Installation and Commissioning Manual Line Differential Protection Terminal Rel551 2.5
Installation and Commissioning Manual Line Differential Protection Terminal Rel551 2.5
Installation and Commissioning Manual Line Differential Protection Terminal Rel551 2.5
COPYRIGHT WE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENT THAT A PATENT IS ISSUED AND A DIFFERENT COMMERCIAL PROPRIETARY RIGHT IS REGISTERED. IMPROPER USE, IN PARTICULAR REPRODUCTION AND DISSEMINATION TO THIRD PARTIES, IS NOT PERMITTED. THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, IN CASE ANY ERRORS ARE DETECTED, THE READER IS KINDLY REQUESTED TO NOTIFY THE MANUFACTURER AT THE ADDRESS BELOW. THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FOR THE CONCEPT OR PRODUCT DESCRIPTION AND IS NOT TO BE DEEMED TO BE A STATEMENT OF GUARANTEED PROPERTIES. IN THE INTERESTS OF OUR CUSTOMERS, WE CONSTANTLY SEEK TO ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST TECHNOLOGICAL STANDARDS. AS A RESULT, IT IS POSSIBLE THAT THERE MAY BE SOME DIFFERENCES BETWEEN THE HW/SW PRODUCT AND THIS INFORMATION PRODUCT. Manufacturer:
ABB Power Technologies AB Substation Automation Products SE-721 59 Vsters Sweden Telephone: +46 (0) 21 34 20 00 Facsimile: +46 (0) 21 14 69 18 www.abb.com/substationautomation
Contents
Chapter
Chapter 1
Page
Introduction ..................................................................... 1
Introduction to the installation and commissioning manual ................. 2 About the complete set of manuals for a terminal .......................... 2 About the installation and commissioning manual.......................... 2 Intended audience .......................................................................... 3 General...................................................................................... 3 Requirements ............................................................................ 3 Related documents......................................................................... 4 Revision notes ................................................................................ 4 Acronyms and abbreviations .......................................................... 4
Chapter 2
Safety information......................................................... 13
Warning signs .................................................................................... 14 Caution signs ..................................................................................... 16 Note signs.......................................................................................... 17
Chapter 3
Overview ........................................................................ 19
Commissioning and installation overview .......................................... 20
Chapter 4
Chapter 5
Contents
Installing the serial communication cable for RS485 SPA/IEC .......... 37 RS485 serial communication module ........................................... 37 Informative excerpt from EIA Standard RS-485 ........................... 39 Data on RS485 serial communication module cable .................... 41 Installing the 56/64 kbit data communication cables.......................... 42
Chapter 6
Chapter 7
Chapter 8
Chapter 9
Contents
Overview............................................................................................ 82 Entering settings through the local HMI............................................. 83 Configuring the setting restriction of HMI function ............................. 84 Activating the restriction of setting ..................................................... 85 Local HMI ..................................................................................... 85 Serial communication, change of active group ............................. 85 Serial communication, setting....................................................... 85 Downloading settings and configuration from a PC........................... 86 Establishing front port communication.......................................... 86 Establishing rear port communication........................................... 86 Using the SPA/IEC rear port.................................................... 86 Using LON rear port ................................................................ 87 Downloading the configuration and setting files ........................... 87
Contents
Releasing the function(s) to be tested ........................................ 105 Checking the disturbance report settings ................................... 105 Identifying the function to test in the technical reference manual ........................................... 106 Autorecloser (AR) ............................................................................ 107 Preparing .................................................................................... 108 Checking the AR functionality..................................................... 109 Checking the reclosing condition ................................................ 109 Checking the Inhibit signal..................................................... 110 Checking the closing onto a fault........................................... 110 Checking the breaker not ready ............................................ 110 Checking the synchro-check condition (for three-phase reclosing cycle) ............................ 110 Checking the operation Stand-by and Off ............................. 110 Testing the multi-breaker arrangement....................................... 111 Completing the test..................................................................... 111 Breaker failure protection (BFP) ...................................................... 112 Verifying the settings .................................................................. 112 Verifying the retrip setting ........................................................... 112 Checking the retrip function with retrip set to off.................... 112 Checking the retrip function with current check ..................... 112 Checking the retrip function without current check ................ 113 Completing the test..................................................................... 113 Broken conductor check (BRC) ....................................................... 114 Measuring the operate and time limit of set values .................... 114 Communication channel test logic (CCHT)...................................... 115 Testing the logic.......................................................................... 115 Current circuit supervision (CTSU) .................................................. 116 Time delayed residual overcurrent protection (TEF)........................ 117 Checking the operate values of the current measuring elements ............................................... 117 Disturbance recorder (DR)............................................................... 120 Event counter (CN) .......................................................................... 121 Event function (EV) .......................................................................... 122 Event recorder (ER) ......................................................................... 123 Instantaneous non-directional overcurrent protection (IOC) ............ 124 Measuring the operate limit of set values ................................... 124 Phase overcurrent protection ................................................ 124 Residual overcurrent protection (non-dir.) ............................. 124 Completing the test..................................................................... 124 Line differential protection, phase segregated (DIFL)...................... 125 Testing the line differential protection ......................................... 127 Testing the charging current compensation................................ 129 Completing the test..................................................................... 130 Supervision of AC input quantities (DA)........................................... 131 Verifying the settings .................................................................. 131 Completing the test..................................................................... 131 Supervision of mA input quantities (MI) ........................................... 132 Verifying the settings .................................................................. 132 Completing the test..................................................................... 133 Multiple command (CM)................................................................... 134 Overload supervision (OVLD) .......................................................... 135 Measuring the operate and time limit of set values .................... 135
Contents
Pole discordance protection (PD) .................................................... 137 Pulse counter logic for metering (PC).............................................. 138 Setting lockout (HMI) ....................................................................... 139 Verifying the settings .................................................................. 139 Completing the test..................................................................... 139 Four parameter setting groups (GRP) ............................................. 140 Verifying the settings .................................................................. 140 Single command (CD) ..................................................................... 141 Thermal phase overload protection (THOL) .................................... 142 Measuring the operate and time limit of set values .................... 142 Testing the protection without external temperature compensation (NonComp) ................................ 142 Definite time non-directional overcurrent protection (TOC) ............ 144 Measuring the operate limit of set values ................................... 144 Time delayed phase overcurrent ........................................... 144 Time delayed residual overcurrent (non-dir.)......................... 144 Completing the test..................................................................... 145 Tripping logic (TR) ........................................................................... 146 3ph operating mode.................................................................... 146 1ph/3ph operating mode............................................................. 146 1ph/2ph/3ph operating mode...................................................... 147 Completing the test..................................................................... 148 Two step time delayed non-directional phase overcurrent protection (TOC2)......................................................... 149 Measuring the operate and time limit for set values ................... 149 Measuring the operate limit of the low step overcurrent protection ............................................................................ 149 Measuring the definite time delay of the low set stage.......... 149 Measuring the inverse time delay of the low set stage.......... 149 Measuring the operate limit of the high step overcurrent protection ............................................................................ 150 Completing the test..................................................................... 150 Sudden change in phase current protection (SCC1) ...................... 151 Measuring the operate limit of set values ................................... 151 Sudden change in current in any phase ................................ 151 Dependability test .................................................................. 151 Time delay test ...................................................................... 151 Completing the test................................................................ 152 Sudden change in residual current protection (SCRC) ................... 153 Measuring the operate limit of set values ................................... 153 Sudden change in residual current........................................ 153 Dependability test .................................................................. 153 Time delay test ...................................................................... 153 Completing the test................................................................ 154 Undercurrent protection (UCP) ........................................................ 155 Measuring the operate limit of set values ................................... 155 Undercurrent in any phase .................................................... 155 Dependbility test .................................................................... 155 Time delay test ...................................................................... 155 Completing the test................................................................ 155 Phase overcurrent protection (OCP) ............................................... 156 Measuring the operate limit of set values ................................... 156 Overcurrent in any phase ...................................................... 156
Contents
Dependability test .................................................................. 156 Time delay test ...................................................................... 156 Completing the test................................................................ 156 Residual overcurrent protection (ROCP) ......................................... 157 Measuring the operate limit of set values ................................... 157 Residual overcurrent ............................................................. 157 Dependability test .................................................................. 157 Time delay test ...................................................................... 157 Completing the test................................................................ 158
Chapter 1 Introduction
Chapter 1 Introduction
About this chapter This chapter introduces the user to the manual.
Chapter 1 Introduction
1.1
Application manual
Operators manual
en01000044.vsd
The Application Manual (AM) contains descriptions, such as application and functionality descriptions as well as setting calculation examples sorted per function. The application manual should be used when designing and engineering the protection terminal to find out when and for what a typical protection function could be used. The manual should also be used when calculating settings and creating configurations. The Technical Reference Manual (TRM) contains technical descriptions, such as function blocks, logic diagrams, input and output signals, setting parameter tables and technical data sorted per function. The technical reference manual should be used as a technical reference during the engineering phase, installation and commissioning phase, and during the normal service phase. The Operator's Manual (OM) contains instructions on how to operate the protection terminal during normal service (after commissioning and before periodic maintenance tests). The operator's manual can be used to find out how to handle disturbances or how to view calculated and measured network data in order to determine the cause of a fault. The Installation and Commissioning Manual (ICM) contains instructions on how to install and commission the protection terminal. The manual can also be used as a reference if a periodic test is performed. The manual covers procedures for mechanical and electrical installation, energizing and checking of external circuitry, setting and configuration as well as verifying settings and performing a directional test. The chapters and sections are organized in the chronological order (indicated by chapter/section numbers) in which the protection terminal should be installed and commissioned.
1.2
Chapter 1 Introduction
The chapter Overview gives an overview over the major tasks when installing and commissioning the terminal. The chapter Unpacking and checking the terminal contains instructions on how to receive the terminal. The chapter Installing the terminal contains instructions on how to install the terminal. The chapter Checking the external circuitry contains instructions on how to check that the terminal is properly connected to the protection system. The chapter Energising the terminal contains instructions on how to start-up the terminal. The chapter Setting and configuring the terminal contains instructions on how to download settings and configuration to the terminal. The chapter Establishing connection and verifying the SPA/IEC-communication contains instructions on how to enter SPA/IEC settings and verifying the SPA/IEC communication. The chapter Establishing connection and verifying the LON communication contains a reference to another document. The chapter Verifying settings by secondary injection contains instructions on how to verify that each included function operates correctly according to the set values. The chapter Primary injection testing describes a test with primary current through the protected zone. The chapter Testing the protection system contains instructions on how to test that the terminal is in contact with the primary system. The chapter Fault tracing and repair contains instructions on how to fault trace.
1.3
1.3.1
Intended audience
General The installation and commissioning manual is addressing the installation, commissioning and maintenance personnel responsible for taking the protection into normal service and out of service. Requirements The installation and commissioning personnel must have a basic knowledge in handling electronic equipment. The commissioning and maintenance personnel must be well experienced in using protection equipment, test equipment, protection functions and the configured functional logics in the protection.
