SET = ACTUAL (switch direction check) Blocked by protection
1) 1)

Command L SI Z P B
1)

Display L A Z P B 1)

Not relevant for 6MD66

6MD66 Manual C53000-G1876-C102-3

23

2 Functions

The following figure shows all interlocking conditions (which usually appear in the display of the device) for three switchgear items with the relevant abbreviations explained in the previous table. All parameterized interlocking conditions are indicated.

Figure 2-3

Example of configured interlocking conditions

Switching authority (for devices with operator panel)

The interlocking condition "Switching Authority" serves to determine the switching authorization. It enables the user to select the authorized command source. For devices with operator panel the following switching authority ranges are defined in the following priority sequence: LOCAL DIGSI REMOTE The object "Switching Authority" serves to interlock or enable LOCAL control, but not remote or DIGSI commands. The 6MD66 is equipped with two key switches. The top switch is reserved for the switching authority. The condition "LOCAL" allows commands from the user interface of the relay. The position "REMOTE" enables remote control. The "Switching authority DIGSI" object is used for interlocking and allows commands to be initiated using DIGSI. Commands are allowed for both a remote and a local DIGSI connection. When a (local or remote) DIGSI PC logs on to the device, it enters its Virtual Device Number (VD). The device only accepts commands having that VD (with switching authority = OFF or REMOTE). When the DIGSI PC logs off, the VD is removed. Commands are checked for their source SC and the device settings, and compared to the information set in the objects "Switching authority" and "Switching authority DIGSI".

Configuration:

Switching authority available: Switching authority DIGSI available: Specific object (e.g. switching device): Specific object (e.g. switching device):

y/n (create appropriate object) y/n (create appropriate object) Switching authority LOCAL (check for Local status): y/n Switching authority REMOTE (check for LOCAL) REMOTE, or DIGSI commands: y/n

24

6MD66 Manual C53000-G1876-C102-3

2.2 Command processing

Table 2-2

Interlocking logic Switching authority DIGSI Command issued Command issued with SC3)=LOCAL from SC=LOCAL or REMOTE Command with SC=DIGSI

Current Switching Authority Status LOCAL (ON)

Not registered not allocated

Interlocked Interlocked 2) "switching authority "DIGSI not regLOCAL" istered" Interlocked 2) Interlocked 2) "switching authority "switching LOCAL" authority LOCAL" Interlocked "DIGSI not registered"

LOCAL (ON)

registered

not allocated

REMOTE (OFF)

not allocated Not registered Interlocked 1) "switching authority REMOTE" registered

REMOTE (OFF)

Interlocked 2) not allocated Interlocked 1) "switching authority "switching authority DIGSI" DIGSI"

1) 2)

3)

also "available" for: switching authority LOCAL (check for local status): n" also "available" for: Switching authority REMOTE (check for LOCAL, REMOTE, or DIGSI status): n" VQ = Source of command

SC = Auto SICAM: Commands that are initiated internally (command processing in the CFC) are not subject to switching authority and are therefore always "available". Switching Authority (for devices without operator panel) Switching Mode (for devices with operator panel) The dongle cable sets the switching authority of the device to "REMOTE". The specifications of the previous section apply.

The switching mode determines whether selected interlocking conditions will be activated or deactivated at the time of the switching operation. The following switching modes (local) are defined: Local commands (SC=LOCAL) interlocked (normal), or non-interlocked switching. The 6MD66 is equipped with two key switches. The bottom switch is reserved for the switching mode. The "Normal" position allows interlocked switching while the "Interlocking OFF" position allows non-interlocked switching. The following switching modes (remote) are defined: Remote or DIGSI commands (SC = LOCAL, REMOTE, or DIGSI) interlocked, or non-interlocked switching. Here de-interlocking occurs through a separate deinterlocking job. The position of the key-switch is irrelevant. For commands from CFC (SC = AUTO SICAM), please observe the notes in the DIGSI CFC manual /3/ (block: BOOL after command).

6MD66 Manual C53000-G1876-C102-3

25

2 Functions

Switching Mode (for devices without operator panel) Zone controls

The dongle cable sets the switching mode of the device to "Normal". The specifications of the previous section apply.

Zone controlled / field interlocking (e.g. via CFC) includes the verification that predetermined switchgear position conditions are satisfied to prevent switching errors (e.g. disconnector vs. ground switch, ground switch only if no voltage applied) as well as verification of the state of other mechanical interlocking in the switchgear bay (e.g. High Voltage compartment doors). Interlockings via the IRC are handled like zone controls. Interlocking conditions can be programmed separately, for each switching device, for device control CLOSE and/or OPEN. The enable information with the data "switchgear is interlocked (OFF/NV/FLT) or enabled (ON)" can be set up, directly, using a single point or double point indication, key-switch, or internal indication (marking), or by means of a control logic via CFC. The current status is queried for a control command and updated cyclically. The assignment is done via "Release object CLOSE/OPEN".

System interlocking Double operation locking

The system interlockings are then considered (allocation via central unit).

Parallel switching operations are interlocked. On arrival of a command all command objects are tested which are also subject to the blockage, as to whether a command is current for them. While the command is being executed, the block is in turn active for all other commands. For switching commands, a check takes place whether the selected switching device is already in the scheduled/desired position (scheduled/actual comparison). This means, if a circuit breaker is already in the CLOSED position and an attempt is made to issue a closing command, the command will be refused, with the operating message "scheduled condition equals actual condition". Switching devices in the fault position are not interlocked by software means. De-interlockings can be bypassed to perform switching operations. This is either done internally by adding a bypass code to the command, or globally by so-called switching modes. SC=LOCAL The switching modes "interlocked (latched)" or "non-interlocked (unlatched)" can be set via the key switch. The position "Interlocking OFF" corresponds to noninterlocked switching and serves the special purpose of unlocking the standard interlocks. REMOTE and DIGSI Commands issued by SICAM or DIGSI are unlocked via global switching mode REMOTE. For de-interlocking a separate job must be issued. De-interlocking is done in each case only for one switch action and only for commands of the same origin source. Job: command to object "Switching mode REMOTE", ON

Device Status Check (setpoint = actual)

De-interlockings

26

6MD66 Manual C53000-G1876-C102-3

2.2 Command processing

Job: switching command to "switching device" Derived command via CFC (automatic command, SC=Auto SICAM): Behaviour configured in the CFC block ("BOOL to command"). 2.2.3.2 Information

No. KeySwitch1 Cntrl Auth KeySwitch2

Message IE

Type of Information DM DM IE IE GW

Description Key Switch 1 (Local/Remote) Control Authority Key Switch 2 (Interlocking OFF/ON) Controlmode LOCAL Controlmode REMOTE Control DIGSI

ModeLOCAL ModeREMOTE CntrlDIGSI

2.2.4
2.2.4.1

Process Data
Description During the processing of the commands, independent of the further message routing and processing, command and process feedback information are sent to the message processing centre. These messages contain information on the cause. With the corresponding allocation (configuration) these messages are entered in the event list, thus serving as a report.

Usercases Requirements

Messages and Operating Messages in Relation to Switching Operations A listing of possible operating messages and their meaning as well as the command types needed for tripping and closing of the switchgear or for raising and lowering of transformer taps are described in the SIPROTEC System Description /1/. All messages with the source of command LOCAL are transformed into a corresponding response and shown in the display of the device.

Acknowledgement of Commands to the Device Front Acknowledgement of commands to Local/Remote/Digsi

The acknowledgement of messages with source of command Local/ Remote/DIGSI are sent back to the initiating point independent of the routing (configuration on the serial digital interface). The acknowledgement of commands is therefore not executed by a response indication as it is done with the local command but by ordinary command and feedback information recording.

Monitoring of feedback information

The processing of commands monitors the command execution and timing of feedback information for all commands. At the same time the command is sent, the monitoring time is started (monitoring of the command execution). This time controls whether the device achieves the required final result within the monitoring time. The monitoring time is stopped as soon as the feedback information arrives. If no feedback

6MD66 Manual C53000-G1876-C102-3

27

2 Functions

information arrives, a response "Timeout command monitoring time" appears and the process is terminated. Commands and information feedback are also recorded in the event list. Normally the execution of a command is terminated as soon as the feedback information (FB+) of the relevant switchgear arrives or, in case of commands without process feedback information, the command output resets and a message is output. The "plus" sign appearing in a feedback information confirms that the command was successful. The command was as expected, in other words positive. The "minus" is a negative confirmation and means that the command was not executed as expected.

28

6MD66 Manual C53000-G1876-C102-3

2.3 Indication processing

2.3
2.3.1

Indication processing
Description
Message processing in High Voltage Bay Control Unit 6MD66 is provided to assure a save and instantaneous transmission of information to the control centre. This is done by giving priority to feedback information from commands before measured values and other messages. Thus the user quickly gets an overview on the current status of the station even when data exchange is very high. Message processing comprises the following Communication with the Substation Controller Utilizing the Priorization Principle Transmission of data to the bay devices connected via inter-relay communication Creation of group alarms in accordance with the configuration in CFC Display of the event list of the device, memorization of 200 messages Display of the signalizing LEDs (in accordance with the configuration carried out)

LED Display and Binary Outputs (output relays)

Important events and conditions are displayed, using LEDs on the front panel of the relay. The device furthermore has output relays for remote indication. All LEDs and binary outputs indicating specific messages can be freely configured. The relay is delivered with a default setting. The Appendix of this manual deals in detail with the delivery status and the allocation options. The output relays and the LEDs may be operated in a latched or unlatched mode (each may be individually set). The latched conditions are protected against loss of the auxiliary voltage. They are reset On site by pressing the LED key on the relay, Remotely using a binary input configured for that purpose, Using one of the serial interfaces. Condition messages should not be latched. Also, they cannot be reset until the criterion to be reported has reset. This applies to messages from monitoring functions, or similar. A green LED displays operational readiness of the relay ("RUN"), and cannot be reset. It goes out if the self-check feature of the microprocessor recognizes an abnormal occurrence, or if the auxiliary voltage is lost. When auxiliary voltage is present, but the relay has an internal malfunction, then the red LED ("ERROR") lights up and the processor blocks the relay. Further information on the functionality, allocation of indications, on how to read out information via DIGSI and the operator panel of the device etc. can be found in the SIPROTEC System Description /1/.

6MD66 Manual C53000-G1876-C102-3

29

2 Functions

2.4
2.4.1
2.4.1.1

Measured value processing


Measurement
Description The Measured values parameter group is used for compiling the user-defined measured values. These measured values are created via DIGSI CFC or arrive via inter relay communication.

Usercases

Limit measured values are used to indicate when a measured value recorded as the operational measured value has exceeded the upper or lower limits. The two measuring transducer inputs (20 mA) contained in the device are already specified in the default setting. These measuring transducer inputs supply non-linearized values which can be converted via DIGSI CFC to measured values such as pressure or temperature. Derived measured values are inserted from the information catalog. Information on configuration of the user-defined measured values can be found in SIPROTEC System Description /1/.

Measured values

2.4.1.2

Information

No. 996 997 Td1= Td2=

Message

Type of Information MW MW Transducer 1 Transducer 2

Description

2.4.2
2.4.2.1

General transducer blocks


Description The measuring transducer blocks form various operands from these input quantities. The measuring transducer function is explained via the following function blocks: Measuring transducer U (MU U) Measuring transducer I (MU I) Measuring transducer one-phase (MU1P) Measuring transducer three-phase (MU3P) Measuring transducer Aron (MUAron) The individual measuring transducer blocks have to be activated in the functional scope of the device and are then displayed in the DIGSI configuration matrix with their input channels and output quantities. They are assigned to current and voltage

30

6MD66 Manual C53000-G1876-C102-3

2.4 Measured value processing

channels of the device. The output quantities can be assigned to various destinations, e.g. system interface, CFC or the display. A functional description of the individual measuring transducer blocks and a list of the accompanying parameters and information can be found in the following chapters.
Table 2-3 Connection variants Star connection Connection examples for a rated transformer voltage Vn secondary from 100 V Functions Measuring transducer 3-phase Measuring transducer 1-phase SYNC function 1 to SYNC function 5 Star connection Vfeederdelta connection Vref 3 x VfeederLE = 57.7 V 1 x VLL = 100 V Measuring transducer 3-phase Measuring transducer 1-phase SYNC function 6 to SYNC function 8 Aron connection 2 x VfeederLL = 100 V 1 x VLL = 100 V Measuring transducer Aron Measuring transducer 1-phase SYNC function 6 to SYNC function 8 Star connection, 3 x VfeederLE = 100 V neutral earthed power 1 x VLE = 100 V supply Measuring transducer 3-phase Measuring transducer 1-phase SYNC function 1 to SYNC function 5
1)

Input voltages Secondary 3 x VfeederLE = 57.7 V 1 x VLE = 57.7 V

Parameter Transformer Vn sec 100 V

Comments for feeder operational measurements for reference operational measurements for synchronisation function for feeder operational measurements for reference operational measurements for synchronisation function for feeder operational measurements for reference operational measurements for synchronisation function for feeder operational measurements for reference operational measurements for synchronisation function

100 V

57.7 V1) 100 V

173.2 V2)

100 V 173.2 V2)

173.2 V2)

100 V 173.2 V2)

173.2 V2)

100 V

2)

Within the SYNC function, the parameter V transformern secondary corresponds to the secondary input voltage. Within the measuring transducer packets, the parameter V transformern secondary is secondary to the 3 x input voltage.

6MD66 Manual C53000-G1876-C102-3

31

2 Functions

2.4.3
2.4.3.1

Parameterizing transducer blocks


Description Configuration is to be performed in the High Voltage Bay Control Unit in each individual case. The device contains pre-defined measuring transducer blocks which can be activated individually.

Configuring the measuring transducer The configuration of measured values is fundamentally different from the configuration of other SIPROTEC 4 devices. It is explained with an example using the function block Measuring transducer 3-phase. Selecting the functional scope First select the measuring transducer blocks from the DIGSI Functional scope dialog box which are to be contained in the functional scope of the device. For this purpose, open the device and click Functional scope in the function selection. Select the available entry on the Measurement 3phase 1.packet line in the Scope column and confirm with OK. The measurement transducer block is activated.

Figure 2-4

Functional scope dialog box

Parameterizing

Click the Measuring transducer object under Parameters in the tree view of DIGSI. The available measuring transducer blocks are listed in the list box. Open Measurement 3phase 1.packet via the context menu and set the values of parameters Secondary Voltage Nominal Value (0.00 V to 200.0 V) and Secondary Current Nominal Value (0.00 A to 5.00 A) depending on your requirements.

32

6MD66 Manual C53000-G1876-C102-3

2.4 Measured value processing

Figure 2-5

Dialog box for setting the parameters

Allocating a measuring transducer Following configuration, the inputs and outputs of the activated measuring transformer block in the allocation matrix of DIGSI are interconnected and the properties of the individual measured values, such as transmission threshold, are configured and interconnection in the CFC is performed. Allocating measured value channels Open the allocation matrix of the device and select Only measured and metered values as the information type. The MU3P_1 group is displayed. Allocate the measured value channels Mvchn to the voltage/current inputs as the source. Allocate the calculated measured values to a destination, e.g. to the system interface, the inter relay communication, the CFC or the display. Configure the properties of the measured values. In the Information item, No. column of the allocation matrix, right-click the information item whose properties you would like to configure and open the Object properties dialog box via the Properties... context menu. Select the Measured value description tab and make the settings. The Measured value description tab is not relevant for the information items MP1_PHI (phase angle), MP1_WLF (active power factor) und MP1_BLF (reactive power factor) and therefore not available.

Allocating measured values Configuring measured values

6MD66 Manual C53000-G1876-C102-3

33

2 Functions

Figure 2-6

Object properties dialog box, Measured value description tab

Select the Transmission threshold tab and make the settings. Use central threshold (10 %) Select this check box to use the factory-preset threshold value of 10 %. This deactivates all the other input and output options in this tab. Parameterised threshold Enter a value between 0 and 2000 in this spin box. The set value multiplied by 0,1 % results in the threshold value. This value is used without any further conditions, provided that neither the Central threshold check box, nor a defined switching object, has been selected.

Figure 2-7

Object properties dialog box, Transmission threshold tab

Configure the object properties of the phase angle 3P1_PHI.

34

6MD66 Manual C53000-G1876-C102-3

2.4 Measured value processing

Figure 2-8

Object properties dialog box, Transmission threshold tab

Allocate the information item 3P1_PHI to C (CFC) as the destination and then link this in the corresponding CFC chart.

Figure 2-9

Example, 3P1_PHI link in CFC chart

Configure the object properties of the block (e.g. LOWER_SETPOINT). For this purpose, right-click the Limit input of the block and select Object properties from the context menu. Observe the working range of -180 to +180 ; the value 100 (%) corresponds to 360 .

6MD66 Manual C53000-G1876-C102-3

35

2 Functions

Figure 2-10

Example, properties of the LOWER_SETPOINT block

The set value 12.5 corresponds to an angle of 45 .

2.4.4
2.4.4.1

Measurement U 1.packet
Description This packet serves to measure an individual voltage. The function provides the r.m.s. value of the fundamental component. The frequency of the voltage is determined from the input signal. If the secondary input voltage on the device falls below 10 Veff, the frequency is marked as invalid. The overflow occurs when the secondary input voltage on the device exceeds 120 Veff. The rated value of the frequency is taken from 36\VWHP 'DWD . Routing of the measurement input to the respective measured value channel Voltage and the routing of the measuring results is performed with DIGSI. Specifications for secondary transformer voltage are made in the properties dialog box of 08 8B. Information on allocation can be obtained from the SIPROTEC System Description /1/.

2.4.4.2

Configuration Notes The factory-preset rated transformer voltage can be set in the predefined range.

6HF9ROWJ1RP9DO

36

6MD66 Manual C53000-G1876-C102-3

2.4 Measured value processing

2.4.4.3
Addr. 0

Settings
Parameter 6HF9ROWJ1RP9DO Setting Options 0.00 .. 200.00 V; < > 0 Default Setting 100.00 V Description Secondary Voltage Nominal Value

2.4.4.4

Information

No. Input U/I U f

Message

Type of Information MK MW MW Voltage U frequency

Description Voltage or Current Input U/I

2.4.5
2.4.5.1

Measurement I 1.packet
Description This packet serves to measure an individual current. The function provides the r.m.s. value of the fundamental component. The frequency of the current is determined from the input signal. If it falls below 10% of the rated value, the frequency is marked as invalid. The rated value of the frequency is taken from 36\VWHP 'DWD . Routing of the measurement input to the respective measured value channel Current and the routing of the measuring results is performed with DIGSI. Specifications for secondary transformer current are made in the properties dialog box of 08 ,B. Information on allocation can be obtained from the SIPROTEC System Description /1/.

2.4.5.2

Configuration Notes The secondary factory-preset rated transformer current can be set in the predefined range.

6HF&XUU1RP9DO

2.4.5.3
Addr. 0

Settings
Parameter 6HF&XUU1RP9DO Setting Options 0.00 .. 5.00 A; < > 0 Default Setting 1.00 A Description Secondary Current Nominal Value

6MD66 Manual C53000-G1876-C102-3

37

2 Functions

2.4.5.4

Information

No. MwCh_I I f

Message

Type of Information MK MW MW Current Input I Current I frequency

Description

2.4.6
2.4.6.1

Measurement 1phase 1.packet


Description This packet serves to perform a monophase measurement (current and voltage). The measuring results of the phase current and the phase voltage are r.m.s. values of the corresponding fundamental component. The phase current is set to the current input of the measuring transducer, whereas the phase voltage is set to the voltage input. The r.m.s. values calculated from these two input signals, the active power, the reactive power, the apparent power, the cos , the sin and the linked sizes and frequency calculated from the voltage (see information overview) are then present at the measuring transducer output. The frequency is determined from the applied phase voltage. If the secondary input voltage on the device falls below 10 Veff, the frequency is marked as invalid. The overflow occurs when the secondary input voltage on the device exceeds 120 Veff. The rated value of the frequency is taken from 3RZHU 6\VWHP 'DWD . Routing of the measurement inputs to the respective measured value channels Phase current and Phase voltage and the routing of the measuring results is performed with DIGSI. Specifications for secondary transformer current and secondary transformer voltage are made in the properties dialog box of 083B. Information on allocation can be obtained from the SIPROTEC System Description /1/.

2.4.6.2

Configuration Notes The factory-preset rated transformer voltage can be set in the predefined range. The secondary factory-preset rated transformer current can be set in the predefined range.

6HF9ROWJ1RP9DO 6HF&XUU1RP9DO

38

6MD66 Manual C53000-G1876-C102-3

2.4 Measured value processing

2.4.6.3
Addr. 0 0

Settings
Parameter 6HF9ROWJ1RP9DO 6HF&XUU1RP9DO Setting Options 0.00 .. 200.00 V; < > 0 0.00 .. 5.00 A; < > 0 Default Setting 100.00 V 1.00 A Description Secondary Voltage Nominal Value Secondary Current Nominal Value

2.4.6.4

Information

No. 1P1Input_U 1P1Input_I 1P1_U 1P1_I 1P1_P 1P1_Q 1P1_S 1P1_ 1P1_cos 1P1_sin 1P1_f

Message

Type of Information MK MK MW MW MW MW MW MW MW MW MW

Description 1P1 Voltage Input U 1P1 Current Input I 1P1 Voltage U 1P1 Current I 1P1 Active Power P 1P1 Reactive Power Q 1P1 Apparent Power S 1P1 Phase Angle Phi 1P1 Active Power Factor Cosine Phi 1P1 Reactive Power Factor Sine Phi 1P1 Frequency of U

2.4.7
2.4.7.1

Measurement 3phase 1.packet


Description This packet serves to perform a three-phase measurement (current and voltage). The measuring results of the phase currents, phase voltages, phase-to-phase voltages, zero sequence current and zero sequence voltage are RMS values of the corresponding fundamental compound. The following phase currents are applied at the current inputs of the measuring transducer: IL1, IL2 and IL3, as were the voltages VL1, VL2 and VL3. The r.m.s. values of the phase currents calculated from these six input signals, phase voltages, phase-to-phase voltages, zero sequence current, phase voltages, phase-to-phase voltages, zero sequence current, zero sequence voltage, active power, reactive power, apparent power, cos , sin and the linked sizes and frequency calculated from the voltage VL1 (see Information overview table) are applied at the output of the measuring transducer. The frequency is determined from the applied phase voltage VL1. If the secondary input voltage on the device falls below 10 Veff, the frequency is determined from the phase voltage VL2 or VL3. If all three voltages are too low, the rated frequency is used as frequency. In this case, the combined variables and the frequency itself are marked invalid. The phase-to-phase voltages and the zero variables start to fluctuate depending on the deviation from the rated frequency. The overflow occurs when the second-

6MD66 Manual C53000-G1876-C102-3

39

2 Functions

ary input voltage on the device exceeds 120 Veff. The rated value of the frequency is taken from 3RZHU 6\VWHP 'DWD . Routing of the measurement inputs to the respective measured value channels Phase currents and Phase voltages and the routing of the measuring results is performed with DIGSI. The direction of rotation can be changed by exchanging the phases. Enter the display factors for the primary values for each required output when routing the results. In this context, it must be observed that the phase-to-phase value is indicated for the phase-ground voltages if the phase-to-phase voltage (rated voltage) was set as primary value. Specifications for secondary transformer current and secondary transformer voltage are made in the properties dialog box of 083B. The phase-to-phase voltage is used as the value for the secondary transformer voltage. 2.4.7.2 Configuration Notes The factory-preset rated transformer voltage can be set in the predefined range. The secondary factory-preset rated transformer current can be set in the predefined range.

6HF9ROWJ1RP9DO 6HF&XUU1RP9DO

2.4.7.3
Addr. 0 0

Settings
Parameter 6HF9ROWJ1RP9DO 6HF&XUU1RP9DO Setting Options 0.00 .. 200.00 V; < > 0 0.00 .. 5.00 A; < > 0 Default Setting 100.00 V 1.00 A Description Secondary Voltage Nominal Value Secondary Current Nominal Value

2.4.7.4

Information

No. 3P1InputU1 3P1InputU2 3P1InputU3 3P1InputI1 3P1InputI2 3P1InputI3 3P1_U0 3P1_U1 3P1_U2 3P1_U3 3P1_U12 3P1_U23 3P1_U31 3P1_I0

Message

Type of Information MK MK MK MK MK MK MW MW MW MW MW MW MW MW

Description 3P1 Voltage Input U1 3P1 Voltage Input U2 3P1 Voltage Input U3 3P1 Current Input I1 3P1 Current Input I2 3P1 Current Input I3 3P1 Zero Sequence Voltage 3P1 Phase to Earth Voltage U1 3P1 Phase to Earth Voltage U2 3P1 Phase to Earth Voltage U3 3P1 Phase to Phase Voltage U12 3P1 Phase to Phase Voltage U23 3P1 Phase to Phase Voltage U31 3P1 Zero Sequence Current

40

6MD66 Manual C53000-G1876-C102-3

2.4 Measured value processing

No. 3P1_I1 3P1_I2 3P1_I3 3P1_P 3P1_Q 3P1_S 3P1_ 3P1_cos 3P1_sin 3P1_f

Message

Type of Information MW MW MW MW MW MW MW MW MW MW

Description 3P1 Phase Current I1 3P1 Phase Current I2 3P1 Phase Current I3 3P1 Active Power Three Phase 3P1 Reactive Power Three Phase 3P1 Apparent Power Three Phase 3P1 Phase Angle Three Phase 3P1 Active Power Factor Three Phase 3P1 Reactive Power Factor Three Phase 3P1 Frequency

2.4.8
2.4.8.1

Measurement Aron 1.packet


Description The ARON switching enables the complete calculation of a three-phase system with only two voltage transformers and two current transformers. The measuring results of the phase currents, phase voltages, phase-to-phase voltages, zero sequence current and zero sequence voltage are r.m.s. values of the corresponding fundamental compound. Two phase currents (e.g. IL2 and IL3) and two phase-to-phase voltages (e.g. VL1L2 and VL1L3) are applied to the measuring transducer inputs. The r.m.s values of phase currents calculated from these four input signals, phase voltages, phase-to-phase voltages, zero sequence current,zero sequence voltage, active power, reactive power, apparent power, cos , sin and the linked sizes and frequency calculated from the voltage VL1L2 (see Information overview table) are then applied at the measuring transducer output. The frequency is determined by means of the applied VL1L2 voltage. If the secondary input voltage on the device falls below 10 Veff, the frequency is determined by means of the VL1L3 voltage. If both voltages are too low, the rated frequency is used as frequency. In this case, the combined variables and the frequency itself are marked invalid. The phase-to-phase voltages and the zero variables start to fluctuate depending on the deviation from the rated frequency. The rated value of the frequency is taken from 3RZHU 6\VWHP 'DWD . Routing of the measurement inputs to the respective measured value channels Currents and Voltages and the routing of the measuring results is performed with DIGSI. Enter the display factors for the primary values for each required output when routing the results.

