Bs 6700 Pipe Sizing
Bs 6700 Pipe Sizing
Bs 6700 Pipe Sizing
qxd
7/24/08
9:35
Page 174
Chapter 5
Pipe sizing
Pipes and ttings should be sized so that the ow rates for individual draw-offs are equal to the design ow rates shown in table 5.1. During simultaneous discharges, ows from taps should not be less than the minimum ow rates shown in table 5.1. BS 6700 recommends that ow velocities should not exceed 3 m/s. BS EN 805 recommends 0.5 m/s to 2 m/s with a maximum of 3.5 m/s in exceptional circumstances. Filling times for cisterns may range from 1 to 4 hours depending on their capacity and the ow rate available from the local water supply. In dwellings the lling time should not exceed 1 hour. Design ow rates may be calculated by dividing the cistern capacity by the required lling time.
Table 5.1 Design ow rates and loading units Design ow rate l/s WC ushing cistern single or dual ush to ll in 2 minutes WC trough cistern 1 Wash basin tap size DN 15 2 Spray tap or spray mixer Bidet 3 Bath tap, nominal size DN 20 4 Bath tap, nominal size 1 DN 25 Shower head (will vary with type of head)
1 Sink tap, nominal size DN 15 2
Outlet tting
Minimum ow rate l/s 0.05 0.10 0.10 0.03 0.10 0.20 0.40 0.10 0.10 0.20 0.40 0.15 0.10 0.002 1.2
0.13 0.15 per WC 0.15 per tap 0.05 per tap 0.20 per tap 0.30 0.60 0.20 hot or cold 0.20 0.30 0.60 0.20 hot or cold 0.15 0.004 per position served 1.5
3 4
DN 20
Sink tap, nominal size 1 DN 20 Washing machine size DN 15 Dishwasher size DN 15 Urinal ushing cistern Pressure ushing valve for WC or urinal
Notes: (1) Flushing troughs are advisable where likely use of WCs is more than once per minute. (2) Mixer ttings use less water than separate taps, but this can be disregarded in sizing. (3) Flow rates to shower mixers vary according to type tted. Manufacturers should be consulted. (4) Manufacturers should be consulted for ow rates to washing machines and dishwashers for other than a single dwelling. (5) For cistern fed urinals demand is very low and can usually be ignored. Alternatively, use the continuous ow. (6) Loading units should not be used for outlet ttings having high peak demands, e.g. those in industrial installations. In these cases use the continuous ow. (7) BS 6700 does not give loading units for sink tap DN 20 or pressure ushing valve for WCs or urinals.
174
HAC_C05.qxd
7/24/08
9:35
Page 175
Correct pipe sizes will ensure adequate ow rates at appliances and avoid problems caused by oversizing and undersizing; see gure 5.1. Oversizing will mean: additional and unnecessary installation costs; delays in obtaining hot water at outlets; increased heat losses from hot water distributing pipes. Undersizing may lead to: inadequate delivery from outlets and possibly no delivery at some outlets during simultaneous use; some variation in temperature and pressure at outlets, especially showers and other mixers; some increase in noise levels.
head
(b) available head (pressure) water main at thethe storage cistern from at point of delivery = vertical distance in metres from water line in cistern to point under consideration = head at main minus height above main Available head = 20 m 4 m (mains supply) = 16 m head Available head (from cistern) head e.g. 4 m
CWSC
point of delivery
In smaller, straightforward installations such as single dwellings, pipes are often sized on the basis of experience and convention. In larger and more complex buildings, or with supply pipes that are very long, it is necessary to use a recognized method of calculation such as that shown in sections 5.1 and 5.2.
head
HAC_C05.qxd
7/24/08
9:35
Page 176
BS EN 806-3 gives an alternative simplied method of pipe sizing that can be used for standard installations.