1.3.2
Chapter 1 Introduction
1.4
Related documents
Documents related to REL 551*2.5 Operator's manual Installation and commissioning manual Technical reference manual Application manual Buyer's guide Identity number 1MRK 506 150-UEN 1MRK 506 151-UEN 1MRK 506 152-UEN 1MRK 506 153-UEN 1MRK 506 179-BEN
1.5
Revision notes
Revision C Description Minor updates in chapter: Configuring the 56/64 kbit data communication modules / Configuring the fibre optical modem Verifying settings by secondary injection / Line differential protection, phase segregated (DIFL)
1.6
AC ACrv2 A/D converter ADBS AIM ANSI ASCT ASD AWG BIM BLKDEL BOM BR BS BSR BST BT
Alternating Current Setting A for programmable overvoltage IDMT curve, step 2 Analog to Digital converter Amplitude dead-band supervision Analog input module American National Standards Institute Auxiliary summation current transformer Adaptive Signal Detection American Wire Gauge standard Binary input module Block of delayed fault clearing Binary output module Binary transfer receive over LDCM British Standard Binary Signal Receive (SMT) over LDCM Binary Signal Transmit (SMT) over LDCM Binary Transfer Transmit over LDCM
Chapter 1 Introduction
C34.97 CAN CAP 531 CB CBM CCITT Controller Area Network. ISO standard (ISO 11898) for serial communication Configuration and programming tool Circuit breaker Combined backplane module Consultative Committee for International Telegraph and Telephony. A United Nations sponsored standards body within the International Telecommunications Union. Current circuit supervision Controller area network emulation module Communication interface module Combined Mega Pulses Per Second Close-Open cycle Way of transmitting G.703 over a balanced line. Involves two twisted pairs making it possible to transmit information in both directions Way of transmitting G.703 over a balanced line. Involves four twisted pairs of with two are used for transmitting data in both directions, and two pairs for transmitting clock signals Central Processor Unit Carrier Receive Cyclic Redundancy Check POR carrier for WEI logic Carrier send Current transformer Input to be used for transmit CT group 1line L1 in signal matrix tool Signal name for CT-group 1line L1 in signal matrix tool Input to be used for transmission of CT-group 2 line L3 to remote end Input to be used for transmission of CT-group 2 neutral N to remote end.
Capacitive voltage transformer Delayed auto-reclosing dead band Dead bus dead line Dead bus live line Direct Current Rail conforming to DIN standard Small switch mounted on a printed circuit board
Chapter 1 Introduction
DLLB DSP DTT EHV network EIA EMC ENGV1 ENMULT EMI ESD FOX 20 FOX 512/515 FOX 6Plus FPGA FRRATED FSMPL G.703
Dead line live bus Digital signal processor Direct transfer trip scheme Extra high voltage network Electronic Industries Association Electro magnetic compatibility Enable execution of step one Current multiplier used when THOL is used for two or more lines Electro magnetic interference Electrostatic discharge Modular 20 channel telecommunication system for speech, data and protection signals Access multiplexer Compact, time-division multiplexer for the transmission of up to seven duplex channels of digital data over optical fibers Field Programmable Gate Array Rated system frequency Physical channel number for frequency calculation Electrical and functional description for digital lines used by local telephone companies. Can be transported over balanced and unbalanced lines Standard for pulse code modulation of analog signals on digital lines Communication interface module with carrier of GPS receiver module General interrogation command Gas insulated switchgear. Generic Object Orientated Substation Event Global positioning system GOOSE Receive (interlock) High level data link control, protocol based on the HDLC standard Fibre connector receiver Human-Machine Interface High-Speed Auto-Reclosing High voltage High voltage direct current Absolute hysteresis for over and under frequency operation Absolute hysteresis for signal magnitude in percentage of Ubase Relative hysteresis for signal magnitude
G.711 GCM GI GIS GOOSE GPS GR HDLC protocol HFBR connector type HMI HSAR HV HVDC HysAbsFreq HysAbsMagn HysRelMagn
Chapter 1 Introduction
HystAbs HystRel IBIAS IDBS IDMT IDMTtmin IdMin IDNSMAG Idunre ICHARGE IEC IEC 186A IEC 60044-6 IEC 60870-5-103 IEEE IEEE 802.12 IEEE P1386.1
Overexcitation level of absolute hysteresis as a percentage Overexcitation level of relative hysteresis as a percentage Magnitude of the bias current common to L1, L2 and L3 Integrating dead-band supervision Minimum inverse delay time Inverse delay minimum time in seconds Operational restrictive characteristic, section 1 sensitivity, multiple Ibase Magnitude of negative sequence differential current Unrestrained prot. limit multiple of winding1 rated current Amount of compensated charging current International Electrical Committee
IEC Standard, Instrument transformers Part 6: Requirements for protective current transformers for transient performance Communication standard for protective equipment. A serial master/slave protocol for point-to-point communication Institute of Electrical and Electronics Engineers A network technology standard that provides 100 Mbits/s on twisted-pair or optical fiber cable PCI Mezzanine Card (PMC) standard for local bus modules. References the CMC (IEEE P1386, also known as Common Mezzanine Card) standard for the mechanics and the PCI specifications from the PCI SIG (Special Interest Group) for the electrical Electro magnetic force Intelligent electronic device Intelligent gas insulated switchgear Real current component, phase L1 Imaginary current component, phase L1 Negative sequence current must be higher than this to be used Present magnitude of residual current Magnitude of instantaneous value Instance name in signal matrix tool Binary Input/Output module Imaginary part of positive sequence current Real component of positve sequence current Enclosure protects against solid foreign objects 12.5mm in diameter and larger but no protection against ingression of liquid according to IEC60529. Equivalent to NEMA type 1.
EMF IED I-GIS IL1RE IL1IM IminNegSeq INAMPL INSTMAGN INSTNAME IOM IPOSIM IPOSRE IP 20
Chapter 1 Introduction
IP 40
Enclosure protects against solid foreign objects 1.0mm in diameter or larger but no protection against ingression of liquid according to IEC60529. Degrees of protection provided by enclosures (IP code) according to IEC 60529. Dust protected. Protected against splashing water. Equivalent to NEMA type 12. Block of the function at high phase current in percentage of base Block of current reversal function Activation of current reversal logic International Telecommunications Union Time multiplier in IDMT mode Time multiplier for IEEE inverse type curve Local area network
IP 54
Ip>block IRVBLK IRV ITU k2 kForIEEE LAN LIB 520 LCD LDCM LDD LED LNT LON MAGN MCB MCM MIM MIP MPPS MPM MV MVB MVsubEna NegSeqROA NSANGLE NUMSTEP NX OCO cycle PCI
Liquid chrystal display Line differential communication module Local detection device Light emitting diode LON network tool Local operating network Magnitude of deadband value Miniature circuit breaker Mezzanine carrier module Milliampere Input Module
Main processing module Medium voltage Multifunction vehicle bus. Standardized serial bus originally developed for use in trains Enable substitution Operate angle for internal/external negative sequence fault discriminator. Angle between local and remote negative sequence currents Number of steps that shall be activated
Chapter 1 Introduction
PCM PISA PLD PMC POTT PPS Process bus PSM PST PT ratio PUTT R1A R1B RADSS RASC RCA REVAL RFPP RFPE RISC RMS value RS422 RS485 RS530 RTU RTC SA SC SCS SLM SMA connector SMS SPA
Pulse code modulation Process interface for sensors & actuators Programmable Logic Device
Permissive overreach transfer trip Precise Positioning System Bus or LAN used at the process level, that is, in near proximity to the measured and/or controlled components Power supply module Parameter setting tool Potential transformer or voltage transformer ratio Permissive underreach transfer trip Source resistance A (near end) Source resistance B (far end) Resource Allocation Decision Support System Synchrocheck relay, from COMBIFLEX range. Functionality characteristic angle Evaluation software Resistance of phase-to-phase faults Resistance of phase-to-earth faults Reduced instruction set computer Root mean square value A balanced serial interface for the transmission of digital data in point-to-point connections Serial link according to EIA standard RS485 A generic connector specification that can be used to support RS422, V.35 and X.21 and others Remote Terminal Unit Real Time Clock Substation Automation Switch or push-button to close Station control system Serial communication module. Used for SPA/LON/IEC communication Sub Miniature version A connector Station monitoring system Strmberg Protection Acquisition, a serial master/slave protocol for point-to-point communication
Chapter 1 Introduction
SPGGIO SRY ST3UO STL1 ST SVC t1 1Ph t1 3PhHS tAutoContWait tCBCLosedMin tExtended t1 THL THOL tInhibit tPulse TP tReporting tRestore TCS TNC connector TPZ, TPY, TPX, TPS tReclaim TRIPENHA TRIPRES TRL1 truck tSync TTRIP UBase U/I-PISA UNom UPS UTC
Single Point Gxxxxx Generic Input/Output Switch for CB ready condition RMS voltage at neutral point Start signal from phase L1 Switch or push-button to trip Static VAr compensation Open time for shot 1, single phase Open time for shot 1, high speed reclosing three phase Wait period after close command before next shot Minimum time that the circuit breaker must be closed before new sequence is permitted Open time extended by this value if Extended t1 is true Thermal Overload Line cable Thermal overload Reset reclosing time for inhibit Pulse length for single command outputs Logic Pulse Timer Cycle time for reporting of counter value Restore time delay Trip circuit supervision Type of bayonet connector, like BNC connector Current transformer class according to IEC Duration of the reclaim time Trip by enhanced restrained differential protection Trip by restrained differential protection Trip signal from phase 1 Isolator with wheeled mechanism Maximum wait time for synchrocheck OK Estimated time to trip (in minutes) Base setting for phase-phase voltage in kilovolts Process interface components that delivers measured voltage and current values Nominal voltage in % of UBase for voltage based timer Measured signal magnitude (voltage protection) Coordinated Universal Time. A coordinated time scale, maintained by the Bureau International des Poids et Mesures (BIPM), which forms the basis of a coordinated dissemination of standard frequencies and time signals
10
Chapter 1 Introduction
V.36 VDC WEI VT VTSZ X1A X1B X1L X.21 XLeak XOL ZCOM-CACC ZCOM-CR ZCOM-TRIP ZCOM-LCG
Same as RS449. A generic connector specification that can be used to support RS422 and others Volts Direct Current Week-end infeed logic Voltage transformer Block of trip from weak-end infeed logic by an open breaker Source reactance A (near end) Source reactance B (far end) Positive sequence line reactance A digital signalling interface primarily used for telecom equipment Winding reactance in primary ohms Zero sequence line reactance Forward overreaching zone used in the communication scheme Carrier Receive Signal Trip from the communication scheme Alarm Signal LIne-check Guard
11
Chapter 1 Introduction
12
13
Warning signs
Warning signs
Warning!
Strictly follow the company and country safety regulations. Working in a high voltage environment requires serious approach to avoid human injuries and damage to equipment.
Warning!
Do not touch circuitry during operation. Potentially lethal voltages and currents are present.
Warning!
Always avoid to touch the circuitry when the cover is removed. The product contains electronic circuitries which can be damaged if exposed to static electricity (ESD). The electronic circuitries also contain high voltage which is lethal to humans.
Warning!
Always use suitable isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present.
Prohibition!
Never connect or disconnect a wire and/or a connector to or from a IED during normal operation. Hazardous voltages and currents are present that may be lethal. Operation may be disrupted and IED and measuring circuitry may be damaged.
Warning!
Always connect the IED to protective earth, regardless of the operating conditions. This also applies to special occasions such as bench testing, demonstrations and off-site configuration. Operating the IED without proper earthing may damage both IED and measuring circuitry and may cause injuries in case of an accident.
Warning!
Never disconnect a secondary connection of current transformer circuit without short-circuiting the transformers secondary winding. Operating a current transformer with the secondary winding open will cause a massive potential build-up that may damage the transformer and may cause injuries to humans.
14
Warning signs
Warning!
Never remove any screw from a powered IED or from a IED connected to powered circuitry. Potentially lethal voltages and currents are present.
