FM-2160 Ve FM-3060 Servis Manueli
FM-2160 Ve FM-3060 Servis Manueli
FM-2160 Ve FM-3060 Servis Manueli
SERVICE MANUAL
MODEL: FM-2160N3L/M/Q FM-3060N4L/M/Q
Contents
Functions...................................................................................................................................... 3 Product Specifications .................................................................................................................6 Dimensions....................................................................................................................................8 Wiring Diagram ...........................................................................................................................10 Refrigeration Cycle Diagram ......................................................................................................11 Operation Details ........................................................................................................................12 Display Function .........................................................................................................................17 Self-diagnosis Function .............................................................................................................17 Installation ...................................................................................................................................18 Operation .....................................................................................................................................32 Disassembly of the parts (Indoor Unit).....................................................................................34 Valve service(3-way) ...................................................................................................................36 Cycle Troubleshooting Guide ....................................................................................................40 Electronic Parts Troubleshooting Guide ..................................................................................41 Electronic Control Device ..........................................................................................................54 Schematic Diagram.....................................................................................................................57 Exploded View and Replacement Parts List.............................................................................59
-2-
Functions
Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature sensor. (THERMISTOR) Room temperature control Maintains the room temperature in accordance with the Setting Temp. Starting Current Control Indoor fan is delayed for 5 seconds at the starting. Time Delay Safety Control Restarting is inhibited for approx. 3 minutes. Indoor Fan Speed Control High, Med, Low, Chaos Operation indication Lamps (LED) --- Lights up in operation --- Lights up in Sleep Mode --- Lights up in Timer Mode --- Lights up in Deice Mode
Soft Dry Operation Mode Intermittent operation of fan at low speed. Sleep Mode Auto Control The fan is switched to low(Cooling), med(Heating) speed. The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Natural Air Control by CHAOS Logic The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed. Airflow Direction Control The louver can be set at the desired position or swing up and down automatically. Deice (defrost) control (Heating) Both the indoor and outdoor fan stops during deicing. Hot start after deice ends. Hot-start Control (Heating) The indoor fan stops until the evaporator piping temperature will be reached at 28C.
-3-
Outdoor Unit
Power relay control If power is on, it will operate to chage capacitor on controller and power relay will operate after about 10sec. Comp. Freq. control The final operating freq. of comp. is set the lowest freq. that limited outdoor temp., discharge pipe temp., target freq., owing to CT. Overheatng. Protection(Power module)
Freq. speed control(up/down speed) V/F control It will be changed the drive voltage of comp. according to operating frequency. Total current control (over current protection) DC peak current control 4 way valve control It is only operated in the heating operation mode except defrosting operation. Outdoor fan motor control High speed/Low speed Discharge pipe temp. control Overpressure protection
-4-
Remote Controller
Operation ON/OFF
) )
Fan Speed Selection (Low) Room, Temperature Display : (High: 39C Temperature Setting
TEMPERATURE HIGH LOW
(Med)
(High)
(CHAOS)
LOW : 11C)
Cooling
JET COOL
Timer Selection
ON OFF
ON
Timer Setting
SET
Timer Cancel
CANCEL
-5-
Product Specifications