5.1
HAC_C05.qxd
7/24/08
9:35
Page 177
8000
30 25
(b) Continuous ows. For some appliances, such as automatic ushing cisterns, the ow rate must be considered as a continuous ow instead of applying probability theory and using loading units. For such appliances the full design ow rate for the outlet tting must be used, as given in table 5.1. However, in the example shown in gure 5.3, the continuous ow for the two urinals of 0.008 l/s (from table 5.1) is negligible and can be ignored for design purposes. (c) Design ow rate. The design ow rate for a pipe is the sum of the ow rate determined from loading units (a) and the continuous ows (b). Determine the effective pipe length (3) (d) Find the measured pipe length. Figure 5.4 is an example showing how the measured pipe length is found.
5 WCs
6 wash basins
cleaners sink
2 1.5 12 wash basins 10 WCs 2 urinal bowls 2 cleaners sinks Total loading units Flow rate in litres per second 11 2 2 3 = = = = 18 20 6 44
Therefore, from figure 5.2, the required flow rate for the system is 0.7 l/s. Figure 5.3 Example of use of loading units
Assumed pipe diameter 20 mm. 1m double check valve assembly stopvalve 0.5 m elbows
There is no need to consider both branch pipes to taps. Example of measured pipe length
HAC_C05.qxd
7/24/08
9:35
Page 178
Table 5.2
Equivalent pipe lengths (copper, stainless steel and plastics) Equivalent pipe length Elbow m 0.5 0.8 1.0 1.4 1.7 2.3 3.0 3.4 Tee m 0.6 1.0 1.5 2.0 2.5 3.5 4.5 5.8 Stopvalve m 4.0 7.0 10.0 13.0 16.0 22.0 34.0 Check valve m 2.5 4.3 5.6 6.0 7.9 11.5
Bore of pipe mm 12 20 25 32 40 50 65 73
Notes: (1) For tees consider change of direction only. For gate valves losses are insignicant. (2) For ttings not shown, consult manufacturers if signicant head losses are expected. (3) For galvanized steel pipes in a small installation, pipe sizing calculations may be based on the data in this table for equivalent nominal sizes of smooth bore pipes. For larger installations, data relating specically to galvanized steel should be used. BS 6700 refers to suitable data in the Plumbing Engineering Services Design Guide published by the Institute of Plumbing.
(e, f) Find the equivalent pipe lengths for ttings and draw-offs. For convenience the frictional resistances to ow through ttings are expressed in terms of pipe lengths having the same resistance to ow as the tting. Hence the term equivalent pipe length (see table 5.2). For example, a 20 mm elbow offers the same resistance to ow as a 20 mm pipe 0.8 m long. Figure 5.5 shows the equivalent pipe lengths for the ttings in the example in gure 5.4. (g) Effective pipe length. The effective pipe length is the sum of the measured pipe length (d) and the equivalent pipe lengths for ttings (e) and draw-offs (f). Therefore, for the example shown in gure 5.4 the effective pipe length would be: Measured pipe length Equivalent pipe lengths elbows 2 0.8 tee 1 1.0 stopvalve1 7.0 taps 2 3.7 check valves 2 4.3 Effective pipe length 4.75 m = = = = = 1.6 m 1.0 m 7.0 m 7.4 m 8.6 m
= 30.35 m
Permissible loss of head (pressure) (4) Pressure can be expressed in the following ways. (i) (ii) In pascals, the pascal (Pa) being the SI unit for pressure. As force per unit area, N/m2. 1 N/m2 = 1 pascal (Pa).
HAC_C05.qxd
7/24/08
9:35
Page 179
Using the example from figure 5.4: 20 mm elbow = 0.8 m pipe length
Figure 5.5
(iii) (iv)
As a multiple of atmospheric pressure (bar). Atmospheric pressure = 100 kN/m2 = 100 kPa = 1 bar. As metres head, that is, the height of the water column from the water level to the draw-off point. 1 m head = 9.81 kN/m2 = 9.81 kPa = 98.1 mb.