15
Caution signs
Caution signs
Caution!
Always transport modules using certified conductive bags. Always handle modules using a conductive wrist strap connected to protective ground and on a suitable antistatic surface. Electrostatic discharge (ESD) may cause damage to the module.
Caution!
Do not connect live wires to the IED. Internal circuitry may be damaged
Caution!
Always use a conductive wrist strap connected to protective ground when replacing modules. Electrostatic discharge (ESD) may damage the module and IED circuitry.
Caution!
Take care to avoid electrical shock if accessing wiring and connection IEDs when installing and commissioning.
Caution!
Changing the active setting group will inevitably change the IEDs operation. Be careful and check regulations before making the change.
16
Note signs
Note signs
Note!
The protection assembly is designed for a maximum continuous current of four times rated value.
Note!
Activating the setting lockout function, which prevents unauthorised changes of the settings, without proper configuration may seriously affect the IEDs operation.
17
Note signs
18
Chapter 3 Overview
Chapter 3 Overview
About this chapter This chapter introduces the user to the installation and commissioning tasks.
19
Chapter 3 Overview
20
21
The user is requested to check that all software functions are included according to the delivery documents after the terminal has been energised.
4. Check for transport damages.
In case of transport damage appropriate action must be taken against the latest carrier and the nearest ABB office or representative should be informed. ABB should be notified immediately if there are any discrepancies in relation to the delivery documents. Store the terminal in the original transport casing in a dry and dust free place, if the terminal is not to be installed or commissioned immediately. Observe the environmental requirements stated in the technical data.
22
23
Overview
Overview
The mechanical and electrical environmental conditions at the installation site must be within permissible range according to the technical data of the terminal. Dusty, damp places, places liable to rapid temperature variations, powerful vibrations and shocks, surge voltages of high amplitude and fast rise time, strong induced magnetic fields or similar extreme conditions should be avoided. Sufficient space must be available in front of and at rear of the terminal to allow access for maintenance and future modifications. Flush mounted terminals should be mounted so that terminal modules can be added and replaced without excessive demounting.
24
25
2.1
(98000037)
Figure 1:
26
Procedure
1. Carefully fasten the mounting angles to the sides of the terminal.
2.2
2 1
xx03000028.vsd
PosNo 1 2 3
Figure 2: Procedure
1.
Side-by-side assembly
27
2.
2.3
28
2 1
5 6 3 4
xx00000129.eps
PosNo 1 2 3 4 5 6
Description Sealing strip Distance frame (only for semi-flush) Sealing strip for distance frame (only for semi-flush) Side holder Groove Locking screw (TORX T10)
Figure 3:
Note!
Flush or semi-flush mount cannot be used for side-by-side mounted terminals when IP 54 must be fulfilled.
29
Procedure
1. Cut the sealing strip in appropriate lengths.
The strip is delivered with the mounting kit. In the semi-flush mounting kit two strips are delivered, one for the terminal and one self-adhering for the distance frame. The length of the strip is enough for the largest available terminal. Cut the strip into four, one part for each side of the terminal. When cutting, make sure no gaps will be present between each part. Preferably, seal the joints at the corners (posNo 1). Repeat the procedure for the self-adhering strip which are to be adhered to the distance frame.
2. Dispose the strip remains.
Thread a side holder into the groove (posNo 5) at the back end of the terminal. Insert and lightly fasten the locking screw (posNo 6). Next, thread a side holder on the other side of the terminal, and lightly fasten its locking screw. Repeat this with the remaining two side holders.
8. Lock the terminal to the cut-out.
Firmly tighten the locking screws. It is important that all four side holder locking screws are tightened the same in order to maintain a good and even seal in IP 54 environments.
2.4
Mounting on a wall
The mounting bars are prepared for adding DIN-rails or equivalent above and below the mounted terminal. If used, make sure all necessary parts such as rails and terminal blocks are available before starting. Make sure the wall mounting kit is available.
30
xx00000130.eps
PosNo 1 2
Figure 4: 2.4.1
Wall mounting
See the Technical reference manual for measurements. Depending on the wall different preparations may be needed, like drilling and inserting plastic or expander plugs (concrete/plasterboard walls) or threading (metal sheet wall).
2. 3. Mount the DIN-rail(s) on the mounting bars. Mount the terminal blocks on the DIN-rail(s).
31
4.
2.4.2
See figure 5.
xx99000287
Figure 5:
View from above over a wall mounted terminal that is prepared for electrical connection.
32
Note!
Screened and twisted pair cables are a requirement for galvanic communications in application with 56/64 kbit/s. The screen must be earthed according to figures in the sections Making the screen connection and Installing the communication cables.
3.1
3.2
Use a solid or stranded conductor with a cross section area between 0.5-2.5 mm2 (AWG20-14). Use a ferrule with plastic collar to connect two conductors, cross section area between 0.5-1.5 mm2 (AWG20-16).
33
X20 X20:5
(98000035)
Figure 6:
Where:
is ferrule
Figure 7:
34
If the terminal is equipped with a test-switch of type RTXP 24 COMBIFLEX wires with 20 A sockets must be used to connect the VT circuits and the auxiliary power.
3.3
3.4
Lc Rx
IED
Cc
Lc Tx
External Equipment
Tx Sc
Rx Sc
en03000087.vsd
35
Caution!
The fibre optical cables are very sensitive to handling. Do not bend too sharply. The minimum curvature radius is 15 cm for the plastic fibre cables and 25 cm for the glass fibre cables. If cable straps are used to fix the cables, apply with loose fit. Always hold the connector, never the cable, when connecting or disconnecting optical fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre attenuation thus making communication impossible.
Note!
Please, strictly follow the instructions from the manufacturer for each type of optical cables/connectors.
36
5.1
A B 1) 1) 1) GND
en03000109.vsd
Figure 8:
The distance between earth points should be < 100 m, see figure 9. Only the outer shielding is connected to the protective earth at the terminal. The inner and outer shieldings are connected to the protective earth at the external equipment. Use insulating tape for the inner shield to prevent contact with the protective earth. Make sure that the terminals are properly earthed with as short connections as possible from the earth screw, for example to an earthed frame. The terminal and the external equipment should preferably be connected to the same battery.
37
Cc
1)
Cc
A B
A B
A B
Terminal
Terminal
PE
PE
PE
PE 1)
en03000111.vsd
Where: 1 The inner shields shall be connected together (with an isolated terminal block) and only have one earthing point in the whole system, preferably at the external equipment (PC). The outer shield shall be connected to Protective Earth (PE) in every cable end i.e. to PE at all relay terminals and to PE at External equipment (PC). The first terminal will have only one cable end but all others of course two. Cc PE Communication cable Protective earth screw
Figure 9:
38
en03000110.vsd
Figure 10:
The EIA standard RS-485 specifies the RS485 network. An informative excerpt is given in section 5.2.
5.2
EIA Standard RS-485 - Electrical Characteristics of Generators and Receivers for Balanced Digital Multipoint Systems
2 Transmission method
The RS485 circuit shall be isolated from earth by: Riso 10 M Ciso 10 pF
39
Three isolation options exist: a) The entire node electronics can be galvanically isolated b) The bus interface circuit can be isolated form the rest of node electronics by optoisolators, transformer coupling or otherwise. c) The RS485 chip can include built-in isolation
2.3 2.3.1 Bus excitation and signal conveyance Requirements
a) The RS485 specification requires the Signal A and Signal B wires. b) Each node also requires (5 V) Excitation of the RS485 termination network. c) Vim - the common mode voltage between any pair of RS485 chips may not exceed 10 V. d) A physical ground connection between all RS485 circuits will reduce noise.
2.3.2 Bus segment termination network
The termination network below required at each end of each Bus Ph-segment.
ExV+ Ru = 390 ohm 1/4 W, 2% Signal B Rt = 220 ohm 1/4 W, 2% Signal A Rd = 390 ohm 1/4 W, 2% DGND
Figure 11:
The specifications of the components are: a) Ru b) Rt c) Rd + 5 V to Signal B Signal B to Signal A Signal A to GND = 390 , 0.25 W 2.5% = 220 , 0.25 W 2.5% = 390 , 0.25 W 2.5%
2.3.3
The end node in each Ph-segment applies 5 V bus excitation power to the Termination network via the Excitation pair (ExV+ and GND) used in the Type 3 Physical layer specification.
40
5.3
Twisted-pair S-STP (Screened Screened Twisted Pair) Individual foil for each pair with overall copper braid Maximum 100 m from one system earth to the next system earth (includes length from platform point to system earth on both sides) According to application 120 Less than or equal to 42 pF/m Belden 9841
41
42
Lc Rx
IED
Cc
Lc Tx
External Equipment
Tx Sc
Rx Sc
en03000087.vsd
Cc Lc Rx Sc Tx
Communication cable Line connector Receive input Screen (or earth/ground) connection Transmit output
Figure 12:
43
44
45
Overview
Overview
The user must check the installation which includes verifying that the terminal is connected to the other parts of the protection system. This is done with the terminal and all connected circuits de-energised.
46
Note!
Do not continue further until any errors are corrected.
Test the circuitry. The following tests are recommended: Polarity check. CT circuit current measurement (primary injection test). Earthing check.
The polarity check verifies the integrity of the circuits and the phase relationship. The check should be performed as close as possible to the terminal. The primary injection test verifies the CT ratio and the wiring all the way through from the primary system to the terminal. Injection must be performed for each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases and the neutral line are measured.
47
48
4
4.1
4.2
49
50
51
Overview
Overview
Before the procedures in this chapter can be carried out the connection to external circuitry must have been checked which ensures that the installation was made correctly. The user must energise the power supply to the terminal to start it up. This could be done in number of ways, from energising a whole cubicle to energising a single terminal. The user should reconfigure the terminal to activate the hardware modules in order to enable the self supervision function detect eventual hardware errors. Then the terminal time must be set. The self supervision function should also be checked to verify that the terminal unit operates properly. The user could also check the software version, the terminals serial number and the installed modules and their ordering number to ensure that the terminal is according to delivery and ordering specifications.
52
1 0
2 10
3 30
4 40
5 70 t (s)
xx02000679.vsd
1 2 3 4 5
Terminal energised. Liquide Crystal Display (LCD) is dark. Green Light Emitting Diod (LED) starts flashing LCD lights up "Terminal startup" is displayed The main menu is displayed. A steady green light indicates a successful startup.
Figure 13:
If the upper row in the window indicates Fail instead of Ready and the green LED is flashing an internal failure in the terminal has been detected. See the self supervision function in this chapter to investigate the fault. After startup the appearance of the local HMI should be as shown in figure 14.
53
Ready Start Trip REx 5xx Ver X.X C=Quit E=Enter menu
C E
Push buttons
en00000422.vsd
Figure 14:
54
3
3.1
3.2
1.
Navigate the menus to: Settings/Time Press the E button to enter the dialog.
2. Set the date and time.
Use the Left and Right arrow buttons to move between the time and date values (year, month, day, hours, minutes and seconds). Use the Up and Down arrow buttons to change the value.
3. Confirm the setting.
Press the E button to set the calendar and clock to the new values.
3.3
3.3.1
55
Procedure
1. Display the self supervision menu.
Use the Left and/or Right arrow buttons to scroll between values.
3.4
InternWarning = Warning A warning has been issued. MPM-modFail = OK MPM-modFail = Fail MPM-modWarning = OK MPM-modWarning = Warning No problem detected.