2.4.8.2

Configuration Notes The factory-preset rated transformer voltage can be set in the predefined range. The secondary factory-preset rated transformer current can be set in the predefined range.

6HF9ROWJ1RP9DO 6HF&XUU1RP9DO

6MD66 Manual C53000-G1876-C102-3

41

2 Functions

2.4.8.3
Addr. 0 0

Settings
Parameter 6HF9ROWJ1RP9DO 6HF&XUU1RP9DO Setting Options 0.00 .. 200.00 V; < > 0 0.00 .. 5.00 A; < > 0 Default Setting 100.00 V 1.00 A Description Secondary Voltage Nominal Value Secondary Current Nominal Value

2.4.8.4

Information

No. A1Input_U1 A1Input_U2 A1Input_I1 A1Input_I2 A1_U12 A1_U13 A1_I2 A1_I3 A1_P A1_Q A1_S A1_ A1_cos A1_sin A1_f

Message

Type of Information MK MK MK MK MW MW MW MW MW MW MW MW MW MW MW

Description A1 Voltage Input U1 A1 Voltage Input U2 A1 Current Input I1 A1 Voltage Input I2 A1 Phase to Phase Voltage U12 A1 Phase to Phase Voltage U13 A1 Phase Current I2 A1 Phase Current I3 A1 Active Power P A1 Reactive Power Q A1 Apparent Power S A1 Phase Angle Phi A1 Active Power Factor Cosine Phi A1 Reactive Power Factor Sine Phi A1 Frequency

42

6MD66 Manual C53000-G1876-C102-3

2.5 Metered value processing

2.5
2.5.1

Metered value processing


Description
The device can add up couner pulses of an external counter recorded via a binary input. Additionally, the bay control unit can calculate energy values from measured values.

Operation of pulse metered value

The High Voltage Bay Control Unit 6MD66 forms the metered value as a sum of the externally generated counter pulses of a power meter. The pulses are read in via a binary input. The metered value receives a unit based on the following table. It has the same precision as the external counter and can also be an adjusted metered value. With the metered values calculated from measured values , the High Voltage Bay Control Unit 6MD66 forms the power from the applied current and voltage values or from any desired measured values and integrates this calculated power value over time. The result is an energy value with the precision of the device (0.5 %), i.e. an operating metered value which cannot be used for adjustment.
Table 2-4 Operating metered values Measured values W p+ W p W q+ W q Real power, output Real power, input Reactive power, output Reactive power, input Possible units kWh, MWh, GWh kWh, MWh, GWh kVARh, MVARh, GVARh kVARh, MVARh, GVARh

Operation of metered values calculated from measured values

The following types of information can be allocated to a metered value window in the DIGSI allocation matrix. Metered values calculated from measured values Pulse metered value The same operations are possible with pulse and metered values calculated from measured values, e.g. reset - to set back to a specified value etc.. Using the pulse metered value In this example, the active power of a 3-phase system is to be integrated over time and displayed as a metered value. The pulse output of an external device which supplies the active power pulse accordingly, is to be applied to a binary input of the device. The power corresponding to a pulse must be known. Inserting a pulse metered value Open the allocation matrix of the device and select Only measured and metered values as the information type. Create the group Energy in the allocation matrix. Open the information catalog and select the line Pulse (PMV) under PowerMeter Pulse.

6MD66 Manual C53000-G1876-C102-3

43

2 Functions

Figure 2-11

Selecting information type pulse metered value

Drag the selected information type with the left mouse button into the Energy group in the allocation matrix. Configuring a pulse metered value Allocate the inserted pulse metered value in the allocation matrix to a binary input as the source. Allocate the inserted pulse metered value in the allocation matrix to the destination Metered value window. Configuring a pulse metered value The properties of the pulse metered values can be configured via a dialog box. Right-click on the information item PulseMV in the Information column, Display text in the allocation matrix. Select Properties... from the context menu. The Object properties dialog box is opened. Select the tab Measured value description and enter the unit kWh and the desired number of decimal places. Enter the value which corresponds to a pulse of the external counter in the unit selected above into the input box Conversion factor. For example, enter 0.1 if a pulse corresponds to the energy 0.1 kWh and the unit kWh was selected above.

Figure 2-12

Object properties dialog box, Measured value description tab

44

6MD66 Manual C53000-G1876-C102-3

2.5 Metered value processing

Select the tab Restore trigger and energy flow direction and enter the restore trigger and energy flow direction. Select the Cyclic option if the metered value is to be transmitted to the control center at cyclic intervals. Otherwise select the None option. By pressing the Settings button, you end up in the dialog box for setting the corresponding time interval. One minute is preset. Note The settings made in the Cyclical restoring tab apply globally for all metered values. Under Energy flow direction, you define whether the metered value summates the quantity of exported or imported energy by selecting one of the two options.

Figure 2-13

Object properties dialog box, Restore trigger and energy flow direction tab

Select the tab Pulse type and error input and make your settings there. Select the Wiping pulse / S0 option if the rising edge of a single pulse is to increment the metered value by one. Select the Double current pulse option if the falling edge of a double current pulse is to increment the metered value by one. As soon as you route a pulse metered value to a binary input, the next binary input can be automatically routed as an fault input. A signal to this fault input can mark the count as corrupt. If you use this procedure, select the Use fault input checkbox. If it is not selected, the binary input following the metered pulse input is available to another application.

Figure 2-14

Object properties dialog box, Pulse type and error input tab

6MD66 Manual C53000-G1876-C102-3

45

2 Functions

Accept the settings with OK. Use metered values calculated from measured values In this example, the active power of a 3-phase system is to be integrated over time and displayed as a metered value. Here, a measuring transducer packet MU3P_1 which must be identified as available in the function scope of the device is used. It is configured with the secondary voltage nominal value 100.00 V and the secondary current nominal value 1 A. The rated data of the network is 110 kV and 20 kA. Inserting metered values calculated from measured values Open the allocation matrix of the device and select Only measured and metered values as the information type. Open the information catalog and select the line PowerMeter (MVMV) under PowerMeter PowerMeter.

Figure 2-15

Selecting information type measured value metered value

Drag the selected information type with the left mouse button into the MU3P_1 group in the allocation matrix. Allocating metered values calculated from measured values Configuring metered values calculated from measured values Allocate the inserted information item to the source Measured value in the allocation matrix and select 3P1_P from the list. Allocate the inserted information item to the Metered value window destination in the allocation matrix. The properties of the metered values calculated from measured values can be configured via a dialog box. Right-click on the information item MeasVMV in the Information column, Display text in the allocation matrix. Select Properties... from the context menu. The Object properties dialog box is opened. Select the tab Measured value description and enter the unit MWh and 2 as the number of decimal places.

46

6MD66 Manual C53000-G1876-C102-3

2.5 Metered value processing

Using the conversion factor, you can convert the input signal to match the selected unit and data of the measuring transducer. The conversion always refers to the 100 % value of the input signal with measured values. If a measuring transducer packet supplies the currents and voltages as the power 3811 MW at a 100 % value, this is the energy value which accumulates in a MWh. This value divided by 60,000 is to be entered as the conversion factor. The High Voltage Bay Control Unit generates 60,000 values per hour internally, which are used for the conversion factor. Enter the calculated value 0.0635 into the Conversion factor input box (3811 MW divided by 60,000).

Figure 2-16

Object properties dialog box, Restore trigger and energy flow direction tab

Select the tab Restore trigger and energy flow direction and enter the restore trigger and energy flow direction. Select the Cyclic option if the metered value is to be transmitted to the control center at cyclic intervals. Otherwise select the None option. By pressing the Settings button, you end up in the dialog box for setting the corresponding time interval. One minute is preset. Note The settings made in the Cyclical restoring tab in this dialog box apply globally for all metered values. Under Energy flow direction, you define whether the metered value summates the quantity of exported or imported energy by selecting one of the two options.

6MD66 Manual C53000-G1876-C102-3

47

2 Functions

Figure 2-17

Object properties dialog box, Restore trigger and energy flow direction tab

Accept the settings with OK.

48

6MD66 Manual C53000-G1876-C102-3

2.6 Threshold-Switch

2.6
2.6.1

Threshold-Switch
Description
Using the Threshold switch function, you can set transmission thresholds and allocate the threshold switches to individual or multiple measured values. The threshold value procedure consists of the Transmission threshold configuration dialog and the threshold switch.

Transmission threshold

The transmission threshold determines the transmission frequency of measured values. It is specified in percentage. If zero is selected as the threshold value for the transmission threshold, each measured value will be transmitted to the higher-level station. A threshold value not equal to zero results in all changes to new measured values being added compared to the last measured value transmitted. If the sum of the changes reaches the set percentage, a new measured value is transmitted at the next possible point in time. Perform the settings in the DIGSI configuration matrix. You can set the central threshold, configured threshold and switching object in the object properties of the measured value, tab Transmission threshold. Use central threshold (10%): Select this check box to use the factory-preset threshold value of 10 %. This de-activates all the other input and output options in this tab. Parameterised threshold: Set the desired value in this rotating box. The set value multiplied by 0.1 % results in the threshold value. Switching object: A changeover from the central and the parameterised threshold can be initiated by the status of a message. From the drop-down menu, select the indication whose status shall initiate a changeover.

Threshold switch

The group Software switch (in the DIGSI configuration matrix) contains all potential switching objects. Threshold 1 is the preset value. You can add additional thresholds (single point indications) from the information catalog. Assign the threshold value switch to one or several measured values via the Switching object setting in the measured-value object properties.

2.6.2

Information

No. ThreshVal1

Message IE

Type of Information

Description Threshold Value 1

6MD66 Manual C53000-G1876-C102-3

49

2 Functions

2.7

Circuit breaker synchronisation


If the synchronisation function of the device is active, the device can check whether the synchronisation conditions of both subnetworks are fulfiled (synchrocheck) when the circuit breaker is closed. The device distinguishes between synchronous and asynchronous networks and reacts differently on the connection. Synchronous networks exhibit small differences regarding phase angle and voltage modulus. The circuit breaker operating time does not need to be considered. On the contrary, asynchronous networks include bigger differences and the time window for switching on is passed more quickly. Consequently, the circuit breaker operating time must be considered in this case. The control command is automatically pre-dated by this time in order to ensure that the circuit breaker contacts close exactly at the right time. The automation functions enabled in the device allow to automatically use various reference voltages of the active busbar for synchronization (whereby the individual reference voltage depends on the isolator position). It is possible to save and hold available for operation maximally eight different setting groups for the synchronisation function. In this way, it is possible to consider the various features of several circuit breakers. The synchronisation groups six to eight differ from the groups one to five essentially due to the connection of the voltage transformers. Various connection examples can be found in the Appendix.

2.7.1
2.7.1.1

SYNC Function group 1


Description The SIPROTEC 4 device 6MD66 has configuration options for eight different synchronisation functions. The function and operation is described in the following using the 6<1& IXQFWLRQ . Special features of SYNC functions 6 to 8 are compiled separately.

functioning

The synchronisation function is used for connecting two subnetworks in a substation control system or for operational switch on or on the protection level after a three-pin short or long interruption. The synchronisation function ensures that the connection is only performed if both subnetworks are synchronous to each other or the deviation is within the defined limits. The connection is performed if the following conditions are met at the moment of establishing the isolated connection: Voltage magnitudes 8PLQ < | V | < 8PD[ Difference of voltage magnitudes | V | < 8PD[ Frequencies IPLQ f IPD[ Difference of frequencies f < IPD[ Difference of angles < max For safety reasons, connection is only permitted below the curve shown in the diagram for large differences in frequency and long circuit-breaker operating times.

50

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Figure 2-18

Maximum permissible difference in frequency as a function of the circuit-breaker operating time

The Dead bus and Dead line connection are special cases. In this case, connection is made depending on the configuration under the following conditions: Dead Line | Vpp | > 8PLQ and | Vline | < 8GHDG and IPLQ fpp IPD[ Dead bus | Vpp | < 8GHDG and | Vline | > 8PLQ and IPLQ fline IPD[ Dead line & Dead bus | Vpp | < 8GHDG and | Vline | < 8GHDG Busbar voltage Vpp and feeder voltage Vline are assigned to voltages V1 and V2 depending on how the device is connected. Connection examples can be found in the Appendix. The connection is performed on an idle busbar, on an idle feeder or on both. A synchronisation comparison with the runtime of the synchronisation function can be executed by means of definitely applied voltages (normal case) or by means of a voltage application via relay. The synchronisation comparison including an application of the voltage is necessary e.g. for multiple busbars or in case of a failure of the coupling circuit breaker (backup switching). Additional preparatory switching operations as well as the selection of the subsettings group are necessary for applying the voltage at the time of the comparison. The settings must be stored in the control device for each combination of subnetworks. The measuring channels of the reference and feeder voltage must be assigned to each synchronisation module individually. Voltage application If the voltage application is used, the user must set a switching sequence with the following components: Voltage application Synchronisation voltage deselection

6MD66 Manual C53000-G1876-C102-3

51

2 Functions

The voltage application option ensures that a 250 ms delay is considered in the measuring algorithm after the synchronisation start. In this way, the measured values can stabilize. Field of application internal control, internal synchronisation The synchronisation with internal control and internal synchronisation is the standard application with 6MD66. Maximally 8 synchronisation modules (SYNC functions group 1 to 8) with different settings groups are available. The assignment of the synchronisation-requiring control device to the corresponding synchronisation settings group is performed via the 6\QF6' setting (control device to be synchronised). At the time of the switching operation, the module selection can be controlled dynamically via the Sync. effective input message. The Sync. effective input message can be configured to a binary input, CFC or IRC. Unsynchronised switching is performed if no synchronisation function is effective (Sync. effective OFF). In this case, the contact between the control and the synchronisation function is performed internally via messages: !6\ 0HDV (Measurement request) 6\QF &ORVH5HO (Enable switch-on) 6\QF V\QFKURQ (in case of an error) Field of application external control, internal synchronisation The 6MD66 also enable the synchronisation via an external control and internal synchronisation. To directly connect an external control (e.g. AR), the setting of the control device to be synchronised must be set to low. At the time of the switching operation, the module selection can be controlled dynamically via the Sync. effective input message. The Sync. effective input message can be configured to a binary input, CFC or IRC. Unsynchronised switching is performed if no synchronisation function is effective (Sync. effective OFF). In this case, the contact between the control and the synchronisation function is performed internally via messages: !6\ 0HDV (Measurement request), on binary input 6\QF &ORVH5HO, on relay (for outputting the switch-on command) 6\QF V\QFKURQ, to relay Subfunctions The synchronisation check is composed of the two subfunctions control and synchronisation. The control function ensures the coordination of the complete command procedure: Coordination of the different switching directions Standard interlockings such as timeout protection Command connection/disconnection of the command relays Command logging CO+/-, FB+/- and COE. Feedback to the operator (operator response). The Synchronisation function processes the measuring phase of: !6\ 0HDV (Measurement request), start of measurement, to 6\QF &ORVH5HO, switching release.

52

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Command processing phases with synchrocheck

Depending on the setting and the current process condition, the individual phases of the command processing are executed, skipped or the command processing is aborted. When integrating the synchronisation procedure into a switching sequence, the deselection phases must be processed correspondingly also in case of an abort. Voltage application: The voltage application (applying measured values at the time of the switching operation) is optional. It is, for example, set via a switching sequence in CFC. The corresponding measured values must be switched to the device analogue inputs via relays. Selection of the SYNC function group(if necessary): The SYNC function group selection (selection of a function module with its settings and messages) is optional. The selection is only required if several SYNC function modules are actually switched active. It is, for example, set via a switching sequence in CFC. The selection is performed by activating the input indication !6\ HII effective. Switchgear interlocking: This phase executes the control subfunction. It serves to execute all switchgear interlocking checks and to state if switching is permitted or not. In additon to this, it is checked if maximally one synchronisation function (measuring phase) is active. Checking start conditions: This phase executes the control subfunction. A check determines whether switching is to occur with or without synchronisation. It serves to execute all switchgear interlocking checks and to state if switching is permitted or not. In additon to this, it is checked if maximally one synchronisation function (measuring phase) is active. Control direction: Control command = ON: Continue with synchronisation check. Control command = OFF: Continue with control phase (no synchronisation required). Synchronisation check: Checks whether the control device concerned shall be switched on synchronised or evaluation of the number of input messages !6\ HII = ON. Analysis of the operating mode Evaluation of the input indications of the selected block.

Table 2-5

Start conditions check phase, SYNC function module selection Number of input messages !6\ HII = ON Irrelevant Unsynchronised control device, continue with control phase Unsynchronised switching, continue with control phase Reaction

Number of SYNC function blocks including the control device to be switched 0

6MD66 Manual C53000-G1876-C102-3

53

2 Functions

Number of SYNC function blocks including the control device to be switched 1

Number of input messages !6\ HII = ON 1

Reaction

Unambiguous allocation, continue with operating mode analysis and activated block Error, abort with BF (too many blocks effective)

>1

>1

Table 2-6

Start conditions check phase, operating mode analysis 6\QF &ORVH5HO Irrelevant ON OFF Abort with BFSwitching enable, continue with control phase Continue with Measuring phase, tripping by: >SyMeasON Reaction

6\QF (UURU ON OFF OFF

Measuring: This phase executes the synchronisation subfunction. This phase is coordinated by means of input indications: !6\ 0HDV, start/stop of measurement !6\ GLU&2, bypassing !6\ EORFN, block switching enable The actual measuring procedure with the output messages starts afterwards: 6\QF &ORVH5HO, switching enable (continue with control phase) 6\QF (UURU, synchronisation failed 6\QF EORFN, switching enable blocked 6\QF0RQ7LPH([F, monitoring time exceeded

54

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Figure 2-19

Input indications and output indications of the synchronisation function

Table 2-7

Controlling the measuring phase Action Measuring Reaction Switching enable: 6\QF &ORVH5HO ON

!6\ 0HDV. ON and !6\ GLU&2 = ON and 6\QF EORFN = OFF !6\ 0HDV ON and !6\ GLU&2. = OFF !6\ 0HDV. OFF Synchronisation conditions reached, or !6\ GLU&2. ON and 6\QF EORFN = OFF Synchronisation conditions reached, or !6\ GLU&2 ON and 6\QF EORFN = ON 6\QF EORFN = OFF 6\QF EORFN = ON Monitoring time exceeded 76<1 '85$7,21 Errors (problems in the synchroni- Stop sation function) Irrelevant Irrelevant Stop Stop Stop Stop Start

Switching enable: 6\QF &ORVH5HO ON

Switching releases are given: 6\QF EORFN OFF Switching enables are blocked: 6\QF EORFN ON Indication: 6\QF0RQ7LPH([F ON Indication: 6\QF (UURU ON

6MD66 Manual C53000-G1876-C102-3

55

2 Functions

A measurement request !6\ 0HDV ON in the state !6\ EORFN ON corresponds to the measurement initiation in the SINAUT LSA. An abort of the measuring phase is initiated via !6\ 0HDV OFF. Control: This phase executes the control subfunction. The command procedure is aborted for: Abort command with AC+ Monitoring time exceeded 76<1 '85$7,21 with CO 6\QF (UURU ON, synchronisation failed with COThe command procedure is started via the following indication: 6\QF &ORVH5HO ON, switching enable comes with CO+ The normal command sequence runs afterwards. Deselection of the SYNC function block: The action selection of the SYNC function block must be terminated. This is also true for an abort of the command procedure. Voltage deselection: The voltage application action must be terminated. This is also true for an abort of the command procedure.

Interfaces

The following data are relevant for the user as an interface: Commands, Commands to the circuit breaker/the function from different initiators. Input indications, Indications for controlling the synchronisation function. Output indications, Indications on the state of the synchronisation function and indications on switchimpeding criteria. Measuring channels, Allocation of the logical inputs of the synchronisation function on the voltage transformer (analogue input). Measured values, calculated measured values of the synchronisation function. Indications, Indications on the command procedure (such as CO+/CO-). Settings, Settings for configuring properties.

56

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Commands

Table 2-8

Start conditions check phase, operating mode analysis Code Explanation Control command from different initiators. ON: Control command for switching the control device on. (with or without synchronisation procedure) OFF: Control command for switching the control device off. (without synchronisation procedure)

Command ON/OFF to 6\QF6'

Command abort - to 6\QF6', or - to all

Abort command, a running command procedure, the synchronisation or switching procedure must be aborted. Abort of the synchronisation procedure is without conditions. Abort of the synchronisation procedure is only possible for a command with operating mode "impulse, interruptible".

Input indications

The input indications are enabled once per synchronisation settings group. For this reason, they are configured as often as synchronisation settings groups are required.
Table 2-9 Code !6\ HII Function effective. Activation and deactivation of a function block. In the "Testing start conditions" phase, the module SYNC function group is selected by means of this indication. For selecting a block or for a unique emergency control, a switching sequence must be set via CFC, e.g. for emergency control: - effective OFF - command ON - effective ON An emergency control can also be reached via !6\ GLU&2 ON, however only if !6\ EORFN OFF. ON: The block is effective. OFF: The block is ineffective (unsynchronised switching). !6\ EORFN Block switching enable. The synchronisation functions normally (the measuring function is executed), but a switching enable is prevented. The blocking of the switching enable is signalled via the 6\QF EORFN output indication. ON: switching enables are blocked. OFF: switching enables are provided. !6\ GLU&2 Bypassing. The measuring function is bridged, i.e. a measurement for !6\ EORFN OFF immediately initiates a switching enable. ON: The measuring function is skipped or stopped with !6\ 0HDV. ON. The switching enable is provided. OFF: The measuring function is started with !6\ 0HDV ON. Input indications, function blocks SYNC function group Explanation

6MD66 Manual C53000-G1876-C102-3

57

2 Functions

Code !6\ 0HDV

Explanation Start/stop of the (measuring) synchronisation function. ON: The synchronisation function is started. OFF: The synchronisation function is aborted.

!6\8!8

Switch test V2 dead on / off. ON: Connection occurs even if voltage V2 is missing. (The threshold value for dead line or busbar can be configured.)

!6\88!

Switch test V1 dead on / off: ON: Connection occurs even if voltage V1 is missing. (The threshold value for dead line or busbar can be configured.)

!6\88

Swtich test V1 & V2 dead on / off. ON: Connection occurs even if voltages V1 and V2 are missing. (The threshold value for dead line or busbar can be configured.)

Measuring channels

The input measuring channels describe a measured-value channel and can be configured directly on an analogue input in the matrix.
Table 2-10 Code 6\ &K8 6\ &K8 Channel of voltage V1. Channel of voltage V2. Input measuring channels, function blocks FB_SYNC 1 to 5 Explanation

Output indications

Status messages are output from the synchronisation function. The status messages are output in the context of the active FB_SYNC function module.
Table 2-11 Code 6\QF &ORVH5HO Output messages of the synchronisation function Explanation Synchronisation conditions exist, switching is enabled. ON: This immediately leads to a switching command (triggering of command relays). 6\QF (UURU 6\QF EORFN 6\QF V\QFKURQ 6\QF 8! 8 6\QF 8 8! 6\QF 8 8 6\QF 9GLII! Error, problems within the synchronisation function. Blocking by external event. The networks meet the synchronisation conditions for asynchronous or synchronous networks. Condition V2 dead exists. Condition V1 dead exists. Condition V1 & V2 dead exists. The difference voltage amount is greater than the setting. The corresponding SVK_Udiff measured-value indication is transmitted additionally. 6\QF IGLII! The difference voltage amount is greater than the setting. The corresponding SVK_Fdiff measured-value indication is transmitted additionally.

6\QF0RQ7LPH([F Monitoring time exceeded

58

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Code 6\QF GLII!

Explanation The amount of the difference angle is greater than the setting. The corresponding SVK_Fdiff measured-value message is transmitted additionally, provided that the Fdiff < FdiffSyn condition is met.

6\QF I!!

The f1 frequency is greater than the fmax setting. The corresponding SVK_F1 measured-value message is transmitted additionally.

6\QF I

The f1 frequency is smaller than the fmin setting. The corresponding SVK_F1 measured-value message is transmitted additionally.

6\QF I!!

The f2 frequency is smaller than the fmax setting. The corresponding SVK_F2 measured-value message is transmitted additionally.

6\QF I

The f2 frequency is smaller than the fmin setting. The corresponding SVK_F2 measured-value indication is transmitted additionally.

6\QF 8!!

The V1 voltage is greater than the Vmax setting. The corresponding SVK_Usyn1 measured-value indication is transmitted additionally.

6\QF 8

The V1 voltage is smaller than the Vmin setting. The corresponding SVK_Usyn1 measured value indication is transmitted additionally, provided that Dead Bus is not switched on or that no Dead Bus voltage was set.

6\QF 8!!

The V2 voltage is greater than the Vmax setting. The corresponding SVK_Usyn2 measured-value indication is transmitted additionally.

6\QF 8

The V2 voltage is smaller than the Vmin setting. The corresponding SVK_Usyn2 measured value indication is transmitted additionally, provided that Dead Line is not switched on or that no Dead Line voltage was set.

Output messages

The measured values are calculated by the measuring function and made available for display or further processing (e.g. for limit-value determination in CFC). It is determined by means of configuration if a measured value is enabled or disabled. The measured values are calculated for each function module SYNC function group. The storage is performed independent of the information objects.
Table 2-12 Code 6\QF 8 6\QF 8 6\QF 9GLII Synchronisation measured values Explanation Synchronisation voltage 6\QF 8 is generally also the reference voltage. Synchronisation voltage 6\QF 8 is generally also the feeder voltage. Difference of synchronisation voltages 6\QF 8 and 6\QF 8.

6MD66 Manual C53000-G1876-C102-3

59

2 Functions

Code 6\QF 6\QF I 6\QF I 6\QF IGLII

Explanation Angles between the voltages 6\QF 8 and 6\QF 8. Frequency of the synchronisation voltage 6\QF 8. Frequency of the synchronisation voltage 6\QF 8. Frequency difference between f(6\QF 8) and f(6\QF 8).