In the sizing of pipes, any of these units can be used. BS 6700 favours the pascal. However, this book retains the use of metres head, giving a more visual indication of pressure that compares readily to the height and position of ttings and storage vessels in the building. (h) Available head. This is the static head or pressure at the pipe or tting under consideration, measured in metres head (see gure 5.1). (i) Head loss through pipes. The loss of head (pressure) through pipes due to frictional resistance to water ow is directly related to the length of the pipe run and the diameter of the pipe. Pipes of different materials will have different head losses, depending on the roughness of the bore of the pipe and on the water temperature. Copper, stainless steel and plastics pipes have smooth bores and only pipes of these materials are considered in this section. (j) Head loss through ttings. In some cases it is preferable to subtract the likely resistances in ttings (particularly draw-offs) from the available head, rather than using equivalent pipe lengths. Table 5.3 gives typical head losses in taps for average ows compared with equivalent pipe lengths. Figures 5.6 and 5.7 provide a method for determining head losses through stopvalves and oat-operated valves respectively. Note Where meters are installed in a pipeline the loss of head through the meter should be deducted from the available head.
HAC_C05.qxd
7/24/08
9:35
Page 180
Table 5.3
Typical head losses and equivalent pipe lengths for taps Flow rate l/s Head loss m 0.5 0.8 0.8 1.5 Equivalent pipe length m 3.7 3.7 11.8 22.0
1 G DN 15 2 1 G DN 15 2 3 G DN 20 4
G 1 DN 25
8 7 6 5 4 3 10 8 6 5 4 2 3 2 11/4 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 Head loss in metres (wall friction gradient) 1 0.8 0.6 0.5 0.4 0.3
3
11/2
/4
0.2
/2
Note Gate valves and spherical plug valves offer little or no resistance to flow provided they are fully open. Figure 5.6 Head loss through stopvalves
HAC_C05.qxd
7/24/08
9:35
Page 181
20 15 Millimetres 10 Inches 8 6 5 4 3 2
11/4 1
15 3 5 1
/16
/4 /8 /2 /8 1 0.8 0.6 0.5 0.4 0.3 0.2 Flow through orifice in litres per second
10 8
6 5 4
1 3
/4 /16
11 20 25 30 40 50
/8
0.01 Based on Q = AV 0.75 V = 2gH where Q is flow (l/s) A is cross sectional area of pipe (m2) V is velocity (m/s) g is acceleration due to gravity (m/s2) H is head of water (m)
Figure 5.7
HAC_C05.qxd
7/24/08
9:35
Page 182
(k) Permissible head loss. This relates the available head to the frictional resistances in the pipeline. The relationship is given by the formula: Permissible head loss (m/m run) = Available head (m) Effective pipe length (m)
This formula is used to determine whether the frictional resistance in a pipe will permit the required ow rate without too much loss of head or pressure. Figure 5.8 illustrates the permissible head loss for the example in gure 5.4.
Pressure at taps 45 m head tee double check valve assembly elbows stopvalve 20 mm pipeline Flow rate for 2 taps 0.4 l/s pipe bend
draw-off taps
Determine the pipe diameter (5) In the example in gure 5.4 a pipe size of 20 mm has been assumed. This pipe size must give the design ow rate without the permissible head loss being exceeded. If it does not, a fresh pipe size must be assumed and the procedure worked through again. Figure 5.9 relates pipe size to ow rate, ow velocity and head loss. Knowing the assumed pipe size and the calculated design ow rate, the ow velocity and the head loss can be found from the gure as follows. (1) Draw a line joining the assumed pipe size (20 mm) and the design ow rate (0.4 l/s). (2) Continue this line across the velocity and head loss scales. (3) Check that the loss of head (0.12 m/m run) does not exceed the calculated permissible head loss of 1.48 m/m run. (4) Check that the ow velocity (1.4 m/s) is not too high by referring to table 5.4.