The main processing mod- Contact your ABB representative for service. ule has failed. No problem detected. There is a problem with: the real time clock. the time synchronization. None. Set the clock. If the problem persists, contact your ABB representative for service. None. Contact your ABB representative for service. Check that the I/O module has been configured and connected to the IOP1- block. If the problem persists, contact your ABB representative for service. None. Set the clock. None. Check the synchronization source for problems. If the problem persists, contact your ABB representative for service.
Slot04BIM1 = Fail I/O module has failed. (Example data, see following section for details) RealTimeClock = OK RealTimeClock = Warning TimeSync = OK TimeSync = Warning No problem detected. The real time clock has been reset. No problem detected. No time synchronization.
56
57
Note!
Total attenuation is fibers, contacts, splices etc.
For multimode fibres: If the total attenuation is less than 3 dB, use Low power setting If the total attenuation is higher than 3 dB, use High power setting
For single-mode fibres: If the total attenuation is less than 2 dB, use Low power setting If the total attenuation is higher than 2 dB, use High power setting
For optimal operation, the optical communication modules in both terminals must be synchronized. To achieve this, one terminal acts as a Master and the other as a Slave. This is set under: Configuration/TerminalCom/RemTermCom/CommSync
Note!
This is an additional setting and should not be mixed up with the Master-Slave setting for the differential protection function. When communicating with FOX 515 Plus, the setting should be Master for version 2.0 and higher. Slave for version 1.1 and 1.2. When operating back-to-back over dedicated fibres the setting shall be Master on one terminal and Slave on the other.
58
Attenuation
0 64 kbit/s MCMI Single mode FC-PC 1300 nm 30.0 nm LED -22 dBm Pin Diode
(R)
Table 3:
Terminal equipment Available power budget (S_R) Equipment margin Type of optical connectors Terminal box Patch panel connectors Connectors for S-R Total available optical power Optical cable Type of optical fibre Fibre attenuation (installed) Splice attenauation Av. cable length between splices Average number of splices Number of repair splices Fibre margin Total fibre attenuation per km Maximum optical transmission distance 0.08 dB per splice 3.0 km 0.33 splice/km 0.10 splice/km Single mode 1300 nm FC-PC for single mode 0.5 dB each
0 Included 16 dB
0 Included 16 dB
0.22 dB/km
0.34 dB/km
59
Note!
If handled carefully the cover plate can be removed with the fibres attached.
Reset
xx00000552.vsd
Figure 15:
Switch 3 and 4 are used to set the source of timing. The function is according to the setting of timing signal, table 4. When using the modem for optical point-to-point transmission, one modem should be set for locally created timing and the other for timing recovered from the received signal. When the modems are communicating with a transceiver 21-15X or 16X the modems shall be set for timing recovered from received optical signal, see setting of timing signal.
Note!
After any change of settings, the modem has to be reset by the Reset button located below the DIP-switch.
60
Table 4:
Switch no. 3 OFF OFF ON ON
There are also some jumpers on the circuit board that have to be correctly set. One, S4 according to figure 17, is for changing the functionality between article number 1MRK 001 370-BA delivered with version 1.1, 1.2 and 2.0.(marked 1MRK001471-BA) and 1MRK 001 370-DA delivered with version 2.3 and higher (marked 1MRK001471-DA). The difference between these two is that the transmitted and received signals are inverted in relation to one another. When a terminal of version 1.1, 1.2 or 2.0 is to communicate with a terminal of version 2.3 or higher it is necessary that the jumper is changed to 1 MRK 001 370-BA in the version 2.3 terminal. This is because older versions of this module lack the capacity to set article number, they are set in 1 MRK 001 370-BA. If both terminals however include modules with capacity to change article number it actually doesnt matter which article number is used as long as the same number is used in both terminals. The other jumper is S3 and must be in the position indicated in figure 17. If it is in the top position the communication will not work. (In top position the transmit clock is supposed to be created in the CPU on the MPM module which is not possible). On JTAG/ISP there shall be no jumpers inserted.
Note!
When using the set up in figure 16 only at one end and for example a direct G.703 connection at the other end a short range fibre optical modem according to 1MRK 001 370-DA must be used.
Figure 16:
61
1 S3
JTAG/ISP
S4
1MRK001471-BA 1MRK001471-DA
1 2
xx01000138.vsd
1 2
Delivered with version 1.1, 1.2 and 2.0 Delivered with version 2.3 or higher
Figure 17:
The jumpers are accessible after the modem has been pulled out. This is done by first removing all green 18-pin connectors at the back, then remove all screws holding the back plate. After the back plate has been removed the modem can be pulled out.
Note!
Pull out the modem only and not the whole double size Euro-card. After the jumper settings have been changed put everything back in reverse order.
Note!
All electronics are sensitive to electrostatic discharge. Proper action must be taken at the work place to avoid electrostatic discharge! Disconnect DC. There are LEDs for supervision of the communication channel that can be seen when the cover around the fibre optic connectors is removed. These LEDs are found above the DIP-switches. The function of the LEDs is explained in table 5.
62
Table 5:
LED RTS CTS DSR DCD TXD RXD RA MA LO LA Sync
Indications
Color Yellow Yellow Yellow Yellow Yellow Yellow Red Red Green Red Green Explanation Request to send Clear to send Data communication correct Detection of carrier signal Transmitted data Received data Remotely detected problem with link Memory function for problem with link Link operation correctly Locally detected problem with link Used when synchronization is selected
63
Line connector
Cover plate
1 2 3 4 5
Off 1 2 3 4 DCD RD TD
On
xx00000555.vsd
Figure 18:
Only switch 1 and 2 are used on the DIP-switch. The function is dependant on the setting of the timing signal, see table 6. In normal operation switch 1 is set in ON position at one end of the communication channel and switch 2 is set ON at the other end. The rest of the switches are set to OFF.
Table 6:
Switch no. 1 OFF OFF ON ON 2 OFF ON OFF ON Unpredictable, normally locally created timing Timing recovered from received signal Locally created timing Timing recovered from received signal
There are also LEDs for the supervision of the communication channel that can be seen when the cover around the fibre optic connectors is removed. These LEDs are found below the DIP-switch. The function of the LEDs is explained in table 7.
64
Table 7:
LED DCD TD RD
Indications
Explanation Detection of carrier signal Transmitted data Received data
65
V.36, RS530
X.21
25 TCLK DTE(A) 24 DTE READY(B)* 23 22 21 8 GND DTE READY(A) 20 7 REQ SEND (B)* 19 6 RCLK 18 5 RCLK(A) 17 4 RXD(A) RXD(B) 16 3 TCLK DCE(A) 15 2 TXD (A) TXD (B) 14 1 SCREEN
13 12 TCLK DCE (B) 11 TCLK DTE (B) 10 9 RCLK (B) 8 7 GND 6 5 4 REQ SEND (A) 3 RXD (A) 2 TXD (A) 1 SCREEN
15 pin DSUB
25 pin DSUB
xx00000544.vsd
Figure 19:
Table 8:
Designation A B DCE DTE DTE READY GND RCLK REQ SEND
DSUB connectors
DSUB connector explanation
Explanation Designations of terminals according to ITU (CCITT), EIA etc. Designations of terminals according to ITU (CCITT), EIA etc. Data communication equipment (= multiplexer, etc.) Data terminal equipment (= protection) Data terminal ready (follows auxiliary voltage) Earth (reference for signals) Receiver signal timing Request to send (follows auxiliary voltage)
66
Explanation Received data Connection of cable screen Transmitter signal timing from DCE Transmitter signal timing from DTE Transmitter data
For the co-directional operation the transmission rate of the transmitted signal must be set.This setting, 56 or 64 kbit/s, is done on the HMI under: Configuration/TerminalCom/RemTermCom/BitRate For X.21 and contra-directional operation no settings are available. For the signals used by the protection, the communication module for V.36 also fulfils the older recommendation for V.35.
67
A B
1 2 3 4 5
TXD RXD On 1 2 3 4
xx01000137.vsd
A B
Figure 20:
Table 9:
LED TD RD
68
Fault tracing
Fault tracing
Procedure
1. 2. 3. Check that the settings are correct. Check that the optical budget is correct. COMFAIL occurs for the following reasons:
The COMFAIL signal will be triggered when there is a problem in the communication link between the two terminals, depending on type of 56/64 modem. Also, normal actions such as a change of setting, switch off of remote terminal during maintenance etc., can cause COMFAIL. 7.0.1 Comfail function
COMFAIL
Figure 21:
Comfail triggering.
The 200 ms alarm dropout delay is, for example, required as hysteresis for terminals with reserve overcurrent, REL 551 or distance reserve function REL 561, if the differential function is blocked by communication delays and interruptions etc. The communication failure signal, COMFAIL, depends on the following internal signals (variables) in each terminal for REx 5xx. Table 10 shows a summary with additional explanations below.
69
Fault tracing
Table 10:
No.
Summary
COMFAIL trigger- Remark ing time (Drop-out delay 200 ms)
50 ms 100 ms
COMFAIL triggering
1 2 3 4
Transmit error Receive error Block differential protection Remote terminal COMFAIL
Messages can not be sent No valid messages received Block of the differential protection due to setting changes etc. COMFAIL from the remote terminal. For error no 1, 2, 3, and no 5, 6, 7, 8, 9, 10 the COMFAIL is sent in the second consecutive message (within 10 ms) Problems in the synchronization of internal differential clock in the differential protection. The clock refers to the synchronized counters 0-39999 s in each terminal. The clock is independent of the real time clock in the terminal. Unacceptable drift of the internal differential clock in the slave terminal compared to the internal differential clock in the master terminal (slave- master -slave) Checks if the loop time (slave - master -slave) in the differential communication channel 31 ms Checks if the loop time (local - remote- local) in the differential communication channel 24 ms Internal differential clock deviation (slavemaster - slave) Long time between attempts to send messages and adjustment of the real time terminal clock . The terminal clock is the real time clock in the terminal for time tagging of events etc.
0 ms 0 ms
2s
> 0 ms
Communication channel loop delay - instantaneous Communication channel loop delay - time delayed Abnormal clock deviation Data flow Only in version *2.3
0 ms
2s
9 10
0 ms 0 ms
7.0.2
Explanation of contents in column 2 of table 42 1. Transmit errors are due to that the terminal cannot send messages via the telecommunication channel (PCM). The line differential function initiates the sending of one message every 5 ms. If this command can not be executed for 10 consecutive times (= 10 x 5 ms) due to blocked, missing or unsynchronized communication channel, COMFAIL is triggered. For non-consecutive interruptions, an integration algorithm is used that prolongs the COMFAIL triggering time. 2. Receive errors occur when no expected messages are received. The line differential function expects to receive one message every 5 ms. If this does not occur 10 consecutive times (= 10x5 ms), COMFAIL is triggered. For non-consecutive interruptions, an integration algorithm is used that prolongs the COMFAIL triggering time.