2.7.1.2

Configuration Notes The circuit breaker closing (operating) time indicates the runtime of the circuit breaker including all relay and contactor pickup times. It can be specified in the predefined range. A default value is preset. Adaptation of the V1 and V2 voltages is possible with the %DODQFLQJ 88. It can be specified in the predefined range. A default value is preset. The phase angle shift is set with the angle adaptation initiated by the transformer vector group. The angle faults of imprecise primary transformers can also be corrected. The phase angle can be set in the predefined range. A default value is preset. Here, the secondary rated transformer voltage V1 of the measured-value input for the relevant reference voltage must be set on the input/output modules. In this context, it must be observed that, in case of a measuring voltage application, transformers with the same transformation ratio and the same connection must be used for all connectable voltages. The voltage can be set in the predefined range. A default value is preset. Here, the secondary rated transformer voltage V2 of the measured-value input for the relevant reference voltage must be set on the input/output modules. In this context, it must be observed that, in case of a measuring voltage application, transformers with the same transformation ratio and the same connection must be used for all connectable voltages. The voltage can be set in the predefined range. A default value is preset. Synchronizable control device. The synchronization function can be used for controlling an internal or external command procedure. In case of an internal command processing, a connection to the control device to be synchronized is established at the parameter 6\QF6'. The command is initiated via a control command to the control device, e.g. from the control display. In case of an external command processing, the parameter is "empty". The lower voltage limit 8PLQ specifies the minimum voltage which may be connected. It can be specified in the predefined range. A default value is preset. The upper voltage limit 8PD[ specifies the maximum voltage which may be connected. It can be specified in the predefined range. A default value is preset. The voltage threshold indicates the voltage maximum up to which a line or busbar is detected as dead. It can be specified in the predefined range. A default value is preset.

7&% FORVH

%DODQFLQJ 88

7U 88

6HF7UDQV1RP9DO

6HF7UDQV1RP9DO

6\QF6'

8PLQ

8PD[

8GHDG

60

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

6\QF8!8

This parameter serves to specify if a connection is to take place in case of a healthy busbar and a dead line or dead generator (Dead Line). The default setting is No. This parameter serves to specify if a connection is to take place in case of a dead busbar and a healthy line (Dead Bus). The default setting is No. This parameter serves to specify if a connection is to take place in case of a dead busbar and a dead line (Dead Line and Dead Bus). The default setting is No. The maximum duration of synchronisation check must be set here. If the connection cannot be established successfully within this period, the synchronization procedure is aborted. It can be specified in the predefined range. A default value is preset. This setting defines the minimum of the frequency range in which the synchronous connection is permissible. The working range of the measuring procedures is not influenced. The lower limit of the frequency working range must be lower than its upper limit. It can be specified in the predefined range. A default value is preset. This setting defines the maximum of the frequency range in which the synchronous connection is permissible. The working range of the measuring procedures is not influenced. The upper limit of the frequency working range must be higher than its lower limit. It can be specified in the predefined range. A default value is preset. This setting indicates the maximum voltage difference of the amounts of Vsyn1 and Vsyn2 for asynchronous conditions. It can be specified in the predefined range. A default value is preset. This setting indicates the maximum frequency difference up to which a connection is permissible for asynchronous systems. It can be specified in the predefined range. A default value is preset. This setting indicates the maximum frequency difference up to which a connection is permissible for synchronous systems. It can be specified in the predefined range. A default value is preset. This setting indicates the maximum voltage difference of the amounts of Vsyn1 and Vsyn2 for synchronous conditions. It can be specified in the predefined range. A default value is preset. This parameter indicates the maximum angle difference between the voltages of the subsystems, for which the connection is performed. It becomes effective if the frequency difference of the subsystems Df FdiffSyn is valid. The angle can be set in the predefined range. A default value is preset. This parameter indicates the switch delay time for synchronous systems. This is the minimum period, the 8GLII6\Q (maximum permissible voltage difference), I 6<1 &+521 (maximum permissible frequency difference) and GLII (angle difference) which must remain in the parameterized range until the control command is initiated. If a value leaves the parameterized range, the time counter is reset. It can be specified in the predefined range. A default value is preset.

6\QF88!

6\QF88

76<1 '85$7,21

IPLQ

IPD[

8GLII$V\Q

IGLII

I 6<1&+521

8GLII6\Q

GLII

7 6<1&+521

6MD66 Manual C53000-G1876-C102-3

61

2 Functions

Note To obtain a stable connection range, the measured values have a hysteresis: 10 % or 1 V for voltages (the respectively lower value is valid). 20 mHz for frequencies. 1 for angles.

2.7.1.3
Addr. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Settings
Parameter 7&% FORVH 76<1 '85$7,21 IPLQ IPD[ 6\QF6' %DODQFLQJ 88 7U 88 6HF7UDQV1RP9DO 6HF7UDQV1RP9DO 8PLQ 8PD[ 8GHDG 6\QF8!8 6\QF88! 6\QF88 8GLII6\Q IGLII GLII 8GLII$V\Q Setting Options 0.01 .. 0.60 sec 1.00 .. 600.00 sec 95 .. 105 % 95 .. 105 % synchronizable switching device 0.80 .. 1.20 0 .. 360 0 .. 170 V; < > 0 0 .. 170 V; < > 0 20 .. 125 V 20 .. 140 V 1 .. 60 V YES NO YES NO YES NO 0.5 .. 40.0 V 0.03 .. 2.00 Hz 2 .. 60 0.5 .. 40.0 V 1.00 0 100 V 100 V 90 V 110 V 5V NO NO NO 2.0 V 0.10 Hz 10 2.0 V Balancing Factor U1/U2 Angle adjustment U1-U2 (Trafo) Secondary Transformer Nominal Value 1 Secondary Transformer Nominal Value 2 Minimum Voltage for Synchronization Maximum Voltage for Synchronization Voltage Treshold for Dead Line/ Dead Bus Synchronize to U1> and U2< Synchronize to U1< and U2> Synchronize to U1< and U2< Maximum voltage difference, synchronous Maximum frequency difference, syn. Maximum angle difference, syn. Maximum voltage differnece, asynchronous Default Setting 0.06 sec 30.00 sec 95 % 105 % Description Closing (operating) time of CB Maximum duration of synchronism-check Minimum frequency Maximum frequency

62

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Addr. 0 0

Parameter I 6<1&+521 7 6<1&+521

Setting Options 10 .. 40 mHz 0.00 .. 60.00 sec

Default Setting 10 mHz 0.05 sec

Description Frequency diff. treshold Sync/ Async. Switch Delay for synchronous systems

2.7.1.4

Information

No. Sy1 ChU1 Sy1 ChU2 >Sy1 eff. >Sy1 block >Sy1 dirCO >Sy1 Meas

Message

Type of Information MK MK EM EM EM EM EM EM EM AM AM AM AM AM AM AM AM AM AM AM AM AM AM AM AM AM AM AM MW MW MW MW MW MW MW

Description Sync1, Voltage input U1 Sync1, Voltage input U2 >Sync1 effective >Sync1 block >Sync1 direct Command Output >Sync1 Measuement only >Sync1 switch to U1> and U2< >Sync1 switch to U1< and U2> >Sync1 switch to U1< and U2< Sync. Release of CLOSE Command Synchronization Error Sync. blocked Sync. Monitoring Time exceeded Sync. Synchron Sync. Condition U1> U2< fulfilled Sync. Condition U1< U2> fulfilled Sync. Condition U1< U2< fulfilled Sync. Voltage difference exceeded Sync. frequency difference exceeded Sync.angle difference exceeded Sync. frequency f1 too high Sync. frequency f1 too low Sync. frequency f2 too high Sync. frequency f2 too low Sync. voltage U1 too high Sync. voltage U1 too low Sync. voltage U2 too high Sync. voltage U2 too low Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2

>Sy1U1>U2< >Sy1U1<U2> >Sy1U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< Sync. U1 Sync. U2 Sync. Vdiff Sync. Sync. f1 Sync. f2 Sync. fdiff

6MD66 Manual C53000-G1876-C102-3

63

2 Functions

2.7.2
2.7.2.1

SYNC function group 6


Description The SYNC function groups 6 to 8 offer other variations for connection of the voltage transformer. Connection examples can be found in the Appendix. SYNC function groups 6 to 8 do not differ from SYNC function groups 1 to 5 in terms of function, operation and configuration options. They are described in detail in Chapter 2.7.1. With SYNC function groups 6 to 8, two channels with phase-to-earth voltage (V11 and V12) are to be allocated for voltage V1. The phase-to-phase voltage V1 is to be formed from these voltages. The relevant phase-to-phase voltage is to be connected to voltage input V2.

Measuring channels

The input measuring channels describe a measured-value channel and can be configured directly on an analogue input with DIGSI.
Table 2-13 Code 6\ &K8 6\ &K8 6\ &K8 Input measuring channels, function blocks FB_SYNC 6 to 8 Explanation Channel of phase-to-earth voltage V11LE. This value is required for calculating a phase-phase voltage V1. Channel of phase-to-earth voltage V12LE. This value is required for calculating a phase-phase voltage V1. Channel of voltage V2.

2.7.3
2.7.3.1

Parameterizing SYNC function


Description Synchronisation is a function which must be set as available in the functional scope.

Inserting the synchronisation function

First select the required synchronisation functions as available in the Functional scope dialog box in DIGSI. For this purpose, open the device and click Functional scope in the function selection and confirm with OK.

64

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Figure 2-20

Specifying functional scope

Configuring synchronisation

Click Synchronisation in the tree view of DIGSI. The available synchronisation function groups are displayed in the list box under Function selection. Double-click the function group (e.g. SYNC function group 1) which you would like to configure. The dialog box for configuration is opened. It contains the tabs System data, General, Asyn. condition and Syn. Condition. Select the tab System data and make your settings.

Figure 2-21

Synchronization, System data tab

Make additional settings in the tabs General, Asyn. condition and Syn. Condition.

6MD66 Manual C53000-G1876-C102-3

65

2 Functions

Figure 2-22

Synchronization, General tab

Figure 2-23

Synchronization, Asyn. tab Condition

66

6MD66 Manual C53000-G1876-C102-3

2.7 Circuit breaker synchronisation

Figure 2-24

Synchronization, Syn. Conditions tab

Exit configuration of synchronisation with OK.

6MD66 Manual C53000-G1876-C102-3

67

2 Functions

2.8
2.8.1

Inter relay communication


Description
Inter relay communication, abbreviated IRC, allows the exchange of information between SIPROTEC 4 devices without a SICAM SAS control centre. For this purpose, the devices are connected to each other via an RS485 connection or via an external converter and fibre optic cable. Process information such as indications and measured values (RMS values) are transferred via this bus. Configuration of the Inter relay communication is performed with the DIGSI operating program. Communication works cyclically on the basis of an image protocol. The cycle time is constant in fault-free operation and dependent on the baud rate, the amount of process information and the number of connected devices. All SIPROTEC 4 devices which communication which each other are called users of an IRC combination. An IRC combination can handle a maximum of sixteen users.

Usercases

An Inter relay communication setup always makes sense if the same process information needs to made available to several SIPROTEC 4 devices. Instead of sending the same process information to several SIPROTEC 4 devices per single line wiring, it is only sent to a single SIPROTEC 4 device. The other SIPROTEC 4 devices receive the required process information via the serial IRC bus. An application for the Inter relay communication could be the interlocking conditions within a bay with a 11/2 circuit breaker method operated with three bay controllers. The OLM (Optical Link Module) interface modules required for an optical connection of the IRC user can be found in the accessory list in the Appendix.

Requirements

Certain requirements must be fulfilled to build an IRC combination The participating SIPROTEC 4 devices must be suited toward Inter relay communication. A corresponding communications module must be installed in the SIPROTEC 4 devices. The DIGSI operating program must be installed on the PC. The project must contain at least two SIPROTEC 4 devices which fulfill the requirements for Inter relay communication and an IRC combination (can be created via configuration).

Function principle

The IRC is based on the Master-Slave principle. One SIPROTEC 4 device of the IRC combination operates as the master. All other users are slaves. The master sends queries to all the slaves one after the other. On receiving this query, each slave transmits its particular process information meant for the IRC combination. The master collects all the process information it receives and collates it, together with its own information, into a single message. It then sends this message to all the slaves. From this message, each slave then extracts the process information which is relevant to the particular slave.

68

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Note Due to the cyclical method of operation of the IRC, only indications whose value changes are pending longer than 20 ms are transferred.

Electrical RS485 connection

Figure 2-25

Connection of bay controllers to inter relay communication (electrical)

The connection between the devices occurs electrically via an RS485 interface. The electrical connections are terminated with resistors at the ends (first and last device), which are set via jumpers in the 6MD66 device. The jumper settings can be found in Chapter Installation and Commissioning. One of the following operating modes can be selected in DIGSI using the serial interface settings.
Table 2-14 Operating mode of the IRC interface (electrical) Baud rate 125 KBaud, 250 KBaud, 1 MBaud, 1.25 MBaud 115 KBaud or 250 KBaud

Transmission mode HDLC UART

6MD66 Manual C53000-G1876-C102-3

69

2 Functions

Optical connection OLM

Figure 2-26

Connection of bay controllers to inter relay communication (optical)

An OLM is used as an interface converter (optical/electrical). The connection from the 6MD66 device to the OLM occurs electrically via an RS485 interface. The electrical connections are to be terminated with resistors. These terminating resistors are set with jumpers in the 6MD66 device and with DIL switches (S1, switches 1 and 2) in the OLM. The jumper settings can be found in Chapter Installation and Commissioning. The connection of the interface converters is optical (in series) and its operation is asynchronous. A theoretical baud rate of 9600 Baud to 115200 Baud is set with a DIL switch (S2, switch 5 off, 6 on, 7 on, 8 off). One of the following operating modes can be selected in DIGSI using the serial interface settings.
Table 2-15 Operating mode of the IRC interface (optical) Baud rate 125 KBaud 500 KBaud

Transmission mode HDLC UART

70

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Application

Figure 2-27

11/2-Circuit breaker method, disconnector and earth electrode not shown

Configuring inter relay communication The procedure for configuring the devices connected with each other in the Inter relay communication is explained in the following sections. Insert SIPROTEC 4 device Objects of type SIPROTEC device are inserted into the project structure from the device catalog via drag and drop. Right-click an object of type Folder. In the context menu, click Insert new object SIPROTEC device. The window Device catalog opens. Alternatively click Device catalog in the context menu. When selecting a device type, note that this must be suitable for a Inter relay communication. After placing the object within the project, the dialog box Properties - SIPROTEC device opens, as usual.

6MD66 Manual C53000-G1876-C102-3

71

2 Functions

Figure 2-28

Properties SIPROTEC device dialog box

Importing a SIPROTEC 4 device

In addition to inserting a new device, a device which is already available in another project can be imported into the project structure. It is to be noted here that a device can then only participate in an IRC combination if it is imported as a SIPROTEC device. A SIPROTEC variant cannot participate in an IRC combination, as the VD address is not unique. Right-click an object of type Folder. In the context menu, click Import device.... The Import device dialog box opens. Select the alternative As SIPROTEC device and confirm with OK.

Specifying the device model

Select an order number (MLFB number) to specify the device model in DIGSI. It is important to select the entry Inter Relay Communication from the drop-down list box Function interface. Click OK when you have defined the entire device model. Proceed in a similar manner with the rest of the objects of type SIPROTEC device which are to be users of the IRC combination. An object of type IRC combination is inserted with the DIGSI Manager. The users of an IRC combination and the required transmission parameters are specified here.

Inserting an IRC combination

The users of an IRC combination and the required transmission parameters are defined in an object of type IRC combination. This object also contains information about the update status of an IRC combination. You can only insert an object of type IRC combination within an object of type Folder. Right-click an object of type Folder. In the context menu, click Insert new object IRC combination. Within a project you can insert any number of objects of type IRC combination. The placement of the object within the project does not have any effect on its functionality. Each SIPROTEC 4 device suitable for an IRC combination is available within a project as a participant to each object of type IRC combination.

72

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

You must only remember that each SIPROTEC 4 device can only function as a user of a single IRC combination at any one time. However, you should select the placement taking clarity of layout into account. Several IRC combinations can also be managed within a single project. Each IRC combination is represented here by its own object of type IRC combination. IRC failure indication For devices selected via the MLFB number, an additional IRC_Fault failure indication is generated in the Device group of the device matrix. This failure indication can be allocated individually. This failure indication is set to ON by the IRC failure monitor at the beginning of the failure and to OFF during establishment connection after the transmission of the current state of process information. When a failure occurs in a device (master or slave), the IRC failure indications for all other devices arrive at the other devices simultaneously. The master repeats the slave query in case of faulty messages. The number of repetitions is configurable. A large number of repetitions (with message errors or a poor connection) extends the cycle time of the bus. Only one repetition should be set for fibre-optic connections. After a connection failure, the master attempts to establish a new connection after a configurable number of bus cycles (pauses). As each (failed) connection establishment extends the bus cycle time, the number of pauses should be as large as possible. Otherwise, a large number of pauses extends the time until a failed device operates on the bus again. A good output value here is 10 bus cycles. Selecting a combination user An IRC combination can comprise up to sixteen users. These users are stored as a property of the object type IRC combination. To select the user of an IRC combination, open the Properties dialog box of the respective object. Right-click the object of type IRC combination. Click Object properties in the context menu. The dialog box Properties - IRC combination opens. Select the User tab.

6MD66 Manual C53000-G1876-C102-3

73

2 Functions

Figure 2-29

Properties dialog box IRC combination, User tab

Available devices

The names of all SIPROTEC 4 devices which can operate as users for the processed IRC combination are shown in the box Available devices. These are the devices from the current project which fulfill the requirements for Inter relay communication, and which are not already users of another IRC combination. In addition to the name of a SIPROTEC 4 device, its position within the project is also displayed. To add a SIPROTEC 4 device to the IRC combination, select its name in the box Available devices. Then click on Add. To remove a SIPROTEC 4 device from the IRC combination, select its name in the Combination users box. Then click Remove. Several devices can be added to, or removed from, the IRC combination simultaneously through multiple selection. Alternatively, add or remove a SIPROTEC 4 device with a double-click on its name in the appropriate box. An IRC combination can comprise a maximum of sixteen users. When this number has been reached, a fault indication is displayed as soon as you want to add another SIPROTEC 4 device.

Selecting a user

Specifying a master

Each IRC combination requires a SIPROTEC 4 device as a master. The first SIPROTEC 4 device you select is automatically defined as the master. The master device is labelled in the box Combination users with a blue circle to the left of the name of the device. If another SIPROTEC 4 device is to be used as a master, select its name in the box Combination users. Then click Master. If the device labelled as the master is removed from the combination, the first SIPROTEC 4 device in the list of users is automatically defined as the new master. Basically, any device in the IRC combination can function as a master. The master function requires additional processor performance. You should therefore select a device which is subjected to the least usage by the actual program run.

74

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Accepting settings

To apply your settings, click OK. The Properties - IRC combination dialog box is closed.

Allocating information of the individual devices involved The purpose of the IRC combination is to distribute process information between SIPROTEC 4 devices. You must therefore make the following decisions for each SIPROTEC 4 device participating in an IRC combination: Which process information from the SIPROTEC 4 device should be made available to the other devices in the IRC combination? Which process information from the SIPROTEC 4 device should be assignable to process information received from the IRC combination? You make this selection for each SIPROTEC 4 device individually in the DIGSI allocation matrix. Open the SIPROTEC device with the DIGSI device processing function. Double-click the object Allocate to display the device matrix. IRC columns One column with the name O is provided in the device matrix for the IRC combination as source and IRC combination as destination. These columns are fundamentally only visible when the functionality of the IRC has been defined in the device model. These columns are shielded as soon as you select the information filter Only commands. This is explained by the fact that commands cannot be swapped within an IRC combination. The following information types can be allocated within an IRC combination: Single point indication (only SI, not SI_F) Double point indication (only OI, not OI_F) Internal single indication (only IS, not IS_F), can only be allocated as destination, use as SI source Internal double point indication Bit pattern indication Transformer tap indication Limit value User-defined limit value Measured value User-defined measured value External counter Routing information to the IRC source Information that is routed to IRC as source can be assigned to information of other users of the IRC combination during the course of the run process. Information received from an IRC combination is represented within the SIPROTEC 4 device by information specific to this device. The assignment between received information and device-specific information takes place with the combination matrix. Information that is routed to IRC as destination can be forwarded to other users of the IRC combination. This forwarding procedure is also defined using the combination matrix.

Allocable Information types

Routing information to the IRC destination

6MD66 Manual C53000-G1876-C102-3

75

2 Functions

Routing rules

Several rules must be observed when routing information. A consistency check monitors whether these rules are complied with. Information initiated by a device or a function (e.g. device ready) cannot be routed as a source. Information can only be routed to the IRC as source if it has not already been routed to another source. Similarly, any item of information routed to the IRC as source may not be routed to any other sources. An item of information cannot be simultaneously routed to the IRC as source and to the IRC as target. Overall, 32 items of information can be routed to the IRC as target. Source and destination must be the same data type (e.g. correct: type SI to SI or ExtSi; incorrect: type SI to OI).

Routing information between the devices involved You have specified information for each individual SIPROTEC 4 device within an IRC combination with the device matrix. You must decide, what information is to be transmitted from which source device to which destination device, and what information is to be created in the destination device by the information it has received. Note The combination matrix is structured similarly to the device matrix. The mechanisms, e.g. to hide and show lines and column, are identical to those of the device matrix. An extensive description of combination matrix operation can be found in the SIPROTEC System Description /1/.

Combination matrix

Several requirements must be fulfilled in order to open the combination matrix: The combination matrix may not already have been opened for another IRC combination. The IRC combination for which the combination matrix is to be opened must comprise at least two SIPROTEC 4 devices. No SIPROTEC 4 device which functions as a user in the combination may be opened for editing. Right-click an object of type IRC combination. Click Open object in the context menu. Alternatively, you can double-click the object. The combination matrix opens.

76

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Figure 2-30

IRC combination matrix

Structure of the combination matrix

After opening the combination matrix you will see that it is divided up both horizontally and vertically. Several columns or rows can be visually combined into blocks by clicking the button at the top or left margin of the combination matrix. Horizontally, the matrix is divided into two main data areas: Source and Destination. Information is compiled vertically in groups. Source Information serves as the source. It is described by the display text, the long text and the type. In the combination matrix, all information is displayed which you have routed to the destination IRC combination for each SIPROTEC 4 device individually in the device matrix. Destination The destination designates the SIPROTEC 4 device to which information is forwarded. A destination column is shown in the combination matrix for each user device in an IRC combination. Group A group represents the scope of information that a user of an IRC combination makes available to the other users. A group is therefore shown in the combination matrix for each SIPROTEC 4 device contained in an IRC combination. Each group bears the same name as the related SIPROTEC 4 device.

Routing information items

Information which has been routed in the device matrix to the IRC as destination is made available in the combination matrix as source information. Conversely, all information which has been routed in the device matrix to IRC as source is made available in the combination matrix as destination information. Note that the destination information is not visible until a routing action takes place.

6MD66 Manual C53000-G1876-C102-3

77

2 Functions

To route a source information to a specific SIPROTEC 4 device in the combination matrix, click the common cell of Information and Destination device. The cell is transformed into a drop-down list box. It offers the display texts of the destination information routed as the source in the destination device and which is of the same data type. Select one of these information packets. Repeat this procedure for all the remaining assignments. Routing rules Some rules must also be observed when routing information within the combination matrix. Their compliance is also monitored, however, as with the device matrix via automatic consistency checking. Only one source information packet may be assigned to a destination information packet. However, a source information packet can be routed to several destination information packets. The sort and type of source and destination information packets must be identical. You cannot, for example, route a single message to an output indication. However, there are two exceptions: incoming-outgoing indications and in-out indications can be routed between each other. This also applies to double point indications and double point indications with fault positions. Saving and terminating routings All your routings must be explicitly saved. Click File Save as in the menu bar for this. To close the combination matrix click File Exit in the menu bar. Setting communication parameters for individual devices A special communication module must be installed in each SIPROTEC 4 device provided for Inter relay communication. This module is already installed and correctly allocated if you ordered a SIPROTEC 4 device with Inter relay communication. For this reason, this section is only relevant for upgrading. The slot to which this communication module is connected in the SIPROTEC 4 device is the only setting which needs to be made in the device-specific communication parameters. Right-click the object of type SIPROTEC device for which you want to edit the parameter for the Inter relay communication. Click Object properties in the context menu. The dialog box Properties - SIPROTEC device opens. Select the Inter relay communication tab. Note This tab is only available if the following requirements are fulfilled simultaneously: The current SIPROTEC 4 device is fundamentally suitable for Inter relay communication. Inter Relay Communication has been selected as the function interface in the Communications module tab. The SIPROTEC 4 device is already a user in an IRC combination.

78

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Setting a slot Note A modification to the slot setting, in comparison to the delivery setting, should only be made if there is just cause and only with the required system knowledge! The set slot and the actual slot are not automatically checked for consistency. Please carefully check your settings yourself. In the Slot drop-down list box select the name of the slot in which the communications module is installed in the SIPROTEC 4 device.

Figure 2-31

Properties - SIPROTEC device dialog box, Inter Relay Communication tab

To apply your settings, click OK. The Properties - SIPROTEC device dialog box is closed. The parameter is not activated until the parameter set is updated. Setting communication parameters for a combination While the slot to which this communications module is connected is the only setting which needs to be made in the device-specific communication parameters, several settings need to be taken into consideration for the combination as a whole. The settings which need to be made are summarised in two groups: Interface settings These serial interface settings must be identical for all the SIPROTEC 4 devices in the IRC combination. Otherwise the devices are not able to communicate with one another. They are therefore defined centrally for the combination. Bus parameters Settings relating to the bus arbitration only affect the parameter set of the SIPROTEC 4 device which serves as the master in the IRC combination. However, as

6MD66 Manual C53000-G1876-C102-3

79

2 Functions

each participating SIPROTEC 4 device can fundamentally be defined as the master, these settings are also made during configuration of the IRC combination. Right-click the object of type IRC combination. Click Object properties in the context menu. The dialog box Properties - IRC combination opens. Select the Transmission parameters tab.

Figure 2-32

Properties dialog box - IRC combination, Transmission parameters tab

Note We recommend using the preset transmission parameters.

