GE Spectra Series Busway Catalogue
GE Spectra Series Busway Catalogue
GE Spectra Series Busway Catalogue
Electrical Distribution
imagination at work
Spectra Series™ Busway
Labor Calculator compares the labor costs Speculator answers busway-related electrical
of installing lighter GE busway versus Square questions.
D busway.
Autobus allows specifiers, electrical contractors
Cable Converter – calculates how busway and others to design and engineer busway in
costs to compare to pipe and wire. 3-D AutoCAD® format.
The Busway Toolkit is available on-line at www.geelectrical.com/elitenet or order the two-CD set (DEU-060) from GE.
www.geelectrical.com 1
Spectra Series™ Busway
State-of-the-Art
Busway Systems
All Spectra Series™ bus bars are integrity-
tested with 5000 Vac – for absolute
performance confidence.
www.geelectrical.com 2
Spectra Series™ Busway
www.geelectrical.com 3
Spectra Series™ Busway
www.geelectrical.com 4
Spectra Series™ Busway
Electrical Data
Integrated housing ground resistance
Spectra Series busway’s all-aluminum housing provides an extremely
low impedance ground path with less resistance (more continuous
current capacity) than internal ground bus bars for both copper and
aluminum systems.
Plug-in outlet grounding is supplied with tin-plated copper tabs bolted to the
aluminum housing for superior continuity through standard bus plug ground
stabs. An internal ground bus bar (50% capacity, .125 inch thick) is also avail-
able to provide a complete system.
Table 5.1
DC Resistance Ohms x 10-3/100 ft. @ 75° C
Bar Width Integrated Housing Aluminum Internal¬ Copper Internal
Ground 50% Ground Bus 50% Ground Bus
0.750 0.65 18.67 10.74
1.125 0.64 12.44 7.16
1.625 1.31 8.62 5.15
1.750 0.61 8.00 4.60
2.250 1.21 6.22 3.72
2.875 1.12 4.87 2.91
3.375 1.06 4.15 2.48
4.000 1.04 3.50 2.10
4.250 0.97 3.29 1.95
4.500 0.95 3.11 1.84
¬ The housing could satisfy 50% ground bus conductor
5.750 0.85 2.44 1.44
6.500 0.80 2.15 1.27
requirements. An internal aluminum ground bar offers
7.500 0.74 1.86 1.07 no electrical advantage and is not available in the
8.250 0.71 1.70 1.00 Spectra II option.
Where full nameplate loading is required, Spectra Series busway should be sized in accordance with Option B; see Table
5.2 and Fig. 5.1 below. By increasing the width of both the phase and neutral bars equally, the busway will operate within
UL heat rise limits at full nameplate rating, while also carrying up to twice the rated current in the neutral conductor.
www.geelectrical.com 5
Spectra Series™ Busway
Short-circuit ratings
The Spectra Series busway design provides predictable, consistent strength and high short-circuit ratings.
The ratings shown below are UL recognized rms symmetrical amps for both feeder and plug-in phase-to-phase
and phase-to-ground. Tests were run at three cycles minimum per UL standards. Additional tests were run at
six cycles. Spectra Series busway is third party certified by KEMA to be in compliance with IEC439-1 and -2
short circuit withstand test for 1 and 3 seconds.
The short-circuit rating of the busway system with protective devices that are part of the busway, such as
power takeoffs and reducers, is equal to the lower of the short-circuit rating of the protective device or the
busway with which the fitting is used. For example, a fusible power takeoff rated 200,000 amps with Class J
fuses when installed on a busway rated 150,000 amps would have a rating of 150,000 amps.
Standard short-circuit busway ratings can be given a higher UL Listed short-circuit rating when protected by
specific J, T, R and Class L fuses as shown below.
Table 6.1
Short-Circuit Ratings Plug-In and Feeder
Aluminum (kA) Copper (kA)
Amp Rating
3 and 6 Cycles 1 Sec. 3 Secs. 3 and 6 Cycles 1 Sec. 3 Secs.