70
Fault tracing
3. Block differential protection. Block of differential protection occurs during change of settings or setting group. 4. Remote terminal COMFAIL. For error No 1, 2, 3 and No 5, 6, 7, 8, 9, 10 the COMFAIL is sent in the second consecutive message (within 10 ms). Thus, some short interruptions can be recorded only in one terminal. The communication channel must be in operation to be able to receive this signal. 5. Time synchronization error refers to synchronization check and is only performed by the terminal set as Slave for the internal differential clocks synchronization. If 50 time synchronization messages (included with every 8 line differential function message) are not correctly received (= 8 x 5 ms x 50 = 2000 ms), COMFAIL will be triggered. If more than 750 synchronization messages are not correctly received, a re-synchronization of the internal differential clock will be made. For non-consecutive interruptions, an integration algorithm prolongs the COMFAIL triggering time. 6. Differential Clock drift refers to a difference > 50 ms between the internal differential clocks in the differential protection in the terminal set as Slave and the one set as Master for synchronization of the internal differential clock. The COMFAIL triggering time depends on a number of factors from a drift compensation algorithm. This check is normally not activated unless the communication channel has been lost for a long time. 7. Communication channel loop delay-instantaneous is checked every 40 ms (at each synchronization message). If the communication channel loop (Slave-Master-Slave) delay is more than 31ms for one message, COMFAIL is triggered instantaneously. This check is done in the terminal set as Slave for the internal differential clock by a comparison with the real time clock in the terminal at sending and receiving of a looped message. 8. Communication channel loop delay-time delayed checks if the communication channel delay for transmitted and received signal is >24 ms (Local-Remote-Local). The check is performed every 40 ms (at each synchronization message) by comparing the real time clock time at sending and receiving of a looped message. COMFAIL is triggered after 50 consecutive messages with excessive loop time. COMFAIL triggering time = 2000 ms (= 50x40 ms). For non-consecutive messages with excessive loop time, an integration algorithm is used that prolongs the COMFAIL triggering. 9. Abnormal clock deviation checks if the synchronization in the Slave of the internal differential clocks in the differential protection have an abnormal deviation, (Slave-MasterSlave). COMFAIL is triggered instantaneously, but will probably only occur after long interruptions in the communication channel. However, the start or re synchronization procedure can also activate COMFAIL due to this function. 10. Data flow checks if the time between initiations of the sending messages from the line differential function is longer than 20 ms, using the real time clock for the check. This check will also trigger the COMFAIL if the external time synchronization of the real time clock by minute pulse or SPA/LON from Station Clock or GPS, adjusts the terminal clock forward > 15 ms. The COMFAIL triggering is instantaneous. The channel interruption measurements for short, medium and long interruptions, presented on the HMI are based on measurements of timing from the real time clock which are made independently in each terminal. These measurements are also independent from the internal differential clock. The mea-
71
Fault tracing
surements presented on the front HMI are not connected to COMFAIL or by indications of channel delay exceeding 12 ms, since the delay is not a channel interrupt, the channel is still working.
72
73
Co-directional operation
Co-directional operation
The connection is made according to table 11.
Table 11:
Transceiver Pin No. V.35 Signal TD RD TTC No 103 104 113 A P R U B S T W V.36 A 4 6 17 B 22 24 35 Comm. eq. Signal RD TD RC No 104 103 115 Direction Comm. eq. -> Transceiver Transceiver -> Comm. eq. Comm. eq. -> Transceiver
Connections
Figure 22 shows the connection. If needed for proper operation of the communication equipment a connection can be made between the RC and TC. Both TD and RD are controlled from TTC.
Communication equipment RD(A) RD(B) TD(A) TD(B) RC(A) RC(B) TC(A) TC(B)
en01000190.vsd
Figure 22:
74
Co-directional operation
Table 12:
Settings
Setting Middle position Bottom position 9 Middle position Has no influence on operation Gives V.35 V.36 64 kbit/s External clock ---
Switch, jumper S1 S1 S2 S3 S4
75
Contra-directional operation
10
Contra-directional operation
Connected according to table 13.
Table 13:
Transceiver Pin No. V.35 Signal TD RD TTC
1)
Connections
V.36 B S T W A 4 6 17 B 22 24 35
A P R U
No 104 103
1)
Direction Comm. eq -> Transceiver Transceiver -> Comm. eq. Comm. eq. -> Transceiver
Figure 23 shows the connection. In this case the connection to TTC can be made either from RC or TC but not from both. Both TD and RD are controlled from TTC.
Communication equipment RD(A) RD(B) TD(A) TD(B) RC(A) RC(B) TC(A) TC(B)
1)
en01000191.vsd
Figure 23:
76
Contra-directional operation
Table 14:
Settings
Setting Middle position Bottom position 9 Middle position Has no influence on operation Gives V.35 V.36 64 kbit/s External clock ---
Switch, jumper S1 S1 S2 S3 S4
77
11
11.1
X.21 operation
The connection is made according to table 15.
Table 15:
Transceiver Pin No. Signal T R S A 2 4 6 B 9 11 13 Signal T R S Direction Comm. eq -> Transceiver Transceiver -> Comm. eq. Comm. eq. -> Transceiver
Connections
Comm. eq.
en01000192.vsd
Figure 24:
78
Table 16:
Settings
Setting Jumpers downwards Second position from bottom 9 Jumper at middle position Has no influence on operation Gives DTE X.21 64 kbit/s External clock ---
Switch, jumper S2, S3, S4, S15, S16 S6 S11 S14 S13
11.2
Connections
Comm. eq. Pin1) 1/2 3/4 Signal RX TX Direction Comm. eq -> Transceiver Transceiver -> Comm. eq.
RJ-45 connector. Numbered from left the connection points will bet this number
If a screen is available in the cable it is connected to Protection Ground (pin 9 on the transceiver) at one or both ends. Figure 25 shows the connection. Note that the signal directions are according to DCE operation for both transceiver and communication equipment.
Figure 25:
79
Table 18:
Settings
Setting
Switch, jumper
G.703 co - con, balanced Nx64 kbps Co-directional Has no influence on operation Has no influence on operation Has no influence on operation 9 (64 kbit/s) External clock No jumper Has no influence on operation
80
81
Overview
Overview
The customer specific values for each setting parameter and a configuration file has to be available before the terminal can be set and configured, if the terminal is not delivered with a configuration. Use the CAP 531 configuration tool to verify if the terminal has the expected configuration. A new configuration is performed with the CAP tool. The binary outputs can be selected from a signal list where the signals are grouped under their function names. It is also possible to specify a user-defined name for each input and output signal. The configuration can be downloaded through the front connector on the local HMI or via the rear SPA port. Each function included in the terminal has several setting parameters which have to be set in order to make the terminal behave as intended. A default value is provided for each parameter from factory. A setting file can be prepared using the parameter setting tool (PST), which is available in the CAP 540 package. All settings can be: Entered manually through the local HMI. Downloaded from a PC, either locally or remotely using SMS/SCS. Front or rear port communication has to be established before the settings can be downloaded.
Note!
Be sure to configure the functional input HMI--BLOCKSET to only one of the available binary inputs before setting the parameter SettingRestrict to Block in the local HMI.
82
83
RESTRICT SETTINGS
en01000152.vsd
Configuration/BuiltInHMI/HMI--BLOCKSET
2. Select a binary input
Select a binary input not used or reserved for any other purpose. Connect the selected binary input to the DC control voltage via a normally closed contact of a control switch, which can be locked by a key. Only when the normally closed contact is open, the change of settings and configuration of the REx 5xx terminal is possible. See figure 26.
84
4
4.1
Configuration/BuiltInHMI/SettingRestrict
2. Set SettingRestrict = Block.
Note!
The HMI--BLOCKSET functional input must be configured to the selected binary input before setting the setting restriction function in operation. Carefully read the instructions.
4.2
Configuration/TerminalCom/SPACom/Rear/ActGrpRestrict
2. Set ActGrpRestrict = Block
4.3
Configuration/TerminalCom/SPACom/Rear/SettingRestrict
2. Set SettingRestrict = Block
85
5
5.1
The slave number and baud rate settings in the REx 5xx terminal is done on the local HMI at: Configuration/TerminalCom/SPACom/Front
4. Set the slave number and baud rate in the PC-program.
The slave number and baud rate must be the same as in the terminal. See the CAP 540 manual.
5.2
5.2.1
Using the SPA/IEC rear port For all settings and configuration via the SPA communication bus, the SPA/IEC 60870-5-103 port on the rear, it is necessary to first deactivate the restriction for settings. Otherwise, no setting is allowed. This setting only applies for the SPA/IEC 60870-5-103 port during SPA bus communication. The parameter can only be set on the local HMI, and is located at: Configuration/TerminalCom/SPACom/Rear/SettingRestrict It is also possible to permit changes between active setting groups with ActGrpRestrict in the same menu section.
86
Selecting the protocols for the rear ports To define the protocols to be used, a setting is done on the local HMI under the menu: Configuration/TerminalCom/SPA-IEC-LON When the protocols have been selected the terminal will automatically restart. When communicating with SMS or SCS with the SPA or IEC 60870-5-103 protocol the slave number and baud rate (communication speed) settings must be equal in the PC-program and in the REx 5xx terminal. Using the SPA rear port The slave number and baud rate settings of the rear SPA port on the REx 5xx terminal, for SPA bus communication, is done on the local HMI at: Configuration/TerminalCom/SPACom/Rear Using IEC 870-5-103 rear port The slave number and baud rate settings of the rear IEC 60870-5-103 port on the REx 5xx terminal, for IEC 870-5-103 bus communication, is done on the local HMI at: Configuration/TerminalCom/IECCom/Communication 5.2.2 Using LON rear port The LON port is not affected by eventual restricted settings valid for the SPA/IEC port. When communicating via the LON port, the settings are done with the LNT, LON Network Tool. The settings are shown on the local HMI at: Configuration/TerminalCom/LON Com From this menu, it is also possible to send the ServicePinMsg to the LNT.
5.3
87
88
89
90
91
Entering settings
Entering settings
If the terminal is connected to a monitoring or control system via any of the rear SPA and/or IEC ports, the applicable selection of protocols for the rear ports must be made.
1.1
Procedure
1. Set the operation of the rear SPA/IEC port to SPA.
The operation of the rear SPA/IEC port can be found on the local HMI at: Configuration/TerminalCom/SPA-IEC-LON When the setting is entered the terminal will automatically restart. After the restart the SPA/IEC port operates as a SPA port.
2. Set the slave number and baud rate for the rear SPA port
The slave number and baud rate can be found on the local HMI at: Configuration/TerminalCom/SPACom/Rear Set the same slave number and baud rate as set in the SMS system for the terminal.
1.2
Procedure
1. Set the operation of one of the rear ports to IEC.
The operation of the rear ports can be found on the local HMI at:
92
Entering settings
Configuration/TerminalCom/SPA-IEC-LON When the setting is entered the terminal will automatically restart. After the restart the selected IEC port operates as a IEC port.
2. Set the slave number and baud rate for the rear IEC port
The slave number and baud rate can be found on the local HMI at: Configuration/TerminalCom/IECCom/Communication Set the same slave number and baud rate as set in the IEC master system for the terminal.
3. Set the main function type of the terminal.
The main function type can be found on the local HMI at: Configuration/TerminalCom/IECCom/FunctionType The main function type can be set to values from 1 to 255 according to the standard. The value zero is default and corresponds to not used. Examples of values that can be used are:
Table 19:
Value
If the setting OpFnType is set to ON then the set value for function type will be used for all event blocks and the disturbance recorder, otherwise the setting on each event block and the disturbance recorder will decide the function type of that function block.
93
2.1
During the following tests of the different functions in the terminal, verify that the events and indications in the SMS/SCS system are as expected.
2.2
3.
During the following tests of the different functions in the terminal, verify that the events and indications in the IEC master system are as expected.
94
Maximum attenuation for REx 5xx 4 dB/km multi mode: 820 nm - 62.5/125 um 0.16 dB/m plastic: 620 nm - 1mm Margins for installation, aging etc. Losses in connection box, two contacts (0.7 dB/contact) Losses in connection box, two contacts (1 dB/contact) Margin for repair splices (0.5 dB/splice) Maximum total attenuation
- 11 dB 4 dB 5 dB 1.4 dB 0.5 dB 11 dB
- 7 dB 4 dB 1 dB 2 dB 7 dB
95
96
97
Reference
Reference
We refere to document: LNT 505 Operators Manual 1MRS751706-MUM, Issued: 31.10.99, Program rev: 1.1.1 Doc. version: B.