Specifying interface settings

The following interface settings can be set: Transmission mode Select the name of a transmission mode from this drop-down list box. At this time you can choose between UART and HDLC. HDLC ensures an approx. 15 % greater transmission density than UART using the same baud rate. The selected transmission mode must be compatible with the communications modules installed in the SIPROTEC 4 devices in the IRC combination. Baud rate Select a baud rate from this drop-down list box. Which baud rates are available for selection depends on the transmission mode you have selected. The higher the transmission rate, the shorter the cycle time or the more users can be connected to the bus with the same cycle time. The processor load of the master increases when the cycle time is small and when many slaves are connected to the bus. In exceptional cases, the parameter Minimal cycle time must be increased for this reason. When using the HDLC protocol, the baud rate is to be set according to the bus configuration: Line bus via RS485: 1 MBit (limited by RS485 and cable length)

80

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Star-shaped via optical star couplers: 512 KBit (limited by mini star couplers) Double ring with OLM: 1 MBit (limited by RS485) Automatic address detection If this check box is activated, the SIPROTEC 4 device only considers a message it receives if it is addressed to it. This action relieves the load on the CPU of the SIPROTEC 4 device. This option can only be selected if UART is set as the transmission mode. Setting the bus arbitration The following parameters can be set for bus arbitration: Maximum number of message repeats If a message is corrupted during transmission, it can be sent again. In this spin box you can enter how many attempts should be made to transmit a message. A maximum of three new transmission attempts are allowed. Number of pauses before a new query is sent to a failed device If a SIPROTEC 4 device in the combination has failed, the master can exempt it from queries for a certain number of cycles. To do this, select a value between 0 and 254 in the drop-down list box. Minimum cycle time The cycle time defines the total duration of a cycle, during which all slave devices are queried by the master device. Select a value between 10 and 10,000 ms. from the spin box. As the length of the cycle time depends on the capacity of the master, the cycle time actually achieved may be higher than the value set in the parameters. To ensure that the master uses the shortest possible cycle time, select the check box Minimum cycle time, continuous. Checking and updating parameter sets The parameter sets of individual or all combination users must be updated either when configuring an IRC combination for the first time, or if the settings of single combination parameters have been altered, according to the modifications which have been made. Right-click the object of type IRC combination. Click Object properties in the context menu. The dialog box Properties - IRC combination opens. Select the Updating tab. The tab Updating gives an overview of the update status of the parameter sets of the individual combination users.

6MD66 Manual C53000-G1876-C102-3

81

2 Functions

Figure 2-33

Properties dialog box IRC combination, Updating tab

Checking the update status

Every device in DIGSI which has a current parameter set is designated in column P with a check mark. If this parameter set has already been transmitted to the real SIPROTEC 4 device, you can manually make a note of this by entering a check mark in column G. To do this, click in the corresponding check box. This selection can only be set if the parameter set in DIGSI 4 is up to date. It is automatically deleted if changes have been made which affect the parameter set of the SIPROTEC 4 device concerned. DIGSI itself detects which parameter sets are no longer up to date. As soon as the update command has been issued, these parameter sets are updated one after the other. However, it is important for you to know after which modification which SIPROTEC 4 device needs to be reinitialised. Here is a brief overview: Changing the slot for the communications module: parameter set of the user concerned. Modification of a serial interface setting on the tab Transmission parameters: parameter sets of all users. Modification of a bus parameter in the tab Transmission parameters: parameter set of the master. Routing changes in the combination matrix: parameter sets of both users concerned. Routing changes in the device matrix of a SIPROTEC 4 device to IRC as the destination: parameter set of the user concerned. Deleting or adding a user: parameter sets of all users.

Updating parameter sets

To update all outdated parameter sets, click Update all parameter sets. Messages detailing the progress of updating are shown in the Report window. The parameter sets are updated in DIGSI.

82

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Figure 2-34

Report, IRC update tab

If you have made changes in the combination matrix, you can update these changes immediately in the affected parameter sets. Click File Save and Generate Parameter Records on the menu bar for this. Printing combination information You can print the following information relating to an IRC: Transmission parameter settings of the IRC combination. The names of the SIPROTEC 4 devices in the IRC combination, including the classification letters of the selected slots. Update information for each individual user in the IRC combination. Right-click an object of type IRC combination. Click Delete Object contents in the context menu. The Print Combination Information dialog box opens.

Figure 2-35

Print combination information dialog box

Specifying the scope of printing

You specify the scope of the information to be printed by selecting individual checkboxes. Subsequently click OK. The Print Manager window opens. This window allows you to call up a page preview for the information you want to print. You can influence the presentation in the Print Manager window.

6MD66 Manual C53000-G1876-C102-3

83

2 Functions

Figure 2-36

IRC combination, print manager

Scrolling

Click Next to show the next print page. This button is inactive if the last available print page is already being displayed. Then click Previous to show the previous print page. This button is inactive if the first print page is already being displayed. Click One page/two pages to alternate between a single page view and a two page view. Click Zoom to zoom the display of the print page in defined stages. This button is inactive as soon as the largest possible display size has been reached. Alternatively, click with the left mouse button for as long as the mouse cursor is in the display area. When you do this the display of the print page is also zoomed in defined stages. Click Zoom out to zoom out the display of the print page in defined stages. This button is inactive as soon as the smallest possible display size has been reached. Note An enlarged or shrunken view has no influence on the print results.

Changing the display mode Changing the scale of the display

Printing information Time synchronization

Click Print to print the displayed information.

In addition to transmitting the process information, the IRC can synchronise the time in the connected devices. The master, which synchronises its time via a radio clock for example, passes on the time each minute to the connected slaves. Time synchronization via IRC must be set in the slaves for this. Open the SIPROTEC device with the DIGSI device processing function. Double-click in the data window on Time synchronization. The Time Synchronisation & Time Format dialog box is displayed.

84

6MD66 Manual C53000-G1876-C102-3

2.8 Inter relay communication

Select the entry Inter relay communication from the Time synchronization source list box and confirm the entry with OK.

Figure 2-37

Time synchronization & time format dialog box

6MD66 Manual C53000-G1876-C102-3

85

2 Functions

86

6MD66 Manual C53000-G1876-C102-3

Installation and Commissioning

This section is primarily for personnel who are experienced in installing, testing, and commissioning protective and control systems. They must be familiar with applicable safety rules, safety regulations, and the operation of a power system. Hardware modifications that might be needed in certain cases are explained. Some of the tests require the protected line or equipment to carry load.

3.1 3.2 3.3 3.4

Installation and Connections Checking Connections Commissioning Final Preparation of the Device

88 107 112 119

6MD66 Manual C53000-G1876-C102-3

87

3 Installation and Commissioning

3.1

Installation and Connections

WARNING!
Warning of improper transport, storage, installation, and application of the device. Nonobservance can result in death, personal injury or substantial property damage. Trouble free and safe use of this device depends on proper transport, storage, installation, and application of the device according to the warnings in this instruction manual. Of particular importance are the general installation and safety regulations for work in a high-voltage environment (for example, ANSI, IEC, EN, DIN, or other national and international regulations.) These regulations must be observed.

3.1.1

Configuration Information
For installation and connection, the following conditions and limitations apply: The rated device data is checked as recommended in the SIPROTEC System Description /1/. The compliance with these data is verified with the power system data.

Requirements

Connection variants Currents/Voltages

Connection examples for the current and voltage transformer circuits are given in the Appendix. As the voltage inputs of the 6MD66 device have an operating range from 0 to 170 V, this means that phase-phase voltages can be assessed up to 3 170 V = 294 V. The configuration of the binary inputs and outputs, i.e. the individual adaptation to the system conditions, is described in /1/. The connections to the system are dependent on this actual configuration.

Binary inputs and outputs

3.1.2
3.1.2.1 General

Hardware Modifications
General Hardware modifications concerning, for instance, rated currents, the control voltage for binary inputs or termination of serial interfaces might be necessary. Follow the procedure described in this subsection, whenever hardware modifications are done. The various input voltage ranges (60/110 V DC and 220 to 250 V DC) of the auxiliary voltage can be changed to one another by changing the plug-in jumpers. When the

Auxiliary voltage

88

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

relay is delivered, these jumpers are set according to the name-plate sticker. Generally, they need not be altered (see also ordering data in the Appendix). Life contact The life contact of the device is a changeover contact, from which either the opener or closer can be applied to the device connections F3 and F4 via a jumper (X40). The assignment of the plug-in jumper to the contact type and the spatial arrangement of the jumper are described in the following. The input transformers of the devices are set to a rated current of 1 A or 5 A with jumpers. The positioning of the plug-in jumpers has been executed in the factory according to the indications on the rating plate. All jumpers must be set for one rated current, i.e. respectively one jumper (X61 to X63) for each input transformer and additionally the common jumper X60. Should you perform a change here, you must not forget to communicate this change to the device also via the parameter Transformer current I, secondary in the measuring transducer packets. Control voltage for binary inputs In the delivery status, the binary inputs are set in a way ensuring that a direct current equalling the supply voltage is set as control variable. If the rated values differ from the power system control voltage, it may be necessary to change the switching threshold of the binary inputs. To change the switching threshold of a binary input, a jumper must be reallocated in each case. Note If binary inputs are used for trip circuit monitoring, note that two binary inputs (or a binary input and a replacement resistor) are connected in series. The switching threshold must lie clearly below one half of the rated control voltage.

Rated currents

Replacing interfaces Terminating serial interfaces

The serial interfaces are replacable. The interfaces which can be replaced, and how this is done, is described in the Interface modules section. If the device is equipped with a serial RS485 interface or PROFIBUS, they must be terminated with resistors at the last device on the bus to ensure reliable data transmission. For this purpose termination resistors are provided on the PCB of the CPU processor module and on the PROFIBUS interface module which can be connected via jumpers. Both jumpers must be always plugged in identically. The termination resistors are disabled on unit delivery.

6MD66 Manual C53000-G1876-C102-3

89

3 Installation and Commissioning

3.1.2.2

Disassembly

Disassembly of the Device Note It is assumed for the following steps that the device is not operative.

Work on the Printed Circuit Boards

Caution!
Caution when changing jumper settings that affect nominal values of the device As a consequence, the ordering number (MLFB) and the ratings that are stated on the nameplate do no longer match the actual device properties. If such changes are necessary, the changes should be clearly and fully noted on the device. Self adhesive stickers are available that can be used as replacement nameplates. To perform work on the printed circuit boards, such as checking or moving switching elements or exchanging modules, proceed as follows: Prepare area of work. Provide a grounded mat for protecting components subject to damage from electrostatic discharges (ESD). The following equipment is needed: screwdriver with a 5 to 6 mm wide tip, 1 Philips screwdriver, 5 mm socket or nut driver. On the rear panel, remove the studs of the subminiature socket at slot "A". If the device has additional system interfaces on slots "B" to "D" in addition to the service interface at slot "A", each of the diagonal screws must be removed. Remove the four or six caps on the front cover and loosen the screws that become accessible. Carefully take off the front cover. With device versions with a detached operator panel it is possible to remove the front cover of the device right after having unscrewed all screws.

90

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

Work on the plug connectors

Caution!
Mind electrostatic discharges Nonobservance can result in minor personal injury or property damage. When handling with plug connectors, electrostatic discharges may emerge by previously touching an earthed metal surface must be avoided. Do not plug or withdraw interface connections under power! When performing work on plug connectors, proceed as follows: Release the connector of the ribbon cable between CPU processor module (1) and front cover at the front cover itself. Press the top latch of the plug connector up and the bottom latch down so that the plug connector of the ribbon cable is pressed out. These activities are not necessary if the device has a detached operator panel. However, on the CPU processor module (1) the 7-pin plug connector X16 behind the subminiture socket and the plug connector of the ribbon cable (connected to the 68-pin plug connector on the rear side) must be removed. Disconnect the plug connectors of the ribbon cable between the CPU processor module (1) and the input/output modules I/O-4 (2) and I/O-5 (3). Remove the modules and place them on a surface suitable for electrostatically sensitive modules (ESD). Check jumpers and change/remove if necessary.

6MD66 Manual C53000-G1876-C102-3

91

3 Installation and Commissioning

Module arrangement of 6MD663

Figure 3-1

Front view of a 6MD663 device after removing the front cover (simplified and reduced in scale)

Module arrangement 6MD664

Figure 3-2

Front view of a 6MD664 device after removing the front cover (simplified and reduced in scale)

92

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

3.1.2.3

Switching elements on the PCBs


Check the set rated voltage of the integrated power supply, the quiescent state of the life contact, the selected control voltages of binary inputs BI1 to BI5 and the integrated RS232/RS485 interface using the layout of the PCB of the CPU processor module and the tables below.

CPU processor module

Figure 3-3

Processor module CPU with representation of the jumpers required for checking the settings

Table 3-1

Jumper setting of the rated voltage of the integrated power supply on the CPU processor module Rated voltage 24 to 48 V DC 60 V DC 12 12 and 34 12 Open 110 V DC 12 12 and 34 12 Open 220 to 250 V DC 23 23 23 12 Not used Not used Not used Not used

Jumper X51 X52 X53 X54

6MD66 Manual C53000-G1876-C102-3

93

3 Installation and Commissioning

Table 3-2

Jumper position of the quiescent state of the Life contact on the CPU processor module Open in the quiescent state 12 Closed in the quiescent state 23 Presetting 23

Jumper X40

Table 3-3

Jumper setting of the control voltages of the binary inputs BI1 to BI5 on the CPU processor module Jumper X21 X22 X23 X24 X25 Threshold 17 V1) 12 12 12 12 12 Threshold 73 V2) 23 23 23 23 23 Threshold 154 V3) 34 34 34 34 34

Binary input BI1 BI2 BI3 BI4 BI5


1) 2) 3)

Factory settings for devices with rated supply voltages of 24 V DC to 60 V DC Factory settings for devices with rated supply voltage DC 110 V Factory settings for devices with rated supply voltages of 220 V DC to 250 V DC

Table 3-4

Jumper settings of the integrated RS232/RS485 interface on the CPU processor module RS232 12 RS485 23

Jumper X105 to X110

Note Jumpers X105 to X110 must be set to the same position. When the device is delivered from the factory, the jumper setting corresponds to the configuration ordered and need not be changed. The R485 interface can be converted into an RS232 interface by modifying the setting of the appropriate jumpers. For an order with MLFB position 12 the same as 0, the interface is set to RS232.
Table 3-5 Jumper X111 Jumper setting for CTS (Flow control) on the CPU processor module /CTS from interface RS232 12 /CTS triggered by /RTS 23

The jumper is always inserted at position 2-3 at the factory. The jumper must be set to 23 for the RS232 connection of DIGSI. Jumper setting 23 is also required for the connection, via star coupler or fibre optic cable; we recommend the connection cable Order No. 7XV51004 for this purpose.

94

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

Jumper setting 12 is required for a modem connection; we recommend a standard connection cable (9-pin/25-pin) for this.
Table 3-6 Jumper setting of the termination resistors of the RS232/RS485 interface on the CPU processor module Termination resistor Connected X103 X104 23 23 Termination resistor Disconnected 12 12 12 12 Factory setting

Jumper

Provided that they are not terminated externally via resistors, each last device must be configured via the jumpers X103 and X104. Note Both jumpers must always be plugged in the same way! Jumper X90 serves for internal test purposes. The factory setting 12 must not be changed.

6MD66 Manual C53000-G1876-C102-3

95

3 Installation and Commissioning

I/O-4 module

The selected control voltages of the binary inputs BE6 to BE65 are checked according to the table below. The assignment of the binary inputs to the installation location of the module can be found in Section Module arrangement.

Figure 3-4

I/O-4 input/output module with representation of the jumpers required for checking the settings

96

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

Table 3-7

Jumper setting for the control voltages of the binary inputs BI6 through BI65 on the I/O-4 input/output module Binary input Jumper BI51 BI52 BI53 BI54 BI55 BI56 BI57 BI58 BI59 BI60 BI61 BI62 BI63 BI64 BI65 X21 X22 X23 X24 X25 X216 X27 X28 X29 X30 X31 X32 X33 X34 X35 Threshold 17 V 1) 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 Threshold 73 V 2) 23 23 23 23 23 23 23 23 23 23 23 23 23 23 23 Threshold 154 V 3) 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34

BI6 BI7 BI8 BI9 BI10 BI1 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20
1) 2) 3)

BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28 BI29 BI30 BI31 BI32 BI33 BI34 BI35

BI36 BI37 BI38 BI39 BI40 BI41 BI42 BI43 BI44 BI45 BI46 BI47 BI48 BI49 BI50

Factory settings for devices with rated supply voltages of 24 V DC to 60 V DC Factory settings for devices with supply voltages DC 110 V Factory settings for devices with rated supply voltages of 110 V DC to 250 V DC

The jumpers X71, X72 and X73 on the I/O-4 input/output modules serve for setting the bus address. Their position may not be changed. The table shows the factory setting of the jumpers.

Table 3-8 Jumper

Module address jumper settings of input/output modules I/O-4 Insertion slot Slot 19 (1) Slot 33 (2) 23(L) 12(H) 23(L) Slot 5 (3) 12(H) 12(H) 23(L) Slot 19 (4) 23(L) 23(L) 12(H) 12(H) 23(L) 23(L)

X71 X72 X73

6MD66 Manual C53000-G1876-C102-3

97

3 Installation and Commissioning

I/O-5 module

Check the set rated currents of the current input transformers here. All jumpers must be set for one rated current, i.e. respectively one jumper (X61 to X63) for each input transformer and additionally the common jumper X60.

Figure 3-5

I/O-5 input/output module with representation of the jumpers required for checking the settings

Jumpers X71, X72 and X73 on the I/O5 input/output module serve for setting the bus address. Their position may not be changed. The table shows the factory setting of the jumpers. The insertion slot of the module is described in Section Module arrangement.
Table 3-9 6MD663 Jumper X71 Position 23 Module address jumper settings of input/output modules I/O-5

98

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

X72 X73 6MD664 Jumper X71 X72 X73

23 12 Position 12 23 12

3.1.2.4

Interface Modules

Replacing interface modules

Figure 3-6

Example, CPU processor module with interface modules

6MD66 Manual C53000-G1876-C102-3

99

3 Installation and Commissioning

Note Please observe the following: Only interface modules with which the unit can be ordered in accordance with the factory order code (see Appendix) can be used.

Table 3-10

Exchangeable interface modules Interface Insertion slot Replacement module RS485 FO 820 nm PROFIBUS FMS RS485

System interface

PROFIBUS FMS Single ring PROFIBUS FMS Double ring PROFIBUS DP RS485 PROFIBUS DP Double ring

DIGSI Service interface

FO 820 nm

The order numbers of the replacement modules are listed in the Appendix. Serial interfaces with bus capability For bus-capable interfaces a termination is necessary at the bus for each last device, i.e. termination resistors must be connected. In the case of the 6MD66, these are variants with RS485 or PROFIBUS interfaces. The termination resistors are located on the corresponding PROFIBUS interface module, which is located on the CPU processor module or directly on the PCB of the CPU processor module. On delivery the jumpers are set so that the termination resistors are disconnected. Both jumpers of a module must always be plugged in the same way.

Figure 3-7

Position of the jumpers for configuration of termination resistors of the PROFIBUS FMS and PROFIBUS DP interface

Terminating resistors for the PROFIBUS interface can also be implemented externally (e.g. on the connection module). In this case, the termination resistors provided on the PROFIBUS interface module or directly on the CPU processor module card must be disconnected.

100

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

Figure 3-8

Termination of the RS485 interface (external)

Note The RS485 interface used with this device for the inter relay communication cannot be provided with termination resistors externally as shown in the figure above, as the +5 V voltage is not routed out with this device. The RS485 interface on the processor module can be terminated directly on the processor module (see the CPU module for the jumper setting). The external termination of the RS485 bus is only possible between the lines A/A and B/B, each with 120 at the end of the bus. The resulting resistance may not be smaller than 60 .

3.1.2.5

Reassembly To reassemble the device, proceed as follows: Insert the modules carefully in the housing. For the model of the device designed for surface mounting, use the metal lever to insert the CPU processor module. The installation is easier with the lever. First, plug the connector of the ribbon cable onto the input/output module I/O and then onto the CPU processor module. Be careful that no connector pins are bent! Dont apply force! Insert the plug connector of the ribbon cable between the processor module CPU and the front cover into the socket of the front cover. This action does not apply to the device version with detached operator panel. Instead of this, the connector of the ribbon cable derived from the 68-pin connector on the device rear panel must be plugged on the connector of the processor module CPU. The 7-pin X16 connector belonging to the ribbon cable must be plugged behind the subminiature socket. The plugging position is not relevant in this context as the connection is protected against polarity reversal. Press the latches of the plug connectors together. Replace the front cover and secure to the housing with the screws. Mount the covers. Re-fasten the interfaces on the rear of the device housing. This activity is not necessary if the device is designed for surface mounting.

6MD66 Manual C53000-G1876-C102-3

101

3 Installation and Commissioning

3.1.3
3.1.3.1

Installation
Panel Flush Mounting

Remove the four covers at the corners and 2 in the centre above and below on the front cover. This exposes the 6 elongated holes in the mounting bracket. Insert the device into the panel cut-out and secure with the six screws. Dimensional drawings can be found in the Technical data section. Replace the 6 covers. Connect the ground on the rear plate of the device to the protective ground of the panel. Using at least one M4 screw. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm 2. Connections are realized via the plug terminals or screw terminals on the rear side of the device according to the circuit diagram. When using forked lugs for direct connections or screw terminal, the screws, before having inserted the lugs and wires, must be tightened in such a way that the screw heads are even with the terminal block. A ring lug must be centred in the connection chamber, in such a way that the screw thread fits in the hole of the lug. Section /1/ has pertinent information regarding wire size, lugs, bending radii, etc.

Figure 3-9

Panel flush mounting of a 6MD66

3.1.3.2

Rack Mounting and Cubicle Mounting To install the device in a frame or cubicle, two mounting brackets are required. The ordering codes are stated in Appendix, Section A.1. Loosely screw the two mounting brackets in the rack or cubicle with four screws.

102

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

Remove the four covers at the corners and 2 in the centre above and below on the front cover. This exposes the 6 elongated holes in the mounting bracket. Tighten the unit with 6 screws at the angle brackets. Reinstall the 6 covers. Tighten the mounting brackets to the rack or cubicle using eight screws. Connect the ground on the rear plate of the device to the protective ground of the panel. Using at least one M4 screw. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm 2. Connections are realised via the plug terminals or screw terminals on the rear side of the device according to the circuit diagram. When using forked lugs for direct connections or screw terminal, the screws, before having inserted the lugs and wires, must be tightened in such a way that the screw heads are even with the terminal block. A ring lug must be centred in the connection chamber so that the screw thread fits in the hole of the lug. The SIPROTEC System Description /1/ has pertinent information regarding wire size, lugs, bending radii, etc.

Figure 3-10

Assembly of a 6MD66 in the rack or cabinet

6MD66 Manual C53000-G1876-C102-3

103

3 Installation and Commissioning

3.1.3.3

Mounting with detached operator panel

Caution!
Be careful when removing or plugging the connector between device and detached operator panel Nonobservance of the following measure can result in property damage. Without the cable the device is not ready for operation! Do never pull or plug the connector between the device and the detached operator panel during operation while the device is alive! For mounting the device proceed as follows: Tighten the device by means of 10 screws. The dimensional drawing can be found in the Technical data section. Connect the ground on the rear plate of the device to the protective ground of the panel. Using at least one M4 screw. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm 2. Connections are realised via the plug terminals or screw terminals on the rear side of the device according to the circuit diagram. When using forked lugs for direct connections or screw terminal, the screws, before having inserted the lugs and wires, must be tightened in such a way that the screw heads are even with the terminal block. A ring lug must be centred in the connection chamber, in such a way that the screw thread fits in the hole of the lug. The SIPROTEC System Description /1/ has pertinent information regarding wire size, lugs, bending radii, etc. For mounting the operator panel please observe the following: Remove the 4 covers on the corners of the front plate. This exposes the 4 elongated holes in the mounting bracket. Insert the operator panel into the panel cut-out and fasten with four screws. The dimensional drawing can be found in the Technical data section. Mount the four covers. Connect the ground on the rear plate of the operator control element to the protective ground of the panel using at least one M4 screw. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm 2. Connect the operator panel to the device. Furthermore, plug the 68-pin connector of the cable belonging to the operator panel into the corresponding connection at the rear side of the device (see SIPROTEC System Description /1/). 3.1.3.4 Mounting without operator panel For mounting the device proceed as follows: Tighten the device by means of 10 screws. The dimensional drawing can be found in the Technical data section. Connect the ground on the rear plate of the device to the protective ground of the panel. Using at least one M4 screw. The cross-sectional area of the ground wire

104

6MD66 Manual C53000-G1876-C102-3

3.1 Installation and Connections

must be equal to the cross-sectional area of any other control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm 2. Connections are realised via the plug terminals or screw terminals on the rear side of the device according to the circuit diagram. When using forked lugs for direct connections or screw terminal, the screws, before having inserted the lugs and wires, must be tightened in such a way that the screw heads are even with the terminal block. A ring lug must be centred in the connection chamber so that the screw thread fits in the hole of the lug. The SIPROTEC System Description has pertinent information regarding wire size, lugs, bending radii, etc.

Caution!
Be careful with pulling or plugging the dongle cable Nonobservance of the following measures can result in minor personal injury or property damage: Do never pull or plug the dongle cable while the device is alive! Without the cable the device is not ready for operation! The connector of the dongle cable at the device must always be plugged during operation! For mounting the D-subminiature connector of the dongle cable please observe the following: Fasten the 9-pin socket of the dongle cable with the accompanying fastening parts according to the following figure (example). The dimensional diagram for the panel or cabinet cut-out can be found in the Technical data section. Plug the 68-pin connector of the cable into the corresponding connection at the rear side of the device.

6MD66 Manual C53000-G1876-C102-3

105

3 Installation and Commissioning

Figure 3-11

Installation of the subminiature socket of the dongle cable in the panel or cabinet door

Note The dongle cable is included in the scope of delivery of the operator interface.

106

6MD66 Manual C53000-G1876-C102-3

3.2 Checking Connections

3.2
3.2.1

Checking Connections
Checking the data connections of the serial interfaces
The following tables list the pin-assignments for the various serial interfaces of the device and the time synchronization interface. The position of the connections can be seen in the following figure.

Figure 3-12

9-pin subminiature sockets

3.2.2

Operator interface
When the recommended communication cable is used, correct connection between the SIPROTEC 4 device and the PC is automatically ensured. See the Appendix, Section A.1 for an ordering description of the cable.

3.2.3

Service / function interface


Check the data connection if the service is used to communicate with the device via hard wiring or a modem. The same applies for the IRC connection.

3.2.4

System interface
When a serial interface of the device is connected to a central substation control system, the data connection must be checked. A visual check of the transmit channel and the receive channel is important. With RS232 and fibre optic interfaces, each connection is dedicated to one transmission direction. The data output of one device must be connected to the data input of the other device, and vice versa. With data cables, the connections are designated according to DIN 66 020 and ISO 2110: TxD = Data output RxD = Data input RTS = request to send

6MD66 Manual C53000-G1876-C102-3

107

3 Installation and Commissioning

CTS = clear to send GND = Signal/Chassis Ground The cable shield is to be grounded at both line ends. In areas of extremely strong EMC interferences, the interference immunity factor can be improved by leading the ground wire in a separate shielded pair of strands. The following tables list the assignments of the D-subminiature connector for the various serial interfaces.
Table 3-11 Pin No. 1 2 3 4 5 6 7 8 9
1)

The assignments of the subminiature connector for the various interfaces Operator interface RxD TxD GND RS232 RS485 RxD TxD GND RTS CTS A/A (RxD/TxD-N) C/C (GND) 1) B/B (RxD/TxDP) B/B (RxD/TxDP) CNTRA (TTL) C/C (GND) +5 V (max. load < 100 mA) A/A (RxD/TxDN) PROFIBUS FMS Slave, RS485 PROFIBUS DP Slave, RS485

Pin 7 also carries the RTS signal with RS232 level when operated as RS485 interface. Pin 7 must therefore not be connected!

