Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.1, 2CDG 110 0xx R0011
The 16 A AC1 Switch Actuators are modular installation devices in proM design for installation in the distribution board on 35 mm mounting rails. The connection to the ABB i-bus EIB / KNX is implemented via Bus Connection Terminal. The device does not require an additional power supply. The actuators switch up to 8 independent electrical loads via potential free contacts. The outputs are connected
using screw terminals with combination drive head screws. Each output is controlled separately via the EIB / KNX. The switch actuators can be manually operated via an operating element which simultaneously indicates the switch status. The actuators are particularly suitable for switching ohmic loads.
6
Technical data Power supply Operating voltage Current consumption EIB / KNX Power consumption EIB / KNX SA/S - type Number of contacts (potential free) Un rated voltage In rated current Power loss per device at max. load AC1 operation (cos = 0.8) EN 60 947-4-1 Fluorescent lighting load AX to EN 60669-1 Minimum switching performance 21...30 V DC, made available by the bus < 12 mA Max. 250 mW 2.16.1 4.16.1 8.16.1 2 4 8 250 / 440 V AC (50/60 Hz) 16 A 16 A 16 A 2.0 W 4.0 W 8.0 W 16 A / 230 V 16 A / 250 V (70 F) 2)
100 mA / 12 V 100 mA / 24 V DC current switching capacity (ohmic load) 16 A / 24 V DC Mechanical endurance > 3 x 106 Electrical endurance to IEC 60 947-4-1 AC1(240 V/cos = 0.8) > 105 Max. number of relay position changes per output and 2.16.1 4.16.1 60 30
minute, if all relays are switched simultaneously. The position changes should be distributed equally within the minute. Max. number of relay position changes per output, and minute if only one relay is switched
Connections
120 120 120 EIB / KNX Bus Connection Terminal, 0.8 mm , single core Load current circuits (2 terminals per contact) Screw terminal with universal head (PZ 1) 0.2...4 mm2 finely stranded, 2x (0.2 2.5 mm2) 0.2...6 mm2 single core, 2x (0.2 4 mm2) Tightening torque Max. 0.8 Nm Red LED and EIB / KNX push button for assignment of the physical address Contact position indication Relay lever IP 20 to EN 60 529 II to EN 61 140 Overvoltage category III to EN 60 664-1 Pollution degree 2 to EN 60 664-1
The specifications apply only after the bus voltage has been applied to the device for at least 30 seconds. The typical elementary delay of the relay is approx. 20 ms. 2) The maximum inrush-current peak (see table 2) may not be exceeded.
1)
SA/S x.16.1
SA/S x.16.1
Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.1, 2CDG 110 0xx R0011
Design
SELV 24 V DC (safety extra low voltage) Operation 5 C ... + 45 C Storage 25 C ... + 55 C Transport 25 C ... + 70 C Modular DIN-Rail Component (MDRC) Modular installation device, ProM SA/S - type 2.16.1 4.16.1 8.16.1 Dimensions (H x W x D) 90 x W x 64 Width W in mm 36 72 144 Mounting width (modules at 18 mm) 2 4 8 Mounting depth in mm 64 64 64 In kg 0.15 0.25 0.46 On 35 mm mounting rail EN 60 715 As required Plastic housing, grey EIB / KNX nach EN 50 090-2-2 Certification In accordance with the EMC guideline and low voltage guideline
Lamp loads Low-volt halogen lamps Dulux lamp Mercury-vapour lamp Switching performance (switching contact) Number of electronic ballasts (T5/T8, single element) 1) Lamps Fluorescent lamp T5 / T8
1)
Incandescent lamp load Uncompensated luminaire Parallel compensated DUO circuit Inductive transformer Electronic transformer Halogen lamp 230V Uncompensated luminaire Parallel compensated Uncompensated luminaire Parallel compensated Max. peak inrush-current Ip (150 s) Max. peak inrush-current Ip (250 s) Max. peak inrush-current Ip (600 s) 18 W (ABB EVG 1x58 CF ) 24 W (ABB EVG-T5 1x24 CY) 36 W (ABB EVG 1x36 CF) 58 W (ABB EVG 1x58 CF) 80 W (Helvar EL 1x80 SC)
2330 W 2300 W 1500 W 1500 W 1200 W 1500 W 2300 W 1100 W 1100 W 2000 W 2000 W 400 A 320 A 200 A 23 23 14 11 10
For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the electronic ballasts.
Application programs Type SA/S 2.16.1 SA/S 4.16.1 SA/S 8.16.1 Name Switch, 2f16/1 Switch, 4f16/1 Switch, 8f16/1 Max. number of communication objects 34 64 124 Max. number of group addresses 254 254 254 Max. number of associations 254 254 254
SA/S x.16.1
SA/S x.16.1
Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.1, 2CDG 110 0xx R0011
Note:
The programming requires the EIB Software Tool ETS2 V1.3 or higher. If the ETS3 is used a .VD3 type file must be imported. The application program is located within the ETS2 / ETS3 in the category ABB/output/Binary output, x-fold/switch, xf16/1 (x = 2, 4 or 8, number of outputs). Detailed information about the application can be found in the product manual for the Switch Actuators SA/S. This manual can be free downloaded under www.abb.de/eib.
Wiring diagram
L1 L2 L3 N L1 L2 L3 N
A 2 B 4
6
1
A 2
B 4
C 6
D 8
E 10
11
F 12
13
G 14
15
H 16
0.8 Nm
0.8 Nm
SA/S 2.16.1
A
O I
SA/S 8.16.1
B
O I
5 1
2CDC 072 094 F0005
A
O I
B
O I
C
O I
D
O I
E
O I
F
O I
G
O I
H
O I
5 1 2 3 4
2CDC 072 101 F0005 2CDC 072 003 F0005
ABB i-bus
U n = 250 / 440 V~ I n = 16 A
ABB i-bus
U n = 250 / 440 V~ In = 16 A
2 3 4
1 2 3 4
5 Contact position indicatior and manual operation 6 Load current circuits, per circuit 2 connection terminals
Note:
All-pole disconnection must be observed in order to avoid dangerous contact voltage which can develop via loads in other phases.
Dimension drawings
58 43.5 6.5
1
10
11
12
13
14
15
16
0.8 Nm
SA/S 8.16.1
A B
O I O I
C
O I
D
O I
E
O I
F
O I
G
O I
H
O I
90
45
ABB i-bus
Un = 250 / 440 V~ In = 16 A
SA/S x.16.1
SA/S x.16.1
Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.1, 2CDG 110 0xx R0011
SA/S x.16.1
SA/S x.16.1