Model Item Cooling Capacitor (Indoor) Cooling Capacitor (Outdoor) Heating Capacitor (Indoor) Heating Capacitor (Outdoor) Moisture Removal Power Supply Air Circulation , V, Hz Indoor, Max Outdoor, Max Indoor, High Noise Level (1m) Indoor, Med Indoor, Low Outdoor, Max Input Running Current Motor Output Dimensions Net Weight Refrigerant Remocon Type Service Valve Sleeping Operation Connection Cable Luquid Gas inch(mm) 3/8"(9.52) Cooling Heating Cooling Heating Indoor Outdoor Indoor Outdoor Indoor Outdoor R-22 W A W mm (W*D*H) Kg g O O L.C.D Wireless 1/4"(6.35) 3/8"(9.52) O O 1/2"(12.7) 1/2"(12.7) 7 7 64 2,100 O O 7.5 802 x 165 x 262 7.5 68 802 x165 x262 888 x 170 x 287 9 1,080 x 181 x314 12 870 x 320 x 655 dB(A)1 CMM 6.5 36 33 30 7.0 56 38 34 32 54 820 ~ 2,690 1,060 ~ 2,700 4.4 ~ 12.7 5.4 ~ 12.8 13 22 40 38 36 44 41 39 Indoor Outdoor Btu/h W Btu/h W Btu/h W Btu/h W l/h 1.0 1.2 1,220-24,050 9.0 13 8,000 2,344 7,000 2,051 LMN0760NL/M/Q LMN0960NL/M/Q LMN1260NL/M/Q FMN1860NL/M/Q FM-2160N3L/M/Q 9,000 2,673 2,051 ~ 7,034 10,000 2,930 2,051 ~ 7,649 1.5 2.5 13,800 4,044 19,000 5,567 12,000 3,517 18,000 5,274
7,000 ~ 24,000
7,000 ~ 26,100
-6-
Product Specifications
Model Item Cooling Capacitor (Indoor) Cooling Capacitor (Outdoor) Heating Capacitor (Indoor) Heating Capacitor (Outdoor) Moisture Removal Power Supply Air Circulation , V, Hz Indoor, Max Outdoor, Max Indoor, High Noise Level (1m) Indoor, Med Indoor, Low Outdoor, Max Input Running Current Motor Output Dimensions Net Weight Refrigerant Remocon Type Service Valve Sleeping Operation Connection Cable Luquid Gas inch(mm) 3/8"(9.52) 3/8"(9.52) Cooling Heating Cooling Heating Indoor Outdoor Indoor Outdoor Indoor Outdoor R-22 W A W mm (W*D*H) Kg g O O 1/4"(6.35) 1/2"(12.7) O O 1/2"(12.7) 7 7 7.5 802 x 165 x 262 7.5 802 x 165 x 262 dB(A)1 CMM 6.5 36 33 30 7.0 38 34 32 Indoor LMN0760NL/M/Q LMN0960NL/M/Q LMN1260NL/M/Q FMN1860NL/M/Q FMN2460NL/M/Q Outdoor Btu/h W Btu/h W Btu/h W Btu/h W l/h 1.0 1.2 8,000 2,344 10,000 2,930 7,000 2,051 9,000 2,637 FM-3060N4L/M/Q 12,000 3,517 7,000 ~ 32,000 2,051 ~ 9,378 13,800 4,044 7,000 ~ 35,000 2,051 ~ 10,257 1.5 1, 220-240, 50 9.0 60 40 38 36 56 820 ~ 3,600 1,060 ~ 3,300 4.4 ~ 18.5 5.4 ~ 16.5 13 68 888 x 170 x 287 1,080 x 181 x 314 1,080 x 181 x 314 870 x 320 x 800 9 75 2,350 O L.C.D Wireless 3/8"(9.52) 5/8"(15.88) O O 12 12 22 32 44 41 39 47 44 41 13 16 2.5 2.8 19,000 5,567 2,600 7,620 18,000 5,274 22,900 6,711
-7-
Dimensions
1. Indoor Unit
D
"D"
20mm
Center
A A
"C"
20mm
Center
Hole Center
70mm
(7K, 9K)
MODEL DIM W H D mm mm mm 802 262 165
(12K)
(18K, 24K)
-8-
2. Outdoor Unit
W
L3
L2
L1
L10 L10 L9 L9
L4
L6
L5
L7
L8
FM-2160N3L/M/Q
870 655 320 370 25 630 25 546 160 160 53 50 40
FM-3060N4L/M/Q
870 800 320 370 25 775 25 546 160 160 53 50 40
-9-
Wiring Diagram
1. Indoor Unit
CN-FAN
OR
MOTOR
YL
BR
CN-POWER
SH-CAPA.
STEP MOTOR
FUSE AC250V/T2A
BR
BL
YL
1(L) 2(N)
TO OUTDOOR UNIT
2. Outdoor Unit
Comp. U V W
RD WH BL
U V W
CNIPM
WH BK
IPM
CNCNGATE1 GATE2
WH BK
YL BR BL BK OR CAPACITOR BR YL
BK
BR
BL BK OR
WH
BK RD
RD
(8PIN)
(7PIN)
(9PIN)
CAPACITOR (400V,165F) BL WH
CNIPM
CN-DC
D-LEV
A-LEV
MAIN PCB
RYPWR
WH
S.V WH
BR BR 2 POWER 4 RELAY 0 1 CT YL BR
BL
B-LEV
(RD)
C-LEV
COND SENSOR AIR SENSOR A-PIPE SENSOR B-PIPE SENSOR C-PIPE SENSOR D-PIPE SENSOR SUCTION SENSOR DISCHARGE SENSOR BK
RY-START
CN-PWR
CN-AC
BR
CN-TH6
WH BK YL YL
RD BL WH NL BK WH
BL
POWER-OUT CN-POWER
(WH)
CN-DATA
BL
FUSE 250V,25A
(WH)
BR
CN-TH1
(RD)
POWER-IN
NOISE FILTER
RD GN/YL BL BR BK
WH
YL GN/YL BL BR BR BL BR BL GN/YL
3 1(L) 2(N)
3 1(L) 2(N)
1(L) 2(N)
OPTION
TO INDOOR UNIT
3854AP7050Z
(FM-2160N3L/M/Q)
(FM-3060N4L/M/Q)
- 10 -
GND
GN/YL
Outdoor Unit
C-gas pipe sensor B-gas pipe sensor A-gas pipe sensor Gas side Service Valve
UNIT-C
UNIT-B
UNIT-A
4-WAY VALVE
Heating sensor
Discharge pipe sensor C-liquid pipe sensor B-liquid pipe sensor A-liquid pipe sensor Indoor temperature sensor
Heat Exchanger
2. FM-3060N4L/M/Q
Indoor Unit Outdoor Unit
D-gas pipe sensor C-gas pipe sensor B-gas pipe sensor A-gas pipe sensor Solenoid Valve Heating sensor
UNIT-D
UNIT-C
UNIT-B
UNIT-A
Section pipe sensor Comp A-LEV B-LEV C-LEV D-LEV Liquid side Service Valve Strainer Heat Exchanger
ex)
- 11 -
Operation Details
1. MAIN UNIT FUNCTION
DISPLAY
Operation Indicator On while in appliance operation, off while in appliance pause Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on) Sleep Timer Indicator On while in sleep timer mode, off when sleep timer cancel or appliance operation pause Timer Indicator On while in timer mode (on/off), off when timer mode is completed or canceled Defrost Indicator Off except when hot start during heating mode operation or while in defrost control
-12-
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33C, when above 35C , it operates with the low airflow speed. If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the outdoor fan is turned on/off according to the indoor pipe temp. While in defrost control, both of the indoor and outdoor fans are turned off.