3.2.5

Termination
For bus-capable interfaces a termination is necessary at the bus for each last device, i.e. termination resistors must be connected for RS485 or PROFIBUS interfaces. The termination resistors are located on the RS485 and PROFIBUS interface module, which is located on the CPU processor module. If the bus is extended, make sure again that only the last device on the bus has the terminating resistors switched-in, and that all other devices on the bus do not.

3.2.6

Time Synchronization Interface


It is optionally possible to process 5 V-, 12 V- or 24 V- time synchronization signals, provided that they are carried to the inputs named in the following table.

108

6MD66 Manual C53000-G1876-C102-3

3.2 Checking Connections

Table 3-12 Pin No. 1 2 3 4 5 6 7 8 9


1)

D-subminiature connector assignment of the time synchronization interface Designation P24_TSIG P5_TSIG M_TSIG 1) Shield P12_TSIG P_TSYNC 1) SHIELD Signal Meaning Input 24 V Input 5 V Return Line 1) Shield Potential Input 12 V Input 24 V 1) Shield Potential

assigned, but not used

3.2.7

Optical Fibers

WARNING!
Warning of Laser rays! Nonobservance of the following measure can result in death, personal injury or substantial property damage. Do not look directly into the fibre-optic elements! Signals transmitted via optical fibers are unaffected by interference. The fibers guarantee electrical isolation between the connections. Transmit and receive connections are shown with the symbols for transmit and for receive. The normal setting of the character idle state for the fibre optic cable interface is "Light off". If the character idle state is to be changed, use the operating program DIGSI, as described in the SIPROTEC System Description /1/.

3.2.8

Checking system connections


Before the device is energized for the first time, the device should be in the final operating environment for at least 2 hours to equalize the temperature, to minimize humidity and avoid condensation. Connections are checked with the device at its final location. The plant must first be switched off and grounded.

6MD66 Manual C53000-G1876-C102-3

109

3 Installation and Commissioning

WARNING!
Warning of dangerous voltages Non-observance of the following measures can result in death, personal injury or substantial property damage. Therefore, only qualified people who are familiar with and adhere to the safety procedures and precautionary measures shall perform the inspection steps.

Caution!
Be careful when operating the device on a battery charger without a battery Non-observance of the following measure can lead to unusually high voltages and consequently, the destruction of the device. Do not operate the device on a battery charger without a connected battery. (Limit values can be found in the technical data). Proceed as follows in order to check the system connections: Protective switches for the power supply and the measured voltages must be opened. Check the continuity of all current and voltage transformer connections against the system and connection diagrams: Are the current transformers grounded properly? Are the polarities of the current transformers the same? Is the phase relationship of the current transformers correct? Are the voltage transformers grounded properly? Are the polarities of the voltage transformers correct? Is the phase relationship of the voltage transformers correct? Is the polarity for current input IE correct (if used)? Is the polarity for voltage input UE correct (if used for broken delta winding)? The short-circuit feature of the current circuits of the device are to be checked. This may be performed with an ohmmeter or other test equipment for checking continuity. Remove the screws of the front cover Remove the ribbon cable connected to the I/O-5 board and pull the board out until there is no contact between the board and the rear connections of the device. At the terminals of the device, check continuity for each pair of terminals that receives current from the CTs. Firmly re-insert the I/O board. Carefully connect the ribbon cable. Do not bend any connector pins! Do not use force! At the terminals of the device, again check continuity for each pair of terminals that receives current from the CTs. Attach the front panel and tighten the screws.

110

6MD66 Manual C53000-G1876-C102-3

3.2 Checking Connections

Connect an ammeter in the supply circuit of the power supply. A range of about 2.5 A to 5 A for the meter is appropriate. Switch on m.c.b. for auxiliary voltage (supply protection), check the voltage level and, if applicable, the polarity of the voltage at the device terminals or at the connection modules. The current input should correspond to the power input in neutral position of the device. The measured steady state current should be insignificant. Transient movement of the ammeter merely indicates the charging current of capacitors. Remove the voltage from the power supply by opening the protective switches. Disconnect the measuring test equipment; restore the normal power supply connections. Apply voltage to the power supply. Close the protective switches for the voltage transformers. Verify that the voltage phase rotation at the device terminals is correct. Open the protective switches for the voltage transformers and the power supply. Check the trip and close circuits to the power system circuit breakers. Verify that the control wiring to and from other devices is correct. Check the signalling connections. Close the protective switches.

6MD66 Manual C53000-G1876-C102-3

111

3 Installation and Commissioning

3.3

Commissioning WARNING!
Warning of dangerous voltages when operating an electrical device Nonobservance of the following measures can result in death, personal injury or substantial property damage. Only qualified people shall work on and around this device. They must be thoroughly familiar with all warnings and safety notices in this instruction manual as well as with the applicable safety steps, safety regulations, and precautionary measures. The device is to be grounded to the substation ground before any other connections are made. Hazardous voltages can exist in the power supply and at the connections to current transformers, voltage transformers, and test circuits. Hazardous voltages can be present in the device even after the power supply voltage has been removed (capacitors can still be charged). After removing voltage from the power supply, wait a minimum of 10 seconds before re-energizing the power supply. This wait allows the initial conditions to be firmly established before the device is re-energized. The limit values given in Technical Data (Chapter 10) must not be exceeded, neither during testing nor during commissioning. When testing the device with secondary test equipment, make sure that no other measurement quantities are connected and that the TRIP command lines and possibly the CLOSE command lines to the circuit breakers are interrupted, unless otherwise specified.

DANGER!
Hazardous voltages during interruptions in secondary circuits of current transformers Nonobservance of the following measure will result in death, severe personal injury or substantial property damage. Short-circuit the current transformer secondary circuits before current connections to the device are opened. For the commissioning switching operations have to be carried out. A prerequisite for the prescribed tests is that these switching operations can be executed without danger. They are accordingly not meant for operational checks.

112

6MD66 Manual C53000-G1876-C102-3

3.3 Commissioning

WARNING!
Warning of dangers evolving from improper primary tests Nonobservance of the following measure can result in death, personal injury or substantial property damage. Primary test may only be carried out by qualified personnel, who are familiar with the commissioning of protection systems, the operation of the plant and the safety rules and regulations (switching, earthing, etc.).

3.3.1

Test Mode and Transmission Block


If the device is connected to a central or main computer system via the SCADA interface, then the information that is transmitted can be influenced. This is only possible with some of the protocols available (see Table "Protocol-dependent functions" in the Appendix A). If Test mode is active, then a message sent by a SIPROTEC 4 device to the main system has an additional test bit. This bit allows the message to be recognized as resulting from testing and not an actual fault or power system event. Furthermore it can be determined by activating the Transmission block that no indications at all are transmitted via the system interface during test mode. The SIPROTEC System Description /1/ describes how to activate and deactivate test mode and blocked data transmission. Note that when DIGSI is being used, the program must be in the Online operating mode for the test features to be used.

Activation and Deactivation

3.3.2

Testing System Ports

Prefacing Remarks

DANGER!
Danger evolving from operating the equipment (e.g. circuit breakers, disconnectors) by means of the test function Nonobservance of the following measure will result in death, severe personal injury or substantial property damage. Equipment used to allow switching such as circuit breakers or disconnectors is to be checked only during commissioning. Do not under any circumstances check them by means of the testing mode during real operation performing transmission and reception of messages via the system interface.

6MD66 Manual C53000-G1876-C102-3

113

3 Installation and Commissioning

Note After termination of this test, the device will reboot. All annunciation buffers are erased. If required, these buffers should be extracted with DIGSI prior to the test. The interface test is carried out Online using DIGSI: Open the Online directory by double-clicking; the operating functions for the device appear. Click on Test; the function selection appears in the right half of the screen. Double-click on Testing Messages for System Interface shown in the list view. The dialogue box Testing System Interface opens (refer to the following figure). Structure of the Test Dialogue Box In the column Indication the display texts of all indications are displayed which were allocated to the system interface in the matrix. In the column Status SETPOINT the user has to define the value for the messages to be tested. Depending on indication type, several input fields are offered (e.g.Indication coming/ Indication going). By clicking on one of the fields you can select the desired value from the pull-down menu.

Figure 3-13

System interface test with dialog box: Generate indications example

Changing the Operating State

Clicking for the first time on one of the field in column Action you will be asked for password no. 6 (for hardware test menus). After you have entered the password correctly you now can send the indications individually. To do so, click on the button Send on the corresponding line. The corresponding indication is issued and can be read out either from the event log of the SIPROTEC 4 device or from the substation. As long as the window is open, further tests can be performed.

114

6MD66 Manual C53000-G1876-C102-3

3.3 Commissioning

Test in Message Direction

For all information that is transmitted to the central station test in Status Scheduled the desired options in the list which appears: Make sure that each checking process is carried out carefully without causing any danger (see above and refer to DANGER!) Click on Send in the function to be tested and check whether the transmitted information reaches the central station and shows the desired reaction. With this procedure the information (beginning with ">) which is normally coupled via binary inputs is also transmitted to the central station. The function of the binary inputs itself is tested separately.

Exiting the Test Mode Test in Command Direction

To end the System Interface Test, click on Close. The device is briefly out of service while the start-up routine is executed. The dialogue box closes. The information transmitted in command direction must be indicated by the central station. Check whether the reaction is correct.

3.3.3

Checking the Binary Inputs and Outputs


The binary inputs, outputs, and LEDs of a SIPROTEC 4 device can be individually and precisely controlled in DIGSI. This feature is used to verify control wiring from the device to plant equipment (operational checks), during commissioning. This test feature should not be used while the device is in service on a live system.

Prefacing Remarks

DANGER!
Danger evolving from operating the equipment (e.g. circuit breakers, disconnectors) by means of the test function Nonobservance of the following measure will result in death, severe personal injury or substantial property damage. Equipment used to allow switching such as circuit breakers or disconnectors is to be checked only during commissioning. Do not under any circumstances check them by means of the testing mode during real operation performing transmission and reception of messages via the system interface.

Note After termination of the hardware test, the device will reboot. All indication buffers are erased. If required, these buffers should be extracted with DIGSI prior to the test. The hardware test can be done using DIGSI in the online operating mode: Open the Online directory by double-clicking; the operating functions for the device appear. Click on Test; the function selection appears in the right half of the screen. Double-click in the list view on Hardware Test. The dialogue box of the same name opens (see the following figure).

6MD66 Manual C53000-G1876-C102-3

115

3 Installation and Commissioning

Structure of the Test Dialogue Box

The dialog box is divided into three groups: BI for binary inputs, REL for output relays, and LED for light-emitting diodes. On the left of each group is an accordingly labelled button. By double-clicking these buttons you can show or hide the individual information of the selected group. In the column Status the current status of the particular hardware component is displayed. It is displayed symbolically. The actual states of the binary inputs and outputs are displayed by the symbol of opened and closed switch contacts, those of the LEDs by a symbol of a lit or extinguished LED. The opposite state of each element is displayed in the column Scheduled. The display is made in plain text. The right-most column indicates the commands or messages that are configured (masked) to the hardware components.

Figure 3-14

Test of the Binary Inputs/Outputs Example

Changing the Operating State

To change the condition of a hardware component, click on the associated switching field in the Scheduled column. Password No. 6 (if activated during configuration) will be requested before the first hardware modification is allowed. After entry of the correct password a condition change will be executed. Further condition changes remain possible while the dialog box is open.

Test of the Binary Outputs

Each individual output relay can be energized allowing a check of the wiring between the output relay of the 6MD66 and the system, without having to generate the indication that is assigned to the relay. As soon as the first change of state for any one of the output relays is initiated, all output relays are separated from the internal device functions, and can only be operated by the hardware test function. This means, that e.g. a

116

6MD66 Manual C53000-G1876-C102-3

3.3 Commissioning

TRIP command coming from a protection function or a control command from the operator panel to an output relay cannot be executed. Proceed as follows in order to check the output relay : Ensure that the switching of the output relay can be executed without danger (see above under DANGER!). Each output relay must be tested via the corresponding Scheduledcell in the dialog box. Finish the testing (see margin title below Exiting the Procedure), so that during further testings no unwanted switchings are initiated. Test of the Binary Inputs To test the wiring between the plant and the binary inputs of the 6MD66 the condition in the plant which initiates the binary input must be generated and the response of the device checked. To do so, the dialogue box Hardware Test must again be opened to view the physical state of the binary inputs. The password is not yet required. Proceed as follows in order to check the binary inputs: Each state in the plant which causes a binary input to pick up must be generated. The response of the device must be checked in the Statuscolumn of the dialogue box. To do this, the dialogue box must be updated. The options may be found below under the margin heading Updating the Display. Finish the testing (see margin heading below "Exiting the Procedure"). If however the effect of a binary input must be checked without carrying out any switching in the plant, it is possible to trigger individual binary inputs with the hardware test function. As soon as the first state change of any binary input is triggered and the password no. 6 has been entered, all binary inputs are separated from the plant and can only be activated via the hardware test function. Test of the LEDs The LEDs may be tested in a similar manner to the other input/output components. As soon as the first state change of any LED has been triggered, all LEDs are separated from the internal device functionality and can only be controlled via the hardware test function. This implies that no LED can be switched on anymore by e.g. a protection function or operation of the LED reset key. During the opening of the dialog box Hardware Test the operating states of the hardware components which are current at this time are read in and displayed. An update occurs: for each hardware component, if a command to change the condition is successfully performed, for all hardware components if the Updatebutton is clicked, for all hardware components with cyclical updating (cycle time is 20 seconds) if the Automatic Update (20sec) field is marked. Exiting the Test Mode To end the hardware test, click on Close. The dialog box closes. The device becomes unavailable for a brief start-up period immediately after this. Then all hardware components are returned to the operating conditions determined by the plant settings.

Updating the Display

6MD66 Manual C53000-G1876-C102-3

117

3 Installation and Commissioning

3.3.4

Testing User-Defined Functions (CFC logic)


The device has a vast capability for allowing functions to be defined by the user, especially with the CFC logic. Any special function or logic added to the device must be checked. Naturally, general test procedures cannot be given. Rather, the configuration of these user-defined functions and the necessary associated conditions must be known and verified. Possible interlocking conditions of switching devices (circuit breakers, disconnectors, earth switch) are of particular importance. They must be considered and tested.

3.3.5

Trip/Close Tests for the Configured Operating Devices


If the configured operating devices were not switched sufficiently in the hardware test already described, all configured switching devices must be switched on and off from the device via the integrated control element. The feedback information of the circuit breaker position injected via binary inputs is read out at the device and compared with the actual breaker position. With 6MD66 this is easy to do with the control display. The switching procedure is described in the SIPROTEC System Description /1/. The switching authority must be set in correspondence with the source of commands used. With the switch mode it is possible to select between interlocked and non-interlocked switching. Note that non-interlocked switching constitutes a safety risk.

Control by Local Command

DANGER!
A test cycle successfully started by the automatic reclosure function can lead to the closing of the circuit breaker! Nonobservance of the following described will result in death, severe personal injury or substantial property damage. Be fully aware that OPEN-commands sent to the circuit breaker can result in a tripclose-trip event of the circuit breaker by an external reclosing device.

Control from a Remote Control Centre

If the device is connected to a remote substation via a system interface, the corresponding switching tests may also be checked from the substation. Please also take into consideration that the switching authority is set in correspondence with the source of commands used.

118

6MD66 Manual C53000-G1876-C102-3

3.4 Final Preparation of the Device

3.4

Final Preparation of the Device


Firmly tighten all screws. Tighten all terminal screws, including those that are not used.

Caution!
Inadmissable tightening torques Nonobservance of the following measure can result in minor personal injury or property damage: The tightening torques must not be exceeded as the threads and terminal chambers may otherwise be damaged! In case service settings were changed, check if they are correct. Check if power system data, control and auxiliary functions to be found with the configuration parameters are set correctly (Section 2). All desired elements and functions must be set ON. Ensure that a copy of the setting values is stored on the PC. The user should check the device-internal clock and set/synchronise it if necessary, provided that it is not synchronised automatically. Refer to the SIPROTEC System Description /1/ for more information on this. The indication buffers are deleted under MAIN MENU Indications Delete/Set, so that in the future they only contain information on actual events and states (see also /1/). The counters in the switching statistics should be reset to the values that were existing prior to the testing (see also SIPROTEC System Description /1/). Press the (6& key, several times if necessary, to return to the default display. The default display appears in the display (e.g. display of operation measured values). Clear the LEDs on the front panel by pressing the /(' key, so that they only show real events and states. In this context, also output relays probably memorized are reset. Pressing the /(' key also serves as a test for the LEDs on the front panel because they should all light when the button is pushed. Any LEDs that are lit after the clearing attempt are displaying actual conditions. The green RUN LED must be on. The red ERROR LED must not be lit. Close the protective switches. If test switches are available, then these must be in the operating position. The device is now ready for operation.

6MD66 Manual C53000-G1876-C102-3

119

3 Installation and Commissioning

120

6MD66 Manual C53000-G1876-C102-3

Technical Data

This chapter provides the technical data of SIPROTEC 6MD66 device and its individual functions, including the limiting values that under no circumstances may be exceeded. The electrical and functional data for the maximum functional scope are followed by the mechanical specifications with dimensional diagrams.

4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8

General Device Data Switchgear control Circuit breaker synchronisation User defined functions (CFC) Operating measured values Inter relay communication Auxiliary functions Dimensions

122 132 133 135 138 140 141 142

6MD66 Manual C53000-G1876-C102-3

121

4 Technical Data

4.1
4.1.1

General Device Data


Analogue inputs and outputs

Current inputs
Rated system frequency Rated current at INom = 1 A at INom = 5 A Current overload capability Thermal (rms) 200 A for 1 s 15 A for 10 s 12 A continuous Dynamic (peak value) Precision 250 INom (half-cycle) 0.5 % of measured value at 50 % to 120 % INom(under
reference conditions)

fNom INom

50 Hz or 60 Hz 1 A or 5 A Approx. 0.05 VA Approx. 0.3 VA

(adjustable)

Burden per phase and ground path

Voltage inputs
Secondary nominal voltage Measuring range Burden at 100 V Voltage overload capacity Thermal (rms) Precision 230 V continuous 0.5 % of measured value at 50 % to 120 % VNom (under
reference conditions)

80 V to 125 V 0 V to 170 V Approx. 0.3 VA

Measuring transducer inputs

Input current Overload capability Input resistance Power input Precision

-20 mA DC to +20 mA DC 100 mA continuous 10 5.8 mW at 24 mA < 1 % from rated value (under reference conditions)

Limit range behaviour, current

Overflow

Phase current > 1.2 x rated current The derived quantities P, Q, S, cos, sin and also overflow as a result.

Limit range behaviour, voltage

Overflow

Secondary input voltage at the device > 120 Veff The derived quantities P, Q, S, cos, sin and also overflow as a result.

122

6MD66 Manual C53000-G1876-C102-3

4.1 General Device Data

Limit range behaviour, power

Zero, invalid Overflow

A phase voltage < 0.1 x rated voltage or the nominal apparanet power S < 1 % A phase current or a phase-earth voltage in overflow

Limit range behaviour, cos, sin,

Zero, invalid Overflow

A phase voltage < 0.1 x rated voltage or the nominal apparanet power S < 1 % A phase current or a phase-earth voltage in overflow

Limit range behaviour, frequency

Zero, invalid Overflow

Frequency < 45 Hz or secondary input voltage at device 10 Veff Frequency > 65 Hz

4.1.2

Auxiliary voltage

DC voltage
Voltage supply via integrated AC/DC converter Rated auxiliary DC VA Permissible voltage ranges Rated auxiliary DC VA Permissible voltage ranges Superimposed AC ripple voltage, peak to peak, IEC 60 255-11 Quiescent power consumption Power consumption plus energised relay Bridging time for failure/short circuit, IEC 60 255-11 50 ms at V 110 V DC 20 ms at V 24 V DC 15 % of the auxiliary voltage Approx. 10.0 W Approx. 0.27 W 24/48 V DC 19 to 58 V DC 110 V DC 88 to 132 V DC 60 V DC 48 to 72 V DC 220 to 250 V DC 176 to 300 V DC

4.1.3

Binary inputs and outputs

Binary inputs
Variant 6MD663* 6MD664* Rated voltage range Peak current at high level Binary input Number 50 (configurable) 65 (configurable) 24 V DC to 250 V DC, bipolar 80 mA ( = 1.5 ms) BI1....6; BI8....19; BI25....36 BI7; BI20....24; BI37 Approx. 1.8 mA Approx. 4 ms

Current consumption, energised (inde- Approx. 1.8 mA per BI pendent of the control voltage) Pickup times Approx. 9 ms

6MD66 Manual C53000-G1876-C102-3

123

4 Technical Data

Switching thresholds for rated voltages for rated voltages for rated voltages Maximum permissible voltage Impulse filter on input

adjustable with jumpers 24/48/60 V DC 110 V DC 220 to 250 V DC 300 V DC 220 nF at 220 V with recovery time > 60 ms Vpu 19 V DC Vdo 14 V DC Vpu 88 V DC Vdo 66 V DC Vpu 176 V DC Vdo 132 V DC

Output relays
Flag/command relay1) Number and Information Order variant 6MD663* 6MD664* Contacts per relay Switching capability ON Switching capability OFF 35 45 1 NO contact 1000 W/VA 1) 30 VA 40 W resistive 25 W/VA at L/R 50ms Switching voltage Permissible current per contact / inrush peak Permissible current per contact On common path Life contact Switching capability ON Switching capability OFF Switching voltage Permissible current
1)Maximum

According to the order variant (allocatable)

250 V 5 A continuous 30 A 0.5 s 5 A continuous 30 A for 0.5 s 1 with 1 NO contact or 1 NC contact (switchable) 30 W/VA 20 VA 250 V 1 A continuous

permissible number of simultaneously energised relays: 29

4.1.4

Communications interfaces

Operator Interface
Connection Operation Transmission Speed Maximum Distance of Transmission front side, non-isolated, RS 232, 9 pin DSUB port for connecting a personal computer with DIGSI min. 4 800 Baud; max. 115 200 Baud; factory setting: 38 400 Baud; Parity: 8E1 49 feet (15 m)

124

6MD66 Manual C53000-G1876-C102-3

4.1 General Device Data

Service / modem interface

Connection Operation Transmission speed RS232/RS485 Connection for flushmounted case

isolated interface for data transfer with DIGSI min. 4,800 Baud; max. 115,200 Baud; Factory setting 38 400 Baud RS232/RS485 according to the ordering variant Rear panel, slot "C", 9-pin subminiature socket

Surface-mounting housing At the housing mounted case on the case bottom; Shielded data cable Test voltage RS232 RS485 Fibre optic cable (FO) Channel distance Channel distance Type of fibre optic cable Connection for flushmounted case For panel surfacemounted case Optical wavelength 500 V; 50 Hz 49.215 ft. (15 m) 3,281 ft. (1,000 m) ST connector Rear panel, mounting location "D" At the housing mounted case on the case bottom = 820 nm

Laser Class 1 according to Using glass fibre 50/125 m or using EN 608251/2 glass fibre 62.5/125 m Permissible link signal attenuation Channel distance Character idle state max. 8 dB, with glass fibre 62.5/125 m max. 0.93 mi. (1.5 km) Configurable; factory setting "Light off"

Inter relay communication interface

Transmission speed electrical HDLC UART optical HDLC UART Isolated interface for data transfer RS485 Connection for flushmounted case Surface-mounting case Rear panel, slot "C", 9-pin subminiature socket At the housing mounted case on the case bottom; Shielded data cable Test voltage Channel distance 500 V; 50 Hz 3,281 ft. (1,000 m) 125 KBaud, 250 KBaud, 1 MBaud, 1.25 MBaud 115 KBaud, 250 KBaud 125 KBaud 500 KBaud

6MD66 Manual C53000-G1876-C102-3

125

4 Technical Data

System interface
PROFIBUS FMS and PROFIBUS DP RS485 Connection for flushmounted case Rear panel, slot "E", 9-pin subminiature socket

For panel surface-mounted At the housing mounted case on the case case bottom Test voltage Transmission speed Channel distance 500 V; 50 Hz up to 1.5 MBd 3,281 ft. (1,000 m) at 93.75 kBd 1,640.5 ft. (500 m) at 187.5 kBd 656.2 ft. (200 m) at 1.5 MBd ST-connector single ring / double ring according to the order for FMS; for DP only double ring available Rear panel, mounting location "E"

Fibre optic cable FO

Type of fibre optical connection Connection for flushmounted case

For panel surface-mounted In console housing on the case bottom, case only RS485 1) Transmission speed Recommended: up to 1.5 MBd > 500 kBd with normal casing 57,600 Bd with detached operator panel Optical wavelength = 820 nm Laser Class 1 according to Using glass fibre 50/125 m or using EN 608251/2 glass fibre 62.5/125 m Permissible link signal attenuation Max. 8 dB, with glass fibre 62.5/125 m

Maximum channel distance 6562 ft. (2,000 m) for glass fibre 62.5/ between two modules with 125 m redundant optical ring topology, baud rates 500 kB/s and glass fibre 62.5/ With plastic fibre: 6.562 ft. (2 m) 125 m At 500 kB/s, 5,249.6 ft. (1,600 m) At 1,500 kB/s, 1,738.93 ft. (530 m) IEC 60 8705103 RS485 Isolated interface for data transfer to a master terminal Connection for flushmounted case Rear panel, slot "E", 9-pin subminiature socket

For panel surface-mounted At the housing mounted case on the case case bottom Test voltage Transmission speed Channel distance 500 V; 50 Hz min. 4,800 Baud; max. 38,400 Baud; Factory setting 38,400 Baud max. 0.621 mi. (1 km)

126

6MD66 Manual C53000-G1876-C102-3

4.1 General Device Data

Fibre optic cable (FO) Type of fibre optic cable Connection for flushmounted case ST connector Rear panel, mounting location "E"

For panel surface-mounted In console housing on the case bottom, case only RS485 1) Optical wavelength = 820 nm Laser Class 1 according to When glass fibre used EN 608251/2 50/12 m or when 62.5/125 m glass fibre is used Permissible path attenuation Channel distance Character idle state
1)

Max. 8 dB, with glass fibre 62.5/125 m 0.93 mi. (1.5 km) Configurable; factory setting "Light off"

Common use of the OLM/G12 (OLM V3) with the optical PROFIBUS interfaces of the SIPROTEC 4 devices may only use the OLM/G12 in compatibility mode (DIL switch S7 = ON)! The reason for this is the fact that the redundancy technology of the OLM V2 is implemented in the SIPROTEC PROFIBUS interfaces, and this varies from OLM V3. An OLM V3 behaves in the same manner as an OLM V2 in compatibility mode. With an incorrect setting, secure data transmission cannot be guaranteed.