HAC_C05.qxd
7/24/08
9:35
Page 183
1 0.80 0.60 0.50 0.40 0.30 0.20 3 2.5 0.10 0.08 0.06 0.05 0.04 0.03 0.02 Velocity in metres per second 0.5 0.01 0.008 0.007 0.006 0.005 0.004 0.003 0.002 0.1 0.25 1.0 0.75 2 1.5
50 40 30 6 Formula applied between these limits only 5 4 20 10 8 6 5 4 3 2 1.0 0.8 0.6 0.5 0.4 0.3 0.2 0.1 0.08 0.06 0.05
76.1 67
80 75 70 65 60 55
54
50 45
42
40 35
22
20
Lamonts smooth pipe formula S3: V = 0.5545 d 0.6935 i 0.5645 Where V is velocity (m/s) d is diameter (mm) i is hydraulic gradient
0.0001
Notes Figures shown are for cold water at 12C. Hot water will show slightly more favourable head loss results. BS 6700 gives head loss in kPa. 1 m head = 9.81 kPa. Figure 5.9 Determination of pipe diameter
HAC_C05.qxd
7/24/08
9:35
Page 184
Table 5.4
Maximum recommended ow velocities Flow velocity Pipes readily accessible m/s 3.0 3.0 2.5 2.0 Pipes not readily accessible m/s 2.0 1.5 1.3 1.0
Water temperature
C 10 50 70 90 Note
5.2
HAC_C05.qxd
7/24/08
9:35
Page 185
Work through the calculation sheet See gure 5.11, using the data shown in gures 5.10 and 5.12.
CWSC
loading units
2.8 m
2 + 1.5 + 10 + 16.5 = 30
2.4 m
1m
2.4 m
Assume draw-offs on each branch all to be at the same level. Size for largest draw-off at each branch, i.e. bath. 7 wc wb b 0.5 m 2m
2.4 m 1m
2 + 1.5 + 10 = 13.5
4 tap 0.5 m
1m 1m 0.3 l/s
Bib tap at 0.3 l/s in frequent use. Note Figure is not to scale for convenience, water level in cistern taken to be at base of cistern. Servicing valves assumed to be full-flow gate valves having no head losses. Refer also to figure 5.12. Figure 5.10 Pipe sizing diagram
HAC_C05.qxd
Figure 5.11 Enter pipe reference on calculation sheet Determine loading unit (table 5.1) Convert loading units to flow rate (figure 5.2) (3) Flow rate (l/s) (4) Pipe size (mm diameter) (5) Loss of head (m/m run) (6) Flow velocity (m/s) (7) Measured pipe run (m) (8) Equivalent pipe length (m) (9) Effective pipe length (m) (10) Head consumed (m) (11) Progressive head (m) (12) Available head (m) (13) Final pipe size (mm) Compare progressive head with available head to confirm pipe diameter or not Notes (14) Remarks Make assumption as to pipe size (inside diameter) Work out frictional resistance per metre (figure 5.9) Determine velocity of flow (figure 5.9) Measure length of pipe under consideration Consider frictional resistances in fittings (table 5.2 and figures 5.6 and 5.7) Add totals in columns 7 and 8 (2) Loading units (1) Pipe reference Calculation sheet Note Calculation sheet explanation of use Head consumed multiply column 5 by column 9 Add head consumed in column 10 to progressive head in previous row of column 11 Record available head at point of delivery If, for any pipe or series of pipes, it is found that the assumed pipe size gives a progressive head that is in excess of the available head, or is noticeably low, it will be necessary to repeat the sizing operation using a revised assumed pipe diameter. This is an example of a suitable calculation sheet with explanatory notes.