225¬ 30/50 11/24 6/14 30/50 17/40 10/21
400¬ 42/85 17/24 10/14 30/50 17/40 10/21
600¬ 50/85 28/24 16/14 42/85 25/40 15/21
800 100 42 24 85 40 21
1000 100 50 29 100 51 29
1200 125 62 36 100 65 37
1350 150 84 49 100 76 44
1600 150 95 55 125 95 55
2000 150 121 70 150 129 75
2500 200 132 76 150 150 107
3000 200 169 97 200 191 110
4000 200 200 140 200 200 149
5000 – – – 200 200 200
¬ Use the first value when selecting Spectra Series II busway.
Table 6.2
Maximum Fuse Sized for Increased Short-Circuit Protection to either 100KA or 200KA
Max “L” Fuse Sizes
Amp Rating For Increased
Short-Circuit Rating
AL CU 100KA 200KA
225 225 1200 800¬
400 400 1200 800¬
– 600 1200 800¬
600 800 2000 1200
– 1000 – 2000
800 1200 – 2500
1000 1350 – 2500
1200 1600 – 3000
1350 2000 – 4000
¬ Also 600J, 800T or 400R
1600 – – 4000
Also 600J, 800T or 600R
2000 2500 – 4000
Standards
Spectra Series busway conforms to the latest revisions of: NEMA BU-1; ANSI/UL857; federal spec W-B-811b;
cUL. Can comply with IEC 439-1 and 2. Contact factory for details.
www.geelectrical.com 6
Spectra Series™ Busway
Electrical Data
Graph 7.1
Busway operation at other frequencies Effect of ambient temperature
Spectra Series busway continuous current ratings are for 50/60 Hz frequency. on busway operation
Maximum hot spot temperature (°C)
For 400 Hz operation, de-rate bus to 85% load. @ 100% of rated load
135
115
Graph 7.1 illustrates the effect of various ambient temperature conditions on
105
busway operating temperature. Spectra Series busway utilizes NEMA Class B
95
130°C insulation. This chart can be used to determine bus operating parameters
85
in accordance with various standards. UL 857 standard
75
Note: Spectra Series busway can be operated in 50°C ambient environments. Derating is required for 65
UL and IEC compliance. At continuous full rated current in 50°C ambient, insulation life would be reduced 55
from 50 years to 25 years. Please verify your application with your project consultants and inspectors.
45 Maximum average ambient temperature (°C)
0 10 20 30 40 45 50 55 60 65 70
1.00 .95 .90 .85 .80 .74 .67
Multiplier for UL and IEC compliance
Fig. 7.1
Plug-In or Feeder, One or Two Stack CEILING
2
inches 50
millimeters
CEILING WALL
6* 3* WALL
152 76
Proximity
Graph 7.2
Below is a drawing that shows the possible positions of busways relative to
Multiplier
walls and to each other. Refer to Graph 7.2 for the proper multiplier required 1.06
Edgewise mounted to wall
to maintain a 55°C rise in a 40°C ambient.
1.04
.92
ce
to
A
A A .90
0 1 2 3 4 5 6 6.5 7
A – Inches
A
www.geelectrical.com 7
Spectra Series™ Busway
60 Hz values shown. For 50 Hz, multiply reactance (X) by 0.83 and resistance values do not change. For 400 Hz,
multiply reactance by 3.9 and multiply resistance by 1.4. Calculate new voltage drop Vd = amps load X √3
(R cos Θ + X sin Θ) ft/100, where cos Θ = Power Factor. Contact your local GE representative for a free copy of
the Busway Tool Kit (DEU-066) to help with electrical calculations.