1.1
1.1.1
Maximum attenuation for REx 5xx 4 dB/km multi mode: 820 nm - 62.5/125 um 0.2 dB/m plastic: 620 nm - 1mm Margins for installation, aging etc. Losses in connection box, two contacts (0.7 dB/contact) Losses in connection box, two contacts (1dB/contact) Margin for repair splices (0.5 dB/splice) Maximum total attenuation
- 7 dB 4 dB 1 dB 2 dB 7 dB
98
99
Overview
Overview
Required tools for testing of a terminal: Calculated settings Configuration diagram Terminal diagram Technical reference manual Three-phase test equipment
The terminal has to be set and configured before the testing can start. The terminal diagram, available in the Technical reference manual, is a general diagram for the terminal. But note that the same diagram is not always applicable for each specific delivery (especially for the configuration of all the binary inputs and outputs). It is for this reason necessary to check before testing that the available terminal diagram corresponds to the terminal. The Technical reference manual contains application and functionality summaries, function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The test equipment should be able to provide a three-phase supply of voltages and currents. The magnitude of voltage and current as well as the phase angle between voltage and current must be variable. The voltages and currents from the test equipment must be obtained from the same source and they must have a very small harmonic contents. If the test equipment cannot indicate the phase angle, a separate phase-angle meter is necessary. Prepare the terminal for test before testing a particular function. Consider the logic diagram of the tested protection function when performing the test. All included functions in the terminal are tested according to the corresponding test instructions in this chapter. The functions can be tested in any order according to user preferences and the test instructions are therefor presented in alphabetical order. Only the functions that are used (Operation is set to On) should be tested. The response from a test can be viewed in different ways: Binary outputs signals Service values in the local HMI (logical signal or phasors) A PC with CAP (configuration software) in debug mode
Note!
This terminal is designed for a maximum continuous current of four times the rated current.
100
Overview
Note!
Please observe the measuring accuracy of the terminal, the test equipment and the angular accuracy for both of them.
Note!
Please consider the configured logic from the function block to the output contacts when measuring the operate time.
101
2
2.1
2.2
102
Warning!
Never disconnect a secondary connection of current transformer circuit without short-circuiting the transformer's secondary winding. Operating a current transformer with the secondary winding open will cause a massive potential build-up that may damage the transformer and may cause injuries to humans.
2.3
The window repeatedly displays Busy and after that the yellow LED starts flashing which indicates that the terminal is in test mode.
2.4
103
IL1 IL2 IL3 IN (I4,I5) UL1 UL2 UL3 UN UN (U4,U5) TRIP L1 TRIP L2 TRIP L3 REx 5xx
en01000162.vsd
Figure 27:
2.5
The phasor menu is located in the local-HMI under: ServiceReport/Phasors/Primary and Secondary Consider set ratio factors for CTs and VTs.
2. Compare the frequency reading with the set frequency and the direction of the power with the injected power.
The frequency and active power are located in the local-HMI under: ServiceReport/ServiceValues
3. 4. Inject a unsymmetrical three-phase current and voltage at rated value in two phases. Compare the injected value with the measured value.
104
2.6
Note!
The function is blocked if the corresponding setting under the BlockFunctions menu remains on and the TEST-INPUT signal remains active. All functions that where blocked or released from previous test mode session are still valid when a new test mode session is entered. Procedure
1. Browse to the BlockFunctions menu.
Use the left and right arrow buttons. Press E when the desired function has been found.
3. 4. Select No. Press C twice to leave the menu.
2.7
105
Test/TestMode/DisturbReport
Table 22:
Operation
Off
Off
Disturbances are not stored. LED information is not displayed on the HMI and not stored. No disturbance summary is scrolled on the HMI. Disturbances are not stored. LED information (yellow - start, red - trip) are displayed on the local HMI but not stored in the terminal. Disturbance summary is scrolled automatically on the local HMI for the two latest recorded disturbances, until cleared. The information is not stored in the terminal. The disturbance report works as in normal mode. Disturbances are stored. Data can be read from the local HMI, a front-connected PC, or SMS.- LED information (yellow - start, red - trip) is stored. The disturbance summary is scrolled automatically on the local HMI for the two latest recorded disturbances, until cleared. All disturbance data that is stored during test mode remains in the terminal when changing back to normal mode.
Off
On
On
On or Off
2.8
106
Autorecloser (AR)
Autorecloser (AR)
The test can be divided into to parts; one to verify the internal logic and one to verify the co-operation with the protection system. This section deals with the first test. Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" in this chapter. The test is performed together with protection and trip functions. Figure 28 illustrates a recommended testing scenario, where the circuit breaker is simulated by an external bistable relay (BR), for example an RXMVB2 or an RXMVD. The following switches are needed: Switch close (SC) Switch trip (ST) Switch ready (SRY).
SC and ST can be push-buttons with spring return. If no bistable relay is available, replace it with two self-reset auxiliary relays and use self-holding connection. Use a secondary injection relay test set to operate the protection function. It is possible to use the BR to control the injected analogue quantities so that the fault only appears when the BR is picked upsimulating a closed breaker position. To make the arrangement more elaborate, include the simulation of the operation gear condition, AR01-CBREADY, for the sequences Close-Open (CO) and Open-Close-Open (OCO). The AR01-CBREADY condition at the CO sequence type is usually low for a recharging time of 5-10 s after a closing operation. Then it is high. The example in figure 28 shows that it is simulated with SRY, a manual switch.
107
Autorecloser (AR)
ST
AR01 - CB READY
To test set
en02000446.vsd
Figure 28:
3.1
Preparing
1. Check the settings of the autorecloser (AR) function.
The operation can be set at Stand-by (Off) in HMI tree: Settings/Functions/Group n/AutoRecloser/AutoRecloser n If any timer setting is changed so as to speed-up or facilitate the testing, they must be set to normal after the testing. A verification test has to be done afterwards.
2. 3. Check that the functional input signal SYNC is set to TRUE if the internal or external synchrocheck is not used. Read and note the reclosing operate counters from the HMI tree:
108
Autorecloser (AR)
ServiceReport/Functions/AutoRecloser/AutoRecloser n/Counters
4. 5. Do the testing arrangements outlined above, for example, as in figure 28. The AR01-CBCLOSED breaker position, the commands Trip and Closing, AR01-CLOSECB, and other signals should preferably be arranged for event recording provided with time measurements.
Otherwise, a separate timer or recorder can be used to check the AR open time and other timers.
3.2
Observe or record the BR operation. The BR relay should trip and reclose. After the closing operation, the SRY switch could be opened for about 5 s and then closed. The AR open time and the operating sequence should be checked, for example, in the event recording. Check the operate indications and the operate counters. Should the operation not be as expected, the reason must be investigated. It could be due to an AR Off state or wrong program selection, or not accepted synchro-check conditions.
6. Repeat procedure 5 for phase L2 and L3, two-phase and three-phase trips, transient, and permanent fault.
The signal sequence diagrams in the Technical reference manual can be of guidance for the checking.
3.3
109
Autorecloser (AR)
3.3.1
1. 2. 3.
Check that the function is operative and that the breaker conditions are okay. Apply an AR01-INHIBIT input signal and start the reclosing function. Check that there is no reclosing.
3.3.2
1. 2. 3.
Set the breaker simulating relay, BR, in position open. Then close it with the SC switch and start the AR within one second. Check that there is no reclosing.
3.3.3
1. 2. 3.
Close the BR breaker relay and see that everything except for AR01-CBREADY is in normal condition (SRY is open). Start the AR function. Check that there is no reclosing.
3.3.4
1. 2. 3.
Check the function at non-acceptable voltage conditions. Wait for the time out, >5 s. Check that there is no reclosing.
3.3.5
1. 2.
Check that no reclosing can occur with the function in Off state. Check the operation in stand-by mode.
Depending on the program selection and the selected fault types that start and inhibit reclosing, a check of no unwanted reclosing can be made. For example, if only single-phase reclosing is selected, a test can verify that there is no reclosing after two-phase and three-phase trips.
110
Autorecloser (AR)
3.4
3.5
1.
Check and record the counter contents (Reset if it is the users preference).
The counters menu is located in the local HMI under: ServiceReport/Functions/AutoRecloser/AutoRecloser n/Counters/Clear Counters
2. 3. 4. Reset the setting parameters as required. Disconnect the test switch or disconnected links of connection terminals. Reset indications and events.
The ClearDistRep menu is located in the local HMI under: DisturbReport/ClearDistRep Continue to test another function or complete the test by setting the test mode to off. Restore connections and settings to the original values, if they were changed for testing purpose.
111
The breaker-failure protection should be tested in co-operation with some other functions, and in particular with the protection and trip functions or via external start.
4.1
Note: If no I> check is set only back-up trip operate at set IP>.
4.2
4.2.1
4.2.2
112
4.2.3
4.3
113
5.1
Values of the logical signals belonging to the broken conductor check function are available under menu tree: ServiceReport/Functions/BrokenConduct/FuncOutputs
2. Quickly set the measured current (fault current) in one phase to about 110% of the setting (IP>) operating current, and switch off the current with the switch.
Observe the maximum permitted overloading of the current circuits in the terminal.
3. Switch on the fault current and measure the operating time of the BRC protection.
Use the BRC--TRIP signal from the configured binary output to stop the timer.
4. 5. 6. Compare the measured time with the set value t. Activate the BRC--BLOCK binary input. Switch on the fault current (110% of the setting) and wait longer than the set value t.
9.
114
6.1
115
The output signals shall reset with a delay of 1 s when the current exceeds 1.5I1b.
3. 4. 5. Inject a current 0.90I1b to phase L1 and a current 0.15I1b to the reference current input (I5). Decrease slowly the current to the reference current input and check that blocking is obtained when the current is about 0.10I1b. Continue to test another function or complete the test by setting the test mode to off.
116
8.1
Values of the logical signals belonging to the time delayed residual overcurrent protection are available under menu tree: ServiceReport/Functions/EarthFault/TimeDelayEF
2. 3. Set the polarising voltage to 2% of Ub and the phase angle between voltage and current to 65, the current lagging the voltage. Check that the operate current of the forward directional element is equal to the IN> Dir setting.
117
65
Upol = -3U0
IN Operation
IN>Dir
99000052.vsd
Figure 29:
6. 7. 8.
To activate the directional function, set Direction = Directional. Set the polarising voltage to 2% of Ub and the phase angle between voltage and current to 65. Check the operate current of the IMin function.
When inverse time delay is selected, check the operate time at three points of the inverse characteristic. The formulas for operate time for different types of inverse time delay curves are shown in table 23.
118
Table 23:
Characteristics
Normal inverse
(Equation 1)
Very inverse
(Equation 2)
Extremely inverse
80 t = ------------- k 2 I 1
t = 5.8 ( 1.35 ln I )
(Equation 3)
Logarithmic inverse
(Equation 4)
Where: I k is a multiple of set current 3I0> is a time multiplying factor, settable in the range of 0.05 to 1.10
Also check the tMin (minimum operate time) and IMin (minimum operate current) functions.
10. Activate the TEF--BC input to check the function of the switch-onto-fault logic. 11. Check that the TEF--TRSOTF output is activated with a 300 ms time delay when injecting a current two times the set IMin operate value in forward direction. 12. Set the phase angle of the polarising voltage to =245 and check that the directional current function and the switch-onto-fault logic gives no operation when the current is in the reverse direction. 13. Connect the rated DC voltage to the TEF--BLOCK configured binary input and switch on the fault current.