HAC_C05.qxd
7/24/08
9:35
Page 187
Estimated maximum demand = 1.4 l/s Probable demand = 0.85 l/s Percentage demand = probable demand 100 estimated maximum demand 1 0.85 100 = 60% 1.4 1
Therefore only 60% of the installation need be considered. For example, if we were designing for a multi-storey building 20 storeys high, only the rst 12 storeys need to be calculated. However, in the example followed here, the whole system has been sized because the last tting on the run has a high ow rate in continuous use. For branches only the pipes to the largest draw-off, i.e. the bath tap, need be sized. Calculation sheet
1 5 2 6 3 7 4
32 20 25 20 25 20 20
Refer also to figure 5.10. Figure 5.12 Calculation sheet example of use
(14) Remarks
HAC_C05.qxd
7/24/08
9:35
Page 188
5.3
However, in clause 5.3.9.4 it recommends a minimum storage capacity of 230 l where the cistern supplies both cold water outlets and hot water apparatus, which was a requirement of byelaws in the past. The author still favours the old byelaw requirements, which are more specic and which still seem to be the normal capacity installed. Cold water storage cistern Feed cistern 115 l minimum No minimum but should be equal to the capacity of the hot store vessel supplied Combined feed and storage cistern 230 l minimum For larger buildings the capacity of the cold water storage cistern depends on: type and use of buildings; number of occupants; type and number of ttings; frequency and pattern of use; likelihood and frequency of breakdown of supply.
These factors have been taken into account in table 5.5, which sets out minimum storage capacities in various types of building to provide a 24-hour reserve capacity in case of mains failure.
HAC_C05.qxd
7/24/08
9:35
Page 189
Assuming 12-hour ll time, the design ow rate to the cistern would be: Design ow rate = 17 450 l cistern capacity 12 hours = 17 540 (12 3600 seconds) = 0.4 l/s
Table 5.5 Recommended minimum storage of hot and cold water for domestic purposes Minimum cold water storage litres (l) 90 per bed space 200 per bed space 45 per employee 40 per employee 7 per meal 15 per pupil 20 per pupil 90 per pupil 135 per bed space 120 per bed space 135 per bed space Minimum hot water storage litres (l) 32 per bed space 45 per bed space 4.5 per employee 4.0 per employee 3.5 per meal 4.5 per pupil 5.0 per pupil 23 per pupil 25 per bed space 45 per bed space 45 per bed space
Type of building
Hostel Hotel Ofce premises: with canteen facilities without canteen facilities Restaurant Day school: nursery # primary $ secondary # technical $ Boarding school Childrens home or residential nursery Nurses home Nursing or convalescent home Note
Minimum cold water storage shown includes that used to supply hot water outlets.
5.4
The feed cistern should have a capacity at least equal to that of the hot storage vessel. Information on storage capacities for larger buildings is given in table 5.5 using data based on the Institute of Plumbings Plumbing Engineering Services Design Guide. The calculations are similar to those in section 5.3 for the minimum cold water storage capacity in larger buildings, and require the number of people to be multiplied by the storage per person, shown in table 5.5. BS 6700 takes a different approach to the sizing of hot water storage and suggests that when sizing hot water storage for any installation, account must be taken of the following: pattern of use; rate of heat input to the stored water (see table 5.6);
HAC_C05.qxd
7/24/08
9:35
Page 190
recovery period for the hot store vessel; any stratication of the stored water.
Typical heat input values Heat input kW 3 3 6 10 10 15
Electric immersion heater Gas-red circulator Small boiler and direct cylinder Medium boiler and indirect cylinder Directly gas-red storage hot water heater (domestic type) Large domestic boiler and indirect cylinder
Stratication (see gure 3.41) means that the hot water in the storage vessel oats on a layer of cold feed water. This enables hot water to be drawn from the storage vessel without the incoming cold feed water mixing appreciably with the remaining hot water. In turn, this allows a later draw-off of water at a temperature close to the design storage temperature, with less frequent reheating of the contents of the storage vessel and savings in heating costs and energy. Stratication is most effective when cylinders and tanks are installed vertically rather than horizontally, with a ratio of height to width or diameter of at least 2:1. The cold feed inlet should be arranged to minimize agitation and hence mixing, by being of ample size and, if necessary, tted with a bafe to spread the incoming water. Stratication is used to good effect in off-peak electric water heaters (see gure 5.13). In this case no heat is normally added to the water during the daytime use and consequently very little mixing of hot and cold water takes place. In other arrangements the heating of the water will induce some mixing.