225 0.750 19 9.11 3.75 9.85 2.46 2.76 3.04 3.30 3.53 3.72 3.83 3.55
Spectra
400 1.125 29 6.38 3.12 7.10 1.69 1.87 2.04 2.19 2.32 2.42 2.46 2.21
Series II
600 1.750 44 4.32 2.35 4.92 3.68 4.03 4.36 4.65 4.89 5.06 5.11 4.49
225 1.625 41 4.09 1.28 4.29 .95 1.09 1.23 1.36 1.47 1.57 1.65 1.59
400 1.625 41 4.20 1.28 4.39 1.72 1.98 2.22 2.46 2.67 2.86 3.01 2.91
600 1.625 41 4.52 1.28 4.70 2.68 3.10 3.50 3.88 4.24 4.56 4.81 4.70
800 2.875 73 2.48 .79 2.60 2.08 2.38 2.67 2.94 3.19 3.41 3.57 3.44
1000 3.375 86 2.17 .68 2.27 2.25 2.58 2.90 3.20 3.47 3.71 3.90 3.76
Aluminum Spectra 1200 4.25 108 1.73 .55 1.81 2.17 2.49 2.79 3.07 3.33 3.56 3.73 3.60
Series 1350 5.75 146 1.24 .41 1.31 1.78 2.04 2.28 2.51 2.71 2.89 3.03 2.90
1600 6.50 165 1.12 .36 1.18 1.88 2.16 2.42 2.66 2.89 3.08 3.23 3.10
2000 8.25 210 .89 .29 .94 1.88 2.15 2.41 2.65 2.88 3.07 3.21 3.08
2500 (2)4.50 114 .82 .26 .86 2.14 2.45 2.75 3.03 3.29 3.52 3.69 3.55
3000 (2)5.75 146 .64 .21 .67 2.04 2.33 2.61 2.87 3.11 3.32 3.47 3.33
4000 (2)8.25 210 .45 .14 .47 1.86 2.14 2.40 2.65 2.88 3.08 3.23 3.12
225 0.750 19 5.10 3.75 6.33 1.99 2.13 2.26 2.36 2.43 2.47 2.43 1.99
Spectra
400 0.750 19 5.58 3.75 6.72 1.82 1.96 2.09 2.20 2.28 2.33 2.31 1.93
Series II
600 1.125 29 3.86 3.12 4.96 2.15 2.29 2.41 2.50 2.56 2.58 2.51 2.01
225 1.625 41 2.33 1.28 2.66 .75 .82 .89 .94 .99 1.03 1.03 .91
400 1.625 41 2.38 1.28 2.70 1.34 1.47 1.59 1.70 1.79 1.85 1.87 1.65
600 1.625 41 2.48 1.28 2.79 2.04 2.25 2.44 2.61 2.75 2.86 2.90 2.58
800 1.625 41 2.62 1.28 2.92 2.78 3.08 3.35 3.60 3.81 3.97 4.04 3.63
1000 2.25 57 1.90 .98 2.14 2.61 2.87 3.12 3.33 3.52 3.65 3.70 3.29
Spectra 1200 2.875 73 1.49 .79 1.69 2.50 2.74 2.97 3.17 3.34 3.46 3.50 3.10
Copper Series 1350 3.375 86 1.27 .68 1.44 2.41 2.65 2.86 3.05 3.21 3.33 3.37 2.97
1600 4.25 108 1.00 .55 1.14 2.29 2.51 2.71 2.88 3.03 3.13 3.16 2.77
2000 5.75 146 .73 .41 .84 2.11 2.31 2.49 2.65 2.78 2.88 2.90 2.53
2500 7.50 191 .57 .32 .65 2.06 2.26 2.43 2.59 2.72 2.81 2.83 2.47
3000 (2)4.00 102 .53 .29 .58 2.26 2.48 2.68 2.86 3.00 3.11 3.14 2.73
4000 (2)5.75 146 .37 .21 .42 2.16 2.36 2.54 2.70 2.83 2.92 2.94 2.56
5000 (2)7.50 191 .28 .16 .32 2.05 2.24 2.41 2.56 2.69 2.77 2.79 2.42
www.geelectrical.com 8
Spectra Series™ Busway
Physical Data
UL firestop system
UL Listed through-penetration firestop system is available for use with GE busway systems. The system is listed
in the UL Fire Resistance Directory under XHEZ, System C-AJ-6003 with F rating = 3 hours and T rating = 1/2
hour for aluminum bars and T rating = 0 hours for copper bars.
The contractor installs a mineral wool batt (4 PCF Nominal) as shown below, on-site during the busway
installation process. For riser applications, the system is used in combination with a standard GE spring
hanger and floor flange. For horizontal applications, the system is used in combination with two wall flanges
(one per side). See publication DEH-40087 for installation instructions.
This information is provided as a guideline for typical fire-stop systems. If you have an annulus (or opening)
greater than 1 inch beyond the busway enclosure, you will need to determine the proper amount of fire-stop
material based on Fig. 9.1. Quantities are based on application of recommended amount of material; more may
be required if over-application occurs.
www.geelectrical.com 9
Spectra Series™ Busway
Table 10.1
Distribution Equipment Connection Standard Flanged-End Stub – Special Standard Flanged-End Stub – Special
(Pbd., Swbd, Swgr, MCC, etc.) Hardware & connections NOT Required Hardware & connections NOT Required.