No TEF--TRIP nor TEF--TRSOTF should appear. But the output TEF--START shall be activated.
16. Continue to test another function or complete the test by setting the test mode to off.
119
120
10
121
11
In Test Mode, individual event blocks can be blocked from the PST. Individually event blocks can also be blocked from the local HMI under the menu: Test/TestMode/BlockEventFunc
122
12
123
13
Ensure that the maximum continuous current of the terminal does not exceed four times its rated value.
13.1
13.1.1
Observe the maximum permitted overloading of the current circuits in the terminal.
4. Compare the measured operating current with the set value.
13.1.2
Observe the maximum permitted overloading of the current circuits in the terminal.
4. Compare the measured operating current with the set value.
13.2
124
14
125
When one of the protections is in test mode, the opposite terminal mode of operation is changed. In the opposite terminal, the received current values (a and b Fourier coefficients) are echoed back to the other terminal, but transposed in the following way: the received value for the L1 phase is returned as the L2 current, L2 is returned as L3, and L3 as L1.
Note!
When a current is injected into phase L1 in the terminal, it will appear as an IDiff in phase L1 and L2 with 50% of the value as an IBias and in phase L3 with 25% of the value as an IBias. When the current is sufficiently high, the protection will operate in phase L1 and L2 in the terminal in test mode, but it will not operate in the remote terminal. For the actual reading of IDiff and IBias, see step 6 in the test procedure. Also see figure 30 and equations 5, 6 and 7.
Figure 30:
Stabilisation characteristic
126
( I Bias ) Evaluate = Max { [ ( I Bias ) Own phase ] OR [ 0.5 ( I Bias ) Other phases ] }
(Equation 7)
The test is performed by injecting a single and a symmetrical three-phase current. If the optional charging current compensation function is included, the CCComp shall be Off and no measuring voltage connected to the terminal.
14.1
The blocking can not be done by the COMBITEST test switch. It has to be made on the station side of the test switch.
2. Set the protection in test mode from the HMI unit.
The TestMode is found in the menu under: Test/TestMode/Operation The TestMode command must be saved in order to be activated. When the protection is equipped with COMBITEST test switch, the test mode is automatically activated but not saved when the test handle is inserted.
3. 4. Prepare the terminal for verification of settings as outlined in section Prepare for test in this chapter. Set the Disturbance report to Off.
This command is found in the menu under: Test/TestMode/Differential This command must be saved in order to be activated. Observe that the command ReleaseLocal will allow the trip outputs to be activated during the tests.
127
6.
Inject a current in L1 and increase the current until operation in phase L1 and L2 takes place.
The injected operation value must correspond to the set IMinOp IrCTFactor. This value is to be read as IDiffL1 and IDiffL2, and 50% of IDiffL1 as IBiasL1 and IBiasL2. The IDiffL3 should be zero and IBiasL3 25% of IDiffL1. These values are read on the HMI under: Service Report/Functions/Differential/Diff Values
7. Repeat step 6 for phase L2 and L3.
The IMinOpIrCTFactor value shall be obtained for operation and read for IDiff in all three phases. 100% of IDiff shall be read for IBias in all three phases.
9. Read the transmission delay on the HMI.
This command is found in the menu under: Service value/Functions/Differential/DiffCom/ComInfo This delay is not allowed to exceed 30ms (changed from 24 ms to 30 ms in software revision 2p5 r03). The displayed value is 2x15 ms i.e. transmission time from line end A to B + B to A.
10. Measure the operating time by injection of a single-phase current in phase L1.
The injected current should be 4 times the operating current. The time measurement is stopped by the trip output from the protection. The operating time should be 28-33 ms + 2 times the communication transmission delay.
11. Disconnect the test equipment and reconnect the current transformer. 12. Read and check the service values of the three-phase current. 13. When the current transformers are connected, put the protection in operation by switching off the test mode.
After the test mode is set to Off, the command must be saved to activate the protection. The yellow LED shall stop flashing.
128
14. With a through load current of minimum 20% of the Ir CTFactor, the IDiff and IBias are read in all phases.
The IDiff should be lower than 10% of the actual secondary current divided by the CTFactor, the IBias should be equal to this current. This measurement is necessary at commissioning to guarantee that there is no phase shift between the terminals.
15. Remove the external blocking of the trip signal when this test has been successfully performed. 16. A complete commissioning or maintenance test requires that the test is repeated at both terminals. 17. When the direct transfer trip is used, this function has to be tested by activating its input, to check that trip is achieved at the remote terminal. During this test, the trip circuit has to be blocked.
14.2
2.
3.
Read the values of the differential and bias currents under the menu: ServiceReport/DiffValues They must correspond to the value:
IDiff = IBias U
The bias currents are available under the same menu. They must be equal to the measured differential current in each phase.
129
4. 5.
Disconnect the voltages from the terminal and connect only one phase to all three voltage inputs of the terminal. Increase the measured voltage to the rated phase value and observe the values of the differential and bias currents, presented on the terminal.
6.
With the terminal in normal operation, not in Test mode, and with the line energised, the IDiffL1, IDiffL2 and IDiffL3 are measured under the service report menu with CCComp temporary set to Off at both terminals. Thereafter measure the values with the CCComp set to On.
Note! Setting CCComp to Off might cause the terminal to trip. Therefore make sure that the trip outputs are blocked.
7. Check the charging current compensation by comparing the measured IDiffLx values.
The measured IDiffLx shall be near zero in each separate phase with the CCC used.
8. Remove the external blocking of the trip signal when this test has been successfully performed.
14.3
130
15
15.1
Check that the values presented on the HMI unit correspond to the magnitude of input measured quantities within the limits of declared accuracy. The mean service values are available under the submenu: Service Report/ServiceValues The phasors of up to five input currents and voltages are available under the submenu: Service Report/Phasors/Primary
2. Check the operation of ADBS or IDBS when applicable. Compare with the expected values.
The operation of ADBS or IDBS function can be checked separately with the RepInt = 0 setting. The value on the HMI follows the changes in the input measuring quantity continuously.
3. Check the set operate levels of the monitoring function by changing the magnitude of input quantities and observing the operation of the corresponding output relays.
The output contact changes its state when the changes in the input measuring quantity are higher than the set values HIWARN, HIALARM, or lower than the set values LOWWARN, LOWALARM.
15.2
131
16
16.1
where:
nm x y
represents the serial number of a slot with tested mA input module represents the serial number of a mA input module in a terminal represents the serial number of a measuring channel on module x.
3.
Check the operation of ADBS or IDBS function when applicable. Compare with the expected values.
The operation of ADBS or IDBS function can be checked separately with the setting of RepInt = 0. The value on the HMI must change only when the changes in input current (compared to the present value) are higher than the set value for the selected dead band.
4. Check the operating monitoring levels by changing the magnitude of input current and observing the operation of the corresponding output relays.
The output contact changes its state when the changes in the input measuring quantity are higher than the set values RMAXAL, HIWARN, HIALARM, or lower than the set values LOWWARN, LOWALARM, RMINAL.
132
16.2
133
17
134
18
18.1
Logical signals for overload supervision protection are available under menu tree: ServiceReport/Functions/OverLoad/FuncOutputs
2. Quickly set the measured current (fault current) in all three phases to about 110% of the setting operating current, and switch off the current with the switch.
Observe the maximum permitted overloading of the current circuits in the terminal.
3. Switch on the fault current and measure the operating time of the OVLD protection.
Use the OVLD-TRIP signal from the configured binary output to stop the timer.
4. 5. 6. Compare the measured time with the set value t. Activate the OVLD-BLOCK binary input. Switch on the fault current (110% of setting) and wait longer than the set value t.
10. Switch on the fault current and wait longer than the set value t.
135
12. Continue to test another function or complete the test by setting the test mode to off.
136
19
Use the PD---TRIP signal from the configured binary output to stop the timer.
2. 3. 4. Compare the measured time with the set value t. Reset the PD---POLDISC binary input. Activate the PD---1POPEN binary input.
10. Continue to test another function or complete the test by setting the test mode to off.
137
20
138
21
21.1
2. 3. 4.
Reading of the values must be possible. The terminal must not respond to any attempt to change the setting value or configuration.
5. 6. Disconnect the control DC voltage from the selected binary input. Repeat the attempt under step 4.
21.2
139
22
22.1
140
23
141
24
24.1
24.1.1
2.
Test/ThermReset
3. Switch on the fault current and read the presented temperature:
ServiceReport/Functions/ThermOverload/ThermOverload/T Line
4. Check the Alarm limit (TAlarm) during injection.
Measure the signal THOL-ALARM until it appears on the corresponding binary output or on the local HMI unit.
5. 6. Compare the measured temperature with the setting. Measure the trip time of the THOL protection.
Use the THOL-TRIP signal from the configured binary output to stop the timer.
7. Take the T Line readings.
142
Measure the signal THOL-START until it disappears on the corresponding binary output or on the local HMI unit, take the T Line readings and compare with the setting of TdReset.
11. Compare the measured trip time with the setting according to the formula. 12. Reset the thermal memory. 13. Continue to test another function or complete the test by setting the test mode to off.
143
25
Ensure that the maximum continuous current of the terminal does not exceed four times its rated value.
25.1
25.1.1
Observe the maximum permitted overloading of the current circuits in the terminal.
4. 5. 6. 7. Compare the measured operating current with the set value IP>. Set the fault current to about 1.5 times the measured operating current. Switch on the fault current and measure the operating time of the TOC protection. Use the TOC--TRP signal. Compare the measured time with the set value tP.
25.1.2
Observe the maximum permitted overloading of the current circuits in the terminal.
144
4. 5. 6. 7.
Compare the measured operating current with the set value IN>. Set the fault current to about 1.5 times the measured operating current. Switch on the fault current and measure the operating time of the TOC protection. Use the TOC--TRN signal. Compare the measured time with the set value tN.
25.2
145
26
26.1
26.2
Consider sufficient time interval between the faults, to overcome a reclaim time of eventually activated autoreclosing function. Only a single-phase trip should occur for each separate fault and only one of the trip outputs (TRIP-TRLn) should be activated at a time. Functional outputs TRIP-TRIP and TRIP-TR1P should be active at each fault. No other outputs should be active.
2. Initiate different phase-to-phase and three-phase faults.
Consider sufficient time interval between the faults, to overcome a reclaim time of eventually activated autoreclosing function. Only a three-phase trip should occur for each separate fault and all of the trip outputs (TRIP-TRLn) should be activated at a time. Functional outputs TRIP-TRIP and TRIP-TR3P should be active at each fault. No other outputs should be active.
3. Initiate a single-phase-to-earth fault and switch it off immediately when the trip signal is issued for the corresponding phase. Initiate the same fault once again within the reclaim time of the used autoreclosing function.
A three-phase trip must be initiated for the second fault. Check that the corresponding trip signals appear after both faults.
146
If not the autoreclosing function is used the functional outputs TRIP-TRIP, TRIP-TR1P and the corresponding phase signal (TRIP-TRLn) should be active at each fault.
4. Initiate a single-phase-to-earth fault and switch it off immediately when the trip signal is issued for the corresponding phase. Initiate the second single-phase-to-earth fault in one of the remaining phases within the time interval, shorter than two seconds and shorter than the dead-time of the autoreclosing function, when included in protection scheme.