2) Fuzzy Operation for Dehumidification According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5C or more below the setting temp, the compressor is turned off. When 0.5C or more above the setting temp, the compressor is turned on. Compressor ON Temp Setting Temp + 0.5C Compressor OFF Temp Setting Temp+0.5C At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26C Intake Air Temp 25C 24C Intake Air Temp<26C Intake Air Temp+1C 22C Intake Air Temp<24C Intake Air Temp+0.5C 18C Intake Air Temp<22C Intake Air Temp Intake Air Temp<18C 18C When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation. 3) Fuzzy Operation for Heating According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3C or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp Setting Temp Compressor OFF Temp Setting Temp + 3C At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 20CIntake Air Temp Intake Air Temp + 0.5C Intake Air Temp<20C 20C When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature.
s On-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance starts to operate. The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached. If the appliance is operating at the time set by the timer, the operation continues. While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
s Off-Timer Operation
When the set time is reached after the time is input by the remote control, the appliance stops operating. The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. If the appliance is on pause at the time set by the timer, the pause continues.
-14-
Slide Switch
-15-
-16-
Display Function
Operation Indicator Cooling, Soft Dry, Fan, Heating Sleep Timer Indicator Sleep Mode Timer Indicator Timer Mode Defrot Indicator Hot-start, Defrost
Self-diagnosis Function
s Error Indicator The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table. If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed. After error occurrence, if error is released, error LED is also released simultaneously. To operate again on the occurrence of error code, be sure to turn off the power and then turn on. Having or not of error code is different from Model.
Error Code
Error contents
Indoor temperature thermistor open/short. Indoor pipe temperature thermistor open/short.
1 2
3sec (5times)
3sec
Outdoor temperature thermistor open/short. Outdoor TH ass'y check Outdoor pipe temperature thermistor open/short. Poor communication Communication line/circuit
5 8 9
3sec (8times)
CT / Current error
3sec (9times)
Main PCB CT check Wiring and PWM cable check Excessive amount of refrigerant Blocking condenser
DC Peak
3sec (10times)
10
3sec (11times)
DC low voltage
11
3sec (1times) (3times)
13
3sec (1times) 3sec (4times) 3sec 3sec 3sec
Overload combination
14
3sec
-17-
Installation
(1) Installation of Indoor, Outdoor unit
1) Selection of the best location
1. Indoor unit There should not be any heat source or steam near the unit. There should not be any obstacles to prevent the air circulation. A place where air circulation in the room will be good. A place where drainage can be easily obtained. A place where noise prevention is taken into consideration. Do not install the unit near the door way. Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
Front Left Rear left Down right Right Rear right
2. Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted. There should not be any animals or plants which could be affected by hot air discharged. Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
Indoor unit
A B
5~7
Outdoor unit
- 18 -
Installation Plate
The lower left and the right side of Installation Plate 7K, 9K Btu
Left rear piping
80mm 20mm 20mm 50mm 70mm 70mm
12K Btu
Left rear piping
A A A A
70mm
70mm
"D"
"C"
Hole Center
70mm
- 19 -
5~7mm
Pipe cutter
90
Slanted
Rough
Pipe
2. Remove burrs. Remove burrs from cut edges of pipes. Turn the pipe end toward down to avoid the metal powder entering the pipe. Caution: If burrs are not removed, they may cause a gas leakage.
Reamer
Point down
3. Flaring the pipes. Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some refrgerant gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting. Fit the copper pipe end into the Bar of flare tool about 0~0.5mm higher. (See illustration) Flare the pipe ends. 4. Tape the flaring portion to protect it from the dust or damages.
Bar
Copper pipe
"A"
Clamp handle = Improper flaring =
Inclined
Surface damaged
Cracked
Uneven thickness
When properly flared, the internal surface flare will evenly shine and be of even thickness. Since the flare part comes into contact with the connectors, carefully check the flare finish.
- 20 -
2) Connection of Pipings
1. Remove the installation plate Pull the two '' marked portion of bottom of the chassis and pull the installation plate out of chassis. 2. Route the drain hose and the indoor tubing.
Installation plate
Pull
Pull
Tubing holder
To remove the holder, press the bottom of the chassis near the holder upwards and the tab is clear of its hole. Turn it clockwise approx. 90 and remove it.
Pull Press
5. Tape the tubing, drain hose and the connecting cable. Be sure that drain hose locates at the lowest side of the bundle. Locating at the upper side can be a reason that drain water overflows drain pan inside the unit.
Gas side piping Connecting cable Liquid side piping Drain hose
- 21 -
6. Indoor unit installation. Hook the indoor unit onto the upper position of the installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots (sound click).
7. Connecting the pipings to the indoor unit. Align the center of the pipings and sufficiently tighten the flare nut with fingers. Finally, tighten the flare nut with torque wrench until the wrench clicks. Wrench tightening the flare nut with forque wrench, ensure the direction for tightening follows the arrows on the wrench. Pipe Size Liquid Side (1/4") Gas Side (3/8") Gas Side (1/2") Gas Side (5/8") Torque 1.8kg m 4.2kg m 5.5kg m 6.6kg m
Flare nut
Pipings
8. Wrap the insulation material around the connecting portion. CAUTION: Take care to arrange the pipings, drain hose and cables as the right upper picture for inserting it into the indoor unit and refixing the tubing holder easily.
Plastic bands
Insulation material
- 22 -
9. Set the pipings and the connecting cable to the back of the chassis with the tubing holder. Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged in the bottom of chassis.
1 Hook
2 Push
10. Indoor unit installation. Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engages with their slots (sound click).