Bus Plugs All Types Acceptable All Types Acceptable
Fittings All Types Acceptable All Types Acceptable
Cable Tap Boxes All Types Acceptable All Types Acceptable
End Boxes All Types Acceptable All Types Acceptable
Acceptable Applications & Constructions Indoor, Drip-Proof & Outdoor Indoor, Drip-Proof & Outdoor
Proximity To Walls Standard ¬ Standard ¬
¬ Drop rod must be bolted through ceiling/floor and secured on both sides with standard washers and nuts.
Summary
These parameters for seismic conditions are identical to the complete standard commercial offering of Spectra Series
busway. Therefore, Spectra Series busway can be used in applications in above seismic conditions without restrictions,
special bracing, connections, or hangers. Plus, Spectra Series busway can connect to equipment (panelboards, switch-
boards, motor control centers, switchgear, etc.) using standard flanged end stubs, cable tap boxes, and bus plugs.
www.geelectrical.com 10
Spectra Series™ Busway
Physical Data
Straight lengths: dimensions
and weights
inches
millimeters
Fig. 11.3
Fig. 11.1 Fig. 11.2 One bar per phase
One bar per phase Two bars per phase plug-in and feeder
"A" "A" A
4.50 IN.
114 MM
5.875 IN.
150 MM
Table 11.1
Plug-in and Feeder, all bus UL Listed @600 Volts
AC Standard Bar +1 Bar DC Approximate
Fig. Weight lbs./ft.
Ampere “A” Width Bar Sizes Width x Thickness “A” Width Bar Size Ampere
No.
Rating Inches MM Inches MM Inches MM Inches MM Rating 3-Wire 4 Wire
225 11.3 3.00 76 .75 x .25 19 x 6 - - - - 225 5 5
Spectra
400 11.3 3.38 86 1.13 x .25 29 x 6 - - - - 600 6 6
Series II
600 11.3 4.00 102 1.75 x .25 44 x 6 - - - - 800 7 8
225 11.1 4.38 111 1.63 x.25 41 x 6 4.38 111 1.63 41 600 5 6
400 11.1 4.38 111 1.63 x.25 41 x 6 4.38 111 1.63 41 — 5 6
600 11.1 4.38 111 1.63 x.25 41 x 6 5.00 127 2.25 57 800/1000 5 6
800 11.1 5.63 143 2.88 x.25 73 x 6 6.13 156 3.38 86 1350 6 7
1000 11.1 6.13 156 3.38 x.25 86 x 6 7.00 178 4.25 108 1600 7 8
Aluminum
1200 11.1 7.00 178 4.25 x.25 108 x 6 7.25 184 4.50 114 — 8 9
Spectra
1350 11.1 8.50 216 5.75 x.25 146 x 6 9.25 235 6.50 165 2500 9 10
Series
1600 11.1 9.25 235 6.50 x.25 165 x 6 11.00 279 8.25 210 — 10 12
2000 11.1 11.00 279 8.25 x.25 210 x 6 15.00 381 (2)4.25 (2)108 3000 12 15
2500 11.2 15.50 394 (2)4.50 x.25 (2)114 x 6 18.00 457 (2)5.75 (2)146 4000 17 20
3000 11.2 18.00 457 (2)5.75 x.25 (2)146 x 6 19.50 495 (2)6.50 (2)165 — 19 23
3200 11.2 19.5 495 (2)6.50 x.25 (2)165 x 6 - - - - 5200 21 24
4000 11.2 23.00 584 (2)8.25 x.25 (2)210 x 6 - - - - 6000 25 30
225 11.3 3.00 76 .75 x .25 225 - - - - 225 7 7
Spectra
400 11.3 3.00 76 .75 x .25 600 - - - - 600 7 7
Series II
600 11.3 3.38 86 1.13 x .25 800 - - - - 800 8 9
225 11.1 4.38 111 1.63 x.25 41 x 6 4.38 111 1.63 41 800 8 9
400 11.1 4.38 111 1.63 x.25 41 x 6 4.38 111 1.63 41 — 8 9
600 11.1 4.38 111 1.63 x.25 41 x 6 4.38 111 1.63 41 — 8 9
800 11.1 4.38 111 1.63 x.25 41 x 6 5.00 127 2.25 57 1000/1200 8 9
1000 11.1 5.00 127 2.25 x.25 57 x 6 5.63 143 2.88 73 1350/1600 10 12
Copper 1200 11.1 5.63 143 2 7⁄8 x.25 73 x 6 6.13 156 3.38 86 — 12 15
Spectra 1350 11.1 6.13 156 3.38 x.25 86 x 6 7.00 178 4.25 108 2000 14 17
Series 1600 11.1 7.00 178 4.25 x.25 108 x 6 7.25 184 4.50 114 2500 16 20
2000 11.1 8.50 216 5.75 x.25 146 x 6 9.25 235 6.50 165 3000 21 26
2500 11.1 10.25 260 7.50 x.25 191 x 6 11.00 279 8.25 210 4000 26 33