Time Synchronization Interface

Time Synchronization Connection for flush-mounted case for surface-mounting case Signal Nominal Voltages Signal Levels and Burdens:

DCF 77 / IRIG BSignal rear panel, mounting location "A"; 9-pole D-SUB miniature connector at the double-deck terminal on the case bottom selectable 5 V, 12 V or 24 V Nominal Signal Voltage 5V 12 V 15.8 V 1.4 V at IILow = 0.25 mA 4.5 mA to 9.3 mA 1930 at VI = 8.7 V 1700 at VI = 15.8 V 31 V 1.9 V at IILow = 0.25 mA 4.5 mA to 8.7 mA 3780 at VI = 17 V 3560 at VI = 31 V 24 V

VIHigh VILow IIHigh RI

6.0 V 1.0 V at IILow = 0.25 mA 4.5 mA to 9.4 mA 890 at VI = 4 V 640 at VI = 6 V

4.1.5

Electrical Tests

Specifications
Standards: IEC 60 255 (Product standards) ANSI/IEEE C37.90.0/ .1/.2 UL 508 DIN 57 435 Part 303 - for more standards see also individual functions

6MD66 Manual C53000-G1876-C102-3

127

4 Technical Data

Insulation Test
Standards: IEC 60 255-5 and IEC 60 870-2-1 High Voltage Test (routine test) All circuits 2.5 kV (rms), 50 Hz except power supply, Binary Inputs, Communication Interface and Time Synchronization Interfaces High voltage test (routine test) Auxiliary voltage and binary inputs 3.5 kV DC

High Voltage Test (routine test) Only Isolated 500 V (rms), 50 Hz Communication and Time Synchronization Interfaces Impulse Voltage Test (type test) All Circuits 5 kV (peak): 1.2/50 s: 0.5 Ws: 3 positive and 3 Except Communication and Time Synchro- negative impulses in intervals of 5 s nization Interfaces, Class III

EMC Tests for Immunity (Type Tests)

Standards:

IEC 60 255-6 and -22, (Product standards) EN 50 082-2 (Generic standard) DIN 57 435 Part 303

High Frequency Test IEC 60255-22-1, Class 2.5 kV (Peak); 1 MHz; = 15 s; 400 Surges per III and VDE 0435 Part 303, Class III s; Test Duration 2 s; Ri = 200 Electrostatic Discharge IEC 60 255-22-2, Class IV and IEC 61 000-4-2, Class IV 8 kV contact discharge; 15 kV air discharge, both polarities; 150 pF; Ri = 330

Irradiation with HF field, non-modulated IEC 10 V/m; 27 MHz to 500 MHz 60 255-22-3 (Report), Class III Irradiation with HF field, amplitude modulated IEC 61 000-4-3, Class III Irradiation with HF field, pulse modulated IEC 61 000-4-3/ENV 50 204, Class III 10 V/m; 80 MHz to 1000 MHz; 80 % AM; 1 kHz 10 V/m; 900 MHz; repetition frequency 200 Hz; duty cycle of 50 %

Fast Transient Disturbance Variables / Burst 4 kV; 5/50 ns; 5 kHz; Burst length = 15 ms; repIEC 60255-22-4 and IEC 61 000-4-4, Class etition rate 300 ms; both polarities: R i = 50 ; IV Test Duration 1 min High Energy Surge Voltages (SURGE), IEC Impulse: 1.2/50 s 61 00045 Installation Class 3 Power Supply Voltage Measuring Inputs, Binary Inputs, Relay Outputs common mode: 2 kV; 12 ; 9 F diff. mode:1 kV; 2 ; 18 F common mode: 2 kV; 42 ; 0.5 F diff. mode: 1 kV; 42 ; 0.5 F

Line Conducted HF, amplitude module. IEC 10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz 61 000-4-6, Class III Power System Frequency Magnetic Field IEC 61 000-4-8, Class IV IEC 60 255-6 Oscillatory Surge Withstand Capability ANSI/IEEE C37.90.1 30 A/m continuous; 300 A/m for 3 s; 50 Hz 0.5 mT; 50 Hz 2.5 to 3 kV (peak value); 1 to 1.5 MHz; damped oscillation; 50 surges per s; Test Duration 2 s; Ri = 150 to 200

Fast Transient Surge Withstand Cap. ANSI/ 4 kV to 5 kV; 10/150 ns; 50 pulses per s; both IEEE C37.90.1 polarities; Test Duration 2 s; Ri = 80 Radiated Electromagnetic Interference ANSI/IEEE Std C37.90.2 Damped Oscillations IEC 60,694, IEC 61 000412 35 V/m; 25 MHz to 1000 MHz 2.5 kV (Peak Value), polarity alternating 100 kHz, 1 MHz, 10 MHz and 50 MHz, Ri = 200

128

6MD66 Manual C53000-G1876-C102-3

4.1 General Device Data

EMC Tests For Noise Emission (type test)

Standard: Radio Noise Voltage to Lines, Only Power Supply Voltage IECCISPR 22 Radio Noise Field Strength IECCISPR 22 Harmonic Currents on the Network Lead at 230 V AC IEC 6100032 Voltage Variations and Flicker on the Network Lead at 230 V AC IEC 61000-3-3

EN 50 081* (Product standards) 150 kHz to 30 MH Limit Class B 30 MHz to 1000 MHz Limit Class B Device is to be assigned Class D; (applies only for devices with > 50 VA power consumption) Limits are observed

4.1.6

Mechanical Stress Tests

Vibration and Shock Stress During Operation

Standards: Vibration IEC 60255-21-1, Class 2 IEC 60068-2-6

IEC 60 25521 and IEC 60 068 Sinusoidal 10 Hz to 60 Hz: 0.075 mm Amplitude; 60 Hz to 150 Hz: 1g acceleration frequency sweep rate 1 Octave/min 20 cycles in 3 orthogonal axes.

Shock IEC 60 255-21-2, Class 1 IEC 60 068-2-27

Half-sine shaped Acceleration 5 g, duration 11 ms, 3 shocks in each direction of 3 orthogonal axes

Seismic Vibration IEC 60 255213, Class 1 Sinusoidal 1 Hz to 8 Hz: 3.5 mm Amplitude IEC 60 06833 (horizontal axis); 1 Hz to 8 Hz: 1.5 mm Amplitude (vertical axis); 8 Hz to 35 Hz: 1 g acceleration Amplitude (horizontal axis) 8 Hz to 35 Hz:0.5 g acceleration (vertical axis) Frequency Sweep Rate 1 Octave/min 1 cycle in 3 orthogonal axes

Vibration and Shock Stress During Transport

Standards: Vibration IEC 60255211, Class 2 IEC 6006826 Shock IEC 60 255212, Class 1 IEC 60 068227

IEC 60 25521 and IEC 60 068 sinussoidal 5 Hz to 8 Hz: 7.5 mm Amplitude; 8 Hz to 15 Hz: 2 g acceleration frequency sweep rate 1 Octave/min 20 cycles in 3 orthogonal axes. Half-sine shaped acceleration 15 g, duration 11 ms, 3 shocks in each direction of 3 orthogonal axes

Continuous Shock IEC 60 255212, Class Half-sine shaped acceleration 10 g, duration 16 1 IEC 60 068229 ms, 1000 shocks in each direction of 3 orthogonal axes

4.1.7

Climatic stress tests

Temperatures
Standards: IEC 60255-6 Type tested (acc. IEC 60086-2-1 and -2, Test 5 C to +55 C Bd, for 16 h)

6MD66 Manual C53000-G1876-C102-3

129

4 Technical Data

Permissible temporary operating temperature (tested for 96 h)

20 C to +70 C in quiescent state, i.e. no pickup and no indications (legibility of display may be restricted from +131 F (+55 C))

Recommended for permanent operation (according to IEC 60 255-6) Limiting temperatures for storage Limit temperatures during transport

+23 F to +131 F (5 C to +55 C) 13 F to +131 F (25 C to +55 C) 13 F to +158 F (25 C to +70 C)

Storage and transport of the device with factory packaging! Limiting temperatures for normal operation (i.e. output relays not energized) Limiting temperatures with maximum load (max. cont. permissible input and output quantities) 4 F to +158 F (20 C to +70 C) 23 F to +104 F (5 C to +40 C)

Humidity
Permissible humidity Mean value per year 75 % relative humidity; on 56 days of the year up to 93 % relative humidity; condensation must be avoided!

Siemens recommends that all devices be installed such that they are not exposed to direct sunlight, nor subject to large fluctuations in temperature that may cause condensation to occur.

4.1.8

Service Conditions

The protective device is designed for use in an industrial environment and an electrical utility environment. Proper installation procedures should be followed to ensure electromagnetic compatibility (EMC). In addition, the following is recommended: All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protective device should, as a rule, be equipped with suitable surge suppression components. For substations with operating voltages of 100 kV and above, all external cables should be shielded with a conductive shield grounded at both ends. For substations with lower operating voltages, no special measures are normally required. Do not withdraw or insert individual modules or boards while the protective device is energized. In withdrawn condition, some components are electrostatically endangered; during handling the EEC standards (standards for Electrostatically Endangered Components) must be observed. They are not endangered when inserted into the case.

4.1.9

Construction

Case Dimensions

7XP20 See dimensional drawings, Section 4.8

Weight (maximum number of components ) approx.

130

6MD66 Manual C53000-G1876-C102-3

4.1 General Device Data

6 MD663 in flush-mount case 6 MD664 in flush-mount case 6 MD663 in case for detachted operator panel 6 MD664 in case for detachted operator panel Detached operator panel International protection under IEC 60 529 For equipment of the flush-mount housing Front Rear In flush-mount case and in model with detached operator panel Front Rear For personal protection

23.1525 lb. (10.5 kg) 24.255 lb. (11 kg) 27.5625 lb. (12.5 kg) 28.665 lb. (13 kg) 5.5125 lb. (2.5 kg)

IP 51 IP20 IP 51 IP 50 IP 2x with cover cap

6MD66 Manual C53000-G1876-C102-3

131

4 Technical Data

4.2

Switchgear control

Number of controlled switchgear units - 6MD663 - 6MD664 Interlocking Indications Commands Switching command to circuit breaker Programmable logic controller Local control Remote control

Depends on the number of binary inputs and outputs available 2-pin command output: 8 switchgear units 1 1/2-pin command output: 10 switchgear units 2-pin command output: 11 switchgear units 1 1/2-pin command output: 14 switchgear units Freely programmable interlocking Single point, double point, output, tagging and tap indications, bit patterns and counters Single command / double command Pulse and continuous outputs 1-, 11/2 - and 2-pin PLC logic, graphic input tool Control via menu control, control keys Assignment of function keys Using communication interfaces Using substation automation system (e.g. SICAM) Using DIGSI (e.g. via Modem)

132

6MD66 Manual C53000-G1876-C102-3

4.3 Circuit breaker synchronisation

4.3

Circuit breaker synchronisation

Operating modes Test programs Synchronisation check, live bus / dead line live bus / dead line dead bus and dead line bypassing, or combination of them Synchronisation Closing the circuit breaker under synchronous and asynchronous power conditions possible (with circuit breaker operating time)

Voltages Maximum working voltage V< for dead status V> for live status Tolerances Dropout V measurements Quantity difference Tolerance Synchronous power conditions -measurement Tolerance f-measurement Tolerance 2 to 60 (1 increments) 2 0.03 Hz to 2.00 Hz (0.01 Hz increments) 15 mHz The maximum permissible frequency difference depends on the circuit breaker operating time Max. angle error Enable delay Asynchronous power conditions f-measurement Tolerance 0.03 Hz to 2.00 Hz (0.01 Hz increments) 15 mHz The maximum permissible frequency difference depends on the circuit breaker operating time Synchronous/asynchronous limits Circuit breaker operating time Times Minimum measuring time Approx. 80 ms 0.01 Hz to 0.04 Hz (1 mHz increments) 0.01 s to 0.60 s (0.01 s increments) 5 for f 2 Hz 0.00 s to 60.00 s (0.01 s increments) 1 V to 40 V (phase-to-phase) (0.1 V increments) 1V 20 V to 140 V (phase-to-phase) (1 V increments) 1 V to 60 V (phase-to-phase) (1 V increments) 20 V to 125 V (phase-to-phase) (1 V increments) 2 % of pickup value or 2 V Approx. 0.9 (V>) or 1.1 (V<); max. 1 V

6MD66 Manual C53000-G1876-C102-3

133

4 Technical Data

Synchronisation function delay after start

250 ms

Maximum wait time (max. synchronisation 0.01 s to 600.00 s (0.01 s increments) duration Tolerance of all times Operating range Synchrocheck at rated frequency 50 Hz 2 Hz 60 Hz 2 Hz 1 % of setting value or 10 ms

134

6MD66 Manual C53000-G1876-C102-3

4.4 User defined functions (CFC)

4.4

User defined functions (CFC)

Function Modules and Possible Assignments to Task Levels

Function Module

Description

Run-Time Level MW_BEA RB (Measured Value Processing) PLC1_BE PLC_BEA ARB RB (Fast (Slow PLC) PLC) X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X SFS_BEARB (Interlocking)

ABSVALUE ADD AND BOOL_TO_CO BOOL_TO_DL BOOL_TO_IC BUILD_DI CMD_CHAIN CMD_INF CONNECT D_FF D_FF_MEMO DI_TO_BOOL DIV DM_DECODE DYN_OR LIVE_ZERO LONG_TIMER LOOP

Magnitude calculation addition AND - Gate Boolean to Control (conversion) Boolean to Double Point (conversion) Bool to internal SI, conversion Create Double Point annunciation Switching sequence Command information Connection D- Flipflop status memory for restart Double Point to Boolean (conversion) division Decode double point dynamic or Timer (max.1193h) Feedback loop

X X X X X X X X X X X X X X X X X X X X X

X X X X X X X X X X X X X X X X X X X X X X X X X

LOWER_SETPOI Lower limit NT MUL NAND NEG NOR OR RS_FF SR_FF SUB TIMER multiplication NAND - Gate Negator NOR - Gate OR - Gate RS- Flipflop SR- Flipflop substraction Timer

SQUARE_ROOT root extractor

UPPER_SETPOI Upper limit NT X_OR ZERO_POINT XOR - Gate Zero supression

6MD66 Manual C53000-G1876-C102-3

135

4 Technical Data

General Limits
Designation Maximum number of all CFC charts considering 32 all task levels Maximum number of all CFC charts considering 16 one task level Maximum number of all CFC inputs considering 400 all charts Maximum number of inputs of one chart for each 400 task level (number of unequal information items of the left border per task level) here the number of elements of the left border per task level is counted. Since the same information is indicated at the border several times, only unequal information is to be counted. corresponds to 18 long timers or 9 universal timers. No test in DIGSI. Limit1) Comments

Maximum number of switching sequences Maximum number of time modules

20 20

Maximum number of reset-resistant flipflops


1)

50

When the limit is exceeded, an error message is output by the device. Consequently, the device starts monitoring.

Device-specific limits

Code Maximum number of synchronous changes of chart inputs per task level Maximum number of chart outputs per task level
1)

Limits 1) 50 150

When the limit is exceeded, an error message is output by the device. Consequently, the device starts monitoring.

General Limits
Additional limits 1) for the following 4 CFC blocks: Run-Time Level MW_BEARB (Measured Value Processing) PLC1_BEARB (Slow PLC) PLC_BEARB (Fast PLC) SFS_BEARB (Interlocking)
1)

Maximum Number of Modules in the Task Levels LONG_TIMER TIMER CMD_CHAIN D_FF_MEMO

18

20

50

When the limit is exceeded, an error message is output by the device. Consequently, the device starts monitoring.

136

6MD66 Manual C53000-G1876-C102-3

4.4 User defined functions (CFC)

Device-specific limits

Maximum number of TICKS 1) on the task levels Priority class MW_BEARB (Measured value processing) PLC1_BEARB (slow PLC processing) PLC_BEARB (fast PLC processing) SFS_BEARB (interlocking)
1)

Limit in TICKS 3000 5000 700 3000

When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error message is output by CFC.

Processing times in TICKS required by the individual elements

Element Block, basic requirement Each input more than 3 inputs for generic modules Connection to an input signal Connection to an output signal Additional for each chart CMD_CHAIN D_FF_MEMO LOOP DM_DECODE DYN_OR ADD SUB MUL DIV SQUARE_ROOT

Number of TICKS 5 1 6 7 1 34 6 8 8 6 26 26 26 54 83

6MD66 Manual C53000-G1876-C102-3

137

4 Technical Data

4.5

Operating measured values

Operational measured values for currents IL1; IL2; IL3 in A (kA) primary and in A secondary or in % of INom Range Tolerance 10 % to 120 % IN < 1 % of INom at | f-fNom | < 5 Hz and at 10 % to 50 % INom < 0.5 % of measured value at | f-fNom | < 5 Hz and at 10 % to 50 % INom Operational measured values for voltages Vmeasured in kV primary, in V secondary or in % of VNom Range Tolerance 10 % to 120 % of VNom < 1 % of VNom at | f-fNom | < 5 Hz and at 10 % to 50 % VN < 0.5 % of measured value at | f-fNom | < 5 Hz and at 50 % to 120 % UNom Operational measured values for power Range Tolerance *) S, apparent power in kVAr (MVAr or GVAr) primary and in % of SNom 50 % to 120 % S/SNom < 0.5 % of measured value at | f-fNom | < 5 Hz for V/VNom and I/INom = 50 to 120 % P, real power in kW (MW or GW) primary and in % PNom Range Tolerance
*)

For | cos | = 0.707 to 1.00 < 0.5 % of measured value at | f-fNom | < 5 Hz For V/VNom and I/INom = 50 to 120 % Q, reactive power in kVAr (MVAr or GVAr) primary and in % of QNom

Range Tolerance *)

For | sin | = 0.707 bis 1.00 < 0.5 % of measured value at | f-fNom | < 5 Hz For V/VNom and I/INom = 50 to 120 %

Operating measured value for power factor cos Range Tolerance For | cos | = 0.707 to 1.00 < 0.5 % of measured value at | f-fNom | < 5 Hz For V/VNom and I/INom = 50 to 120 % and at | cos | < 0.707 < 0.01 % Operating measured value for power factor cos Range Tolerance For | cos | = 0.707 to 1.00 < 0.5 % of measured value at | f-fNom | < 5 Hz For V/VNom and I/INom = 50 to 120 % and at | cos | < 0.707 < 0.01 % Operating measured value for power factor sin Range For | sin | = 0.707 to 1.00

138

6MD66 Manual C53000-G1876-C102-3

4.5 Operating measured values

Tolerance

< 0.5 % of measured value at | f-fNom | < 5 Hz For V/VNom and I/INom = 50 to 120 % and at | sin | < 0.707 < 0.01 %

Operational measured values for angles Tolerance Operational measured values for frequency Range Tolerance Measuring transducer limit range behaviour Current, overflow range

in < 0.5 f in Hz 20 mHz at V/VNom = 10 to 120 % and at f = fNom 5 Hz 20 mHz Phase current > 1.2 INom The derived quantities P, Q, C, sin, cos and are then invalid

Voltage, overflow range

Voltage > 1.2 INom The derived phase-phase voltages and quantities P, Q, C, sin, cos and are then invalid

Power, zero range, are invalid Power, overflow range Phase angle, zero range, are invalid Frequency, zero range, is invalid Frequency, overflow range Rated input current Measuring range Input resistance Active power input Tolerance Metered values as binary pulses Max. metered frequency Precision

P, Q, S A phase voltage < 0.1VNom or the nominal apparanet power S < 1 % A phase current or a phase-earth voltage in overflow sin , cos , and A phase voltage < 0.1VNom or the nominal apparanet power S < 1 % f < 45 Hz or a phase voltage < 0.1VNom f > 65 Hz - 20 to 20 mA - 24 to 24 mA 11% 5.76 W at INom = 24 mA 1.0 %, relative to rated value of 20 mA 50 Hz < 0.5 % of measured value at | f-fNom | < 5 Hz and at 50 % to 120 % VNom or at 50 % to 120 % INom

Measured values, technical data of the 20 mA inputs

Metered values calculated from current and voltage

*) Tolerance values apply to system frequency 50 Hz; with system frequency 60 Hz < 1%

6MD66 Manual C53000-G1876-C102-3

139

4 Technical Data

4.6

Inter relay communication

Number of users in the IRC combination Number of information items which each IRC user can apply to the IRC bus Minimum appearance duration for indications which are to be transferred via inter relay communication

Max. 16 Max. 32 20 ms (due to IRC cycle time)

140

6MD66 Manual C53000-G1876-C102-3

4.7 Auxiliary functions

4.7

Auxiliary functions

Time Stamping
Resolution for Event Log Maximum Time Deviation (Internal Clock) Battery 1 ms 0.01 % Lithium battery 3 V/1 Ah, type CR 1/2 AA Message "Fail Battery if battery changes is low

Commissioning aids

Operational measured values Switching device test

Clock
Time Synchronization DCF 77 / IRIG B-Signal Binary input Communication Operating Modes for Time Tracking No. 1 2 3 4 5 6 7 Operating Mode Internal IEC 60870-5-103 PROFIBUS FMS Time signal IRIG B Time signal DCF77 Time signal Sync. Box Pulse via binary input Explanations Internal synchronization using RTC (presetting) External synchronization using system interface (IEC 60 8705103) External synchronization using PROFIBUS interface External synchronisation via IRIG B (telegram format IRIG_B000) External synchronization using DCF 77 External synchronization using SIMEAS Sync. Box External synchronization with pulse via binary input

6MD66 Manual C53000-G1876-C102-3

141

4 Technical Data

4.8
4.8.1

Dimensions
Flush-mount and cabinet installation

Figure 4-1

Dimensional drawing of a 6MD66 for panel surface and cabinet mounting

142

6MD66 Manual C53000-G1876-C102-3

4.8 Dimensions

4.8.2

Mounting with detached operator panel or without operator panel

Figure 4-2

Dimensional drawing of a 6MD66 for surface mounting with/without operator control unit

6MD66 Manual C53000-G1876-C102-3

143

4 Technical Data

4.8.3

Detached Operator Panel

Figure 4-3

Dimensional drawing of a detached operator panel

144

6MD66 Manual C53000-G1876-C102-3

4.8 Dimensions

4.8.4

D-SUB miniature Connector of Dongle Cable (Panel Flush or Cubicle Door Cutout)

Figure 4-4

Dimensions of panel flush or cubicle door cutout of D-SUB miniature connector of dongle cable

6MD66 Manual C53000-G1876-C102-3

145

4 Technical Data

146

6MD66 Manual C53000-G1876-C102-3

Appendix

A
This appendix is primarily a reference for the experienced user. This section provides ordering information for the models of this device. General diagrams indicating the terminal connections of the models of this device are included. Following the general diagrams are diagrams that show the proper connections of the devices to primary equipment in many typical power system configurations. Tables with all settings and all information available in this device equipped with all options are provided. Default settings are also given.