- 23 -
9.5212.7 9.5215.88
3. Finally, tighten the flare nut with torque wrench until the wrench clicks. s When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit
Connector Liquid side piping C-UNIT
*Connecting pipe size Indoor Units 7K 9K 12K 18K 24K Gas side 9.52(3/8) 9.52(3/8) 12.7(1/2) 12.7(1/2) 15.88(5/8) Liquid side 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
B-UNIT
A-UNIT
Torque wrench
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source. 5) Confirm that electrical capacity is sufficient. 6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. Proper starting power is not given to the compressor.
- 24 -
Outdoor unit
Terminal block Over 5mm Holder for power supply cord Cover control Connecting cable Power cord
OUTDOOR UNIT
1(L) 2(N)
Power cord
1(L) 2(N)
1(L) 2(N)
1(L) 2(N)
1(L) 2(N)
Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT D-UNIT C-UNIT B-UNIT A-UNIT
OUTDOOR UNIT
1(L) 2(N)
Power cord
1(L) 2(N)
1(L) 2(N)
1(L) 2(N)
2. Secure the cable onto the control board with the holder (clamper). 3. Refix the cover control to the original position with the screw. 4. Use a recongnized circuit breaker between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
CAUTION If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Main power source Main power source
Air Conditioner
Circuit Breaker Use a 20A circuit breaker or time delay fuse. (21K)
Air Conditioner
Circuit Breaker Use a 25A circuit breaker or time delay fuse. (30K)
CAUTION The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
8.5mm
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H07RN-F approved by HAR or SAA).
7.5mm
GN
/YL 20
GN
/YL 20
- 25 -
Screw
2. Check the drainage Pour a glass of water on the evaporator. Ensure if water flows drain hose of indoor unit without any leakage.
Connecting cable
- 26 -
OUTDOOR UNIT
1(L) 2(N)
Power cord
Connecting cable
1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3 1(L) 2(N) 3
Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT Terminal on the INDOOR UNIT D-UNIT C-UNIT B-UNIT A-UNIT
OUTDOOR UNIT
1(L) 2(N)
Power cord
1(L) 2(N)
1(L) 2(N)
1(L) 2(N)
2. Attach the Grille onto the cabinet. Grasp lower the left and right side of the Grille and engage four tabs on the top inside edge of the chassis. Press the Grille toward the chassis until it will be back into place.
- 27 -
Plastic band
2. Tape the Pipings, drain hose and Connecting Cable from down to up. 3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
Trap is required to prevent water from entering into electrical parts. Power supply cord
In case of the Outdoor unit is installed upper position of the Indoor unit.
Seal a small opening around the pipings with gum type sealer. Trap
1. Tape the Pipings and Connectiong cable from down to up. 2. Form the pipings gathered by taping along the exterior wall and the Trap to be required to prevent the room from entering the water. 3. Fix the pipings onto the wall by saddle or equivalent.
- 28 -
Indoor unit
Gas side
Closed
- 29 -
B(Length) INDOOR UNIT A(Height) OUTDOOR UNIT C(Height) INDOOR UNIT D(Length)
** A, B mean indoor unit higher located than outdoor unit. C, D mean outdoor unit higher located than indoor unit.
- 30 -
Tubing connection
Discharge air
- 31 -
Operation
(1) Name and Function-Remote Control (Door Closed)
Remote Control
Signal transmitter Transmits the signals to the room air conditioner.
Signal transmitter
START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
2 3
5 4 6 1 3
5
Flip-up door (closed)
JET COOL
Used to start or stop the speed cooling. (Speed cooling operates super high fan speed in cooling mode.)
-32-
Remote Control
Signal transmitter Transmits the signals to the room air conditioner.
Signal transmitter
1 2 3
4
ON OFF
1 2
SET CANCEL
4 5 6 7
6 7
RESET BUTTON
Used prior to resetting time or after replacing batteries.
-33-
To remove the Grille from the Chassis. Set the up-and-down air discharge louver to open position (horizontally) by finger pressure. Remove the securing screws To remove the Grille, pull the lower left and right side of the grille toward you (slightly tilted) and lift it straight upward.
Screw
1. To remove the sensor, housing connect, earth conductor & step motor conductor with sensor holder, Motor, Evaporator & P.C.B.
Earth Conductor
- 34 -
2. To remove the Control Box. Remove securing screws. Pull the control box out from the chassis carefully.
3. To remove the Discharge Grille. Pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator. Remove screws securing the evaporator and the holder eva.
Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Cross-Flow Fan Loosen the screw securing the cross-flow fan to the fan motor (do not remove). Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from the self-aligning bearing.
- 35 -
To outdoor unit
To outdoor unit
Works Shipping
Service port Closed (with cap) Open (push-pin or with vacuum pump) Closed (with cap) Open (connected manifold gauge) Open (connected manifold gauge) Open (with charging cylinder) Open (connected manifold gauge) Open (connected manifold gauge)
1.
Open Open (counter-clockwise) (push-pin or with vacuum pump) Open (with valve cap) Closed (clockwise) Closed (with cap) Closed (with cap)
Operation
2.
3.
Evacuation (Servicing)
Open
Open
4.
Open
Open
5.
Open
Open
6.
Open
Open
- 36 -
Indoor unit
Gas side
Closed
manifold gauge
3-way valve
Low-handle (CLOSE)
Open
Procedure 1. Confirm that both the gas side and liquid side valves are set to the open position. - Remove the valve stem caps and confirm that the valve stems are in the raised position. - Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the manifold gauge to the service port of the gas side valve. - Connect the hose of the gauge with the push pin to the service port. 4. Air purging of the charge hose. - Open the Low-handle valve on the gauge slightly to air purge from the hose. 5. Set the liquid side valve to the closed position. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm g.