3000 11.2 14.50 368 (2)4.00 x.25 (2)102 x 6 15.00 381 4.00 102 5000 32 40
3200 11.2 15.50 394 (2)4.50 x.25 (2)114 x 6 - - - - 5200 34 43
4000 11.2 18.00 457 (2)5.75 x.25 (2)146 x 6 19.50 495 (2)6.50 (2)165 6000 42 52
5000 11.2 21.50 546 (2)7.50 x.25 (2)191 x 6 23.00 584 (2)8.25 (2)210 8000 52 66
www.geelectrical.com 11
Spectra Series™ Busway
83"
Benefits of busway over wire and conduit 211cm
• Better efficiency Spectra Series busway requires less space than wire
and conduit
• No cutters, benders, oils, jellies, grease, scrap or cable reels
• Future expansion flexibility
• Higher short-circuit ratings
• Lower voltage drop
• Higher integrity and reliability
Fig. 12.1
Installation Labor Costs
Busway Busway
www.geelectrical.com 12
Spectra Series™ Busway
Physical Data
Spectra Series busway provides optimum performance in the most demanding applications. Through superior design
and applied materials technology, it assures uptime and reliability, even in severe-duty weather environments.
Construction options
Table 13.1
Construction IEC Degree of Joint
Type Protection Insulator
Indoor (NEMA 1) Feeder, Plug-in, Riser IP-40 Standard
Drip-proof ¬ Feeder, Plug-in, Riser IP-43 Standard
Splash-proof¬ Feeder, Plug-in, Riser IP-54 Weathershield
Outdoor
(NEMA 3R)¬
Feeder (Only) IP-65/66 Weathershield
The materials and processes used in these construction options are the result of an intensive Design for Six Sigma
(DFSS) design and testing process. These products combine high reliability with new features that reduce assembly
time by more than 50%. The joint shield, as shown in the photo below, uses an integral spring latch clamping system.
This system provides optimum gasket compression at all joint connections, and eliminates the need for additional joint
cover hardware.
The Splash-proof and Outdoor designs feature an industry-exclusive 100% epoxy insulation system throughout the
bus and joints. This system includes GE Bluecoat™ epoxy on the bus bars and WEATHERSHIELD™ insulators in the joints.
Innovative joint shield design provided with drip-proof, Complete outdoor run of Spectra Series busway.
splash-proof, and outdoor bus.
www.geelectrical.com 13
Spectra Series™ Busway
Plug-in lengths are available in 2-, 4-, 6-, 8-, and 10-foot lengths, and feeder
lengths are also available in 2- to 10-foot lengths in 1⁄8-inch increments.
The ± 1⁄2-inch (13 mm) adjustable, removable joint is attached to one end of
each section (AKA “joint-end”).
Plug-in busway has up to 10 unobstructed, usable plug outlets, standard as Spectra Series plug-in bus with bus plug
shown (trapeze hanger positions may obstruct some openings). Vertical riser
plug-in busway is also available with plug outlet openings on one side (when
the other side is inaccessible) for even greater value. Plug outlet covers are
molded of tough, impact and chemical resistant polycarbonate thermoplastic.
inches
millimeters
JOINT JOINT
Available as 4 or 10 outlets per 10-foot section
(Circled outlets omitted in 4-outlet design)
www.geelectrical.com 14
Spectra Series™ Busway
Physical Data
Fittings
Spectra Series busway has a complete family of fittings to meet virtually all
layout requirements using the compact minimum sizes shown. Special turns
such as flat angles greater than 90° and crosses are also available.