26.3
Consider sufficient time interval between the faults, to overcome a reclaim time of eventually activated autoreclosing function. Only a single-phase trip should occur for each separate fault and only one of the trip outputs (TRIP-TRLn) should be activated at a time. Functional outputs TRIP-TRIP and TRIP-TR1P should be active at each fault. No other outputs should be active.
2. Initiate one-by one different phase-to-phase faults.
Consider sufficient time interval between the faults, to overcome a reclaim time of eventually activated autoreclosing function. Only a two-phase trip should occur for each separate fault and only corresponding two trip outputs (TRIP-TRLn) should be activated at a time. Functional outputs TRIP-TRIP and TRIP-TR2P should be active at each fault. No other outputs should be active.
3. Initiate a three-phase fault.
Consider sufficient time interval between the faults, to overcome a reclaim time of eventually activated autoreclosing function. Only a three-phase trip should occur for the fault and all trip outputs (TRIP-TRLn) should be activated at the same time. Functional outputs TRIP-TRIP and TRIP-TR3P should be active at each fault. No other outputs should be active.
4. Initiate a single-phase-to-earth fault and switch it off immediately when the trip signal is issued for the corresponding phase. Initiate the same fault once again within the reclaim time of the used autoreclosing function.
A three-phase trip must be initiated for the second fault. Check that the corresponding trip signals appear after both faults.
147
If not the autoreclosing function is used the functional outputs TRIP-TRIP, TRIP-TR1P and the corresponding phase signal (TRIP-TRLn) should be active at each fault.
5. Initiate a single-phase-to-earth fault and switch it off immediately when the trip signal is issued for the corresponding phase. Initiate the second single-phase-to-earth fault in one of the remaining phases within the time interval, shorter than two seconds and shorter than the dead-time of the autoreclosing function, when included in protection scheme.
Check that the second trip is a single-phase trip in a second initiated phase.
6. Initiate a phase-to-phase fault and switch it off immediately when the trip signal is issued for the corresponding two phases. Initiate another phase-to-phase fault (not between the same phases) within the time, shorter than 2 seconds.
Check, that the output signals, issued for the first fault, correspond to two-phase trip for included phases. The output signals for the second fault must correspond to the three-phase tripping action.
26.4
148
27
27.1
27.1.1
27.1.2
Measuring the definite time delay of the low set stage Procedure
1. 2. Set a current 1.5 times I>Low on the injection test equipment. Switch the current on and compare the operation time on TOC2-TRLS with the set value tLow.
The operate time shall be tLow+operate time of the low set stage. 27.1.3 Measuring the inverse time delay of the low set stage Procedure
1. Set temporarily tLow = 0.000 s.
If I>Low is set higher than I>Inv, check that there is no trip signal TOC2-TRLS when the current is less than I>Low.
2. Check the time delay at two points of the inverse time curve.
Check with the current I>Low or 2I>Inv (the highest value of these two) and the current that according to the inverse time curve corresponds to tMin.
3. Increase the current 10% and check that the operation time is equal to tMin.
149
4.
Set tLow to the correct value and check with a high current that the operation time is equal to tMin+tLow.
27.1.4
1. 2. 3. 4. 5. 6. 7.
Set temporarily tHigh=0.000 s. Inject a phase current slightly smaller than the operation value I>High. Increase the current slowly and check the operation value by observing when the signal TOC2-TRHS appears. Compare the result of the measurement with the set value. Set tHigh to the correct value. Set a current 1.5 times I>High on the injection test equipment Switch the current on and compare the operation time with the set value tHigh.
27.2
150
28
28.1
28.1.1
28.1.2
28.1.3
151
5. 6. 7.
Measure the time between the change in current and the SCC1_START (SCC1_TRIP) signal. Compare the measured time with the set values tHStart and tHTrip. Repeat item 11-16 for the other two phases.
28.1.4
Completing the test Continue to test another function or complete the test by setting the test mode off.
152
29
29.1
29.1.1
29.1.2
8. 9.
29.1.3
3. 4.
153
5. 6.
Measure the time between the change in residual current and the SCRC_START (SCRC_TRIP) signal. Compare the measured time with the set values tHStart and tHTrip.
29.1.4
Completing the test Continue to test another function or complete the test by setting the test mode off.
154
30
30.1
30.1.1 30.1.2
30.1.3
2.
3.
4.
30.1.4
Completing the test Continue to test another function or complete the test by setting the test mode off.
155
31
31.1
31.1.1 31.1.2
31.1.3
2.
3. 4.
31.1.4
Completing the test Continue to test another function or complete the test by setting the test mode off.
156
32
32.1
32.1.1
32.1.2
32.1.3
4. 5.
157
6.
Change the level of the injected current and measure the operating time of the ROCP function. Use the ROCP_TRHIGH signal. Compare this operating time with the set value tHigh
32.1.4
Completing the test Continue to test another function or complete the test by setting the test mode off.
158
159
Overview
Overview
Before start of this process, all individual devices that are involved in the fault clearance process must have been tested as individuals and set in operation. The breaker must be ready for an open-close-open cycle. The shaping of the test process is dependent on the complexity of the design of the switchyard. Hereby follows some items which could be used as guidelines.
160
Check that correct trip has been accomplished according to configuration and philosophy. Check that all binary output signals that should be activated have been activated. Check that all other protection functions that should be activated by this type of fault have been activated. Check that no other protection functions that should not be activated have not been activated. Check whenever applicable that the disturbance report, event list and disturbance recorder have been activated and performed correct information.
161
162
163
Overview
Overview
Before start of this process, all individual devices that are involved in the fault clearance process of the protected object must have been tested as individuals and set in operation. The breaker must be ready for an open-close-open cycle. Scheme performance test is the final test that should be carried out before the protected object is taken into service. Due to the complexity in combination with already performed tests, it is not necessary to test all protection functions and all fault types in this process. The most important protection functions in the terminal for single line to earth fault and phase-phase fault could be used for the test. The shaping of the test process is dependent on the complexity of the design of the switchyard. Hereby follows some items which could be used as guidelines.
164
7.
Check that correct trip has been accomplished according to configuration and philosophy. Check that the autoreclosure have made an reclosing of the protected object. Check that activation of all other external devices have been accomplished according to configuration and protection philosophy. - Check, whenever applicable, that carrier receive signal has arrived at remote end. - Check, whenever applicable, that start of external disturbance recorder has been accomplished. - Check that event and alarm signals has been given etc. Check that no abnormal events have occurred. Notice the AR dead time and do corrections if needed.
Make a new fault case for permanent fault and repeat the steps 1 - 6 above.
Specially note that a permanent trip should occur after the last attempt according to the programming of the AR. It is recommended to repeat the procedure 1 - 6 for a protection function which detects earth-faults i.e. residual overcurrent protection.
165
166
167
Fault tracing
1
1.1
Fault tracing
Using information on the local HMI
If an internal fault has occurred, the local HMI displays information under: TerminalReport SelfSuperv Under these menus the indications of eventual internal failure (serious fault) or internal warning (minor problem) are listed. Shown as well, are the indications regarding the faulty unit according to table 24.
Table 24: HMI information
Signal name Activates summary signal Description
HMI information
Internal fail summary Internal warning summary Main processing module failed Main processing module warning (failure of clock, time synch., fault locator or disturbance recorder) A/D conversion module failed I/O module yy failed Internal clock is reset - Set the clock No time synchronisation
Also the internal signals, such as INT--FAIL and INT--WARNING can be connected to binary output contacts for signalling to a control room. In the Terminal Status - Information, the present information from the self-supervision function can be viewed. Indications of failure or warnings for each hardware module are provided, as well as information about the external time synchronisation and the internal clock. All according to table 25. Loss of time synchronisation can be considered as a warning only. The REx 5xx terminal has full functionality without time synchronisation.
168
Fault tracing
1.2
When an internal fault has occurred, extensive information can be retrieved about the fault from the list of internal events. The list is available in the TERM-STS Terminal Status part of the CAP tool. This time-tagged list has information with the date and time of the last 40 internal events. The internal events in the list do not only refer to faults in the terminal, but also to other activities, such as change of settings, clearing of disturbance reports and loss of external time synchronisation The following events are logged as Internal events:
Table 25: Internal events
Description Set/reset event
Event message
INT--FAILOff INT--FAILOn INT--WARNINGOff INT--WARNINGOn INT--CPUFAILOff INT--CPUFAILOn INT--CPUWARNOff INT--CPUWARNOn INT--ADCOff INT--ADCOn INT--IOnOff INT--IOn On INT--RTC Off INT--RTC On INT--TSYNC Off INT--TSYNC On DREP-MEMUSED On SETTING CHANGED DISTREP CLEARED
Main processing module non-fatal Reset event error status Set event A/D conversion module status Reset event Set event In/Out module No. n status Reset event Set event Real Time Clock (RTC) status Reset event Set event External time synchronisation sta- Reset event tus Set event >80% of the disturbance recording memory used Any settings in terminal changed All disturbances in Disturbance report cleared Set event
The events in the internal event list are time tagged with a resolution of 1 ms. This means that when using the PC for fault tracing, it provides information on the:
169
Fault tracing
Module that should be changed. Sequence of faults, if more than one unit is faulty. Exact time when the fault occurred.
170
Repair instruction
Repair instruction
Warning!
Never disconnect a secondary connection of current transformer circuit without short-circuiting the transformers secondary winding. Operating a current transformer with the secondary winding open will cause a massive potential build-up that may damage the transformer and may cause injuries to humans.
Warning!
Never connect or disconnect a wire and/or a connector to or from a terminal during normal service. Hazardous voltages and currents are present that may be lethal. Operation may be disrupted and terminal and measuring circuitry may be damaged. An alternative is to open the terminal and send only the faulty circuit board to ABB for repair. When a printed circuit board is sent to ABB, it must always be placed in a metallic, ESD-proof, protection bag. The user can also purchase separate modules for replacement.
Note!
Strictly follow the company and country safety regulations.
Caution!
Always use a conductive wrist strap connected to protective earth when replacing modules. Electrostatic discharge (ESD) may damage the module and terminal circuitry. Most electronic components are sensitive to electrostatic discharge and latent damage may occur. Please observe usual procedures for handling electronics and also use an ESD wrist strap. A semi-conducting layer must be placed on the workbench and connected to earth. Disassemble and reassemble the REx 5xx terminal accordingly: 1. Switch off the dc supply. 2. Short-circuit the current transformers and disconnect all current and voltage connections from the terminal. 3. Disconnect all signal wires by removing the female connectors. 4. Disconnect the optical fibres. 5. Unscrew the main back plate of the terminal. 6. If the transformer module is to be changed unscrew the small back plate of the terminal. 7. Pull out the faulty module. 8. Check that the new module has correct identity number.
171
Repair instruction
9. Check that the springs on the card rail have connection to the corresponding metallic area on the circuit board when the new module is inserted. 10. Reassemble the terminal. If the REx 5xx terminal has the optional increased measuring accuracy, a file with unique calibration data for the transformer module is stored in the Main processing module. Therefore it is not possible to change only one of these modules with maintained accuracy.
172
Repair support
Repair support
If a REx 5xx terminal needs to be repaired, the whole terminal must be removed and sent to ABB Logistic Center. Before returning the material, an inquiry must be sent to ABB Logistic Center. e-mail: [email protected]
173
Repair support
174
ABB Power Technologies AB Substation Automation Products SE-721 59 Vsters Sweden Telephone: +46 (0) 21 34 20 00 Facsimile: +46 (0) 21 14 69 18 Internet: www.abb.com/substationautomation Printed on recycled and ecolabelled paper at Elanders Novum