2
7. Immediately set the gas side valve to the closed position. - Do this quickly so that the gauge ends up indicating 1kg/cm g.
2
8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m) - Be sure to check for gas leakage.
- 37 -
(2) Evacuation
(All amount of refrigerant leaked)
Indoor unit
Gas side
Open
manifold gauge
Vacuum pump
3-way valve
Lowhandle (OPEN)
Open
Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position. 2. Connect the vaccum pump to the center hose of the manifold gauge. 3. Connect the service port of the gas side valve to the low side of the gauge. 4. Evacuation for approximately one hour. - Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less). 5. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge needle does not move(approximately 5 minutes after turning off the vacuum pump). 6. Disconnect the charge hose from the vacuum pump. - Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted,replenish as needed. 7. Mount the valve caps and the service port caps.
- 38 -
Indoor unit
Gas side
Closed
Charging cylinder
manifold gauge
3-way valve
Open
Procedure
1. Connect the gauge to the charging cylinder. - Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. - If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid. 2. Purge the air from the charge hose. - Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder. 3. Open the low handle on the gauge and charge the system with liquid refrigerant. - If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure(pumping down-pin). 4. Immediately disconnect the charge hose from the gas side valve's service port. This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner. - Stopping partway will allow the gas to be discharged. - If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose. 5. Mount the valve stem nuts and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.) - Be sure to check for gas leakage.
- 39 -
Temp. Difference Temp. difference Current Operating Current Temp. difference Current : less than 8C : near the rated current Excessive amount of refrigerant : approx. 8C : less than 80% of rated current Refrigerant leakage Clog of refrigeration cycle Defective compressor
Temp. difference
: over 8C
Normal
Notice: Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Temperature (Compared with the normal value) High Higher Normal Excessive amount of refrigerant Insufficient amount of refrigerant(Leakage) Clogging High pressure does not quickly rise at the beginning of operation. Current is low.
Lower
Higher
Notice: 1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
2
- 40 -
Trouble 1
Does "Beeping" sound is made from the indoor unit? NO Check the voltage of power(AC220V/AC240V, 50Hz). The voltage of main power. The voltage applied to the unit. The connecting method of Indoor/Outdoor connecting cable (each color) The P.W.B. Ass'y (Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.) YES Primarily, the operating condition of Micom is O.K.
Check CN-DISP1
The operation check of the P.C.B. Ass'y Procedure 1) The input voltage of power transformer. 2) The output voltage of power transformer. 3) IC01D(7812) 4) IC02D(7805) 5) IC01A(KIA7036) Specification 1) AC230V 30V : Check the rated voltage 2) 14V 3V 3) DC12V 4) DC5V 5) The voltage of micom pin 29 : DC4.5V Remedy 1) Replace power transfomer. 2) Replace power transfomer. 3) Replace IC01D. 4) Replace IC02D. 5) Replace IC01A.
-41-
Trouble 2
While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
When the detect switch (double key) inside the remote controller door is fault, it is impossible to operate temperature regulating(v / w) and wind speed selecting.
-42-
Trouble 3
Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1C at least.
Check the sensor for Indoor temperature is attatched as close as to be effected by the themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor fan is stopped. Check the related circuit of R02H(12.1K), R01H(1K), R04H(6.2K), R03H(1K), C01H(102), C02H(102), Micom(pin No. , ). Check the Indoor temperature sensor is disconnected or not (about 10K at 25C).
Check the Relay(RY-PWR, RY-START) for driving Compressor. Check the voltage between brown and blue cable of terminal to connect the Outdoor (About AC220V / 240V). Check the related circuit of relay in Outdoor PCB Ass'y. Check Point Between Micom(No. 19) and GND Between IC01M(No. 10) and GND Comp. ON DC 5V DC 1V Comp. OFF DC 0V DC 12V
Check the electrical wiring diagram of Outdoor side. Check the open or short of connecting wires between Indoor and Outdoor.
-43-
Trouble 4
Check the related circuit of indoor Fan Motor. The pin No. 38 of micom and the part for driving SSR.(Q01M) Check the related pattern. Check the SSR. - SSR Open: Indoor Fan Motor never operate. - SSR short: Indoor Fan Motor always operates in case of ON or OFF.
Check the SSR high speed operation by remote control. (the Indoor Fan Motor is connected) The voltage of Pin No 1(orange) and 3(black) of CN-FAN.
Check SSR
-44-
Trouble 5
Confirm that the vertical louver is normally geared with the shaft of Stepping Motor. If the regular torque is detected when rotating the vertical louver with hands Normal
Check the connecting condition of CN-U/D Connector Check the soldering condition(on PCB) of CN-U/D Connector
Check the operating circuit of the vertical louver Confirm that there is DC +12V between pin of CN-U/D and GND. Confirm that there is a soldering short at following terminals. - Between 1 , 2 , 3 and 4 of MICOM - Between 17 , 18 , 19 and 20 of MICOM - Between 4 , 5 , 6 and 7 of IC01M - Between 5 , 6 , 7 and 8 of IC01M
If there are no problems after above checks. Confirm the assembly condition that are catching and interfering parts in the link of the vertical louver
-45-
Trouble 6
Does the Operating LED of indoor unit blink when Operation's ON? NO NO Is the Connection between CN-Power of indoor unit and terminal block? YES NO Is the connection of cable between indoor and outdoor unit right?