HAC_C05.qxd
7/24/08
9:35
Page 191
(a) Bottom entry heater more even temperature throughout cylinder With a bottom entry immersion heater mixing will occur when the water is being heated.
(b) Top entry heater hot at top warm cold at bottom With top entry immersion heater stratification will prevent mixing.
(c) Twin entry immersion heater hot warm With a twin entry immersion heater the top entry element can provide economical energy consumption for normal use with the bottom entry element operating when large quantities of water are needed, for example, for bathing and washing. With off-peak heaters the top element can be brought into use during on-peak periods when needed to top up hot water, and stratification will ensure that on-peak electricity is not used to excess.
cold
Figure 5.13
Effects of stratication
The application of this formula to the sizing of hot water cylinders is best illustrated by the following examples, in which gures have been rounded. In these examples a small dwelling with one bath installed has been assumed. Maximum requirement: 1 bath (60 l at 60C plus 40 l cold water) plus 10 l hot water at 60C for kitchen use, followed by a second bath ll after 25 min. Thus a draw-off of 70 l at 60C is required, followed after 25 min by 100 l at 40C, which may be achieved by mixing hot at 60C with cold at 10C.
Example 1
Good stratication could be obtained, for example, by heating with a top entry immersion heater. With a rate of heat input of 3 kW, the time to heat the 60 l for the second bath from 10C to 60C is: M = VT/(14.3P) M = (60 50)/(14.3 3) M = 70 min
HAC_C05.qxd
7/24/08
9:35
Page 192
Since the second bath is required after 25 min, it has to be provided from storage. But in the 25 min the volume of water heated to 60C is: V = M (14.3)/T V = (25 14.3 3)/50 V = 21 l Therefore the minimum required storage capacity is: 70 + 6 21 = 109 l
Example 2
Good mixing of the stored water would occur, for example, with heating by a primary coil in an indirect cylinder. Immediately after drawing off 70 l at 60C for the rst bath and kitchen use, the heat energy in the remaining water plus the heat energy in the 70 l replacement at 10C equals the heat energy of the water in the full cylinder. The heat energy of a quantity of water is the product of its volume and temperature. Then, if V is the minimum size of the storage cylinder and T is the water temperature in the cylinder after relling with 70 l at 10C: (V 70) 60 + (70 10) = VT T = (60V 4200 + 700)/V T = (60V 3500)/V T = 60 3500/V The second bath is required after 25 min. Hence, with a rate of heat input of 3 kW: 25 = VT/(14.3 3) and the temperature rise T = (25 14.3 3)/V and T = 1072.5/V A temperature of at least 40C is required to run the second bath. Therefore the water temperature of the relled cylinder after the rst draw-off of 70 l, plus the temperature rise after 25 min, must be at least 40C, or: (60 3500/V) + (1072.5V) = 40 (or more) 60 2427.5/V = 40 20 = 2427.5/V V = 122 l These calculations, which may be carried out for any situation, show the value of promoting stratication wherever possible. They also show the savings in storage capacity that can be made, without affecting the quality of service to the user, by increasing the rate of heat input to the water. Results of similar calculations are shown in table 5.7 and are taken from BS 6700.
HAC_C05.qxd
7/24/08
9:35
Page 193
Table 5.7
Hot water storage vessels minimum capacities Dwelling with 1 bath With stratication litres (l) 109 88 70 70 With mixing litres (l) 122 88 70 70 Dwelling with 2 baths* With stratication litres (l) 165 140 130 120 With mixing litres (l) 260 200 130 130
* Maximum requirement of 130 l drawn off at 60C (2 baths plus 10 l for kitchen use) followed by a further bath (100 l at 40C) after 30 min.