A.1 A.2 A.3 A.4 A.5 A.6 A.7 A.8 A.9 A.10

Ordering Information and Accessories Terminal Assignments Connection Examples Default Settings Protocol-Dependent Functions Functional Overview Settings Information Lists Group Alarms Measured Values

148 152 164 167 171 172 173 176 189 190

6MD66 Manual C53000-G1876-C102-3

147

A Appendix

A.1
A.1.1
A.1.1.1

Ordering Information and Accessories


Ordering Information
6MD66 V 4.2

6 High-voltage bay controller 6 M D 6 6

7 -

10 11 12 -

13 A A 0 +

17 18 19 L

Equipment 50 single point indications 32 one-pole single commands (can also be compiled with double-pole commands and double commands) Three current transformers, four voltage transformers, two measurement inputs 20 mA 65 single point indications 42 one-pole single commands (can also be compiled with double-pole commands and double commands) Three current transformers, four voltage transformers, two measurement inputs 20 mA 4 3

Item 6

Rated current INom = 1 A INom = 5 A 1 5

Item 7

Power Supply, Binary Input Pickup Threshold Setting 24 to 48 V DC, Binary Input Threshold 17 V 60 V DC, Binary Input Threshold 17 V 1) 110 V DC, Binary Input Threshold 73 V
1) 1)

Item 8 2 3 4 5

220 to 250 V DC, Binary Input Threshold 154 V 1)

Construction Surface-mounting case, detached operator panel, installation in a low-voltage compartment Plug-in terminals (2/3 pin connectors) Surface-mounting case, no operator panel, installation in a low-voltage compartment Plug-in terminals (2/3 pin connectors) Surface-mounting case, detached operator panel, installation in a low-voltage compartment Screw-type terminals (direct connection / ring and spade lugs) Flush mounted case with integrated local operation (graphic display, keyboard) Plug-in terminals (2/3 pin connectors) B A

Item 9

C D

148

6MD66 Manual C53000-G1876-C102-3

A.1 Ordering Information and Accessories

Construction Flush mounted case with integrated local operation (graphic display, keyboard) Screw-type terminals (direct connection / ring and spade lugs) Surface-mounting case, no operator panel, installation in a low-voltage compartment, screw-type terminals (direct connection / ring and spade lugs) F E

Item 9

Region-specific Default / Language Settings and Function Versions Region DE, 50 Hz, IEC, Language German (Language can be changed) Region World, 50/60 Hz, IEC/ANSI, Language English (Language can be changed) Region US, 60 Hz, ANSI, Language American English (Language can be changed)

Item 10 A B C

System Interface (Rear Side, Port B) IEC-Protocol, electrical RS485 IEC-Protocol, Optical, 820 nm, ST-Connector PROFIBUS FMS Slave, electrical RS485 PROFIBUS FMS Slave, Optical, Single ring, ST-Connector PROFIBUS FMS Slave, Optical, Double ring, ST-Connector For further interface options see Additional Information L

Item 11 2 3 4 5 6 9

Service/Function interface (back of device, interface C and D) No DIGSI interface at the back DIGSI/Modem, electrical RS232, interface C: DIGSI/Modem, electrical RS458, interface C: DIGSI/Modem, Optical 820 nm, ST-Connector, interface D: Inter relay communication, electrical RS458, interface C:

Item 12 0 1 2 3 4

Inter relay communication, electrical RS458, interface C and DIGSI, optical 820 nm, ST-Connector, interface D: 5

Additional information L on further system interfaces (device rear) (only if item 11 = 9) PROFIBUS DP Slave, RS485 PROFIBUS DP Slave, 820 nm, Optical double ring, ST-Connector
1)

Item 17 L L

Item 18 0 0

Item 19 A B

The thresholds can be changed between 17 V, 73 V and 154 V for each indication input

6MD66 Manual C53000-G1876-C102-3

149

A Appendix

A.1.2

Accessories
Name RS485 FO 820 nm PROFIBUS FMS RS485 PROFIBUS FMS Double ring PROFIBUS FMS Single ring Order No. C73207-A322-D632-1 C73207-A322-D633-1 C73207-A322-D601-1 C73207-A322-D602-1 C73207-A322-D603-1

Exchangeable interface modules

Optical Link Module (OLM)

Name Optical Link Module Power supply 24 V DC for OLM

Order No. 6GK1502-3CB10 7XV5810-0BA00

Cover caps

Covering cap for terminal block type 18-pin voltage terminal, 12-pin current terminal 18-pin voltage terminal, 12-pin current terminal

Order No. C73334-A1-C31-1 C73334-A1-C32-1

Short-circuit links

Covering cap for terminal type 18-pin/12-pin voltage terminal 12-pin/8-pin voltage terminal

Order No. C73334-A1-C34-1 C73334-A1-C33-1

Socket housing

Socket housing 2-pin 3-pin

Order No. C73334-A1-C35-1 C73334-A1-C36-1

Mounting Rails for 19"-Racks

Name Angle Strip (Mounting Rail)

Order No. C73165-A63-C200-2

Battery

Lithium battery 3 V/1 Ah, type CR 1/2 AA VARTA SONNENSCHEIN

Order No. 6127 501 501 1110 150 301

150

6MD66 Manual C53000-G1876-C102-3

A.1 Ordering Information and Accessories

Interface Cable

Interface cable between PC and SIPROTEC Cable with 9-pin male/female connections

Order No. 7XV5100-4

Round cable assembly, 3-pin

Name Round cable assembly, 3-pin

Order No. C73195-A100-B65-1

DIGSI operating software

DIGSI protection operation and configuration software DIGSI, basic version with licenses for 10 computers DIGSI, complete version with all option packages

Order No. 7XS5400-0AA00 7XS5402-0AA00

Display Editor

Software for creating basic and mimic control pictures (option package of the complete version of DIGSI) Display Editor 4; Full version with license for 10 PCs

Order No. 7XS5420-0AA0

Graphic Tools

Graphic Tools Full version with licenses for 10 computers

Order No. 7XS5430-0AA0

DIGSI REMOTE 4

Software for remotely operating protective devices via a modem (and possibly a star connector) using DIGSI (option package of the complete version of DIGSI)

7XS5440-1AA0

SIMATIC CFC 4

Graphical software for setting interlocking (latching) control conditions and creating additional functions (option package of the complete version of DIGSI)

7XS5450-0AA0

6MD66 Manual C53000-G1876-C102-3

151

A Appendix

A.2
A.2.1

Terminal Assignments
Panel Flush Mounting or Cabinet Mounting

6MD663*-*D/E (Page 1)

152

6MD66 Manual C53000-G1876-C102-3

A.2 Terminal Assignments

6MD663*-*D/E (Page 2)

Figure A-1

General diagram 6 MD663*-*D/E (panel flush mounted or cabinet mounted)

6MD66 Manual C53000-G1876-C102-3

153

A Appendix

6MD664*-*D/E (Page 1)

154

6MD66 Manual C53000-G1876-C102-3

A.2 Terminal Assignments

6MD664*-*D/E (Page 2)

Figure A-2

General diagram 6 MD664*-*D/E (panel flush mounted or cabinet mounted)

6MD66 Manual C53000-G1876-C102-3

155

A Appendix

A.2.2

Housing with Detached Operator Panel

6MD663*-*A/C (Page 1)

156

6MD66 Manual C53000-G1876-C102-3

A.2 Terminal Assignments

6MD663*-*A/C (Page 2)

Figure A-3

General diagram 6 MD663*-*A/C (panel surface mounting with detached operator panel)

6MD66 Manual C53000-G1876-C102-3

157

A Appendix

6MD664*-*A/C (Page 1)

158

6MD66 Manual C53000-G1876-C102-3

A.2 Terminal Assignments

6MD664*-*A/C (Page 2)

Figure A-4

General diagram 6 MD664*-*A/C (panel surface mounting with detached operator panel)

6MD66 Manual C53000-G1876-C102-3

159

A Appendix

A.2.3

Housing for installation without operator panel

6MD663*-*B/F (Page 1)

160

6MD66 Manual C53000-G1876-C102-3

A.2 Terminal Assignments

6MD663*-*B/F (Page 2)

Figure A-5

General diagram 6 MD663*-*B/F (devices for panel surface mounting without operator panel)

6MD66 Manual C53000-G1876-C102-3

161

A Appendix

6MD664*-*B/F (Page 1)

162

6MD66 Manual C53000-G1876-C102-3

A.2 Terminal Assignments

6MD664*-*B/F (Page 2)

Figure A-6

General diagram 6 MD664*-*B/F (devices for panel surface mounting without operator panel)

6MD66 Manual C53000-G1876-C102-3

163

A Appendix

A.3

Connection Examples

Figure A-7

Transformer connections to a current transformer and a voltage transformer (1-phase measuring transducer packet)

Figure A-8

Transformer connections to 3 current transformers and 3 voltage transformers (3-phase measuring transducer packet)

164

6MD66 Manual C53000-G1876-C102-3

A.3 Connection Examples

Figure A-9

Transformer connections to 2 current transformers and 2 voltage transformers for an Aron connection and circuit breaker synchronisation connection with VLL

6MD66 Manual C53000-G1876-C102-3

165

A Appendix

Figure A-10

Connection of measured values for the synchronisation blocks 1 to 5 (measurement transducer connection in accordance with connection examples 1 and 2)

Figure A-11

Connection of measured values for the synchronisation blocks 6 to 8 (measurement transducer connection in accordance with connection examples 1 and 2)

166

6MD66 Manual C53000-G1876-C102-3

A.4 Default Settings

A.4

Default Settings
When the device leaves the factory, a large number of LED indications, binary inputs and outputs as well as function keys are already preset. They are summarised in the following table.

A.4.1

LED
Table A-1 LED LED none LED indication presettings Brief Text Function No. Remarks

A.4.2

Binary Input
Table A-2 Binary Input BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 Binary input presettings for all devices and ordering variants Brief Text Q0 Q0 Q1 Q1 Q2 Q2 Q8 Q8 Q9 Q9 Function No. Remarks circuit breaker Q0 circuit breaker Q0 bus disconnector Q1 bus disconnector Q1 bus disconnector Q2 bus disconnector Q2 earthing isolator Q8 earthing isolator Q8 feeder disconnector Q9 feeder disconnector Q9

A.4.3

Binary Output
Table A-3 Output relay presettings for all devices and ordering variants Function No. Remarks circuit breaker Q0 circuit breaker Q0 bus disconnector Q1 bus disconnector Q1 -

Binary Output Brief Text BO1 Q0 BO2 BO3 BO4 OPEN Q0 CLOSED Q1 OPEN Q1 CLOSED

6MD66 Manual C53000-G1876-C102-3

167

A Appendix

Binary Output Brief Text BO6 Q0 BO7 BO8 BO9 BO10 BO11 BO12 BO15 BO16 BO19 BO20 Common contact Q2 OPEN Q2 CLOSED Q1 Common contact Q2 Common contact Q8 OPEN Q8 CLOSED Q9 OPEN Q9 CLOSED Q8 Common contact Q9 Common contact

Function No.

Remarks circuit breaker Q0 bus disconnector Q2 bus disconnector Q2 bus disconnector Q1 bus disconnector Q2 earthing isolator Q8 earthing isolator Q8 feeder disconnector Q9 feeder disconnector Q9 earthing isolator Q8 feeder disconnector Q9 -

A.4.4

Function Keys
Table A-4 Applies to all devices and ordered variants Function No. Remarks

Function Keys Brief Text F1 Display of operational indications F2 Display of the primary operational measured values

168

6MD66 Manual C53000-G1876-C102-3

A.4 Default Settings

A.4.5

Default display

Figure A-12

Default display 6 MD 66

A.4.6

Pre-defined CFC-charts
A CFC chart is already installed when the SIPROTEC 4 device is delivered.

Key switches

Figure A-13

CFC chart KeySwitches

By interconnecting both DI_TO_BOOL blocks, the Switching Authority function of both key switches of the device is implemented.

6MD66 Manual C53000-G1876-C102-3

169

A Appendix

Interlocking

Figure A-14

CFC chart Interlocking

The CFC chart starts the interlocking check which is performed when switching operations of switching elements linked on the left side are executed.

170

6MD66 Manual C53000-G1876-C102-3

A.5 Protocol-Dependent Functions

A.5

Protocol-Dependent Functions

Interface Function Operating Measured Values Metered values Indications

IEC 608705103

PROFIBUS FMS

PROFIBUS DP

Inter relay communication (IRC, optional) Yes Yes Yes (setting taggings; without time stamp)

Yes Yes Yes

Yes Yes Yes

Yes (without current message) Yes (without current message) Yes (without time stamp)

commands

According to VDEW Yes (no system interlocking with local control) Yes Yes

Yes (without status Yes (setting taginformation) gings; without time stamp) Yes (not available Yes with all control centres) No Yes No No

Time Synchronization

Commissioning Aids Indicate measured value Yes blocking Create test indications (DIGSI) Physical properties Transmission mode Baud rate Cyclically/Event 4800 to 38400 Cyclically/Event Up to 1.5 MBaud Cyclically Cyclically Up to 1.5 MBaud Up to 1.25 MBaud (optical), up to 6 MBaud (electrical) Electrical: RS485 Optical: ST connector (double ring) Electrical: RS485 optical via external converter Yes Yes Yes

Connection to device

Electrical: RS485 Electrical: RS485 Optical: ST connector Optical: ST connector (single or double ring)

6MD66 Manual C53000-G1876-C102-3

171

A Appendix

A.6

Functional Overview

Addr. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Parameter 08 9B 08 ,B 083B 083B 083B 083B 08$URQB 6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ  6\QFKURQL]LQJ 

Setting Options Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled

Default Setting Disabled Disabled Enabled Disabled Disabled Enabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled

Description Measurement V Measurement I Measurement 1phase 1.packet Measurement 1phase 2.packet Measurement 1phase 3.packet Measurement 3phase 1.packet Measurement Aron 1.packet Synchronizing Function 1 Synchronizing Function 2 Synchronizing Function 3 Synchronizing Function 4 Synchronizing Function 5 Synchronizing Function 6 Synchronizing Function 7 Synchronizing Function 8

172

6MD66 Manual C53000-G1876-C102-3

A.7 Settings

A.7

Settings

Addr. 0

Parameter SecVoltgNomVal

Function MU U_1 MU1P_1 MU1P_2 MU1P_3 MU3P_1 MUAron_1 MU I_1 MU1P_1 MU1P_2 MU1P_3 MU3P_1 MUAron_1 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8

Setting Options 0.00 .. 200.00 V; < > 0

Default Setting 100.00 V

Description Secondary Voltage Nominal Value

SecCurrNomVal

0.00 .. 5.00 A; < > 0

1.00 A

Secondary Current Nominal Value

T-CB close

0.01 .. 0.60 sec

0.06 sec

Closing (operating) time of CB

T-SYN. DURATION

1.00 .. 600.00 sec

30.00 sec

Maximum duration of synchronismcheck

fmin

95 .. 105 %

95 %

Minimum frequency

fmax

95 .. 105 %

105 %

Maximum frequency

SyncSD

synchronizable switching device

Balancing U1/U2

0.80 .. 1.20

1.00

Balancing Factor U1/U2

Tr. U1-U2

0 .. 360

Angle adjustment U1-U2 (Trafo)

6MD66 Manual C53000-G1876-C102-3

173

A Appendix

Addr. 0

Parameter SecTransNomVal1

Function SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8

Setting Options 0 .. 170 V; < > 0

Default Setting 100 V

Description Secondary Transformer Nominal Value 1

SecTransNomVal2

0 .. 170 V; < > 0

100 V

Secondary Transformer Nominal Value 2

Umin

20 .. 125 V

90 V

Minimum Voltage for Synchronization

Umax

20 .. 140 V

110 V

Maximum Voltage for Synchronization

Udead

1 .. 60 V

5V

Voltage Treshold for Dead Line/ Dead Bus

Sync.U1>U2<

YES NO

NO

Synchronize to U1> and U2<

Sync.U1<U2>

YES NO

NO

Synchronize to U1< and U2>

Sync.U1<U2<

YES NO

NO

Synchronize to U1< and U2<

UdiffSyn

0.5 .. 40.0 V

2.0 V

Maximum voltage difference, synchronous

174

6MD66 Manual C53000-G1876-C102-3

A.7 Settings

Addr. 0 fdiff

Parameter

Function SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 SYNC function 1 SYNC function 2 SYNC function 3 SYNC function 4 SYNC function 5 SYNC function 6 SYNC function 7 SYNC function 8 P.System Data 1 Device, General Device, General

Setting Options 0.03 .. 2.00 Hz

Default Setting 0.10 Hz

Description Maximum frequency difference, syn.

diff

2 .. 60

10

Maximum angle difference, syn.

UdiffAsyn

0.5 .. 40.0 V

2.0 V

Maximum voltage differnece, asynchronous

f SYNCHRON

10 .. 40 mHz

10 mHz

Frequency diff. treshold Sync/ Async.

T SYNCHRON

0.00 .. 60.00 sec

0.05 sec

Switch Delay for synchronous systems

214 401 402

Rated Frequency T Backlight on DIGSI backplane

50 Hz 60 Hz 1 .. 60 min Disabled Port C Port D

50 Hz 10 min Disabled

Rated Frequency Time Backlight on Serviceport for DIGSI

6MD66 Manual C53000-G1876-C102-3

175

A Appendix

A.8

Information Lists
Indications for IEC 60,870-5-103 are always reported ON / OFF if they are subject to general interrogation for IEC 60,870-5-103. If not, they are reported only as ON. New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to ON / OFF and subjected to general interrogation if the information type is not a spontaneous event (".._Ev"). In columns "Event Log, "Trip Log and "Ground Fault Log the following applies: UPPER CASE ON/OFF: lower case on/off: *: <blank>: definitely set, not allocatable preset, allocatable not preset, allocatable neither preset nor allocatable
Function Type of Information Log Buffers Marked in Oscill. Record Trip (Fault) Log ON/OFF Trip (Fault) Log ON/OFF Event Log ON/OFF Configurable in Matrix IEC 60870-5-103 General Interrogation yes yes yes yes Information Number 20 21 85 86

No.

Description

Chatter Blocking

Binary Output

Function Key

Binary Input

>Light on

Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Cntrl Authority (Command processing) Cntrl Authority (Command processing) Cntrl Authority (Command processing) Cntrl Authority (Command processing)

SP

on off on off on off on off

LED BI

BO

DataStop

IntSP

LED

BO

106

Test mode

IntSP

LED

BO

106

HWTestMod

IntSP

LED

BO

SynchClock

IE_W

LED

BO

Error FMS1

OUT

on off on off on off ON OF F on off ON OF F

LED

BO

Error FMS2

OUT

LED

BO

KeySwitch1

DM

LED

Cntrl Auth

IntSP

LED

101

KeySwitch2

DM

LED

ModeLOCAL

IntSP

LED

101

176

6MD66 Manual C53000-G1876-C102-3

Data Unit 1 1 1 1

Type

LED

A.8 Information Lists

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

ModeREMOTE

Cntrl Authority (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Control Device (Command processing) Thresh.-Switch Protocol (General functions)

IntSP

ON OF F on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED

Q0

BR_D2

BO

240

160

20

Q0

DM

BI

CB

240

160

Q1

BR_D2

BO

240

161

20

Q1

DM

BI

CB

240

161

Q2

BR_D2

BO

240

162

20

Q2

DM

BI

CB

240

162

Q8

BR_D2

BO

240

164

20

Q8

DM

BI

CB

240

164

Q9

BR_D2

BO

240

163

20

Q9

DM

BI

CB

240

163

ReleaseQ0

IntSP

LED

BO

ReleaseQ1

IntSP

LED

BO

ReleaseQ2

IntSP

LED

BO

ReleaseQ8

IntSP

LED

BO

ReleaseQ9

IntSP

LED

BO

ThreshVal1 SysIntErr.

IntSP IntSP

LED BI LED

FK

BO BO

CB

6MD66 Manual C53000-G1876-C102-3

177

General Interrogation yes yes yes yes yes

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A Appendix

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

>Sy1 eff.

SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation)

SP

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED BI

BO

>Sy1 block

SP

LED BI

BO

>Sy1 dirCO

SP

LED BI

BO

>Sy1 Meas

SP

LED BI

BO

>Sy1U1>U2<

SP

LED BI

BO

>Sy1U1<U2>

SP

LED BI

BO

>Sy1U1<U2<

SP

LED BI

BO

Sync. CloseRel

OUT

LED

BO

41

201

Sync. Error

OUT

LED

BO

41

202

Sync. block

OUT

LED

BO

41

204

Sync.MonTimeExc

OUT

LED

BO

41

205

Sync. synchron

OUT

LED

BO

41

206

Sync. U1> U2<

OUT

LED

BO

Sync. U1< U2>

OUT

LED

BO

Sync. U1< U2<

OUT

LED

BO

Sync. Vdiff>

OUT

LED

BO

41

207

Sync. fdiff>

OUT

LED

BO

41

208

178

6MD66 Manual C53000-G1876-C102-3

General Interrogation yes yes yes yes yes yes yes

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A.8 Information Lists

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. diff>

SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2

OUT

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED

BO

41

209

Sync. f1>>

OUT

LED

BO

Sync. f1<<

OUT

LED

BO

Sync. f2>>

OUT

LED

BO

Sync. f2<<

OUT

LED

BO

Sync. U1>>

OUT

LED

BO

Sync. U1<<

OUT

LED

BO

Sync. U2>>

OUT

LED

BO

Sync. U2<<

OUT

LED

BO

>Sy2 eff. >Sy2 block >Sy2 dirCO >Sy2 Meas >Sy2U1>U2< >Sy2U1<U2> >Sy2U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc

SP SP SP SP SP SP SP OUT OUT OUT OUT

LED BI LED BI LED BI LED BI LED BI LED BI LED BI LED LED LED LED

BO BO BO BO BO BO BO BO BO BO BO

6MD66 Manual C53000-G1876-C102-3

179

General Interrogation yes

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A Appendix

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< >Sy3 eff. >Sy3 block >Sy3 dirCO >Sy3 Meas >Sy3U1>U2< >Sy3U1<U2> >Sy3U1<U2< Sync. CloseRel

SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 2 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3

OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT SP SP SP SP SP SP SP OUT

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED BI LED BI LED BI LED BI LED BI LED BI LED BI LED

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

180

6MD66 Manual C53000-G1876-C102-3

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A.8 Information Lists

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< >Sy4 eff. >Sy4 block >Sy4 dirCO >Sy4 Meas >Sy4U1>U2<

SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 3 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4

OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT SP SP SP SP SP

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED BI LED BI LED BI LED BI LED BI

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

6MD66 Manual C53000-G1876-C102-3

181

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A Appendix

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

>Sy4U1<U2> >Sy4U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< >Sy5 eff. >Sy5 block

SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 4 SYNC function 5 SYNC function 5

SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT SP SP

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED BI LED BI LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED BI LED BI

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

182

6MD66 Manual C53000-G1876-C102-3

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A.8 Information Lists

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

>Sy5 dirCO >Sy5 Meas >Sy5U1>U2< >Sy5U1<U2> >Sy5U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>>

SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5 SYNC function 5

SP SP SP SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED BI LED BI LED BI LED BI LED BI LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

6MD66 Manual C53000-G1876-C102-3

183

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A Appendix

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. U2<< >Sy6 eff. >Sy6 block >Sy6 dirCO >Sy6 Meas >Sy6U1>U2< >Sy6U1<U2> >Sy6U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<<

SYNC function 5 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6

OUT SP SP SP SP SP SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED LED BI LED BI LED BI LED BI LED BI LED BI LED BI LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

184

6MD66 Manual C53000-G1876-C102-3

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A.8 Information Lists

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< >Sy7 eff. >Sy7 block >Sy7 dirCO >Sy7 Meas >Sy7U1>U2< >Sy7U1<U2> >Sy7U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff> Sync. fdiff> Sync. diff> Sync. f1>>

SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7

OUT OUT OUT OUT SP SP SP SP SP SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED LED LED LED LED BI LED BI LED BI LED BI LED BI LED BI LED BI LED LED LED LED LED LED LED LED LED LED LED LED

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

6MD66 Manual C53000-G1876-C102-3

185

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A Appendix

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< >Sy8 eff. >Sy8 block >Sy8 dirCO >Sy8 Meas >Sy8U1>U2< >Sy8U1<U2> >Sy8U1<U2< Sync. CloseRel Sync. Error Sync. block Sync.MonTimeExc Sync. synchron Sync. U1> U2< Sync. U1< U2> Sync. U1< U2< Sync. Vdiff>

SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 7 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8

OUT OUT OUT OUT OUT OUT OUT SP SP SP SP SP SP SP OUT OUT OUT OUT OUT OUT OUT OUT OUT

on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off

LED LED LED LED LED LED LED LED BI LED BI LED BI LED BI LED BI LED BI LED BI LED LED LED LED LED LED LED LED LED

BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO BO

186

6MD66 Manual C53000-G1876-C102-3

General Interrogation

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A.8 Information Lists

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

Sync. fdiff> Sync. diff> Sync. f1>> Sync. f1<< Sync. f2>> Sync. f2<< Sync. U1>> Sync. U1<< Sync. U2>> Sync. U2<< >Time Synch

SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 8 Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions)

OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT EM_W

on off on off on off on off on off on off on off on off on off on off

LED LED LED LED LED LED LED LED LED LED LED BI FK

BO BO BO BO BO BO BO BO BO BO BO 135 48 1

16

>DataStop

SP

LED BI

BO

135

54

51

Device OK

OUT

on off on

LED

BO

135

81

55

Reset Device

OUT

LED

BO

56

Initial Start

OUT

on

LED

BO

106

60

Reset LED

OUT_E v OUT

on

LED

BO

106

19

67

Resume

on

LED

BO

68

Clock SyncError

IntSP

on off on off on off

LED

BO

69

DayLightSavTime

OUT

LED

BO

70

Settings Calc.

OUT

LED

BO

105

22

6MD66 Manual C53000-G1876-C102-3

187

General Interrogation yes yes yes

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A Appendix

No.

Description

Function

Marked in Oscill. Record

Trip (Fault) Log ON/OFF

Trip (Fault) Log ON/OFF

71

Settings Check

Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions) Device, General (General functions)

OUT

LED

BO

72

Level-2 change

OUT

on off

LED

BO

73

Local change

OUT

LED

BO

110

Event Lost

OUT_E v OUT on off on off on off on off on off on off on off on off on off on off LED BO

135

130

125

Chatter ON

135

145

147

Error PwrSupply

OUT

LED

BO

177

Fail Battery

OUT

LED

BO

183

Error Board 1

OUT

LED

BO

184

Error Board 2

OUT

LED

BO

185

Error Board 3

OUT

LED

BO

186

Error Board 4

OUT

LED

BO

187

Error Board 5

OUT

LED

BO

188

Error Board 6

OUT

LED

BO

189

Error Board 7

OUT

LED

BO

188

6MD66 Manual C53000-G1876-C102-3

General Interrogation yes

Information Number

Event Log ON/OFF

Type of Information

Log Buffers

Configurable in Matrix

IEC 60870-5-103

Chatter Blocking

Binary Output

Function Key

Binary Input

Data Unit

Type

LED

A.9 Group Alarms

A.9

Group Alarms

No.

Description

No.