YES
in outIs the voltage of CN-POWER , door PCB Ass'y about AC220V / 240V ? YES NO Is the operation of outdoor Ass'y right? (IC04D, IC01A)
Check the Fuse of Outdoor PCB Ass'y. Check the connecting state of wires.
NO
-46-
Trouble 7-1
s Communication error between Indoor and Outdoor (Error Code NO Does the operating LED in display PCB Ass'y blink 5 times? YES NO Is the connecting state of connector outdoor PCB Ass'y right. YES NO Is the connection of CN-DATA between indoor and outdoor unit right? YES
Check the state of connecting cable (4 line) bewteen indoor and outdoor unit .
Electrical wiring diagram(Colors) Check the connecting state of connectors in outdoor PCB Ass'y (CN_Data - Terminal Block.)
-47-
Trouble 7-2
Does the operating LED in Display PCB Ass'y blink 8 times? YES NO Is the current transformer(CT) in Main PCB Ass'y right? YES NO Is the connecting state of connectors right? (CN-IPM, U.V.W and Compressor wires) YES NO Is the indoor/outdoor fan locked? YES NO Is the discharge temperature of Indoor unit right(11C~17C) in the cooling mode? YES NO Is the refrigerant pressure right? YES
Replace the PCB Ass'y. Main PCB Ass'y(Outdoor) Control Box Ass'y(Outdoor)
-48-
Trouble 7-3
Does the operating LED in display PCB Ass'y blink 9 times? YES NO Is the connecting state of connectors in outdoor Sub. PCB Ass'y right? (CN-UVW, CN-IPM, CN-Gate 1, CN-Gate 2) YES NO Is the power module in Sub PCB Ass'y right? YES NO Is the voltage of CN-AC over than AC170V? YES NO Is the voltage of CN-DC over than about DC260V? YES Check CN-IPM connector(Pin No. 12) Replace the Sub PCB Ass'y. Check the supplied voltage. Check the short P-N P-U, V, W, and N-U, V, W of IPM and then collector, emiter of IGBT Replace the Sub PCB Ass'y. Electrical wiring diagram (Colors) Check the connecting state of connectors in PCB Ass'y(Main/Sub) If CN-UWV is connected, the comprressor can be operated a opposite direction.
Replace the PCB Ass'y. Main PCB Ass'y Sub PCB Ass'y Control Box Ass'y
-49-
Trouble 7-4
Does the operating LED in display PCB Ass'y blinks 10 times? YES NO Is the connecting state of connectors in outdoor PCB Ass'y right? (CN-DC, CN-AC) YES NO Is the voltage of capacitor over 187Vdc? YES NO Is the connecting state of wires in outdoor unit? YES Check the electrical wiring diagram (Colors) Check the wiring state. Reconnect the connector.
-50-
Trouble 7-5
Does the operating LED in display PCB Ass'y blink 11 times? YES NO Is the installation condition of outdoor unit right. YES NO Is the indoor/outdoor fan locked? YES NO Is the refrigerant pressure right? YES Remove or supply the refrigerant. Check the indoor/outdoor fan motor. Check the installation condition.
-51-
CN-POWER (1,2)
OPEN
Malfunctions all indoor & outdoor unit. Malfunctions remocon, force, test operation mode. Malfunctions outdoor unit. Stop compressor and outdoor fan motor. The operation LED blinks 5 times. Communicaion error. Malfunctions indoor fan motor. Malfunctions remote controller. Don't operate the power display module. The operation LED blinks once. Enable to receive remote singnal. Malfunctions UP/DOWN step motor. Don't operate louver.
CN-POWER (3)
OPEN
CN-FAN CN-DISP1
OPEN OPEN
CN-TH
OPEN/SHORT
CN-U/D
OPEN
- 52 -
CN-POWER
OPEN
CN-AC
OPEN
CN-DC
OPEN
CN-IPM
OPEN
CN-COMP
OPEN/SHORT
CN-IPM
OPEN
CN-Gate 1, 2
OPEN
- 53 -
1. Indoor Unit
CN-POWER
ZNR01J NF01J
C01J FUSE 250V/T2A NF01M D02K R05K ZNR01M CN-FAN R01M C01M ZNR01K
C02J
D02D D01D D03D R05C C02D C01D C04D IC01D IC01K IC02D D04D D05D R04C J8 J16 C02C C03D C05D Q01C Q01M J13 J14 R02C J15 R01C J17 C01C J18 R01B R05T R04T R03T R02T R01T CN-SUB MICOM IC01M C06D OSC01B R02A C01L C01A R01L R01A IC01A R03C IC02K
SSR-MOTOR R04K J9 C02A R02K C01K R03A R01K Q01K R02Z R02H R04H R01Z C01Z Q01Z J6 J7
D01K R03K J1
CN-TH
CN-SW
- 54 6871A20109
EEPROM R01E J11 J12 R01H R03H R02E IC02M C01F C02F R06G R01G R07G R02G R04G R05G R03G OP6 R15H OP5 R14H R13H OP3
CN-ION
6871A20212
J10 C01H
R03F R01F
SLIDE S/W
J5
J4
J3
J2
CN-DISP2
2. Outdoor Unit
MAIN P.C.B ASM
-55-
3. Display ASSY
- 56 -
5V
R04F,10K R02F,10K
1
R03F,1K R01F,1K
4 MICOM GMS81516
5V
R02H 12.1K 1% 1% 6.2K 12.1K 12.1K 12.1K 12.1K 12.1K 12.1K R04H R16H R15H R14H R13H R12H R11H
DISPLAY
DC 5V
R16G,6.8K R15G,6.8K Q13G KTA1270Y
GND
REMOCON
Vout
1
C01M
Vdd RD Wt R/W C SYNC MP AVss AVref R67/AN7 R66/AN6 R65/AN5 R64/AN4 R63/AN3 R61/AN1
R30 64 R31 63
C02F,0.01/50V C01F,0.01/50V R14G,6.8K
3
R13G,6.8K Q12G
LED4
Vcc
2 3 4 5 6 7
LED3
0.01 50V
5
R12G,6.8K R11G,,6.8K Q11G
LED2
C02L
6
KRA1270Y
LED1
CN-DISP1
CN-TH
10V
16 15 14
R01G,220 R07G,220
8 9
R03H,1K
PIPE-TH
CN-DISP2
1 2 3
R01H,1K
1 2 3 4
C01H C02H
10 R62/AN2 11 12 13 14 15
DC12V
11 8 7 6 5 4 3 2 1 12 13 14 15 16 17 18 10
OP6 XXXK OP5 XXXK OP4 XXXK OP3 XXXK OP2 XXXK OP1 XXXK
2
4 13
R02G,220
4
ROOM-TH
R03 53 R04 52 R05 51 R06 50 R07 49 A0 A1 A2 A3 A4 A5 R45/EC2 R44/EC0 R43/INT3 A6 A7 A8 R10 48 R11 47 R12 46 R13 45 R14 44 R15 43 R16 42 R17 41 R20 40 EEPROM S 1 C 2 D 3 Q 4 8 VCC
4
5 6 7 8 12 11 10 9
R04G,220 R05G,220 R03G,220
0.01 50V
CN-U/D
RD
1 1
DC 12V
9
DC 5V
8 7 DU 6 ORG 5 Vss
OR
2 3 4 5 5 4 3 2
DC 5V
YL PK BL
STEP MOTOR UP/DOWN
DC 12V
R01T,10K R02T,10K R03T,10K R04T,10K R05T,10K
DC 5V
7
TX RX
7
25 26 27
IC01M KID65084AP
8 R42/INT2 R41/INT1
28 R40/INT0
R02A,4.7K R01A,1K
9
DC 12V
SSR-MOTOR
CN-SUB
R02E,20
Schematic Diagram
29 30
R01B,1M
RESET' XIN
IC01A C02A 10uF/50V
+
Q01M KRC107M
R01E,1K
BZ01E
R02L,10K
5V
IC01K(TLP621)
R01L,1K
REMOCON
D01K 1SR139-600
RX
5V
4 IC02K(TLP627) 2
R03K 1K
ZNR01K 14D271
NF01M
ZNR01M INR14D471K
CN-FAN
3
NF01M
R02C,4.7K
R01C,1K
SSR-MOTOR
INDOOR
5V
R04C,10K
FREQUENCY
R03C,20K R05C 4.7K M C02C 0.015 50V Q01C KTC3198Y C01C 0.01 25V
DC 5V
C06D 0.01 25V +
Q01K KRC102M
R04K 680
R05K 25K,3W,1%
R01M,120,1/2W
C01M,0.1,AC275V
FAN MOTOR
IC02D
O 7805 C05D 470uF 16V I D02K 1SR139-600
C01J 0.1, AC275V NF01J
COM
1. Indoor Unit
FUSE 250V/T2A
FREQUENCY
LIVE
IC01D
DC 12V
C04D 0.01 25V + O C03D 470uF 25V 7812 I + C02D 0.1 50V
D01D 1SR139-600
D02D-05D 1SR139-600
NEUTRAL
CN-POWER
POWER TRANS
6171AQ3124C
- 57 -
TSUP_B/A PIPE
OUT
CN-TH5
4 1 4 1
4 3 2 3 2 1
CN-TH6
4 1
3 2 3 2
DISCHARGE TSUP_C
SUCTION
TSUP_D
+5V
R16H 6.2K,1% R14H 12.1K,1% R08H 6.2K,1% R12H 6.2K,1% R10H 6.2K,1% R06H 6.2kK,1% R04H 6.2K,1% R02H 18K,1% R15H R13H R11H R09H R07H R05H R03H R01H
+5V R13K 1K
2
IC07K TLP627
1 4
CN-TH1
3 3 3 3
1 2 1 2 3
CN-TH2
1 2 1 2 3
CN-TH3
1 2 1 2 3 1 2 1 2 3
CN-TH4
1K 1K 1K 1K 1K 1K 1K 1K
+5V
4 1
D08K 1SR139-600
IC08K
TLP621
R16K
R20K 82K,3W
C06H 104K
C05H 104K
C04H 104K
C03H 104K
C02H 104K
C01H 104K