Description

6MD66 Manual C53000-G1876-C102-3

189

A Appendix

A.10 Measured Values

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

Control DIGSI

Cntrl Authority (Command processing) MU U_1 (Mea- sured value processing) MU U_1 (Mea- sured value processing) MU U_1 (Mea- sured value processing) MU I_1 (Measured value processing) MU I_1 (Measured value processing) MU I_1 (Measured value processing) -

CFC CFC

CD

Voltage or Current Input U/I

Voltage U

CFC

CD

frequency

CFC

CD

Current Input I

Current I

CFC

CD

frequency

CFC

CD

1P1 Voltage Input U

MU1P_1 (Mea- sured value processing) MU1P_1 (Mea- sured value processing) MU1P_1 (Mea- 106 sured value processing) 134 MU1P_1 (Mea- 106 sured value processing) 134 MU1P_1 (Mea- 106 sured value processing) 134 MU1P_1 (Mea- 106 sured value processing) 134 MU1P_1 (Mea- 134 sured value processing) MU1P_1 (Mea- 134 sured value processing) MU1P_1 (Mea- 134 sured value processing) MU1P_1 (Mea- 134 sured value processing)

1P1 Current Input I

1P1 Voltage U

146

no

CFC

CD

152 146

no no

9 3

1 1 CFC CD

1P1 Current I

152 146

no no

9 3

2 3 CFC CD

1P1 Active Power P

152 146

no no

9 3

3 4 CFC CD

1P1 Reactive Power Q

152 152

no no

9 9

4 5 CFC CD

1P1 Apparent Power S

1P1 Phase Angle Phi

152

no

CFC

CD

1P1 Active Power Factor Cosine Phi

152

no

CFC

CD

1P1 Reactive Power Factor Sine Phi

152

no

CFC

CD

190

6MD66 Manual C53000-G1876-C102-3

A.10 Measured Values

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

1P1 Frequency of U

MU1P_1 (Mea- 134 sured value processing) MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_2 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 MU1P_3 134 134 134 134 134 134 134 134 134 134 134 134 134 134 134 134 134 134

152

no

CFC CFC

CD

1P2 Voltage Input U 1P2 Current Input 1P2 Voltage U 1P2 Current I 1P2 Active Power P 1P2 Reactive Power Q 1P2 Apparent Power S 1P2 Phase Angle Phi 1P2 Active Power Factor Cosine Phi 1P2 Reactive Power Factor Sine Phi 1P2 Frequency of U 1P3 Voltage Input U 1P3 Current Input I 1P3 Voltage U 1P3 Current I 1P3 Active Power P 1P3 Reactive Power Q 1P3 Apparent Power S 1P3 Phase Angle Phi 1P3 Active Power Factor Cosine Phi 1P3 Reactive Power Factor Sine Phi 1P3 Frequency of U 3P1 Voltage Input U1

153 153 153 153 153 153 153 153 153 154 154 154 154 154 154 154 154 154 -

no no no no no no no no no no no no no no no no no no -

9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 -

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 CFC CFC CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD CD CD CFC CFC CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD CD CD

MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 106 sured value processing) 134

3P1 Voltage Input U2

3P1 Voltage Input U3

3P1 Current Input I1

3P1 Current Input I2

3P1 Current Input I3

3P1 Zero Sequence Voltage

151

no

CFC

CD

3P1 Phase to Earth Voltage U1

148

no

CFC

CD

151 148

no no

9 9

2 5 CFC CD

3P1 Phase to Earth Voltage U2

151

no

6MD66 Manual C53000-G1876-C102-3

191

A Appendix

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

3P1 Phase to Earth Voltage U3

MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 106 sured value processing) 134 MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- 134 sured value processing) MU3P_1 (Mea- sured value processing) MU3P_1 (Mea- 106 sured value processing) 134 MUAron_1 (Measured value processing) MUAron_1 (Measured value processing)

148

no

CFC CFC

CD

151 151

no no

9 9

4 5 CFC CD

3P1 Phase to Phase Voltage U12

3P1 Phase to Phase Voltage U23

151

no

CFC

CD

3P1 Phase to Phase Voltage U31

151

no

CFC

CD

3P1 Zero Sequence Current

151

no

CFC

CD

3P1 Phase Current I1

148

no

CFC

CD

151 148

no no

9 9

9 2 CFC CD

3P1 Phase Current I2

151 148

no no

9 9

10 3 CFC CD

3P1 Phase Current I3

151 148

no no

9 9

11 7 CFC CD

3P1 Active Power Three Phase

151 148

no no

9 9

12 8 CFC CD

3P1 Reactive Power Three Phase

151 151

no no

9 9

13 14 CFC CD

3P1 Apparent Power Three Phase

3P1 Phase Angle Three Phase

CFC

CD

3P1 Active Power Factor Three Phase

151

no

15

CFC

CD

3P1 Reactive Power Factor Three Phase

CFC

CD

3P1 Frequency

148

no

CFC

CD

151 -

no -

9 -

16 -

A1 Voltage Input U1

A1 Voltage Input U2

192

6MD66 Manual C53000-G1876-C102-3

A.10 Measured Values

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

A1 Current Input I1

MUAron_1 (Measured value processing) MUAron_1 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) MUAron_1 134 (Measured value processing) SYNC function 1 (Circuit breaker synchronisation) SYNC function 1 (Circuit breaker synchronisation) SYNC function 130 1 (Circuit breaker synchronisation)

A1 Voltage Input I2

A1 Phase to Phase Voltage U12

155

no

CFC CFC

CD

A1 Phase to Phase Voltage U13

155

no

CFC

CD

A1 Phase Current I2

155

no

CFC

CD

A1 Phase Current I3

155

no

CFC

CD

A1 Active Power P

155

no

CFC

CD

A1 Reactive Power Q

155

no

CFC

CD

A1 Apparent Power S

155

no

CFC

CD

A1 Phase Angle Phi

155

no

CFC

CD

A1 Active Power Factor Cosine Phi

155

no

CFC

CD

A1 Reactive Power Factor Sine Phi

155

no

10

CFC

CD

A1 Frequency

155

no

11

CFC

CD

Sync1, Voltage input U1

Sync1, Voltage input U2

Sync. voltage U1

no

CFC

CD

6MD66 Manual C53000-G1876-C102-3

193

A Appendix

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

Sync. voltage U2

SYNC function 130 1 (Circuit breaker synchronisation) SYNC function 130 1 (Circuit breaker synchronisation) SYNC function 130 1 (Circuit breaker synchronisation) SYNC function 130 1 (Circuit breaker synchronisation) SYNC function 130 1 (Circuit breaker synchronisation) SYNC function 130 1 (Circuit breaker synchronisation) SYNC function 2 SYNC function 2 SYNC function 130 2 SYNC function 130 2 SYNC function 130 2 SYNC function 130 2 SYNC function 130 2 SYNC function 130 2 SYNC function 130 2 SYNC function 3 SYNC function 3 SYNC function 130 3 SYNC function 130 3 SYNC function 130 3 SYNC function 130 3 SYNC function 130 3 SYNC function 130 3 SYNC function 130 3

no

CFC CFC

CD

Sync. voltage difference U1,U2

no

CFC

CD

Sync. angle between U1,U2

no

CFC

CD

Sync. frequency f1

no

CFC

CD

Sync. frequency f2

no

CFC

CD

Sync. frequency difference f1, f2

no

CFC

CD

Sync2, Voltage input U1 Sync2, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2 Sync3, Voltage input U1 Sync3, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2

2 2 2 2 2 2 2 3 3 3 3 3 3 3

no no no no no no no no no no no no no no

9 9 9 9 9 9 9 9 9 9 9 9 9 9

1 3 2 6 4 7 5 1 3 2 6 4 7 5 CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD

194

6MD66 Manual C53000-G1876-C102-3

A.10 Measured Values

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

Sync4, Voltage input U1 Sync4, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2 Sync5, Voltage input U1 Sync5, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2 Sync6, Voltage input U1, 1.PE Sync6, Voltage input U1, 2.PE Sync6, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2 Sync7, Voltage input U1, 1.PE

SYNC function 4 SYNC function 4 SYNC function 130 4 SYNC function 130 4 SYNC function 130 4 SYNC function 130 4 SYNC function 130 4 SYNC function 130 4 SYNC function 130 4 SYNC function 5 SYNC function 5 SYNC function 130 5 SYNC function 130 5 SYNC function 130 5 SYNC function 130 5 SYNC function 130 5 SYNC function 130 5 SYNC function 130 5 SYNC function 6 SYNC function 6 SYNC function 6 SYNC function 130 6 SYNC function 130 6 SYNC function 130 6 SYNC function 130 6 SYNC function 130 6 SYNC function 130 6 SYNC function 130 6 SYNC function 7

4 4 4 4 4 4 4 5 5 5 5 5 5 5 6 6 6 6 6 6 6 -

no no no no no no no no no no no no no no no no no no no no no -

9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 -

1 3 2 6 4 7 5 1 3 2 6 4 7 5 1 3 2 6 4 7 5 CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD

CFC

6MD66 Manual C53000-G1876-C102-3

195

A Appendix

No.

Description

Function Information Number

IEC 60870-5-103 Compatibility

Configurable in Matrix Control Display Default Display DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD DD

Data Unit

Position

Type

996

Sync7, Voltage input U1, 2.PE Sync7, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2 Sync8, Voltage input U1, 1.PE Sync8, Voltage input U1, 2.PE Sync8, Voltage input U2 Sync. voltage U1 Sync. voltage U2 Sync. voltage difference U1,U2 Sync. angle between U1,U2 Sync. frequency f1 Sync. frequency f2 Sync. frequency difference f1, f2 Wp Forward Wq Forward Wp Reverse Wq Reverse Pulsed Energy Wp (active) Pulsed Energy Wq (reactive) Transducer 1

SYNC function 7 SYNC function 7 SYNC function 130 7 SYNC function 130 7 SYNC function 130 7 SYNC function 130 7 SYNC function 130 7 SYNC function 130 7 SYNC function 130 7 SYNC function 8 SYNC function 8 SYNC function 8 SYNC function 130 8 SYNC function 130 8 SYNC function 130 8 SYNC function 130 8 SYNC function 130 8 SYNC function 130 8 SYNC function 130 8 Energy Energy Energy Energy Energy Energy 133 133 133 133 133 133

7 7 7 7 7 7 7 8 8 8 8 8 8 8 51 52 53 54 55 56 136

no no no no no no no no no no no no no no no no no no no no no

9 9 9 9 9 9 9 9 9 9 9 9 9 9 205 205 205 205 205 205 9

1 3 2 6 4 7 5 1 3 2 6 4 7 5 1 CFC CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD CD CD CD CD CD CD CD CFC CFC CFC CFC CFC CFC CFC CD CD CD CD CD CD CD

Measurement 134 (Measured value processing) Measurement 134 (Measured value processing)

997

Transducer 2

136

no

CFC CFC

CD

196

6MD66 Manual C53000-G1876-C102-3

Glossary
Control display The display which is displayed on devices with a large (graphic) display after you have pressed the control key is called the control display. It contains the switchgear that can be controlled in the feeder with status display. It is used to perform switching operations. Defining this diagram is part of the configuration. Output indication Output indication fleeting Transient information Command without feedback Command with feedback The left pane of the project window displays the names and symbols of all containers of a project in the form of a folder tree. This area is called the tree view. If an object can contain other objects, it is called a container. The object Folder is an example of such a container. Bit pattern indication is a processing function by means of which items of digital process information applying across several inputs can be detected together in parallel and processed further. The bit pattern length can be specified as 1, 2, 3 or 4 bytes. Bit pattern indication (Bitstring Of x Bit), x designates the length in bits (8, 16, 24 or 32 bits). Continuous Function Chart. CFC is a graphics editor with which a program can be created and configured by using ready-made blocks. Blocks are parts of the user program delimited by their function, their structure or their purpose. Common Format for Transient Data Exchange, format for fault records. The extremely precise official time is determined in Germany by the "PhysikalischTechnischen-Bundesanstalt PTB" in Braunschweig. The atomic clock unit of the PTB transmits this time via the long-wave time-signal transmitter in Mainflingen near Frankfurt/Main. The emitted time signal can be received within a radius of approx. 1,500 km from Frankfurt/Main.

OUT OI_F C_xx CF_xx Tree view

Container

Bit pattern indication

BP_xx

CFC

CFC blocks

COMTRADE DCF77

6MD66 Manual C53000-G1876-C102-3

199

Glossary

Data pane

The right-hand area of the project window displays the contents of the area selected in the navigation window, for example indications, measured values, etc. of the information lists or the function selection for the device configuration. Double-point indication Double point indication, intermediate position 00 Double commands are process outputs which indicate 4 process states at 2 outputs: 2 defined (for example ON/OFF) and 2 undefined states (for example intermediate positions) Double-point indications are items of process information which indicate 4 process states at 2 inputs: 2 defined (for example ON/OFF) and 2 undefined states (for example intermediate positions). Copying, moving and linking function, used at graphics user interfaces. Objects are selected with the mouse, held and moved from one data area to another. ESD protection is the total of all the means and measures used to protect electrostatic sensitive devices. Single commands are process outputs which indicate 2 process states (for example, ON/OFF) at one output. Single indications are items of process information which indicate 2 process states (for example, ON/OFF) at one output. Electromagnetic compatibility (EMC) is the ability of an electrical apparatus to function fault-free in a specified environment without influencing the environment unduly. Single point indication Single-point indication fleeting Transient information, Single point indication Electromagnetic compatibility The conductive earth whose electric potential can be set equal to zero at every point. In the area of ground electrodes the earth can have a potential deviating from zero. The term "Ground reference plane" is often used for this state. Earthing means that a conductive part is to connect via an earthing system to the earth. Without electrical connection to the Earth. Earthing is the total of all means and measured used for earthing.

DP DP_I Double command

Double-point indication

Drag-and-drop

ESD protection

Single command

Single point indication Electromagnetic compatibility SI SI_F EMC Earth

Earthing

Floating Earthing

200

6MD66 Handbuch C53000-G1840-C102-3

Glossary

ExC ExCF ExBPxx

External command without feedback via an ETHERNET connection, device-specific External command with feedback via an ETHERNET connection, device-specific External bit pattern indication via an ETHERNET connection, device-specific Bit pattern indication External double point indication via an ETHERNET connection, device-specific Double-point indication External double point indication via an ETHERNET connection, intermediate position 00, device-specific Double-point indication External single point indication via an ETHERNET connection, device-specific Single point indication External single point indication via an ETHERNET connection, device-specific Transient information, Single point indication External metered value via an ETHERNET connection, device-specific Generic term for all devices assigned to the field level: Protection devices, combination devices, bay controllers. Bay controllers are devices with control and monitoring functions without protective functions. A rapidly intermittent input (for example, due to a relay contact fault) is switched off after a configurable monitoring time and can thus not generate any further signal changes. The function prevents overloading of the system when a fault arises. Within an FMS communication branch the users communicate on the basis of the PROFIBUS FMS protocol via a PROFIBUS FMS network. During the system start-up the state of all the process inputs, of the status and of the fault image is sampled. This information is used to update the system-end process image. The current process state can also be sampled after a data loss by means of a GI. In the Component View, all SIPROTEC 4 devices are assigned to an object of type Device container. This object is a special object of DIGSI Manager. However, since there is no component view in DIGSI Manager, this object only becomes visible in conjunction with STEP 7. Global Positioning System. Satellites with atomic clocks on board orbit the earth twice a day in different parts in approx. 20,000 km. They transmit signals which also contain the GPS universal time. The GPS receiver determines its own position from the signals received. From its position it can derive the running time of a satellite and thus correct the transmitted GPS universal time.

ExDP

ExDP_I

ExSI

ExSI_F

ExMV Field devices

Bay controllers

Chatter blocking

FMS communication branch General interrogation (GI)

Device container

GPS

6MD66 Handbuch C53000-G1840-C102-3

201

Glossary

LV LVU Hierarchy level

Limit value Limit value, user-defined Within a structure with higher-level and lower-level objects a hierarchy level is a container of equivalent objects. The HV project description file contains details of fields which exist in a ModParaproject. The actual field information of each field is memorized in a HV field description file. Within the HV project description file, each field is allocated such a HV field description file by a reference to the file name. All the data is exported once the configuration and parameterisation of PCUs and submodules using ModPara has been completed. This data is split up into several files. One file contains details about the fundamental project structure. This also includes, for example, information detailing which fields exist in this project. This file is called a HV project description file. Internal double point indication Double-point indication Internal double point indication intermediate position 00, Double-point indication Internal single point indication Single point indication Single-point indication fleeting Transient information, Single point indication International Electrotechnical Commission Within an IEC bus a unique IEC address has to be assigned to each SIPROTEC 4 device. A total of 254 IEC addresses are available for each IEC bus. Within an IEC communication branch the users communicate on the basis of the IEC60-870-5-103 protocol via an IEC bus. Inter Relay Communication, IRC, is used for directly exchanging process information between SIPROTEC 4 devices. You require an object of type IRC combination to configure an Inter Relay Communication. Each user of the combination and all the necessary communication parameters are defined in this object. The type and scope of the information exchanged among the users is also stored in this object. IRC combination

HV field description

HV project description

ID ID_S IS IS_F IEC IEC Address

IEC communication branch IRC combination

Inter relay communication Initialization string

An initialization string comprises a range of modem-specific commands. These are transmitted to the modem within the framework of modem initialization. The commands can, for example, force specific settings for the modem. Pulse metered value

PMV

202

6MD66 Handbuch C53000-G1840-C102-3

Glossary

IRIG-B ISO 9001

Time signal code of the Inter-Range Instrumentation Group The ISO 9000 ff range of standards defines measures used to ensure the quality of a product from the development stage to the manufacturing stage. Combination devices are bay devices with protection functions and a control display.

Combination devices Communication reference CR Communication branch Component view

The communication reference describes the type and version of a station in communication by PROFIBUS. A communications branch corresponds to the configuration of 1 to n users which communicate by means of a common bus. In addition to a topological view, SIMATIC Manager offers you a component view. The component view does not offer any overview of the hierarchy of a project. It does, however, provide an overview of all the SIPROTEC 4 devices within a project. The link address gives the address of a V3/V2 device. The right pane of the project window displays the names and icons of objects which represent the contents of a container selected in the tree view. Because they are displayed in the form of a list, this area is called the list view. Masters may send data to other users and request data from other users. DIGSI operates as a master. MLFB is the abbreviation for "MaschinenLesbare FabrikateBezeichnung" (machinereadable product designation). This is the equivalent of an order number. The type and version of a SIPROTEC 4 device are coded in the order number. A modem profile consists of the name of the profile, a modem driver and may also comprise several initialization commands and a user address. You can create several modem profiles for one physical modem. To do so you need to link various initialization commands or user addresses to a modem driver and its properties and save them under different names. Modem profiles for a modem connection are saved in this object type. This object type contains information on both partners of a modem connection, the local modem and the remote modem. Measured value Measured value, user-defined Measured value with time

Link address List view

Master

MLFB Number

Modem profile

Modems Modem connection

MV MVU MVT

6MD66 Handbuch C53000-G1840-C102-3

203

Glossary

MVMV Navigation pane

Metered value which is formed from the measured value The left pane of the project window displays the names and symbols of all containers of a project in the form of a folder tree. Each element of a project structure is called an object in DIGSI. Each object has properties. These might be general properties that are common to several objects. An object can also have specific properties. In Off-line mode a link with the SIPROTEC 4 device is not necessary. You work with data which are stored in files. When working in On-line mode, there is a physical link to a SIPROTEC 4 device which can be implemented in various ways. This link can be implemented as a direct connection, as a modem connection or as a PROFIBUS FMS connection. This object type is used to create the hierarchical structure of a project. General term for all adjustments made to the device. Parameterization jobs are executed by means of DIGSI or, in some cases, directly on the device. The parameter set is the set of all parameters that can be set for a SIPROTEC 4 device. PROcess FIeld BUS, the German process and field bus standard, as specified in the standard EN 50170, Volume 2, PROFIBUS. It defines the functional, electrical, and mechanical properties for a bit-serial field bus. Within a PROFIBUS network a unique PROFIBUS address has to be assigned to each SIPROTEC 4 device. A total of 254 PROFIBUS addresses are available for each PROFIBUS network. Content-wise, a project is the image of a real power supply system. Graphically, a project is represented by a number of objects which are integrated in a hierarchical structure. Physically, a project consists of a series of folders and files containing project data. Devices with a process bus interface allow direct communication with SICAM HV modules. The process bus interface is equipped with an Ethernet module. The buffer battery ensures that specified data areas, flags, timers and counters are retained retentively. Frequent addition and deletion of objects gives rise to memory areas that can no longer be used. By cleaning up projects, you can release these memory areas again. However, a clean up also reassigns the VD addresses. The consequence of that is that all SIPROTEC 4 devices have to be reinitialised.

Object Object properties

Off-line

On-line

Folder Setting parameters

Parameter set

PROFIBUS

PROFIBUS Address

Project

Process bus

Battery

Reorganizing

204

6MD66 Handbuch C53000-G1840-C102-3

Glossary

RIO file RSxxx-interface Protection devices Service port SICAM SAS

Relay data Interchange format by Omicron. Serial interfaces RS232, RS422/485 All devices with a protective function and no control display. Rear serial interface on the devices for connecting DIGSI (for example, via modem). Modularly structured station control system, based on the substation controller SICAM SC and the SICAM WinCC operator control and monitoring system. Substation Controller. Modularly structured substation control system, based on the SIMATIC M7 automation system. The SICAM WinCC operator control and monitoring system displays the state of your network graphically, visualizes alarms, interrupts and indications, archives the network data, offers the possibility of intervening manually in the process and manages the system rights of the individual employee. The registered trademark SIPROTEC is used for devices implemented on system base V4. This object type represents a real SIPROTEC 4 device with all the setting values and process data it contains. This object type represents a variant of an object of type SIPROTEC 4 device. The device data of this variant may well differ from the device data of the source object. However, all variants derived from the source object have the same VD address as the source object. For this reason they always correspond to the same real SIPROTEC 4 device as the source object. Objects of type SIPROTEC 4 variant have a variety of uses, such as documenting different operating states when entering parameter settings of a SIPROTEC 4 device. A slave may only exchange data with a master after being prompted to do so by the master. SIPROTEC 4 devices operate as slaves. Rear serial interface on the devices for connecting to a control system via IEC or PROFIBUS. Up to 16 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination. The individual participating devices are called users. A user address comprises the name of the station, the national code, the area code and the user-specific phone number. User addresses for a modem connection are saved in this object type.

SICAM SC

SICAM WinCC

SIPROTEC

SIPROTEC 4 device

SIPROTEC 4 variant

Slave

SCADA Interface

Users

User address

Phone book

6MD66 Handbuch C53000-G1840-C102-3

205

Glossary

TxTap Topological view

Transformer Tap Indication DIGSI Manager always displays a project in the topological view. This shows the hierarchical structure of a project with all available objects. Transformer tap indication is a processing function on the DI by means of which the steps of the transformer adjustment can be detected together in parallel and processed further. A VD (Virtual Device) includes all communication objects and their properties and states that are used by a communication user through services. A VD can be a physical device, a module of a device or a software module. The VD address is assigned automatically by DIGSI Manager. It exists only once in the entire project and thus serves to identify unambiguously a real SIPROTEC 4 device. The VD address assigned by DIGSI Manager must be transferred to the SIPROTEC 4 device in order to allow communication with DIGSI Device Editor. Up to 16 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination (IRC combination). Which device exchanges which information is defined with the help of the combination matrix. A VFD (Virtual Field Device) includes all communication objects and their properties and states that are used by a communication user through services. A transient information is a brief transient single-point indication at which only the coming of the process signal is detected and processed immediately. Metered values are a processing function with which the total number of discrete similar events (counting pulses) is determined for a period, usually as an integrated value. In power supply companies the electrical work is usually recorded as a metered value (energy purchase/supply, energy transportation). Time stamp is the assignment of the real time to a process event.

Transformer Tap Indication

VD

VD address

Combination matrix

VFD

Transient information Metered value

Time stamp

206

6MD66 Handbuch C53000-G1840-C102-3

Literature
/1/ /2/ /3/ /4/ /5/ /6/ SIPROTEC 4 System Description; E50417-H1176-C151-A2 SIPROTEC DIGSI, Start UP; E50417-G1176-C152-A2 DIGSI CFC, Manual; E50417-H1176-C098-A4 SIPROTEC SIGRA 4, Manual; E50417-H1176-C070-A2 PROFIBUS DP Communication profile (available on DIGSI CD and on the Internet); C53000L1840B00103 PROFIBUS DP Bus mapping 6MD663 / 6MD664 (available on DIGSI CD and on the Internet); C53000L1840B01103

6MD66 Manual C53000-G1876-C102-3

197

Literature

198

6MD66 Handbuch C53000-G1840-C102-3

Index
A
Acknowledgement of commands 27 Analogue inputs and outputs 122 Angle adjustment 60 Assignment of the D-subminiature connector 108 Auxiliary functions 141 Auxiliary voltage 88, 123 Dead Bus 61 Dead bus connection 51 Dead Line 61 Dead line connection 51 Declaration of Conformity i Dimensions: Cabinet mounting 142 Dimensions: D-subminiature connector Dongle cable 145 Dimensions: Detached operator panel 144 Dimensions: Panel flush mounting 142 Dimensions: Surface-mounted housing with detached operator panel 143 Dimensions: Surface-mounted housing without operator panel 143 Disassembly of the Device 90 Display lighting 12, 15 Dongle Cable 105 Double operation locking 26

B
Binary input switching threshold 89 Binary inputs 97, 123 Binary outputs 123 Breaker Control 17

C
CFC 8 Chatter Blocking 13 Checking: Binary Inputs and Outputs 115 Checking: command job 20 Checking: Switching Configured Operating Devices 118 Circuit breaker closing time 60 Climatic stress tests 129 Clock synchronisation 13 Clock Time Synchronisation 141 Command types 19 Commissioning aids 141 Connection plug connector tests 110 Construction 130 CPU jumper settings 93, 97, 98 Cubicle Mounting 102 Current inputs 2, 122

E
Electrical Tests 127 EMC 108 EMC Tests for Immunity (Type Tests) 128 EMC Tests For Noise Emission (type test) 129 External minute pulse 13

F
Feeder voltage 51 Final Preparation of the Device 119 Frequency difference 61 Frequency range 61 Function Modules 135 Functional scope 10, 10

H
Humidity 130 Hysteresis 62

D
DC voltage 123 De-interlockings 26

6MD66 Manual C53000-G1876-C102-3

207

Index

Immunity 108 Input/output modules Insulation Test 128 Inter relay communication 4, 8, 101 Inter relay communication interface 125 Interfaces serial 89, 100 Interlocking checks 7 Interruption in Communication 16 IRC operating mode of the interface 69, 70

Operating measured values 30, 138 Operating metered values 43 Operator Interface 124 Ordering Information 148 Output relays binary outputs 124

P
Password 10 Power metering 43 Power supply 123 PROFIBUS 89, 100, 100, 108 PROFIBUS DP 6 Pulse metered value 43

J
Jumpers 88, 88, 89, 89, 89, 94, 95, 97, 100

K
Keyswitch 7

Q
Qualified Personnel ii

L
Life contact 93 Limit measured values 30 Limit range behaviour 122, 122, 123, 123, 123 Limits for CFC blocks 136 Limits for User Defined Functions 136 Line screen 108 Lower voltage limit Vmin 60

R
Rack mounting 102 Rated system frequency 11 Rated transformer current 37, 38, 40, 41 Rated transformer voltage 36, 38, 40, 41 Reassembly of Device 101 Reference voltage 51 Reference voltages 50

M
Measured value processing 7 Measured values user-defined 30 Measurement monophase 38 Measurement inputs, binary outputs 2 Measuring transducer 3, 10, 46 Measuring transducer inputs 122 Measuring transducer packets 43 Mechanical Stress Tests 129 Metered values precision 43 Module arrangement 6MD664 92 Module arrangement of 6MD663 92 Monitoring functions 8 Monitoring of feedback information 27

S
Secondary rated transformer voltage V1 60 Secondary rated transformer voltage V2 60 Sequence in the command path 20 Service / modem interface 125 Service Conditions 130 Service interface 90 Set points 8 Specifications 127 Standard Interlocking 22 Subminiature socket 108 Subnetwork 5, 61 Summertime 14 Switch delay time 61 Switchgear control 132 Switchgear interlocking 53 Switching authority 7, 10, 24 Switching direction check 26 Switching Mode 25 Switching mode 7, 10 Switching sequence 53

6MD66 Manual C53000-G1876-C102-3

208

Index

Switching sequences 8 Synchrocheck 5, 52 Synchronisation 2, 7 Synchronisation conditions 50 Synchronisation check Duration 61 Synchronization 10 System interface 90, 126 System interlocking 22

T
Temperatures 129 Termination resistors 89, 100, 100 Test Mode 13, 113 Test: System Interface 113 Threshold switch 49, 49 Threshold value 60 Time Stamping 141 Time synchronisation 8 Time Synchronization Interface 108, 127 Transmission Block 113 Transmission thresholds 49

U
Upper voltage limit Vmax 60

V
Vibration and Shock Stress During Operation 129 Vibration and Shock Stress During Transport 129 Voltage application 52, 53 Voltage difference 61 Voltage inputs 2, 122

Z
Zone Control 22

6MD66 Manual C53000-G1876-C102-3

209

Index

6MD66 Manual C53000-G1876-C102-3

210

You might also like