+5V R09K 1K
IC05K TLP627
1 4
MICOM
R05T, 270 1/8W
5V
+5V
LEV D_1
TMP88CK49
1 P70
R04Z 12.1K 1%
+5V
4 1
1 1
R06T, 270 1/8W
R02Z 12.1K 1%
VDD 64
LEV D_2 LEV D_3 LEV D_4
MODEL OP
63 62 5 P74 P75
DISCHARGE SUCTION
R11K 10K
IC06K
TLP621
R12K
R19K 82K,3W
2 2
R07T, 270 1/8W
AIN04
OP1 LOW
6
R03Z,1K
R09Z 12K OP2 HIGH MED
AIN03
61 60 TSUP_C TSUP_B 59 7
DC_LINK
TSUP_D
+5V R05K 1K
2
IC03K TLP627
1 4
3 3 4
R09T, 270 1/8W R10T, 270 1/8W
CN_DATA
3
DATA_D
4 5 5 6
+5V
+5V
4 1
DATA_C
R18K 82K,3W
DATA_B
IC04K
TLP621
R08K
D06K 1SR139-600
6 7
R02T,10K R03T,1K
DATA_A
1
IC01K TLP627
1 4
7 8 9
CN-IPM
8 9
C02T 103
C03T
+
Q01T
R01T 10k
C01M 104K
+12V RY-PWR IC01M KID65004AP RY-4WAY RY-FAN H RY-FAN L RY-SV 9 10 11 12 13 14 8 7 6 5 4 3
MGT INT
16V
107M
+5V
+5V
4 1
1 8 8
IC07S
2 9 9
R04T CN-IPM
3 3
IC02S IC05S IC06S IC03S IC04S
4 4
C01T 103 1K LED01T (GREEN)
5 5 6 7
R17K 82K,3W
1
IC01S
IC02K
TLP621
R04K
D05K 1SR139-600
+12V
CN-LEV C
CN-GATE2
+12V
5 5 23 P16
RY-START
IC04D
CN-GATE2 1 1N4937x4
D10D
7 6 5 4 3 2 1
3 2 1
15 16
7805
2 1
D08D RU2YX
+12V
D09D 1SR139-600
P40 41 NC
1 1
9 1
10 18
3 25 P20
CN-TEST2
C15D C16D 103 104 C04D 470UF
+
LEV C
2 17
IC03M
R08D 1.2K
16
ULN2804
1 P35 38
3 3 4 4
1
4 15
5 4
CN-LEV B
7 1
D12D
+
7 6
5
5 14 6 13
4 1 2
+5V
3
7 8 12 11
LEV B
4 3 2 1
3 2 1
1
C11D,473,630V C112D,100P,1KV
1 C02M 104K
R04V 10K
D06D 1N4937
+12V
R03V 33K
FB01D FBA04HA900
+
CN-LEV A
5 5
IC01V TLP621-BL Q01V C3198
C02D 47UF 25V
+
7 6 5
C01S 10UF
+
C02S 10UF
C03S 10UF
5 4
8 7 6
C04S 33UF
F0 15
AR01Z 10K,5%
Vup1 3 2 11 Wn Vnc 14 10
9 1 2
FUSE 250V,3A/3.15A
10 18 17 3 4 16 15
C04M 330uF/25V
LEV A
CN-GATE1
2 CN-GATE1
CN-LEV D
D07D FB02D 1N4937
IC01D
R05D 5.6K 1/4W
5
4 D01D~D04D 1SR139-600 R01D 27,5W
R07D 2.2,1/4W C13D 680P
+
5
5
NF01J
~
LEV D_4 2
G6551
R06D,680 1/4W 5
14
LEV D_3
4
6 13
4 CT01N
~
Fo
Vcc Vcc
Fo
Fo
Out Si
GND GND
Out Si GND
Out Si GND
Out Si GND
ZNR01J ZNR561D14 3 68UF 400V R02D 82K,1W 250V C02J 104 C01J 104,250V
~
3 D06N 1N4148
+
3
LEV D_2 LEV D_1
LEV D
7 8 12 11
IPM
P U V W N
1SR139-600 D09K
R07Y,1K DC LOW
NTC01K 100D-9
RY-Start
RY-FAN_H
C09K 471,250V
C10K 15uF,450V
RY-4WAY
RY-FAN_L
RY-Power
R21K 1M,1W
RY-SV
+5V 1/4W
3
Q02Y C3198 Q01Y C3198 DZ01Y 20V 1W R06Y,10K IC01Y TLP521
3
CN- TEST1
R01Y 51K,3W
R01J 1M,1/2W
CN-POWER OUTPUT (WH)
RY-DISC
ZNR01J,02J SVC561
NF01J 9mH
C01Y~C03Y 472M
C01X 1.0uF
FUSE 250V/25A 3
COMP
2
CN-AC2 CN-AC1 CN-POWER
2 2
R11Y,R12Y 56K,3W RY-DISC
2 2 4WAY
CN-DC
1 1
3 3
2 2
1 1
Comp OLP
4 4
3 3
2 2
1 1
1 1
WH
1 1
WH
BK
474/450V
2
~
1
DB02J,S50VB60
FAN MOTOR 2
2200UF,400V REACTOR
+ +
SURGE DSA-362MA-05F25(UL)
CN-GND
Magnet
GREEN /YELLOW
1 1
~ +
DB01J,S50VB60 165UF,400V
+ ~
G/Y
High Press
BK Power Relay
-
2. Outdoor Unit
-582 1
~
R04S 560
R05S 560
S-TRANS
P41 42
AR02Z 10K,5%
C03M 330uF/25V
4 4
131410
354210
152313
135314
268714
- 60 -
131410
354210
267110 159901-1
135311
152313
135314
268714
- 62 -
131410
342800
135311
354210
267110
159901-1 159901-2
346810
135314 263230
W0CZZ
268714
- 64 -
137213-1
435512
546810 649950
559010 668713-2 W0CZZ-3 437210 W0CZZ-2 349600 W6920 447910 W0CZZ-1 W6640-2 W6640-1 668713-1
566000
435301
349480
- 66 -
554031 435512
137213-1 263230-6
435300
137213-2
349600
668713-2
668713-1 W6640-1
437210
W6640-2
658740 668711
556000-2
561410-1 561410-2
435311
561411-4
- 68 -