Nomenclature for completely defining the turn is defined by looking into the
joint end with phase Ø side facing down on the busway as shown in Fig. 15.1.
Flatwise elbow
Each piece of busway is labeled to maintain proper phasing. All turn dimensions
are defined from the centerline of the joint end to the centerline of the
busways as “X”, “Y”, and “Z” (where applicable) leg lengths. Tables 16.1 - 16.4
Dimensions listed are standard. Variable leg lengths are available in 1⁄8” incre-
ments (except joint elbows). The total footage of any one fitting cannot
exceed 10 feet in length.
Note: Offsets and combination elbows are typically used only when standard
elbows will not fit.
Fig. 15.1 UP
Edgewise elbow
LEFT
RIGHT
JOINT NUT
Edgewise joint elbow (indoor only)
G
PHASE N Bar Centerline to Centerline Dimensions
RELATIONSHHIP C Configuration Amperage Flatwise Joint Elbow Edgewise Joint Elbow
Width Inches MM Inches MM
B "Ø SIDE"
A ON BOTTOM Al 225-800
1.63-2.88 3 76 6 152
Cu 225-1200
DOWN Al 1000-1200
JOINT END Single Stack 3.38-4.50 4 102 6 152
Cu 1350-1600
Al 1350-2000
5.75-8.25 5 127 6 152
Cu 2000-2500
Al-2500
4.25-4.5 8 203 6 152
Cu-3000
Al-3000
Double Stack 5.75-6.50 10 254 6 152
Cu-4000
Al-4000
7.5-8.25 12 305 6 152
Cu-5000
www.geelectrical.com 15
Spectra Series™ Busway
For use in applications where joint elbows do not apply, e.g., variable lengths, drip-proof, splash-proof and outdoor.
Table 16.3
Flat Offsets .25 41⁄2
6 114
Standard Dimensions Down tee shown Right tee shown
Amps X X Y Y Z Z
Inches MM Inches MM Inches MM
225-1350 12 305 5 127 12 305 Offsets
Aluminum 1600-3000 18 457 5 127 18 457 Up or down offsets (Edgewise) Left or right offsets (Flat)
4000 24 610 8 203 24 610
225-2000 12 305 5 127 12 305
Copper 2500-4000 18 457 5 127 18 457
5000 24 610 9 229 24 610 10
254
Table 16.4 10
Combination Elbows 6 254
152
Standard Dimensions
Down offset shown Right offset shown
Amps X X Y Y Z Z
Inches MM Inches MM Inches MM
225-1350 10 254 8 203 12 305 Combination Elbow
Aluminum 1600-2500 10 254 12 305 18 457
3000-4000 10 254 16 406 24 610
225-2000 10 254 8 203 12 305
Copper 2500-3000 10 254 12 305 18 457
4000-5000 10 254 16 406 24 610
www.geelectrical.com 16
Spectra Series™ Busway
Physical Data
Cable Tap Boxes
Spectra Series tap boxes are used where a run of busway is fed by cable and
conduit. Our corner post design permits removal of up to three side walls for
cable access/entrance and for greater flexibility and installation ease. Lugs
are provided as shown in Table 17.1. Universal lug terminal plates are available
to accept almost all NEMA and non-NEMA mechanical and compression lugs.
(Maximum 17⁄8 inches wide).
48 mm End cable tap box (with side removed)
IMPORTANT: Certain local/city code requirements can affect the dimensions, number of lugs furnished, lug position,
etc. of fittings. In these situations, refer to factory.
Table 17.1
Dimensions, Cable Bending Space and Lug Data “C” Cable Number
Number Aluminum Copper Bend of #2-600
H H
of Bars Amp W W Space MCM Lugs
Per Phase¬
Per Phase Inches MM Inches MM Inches MM Inches MM Inches MM
225 17 432 26 660 17 432 26 660 15 381 1
400 17 432 26 660 17 432 26 660 15 381 2
600 17 432 26 660 17 432 26 660 15 381 2
800 17 432 26 660 17 432 26 660 15 381 3
1 1000 17 432 26 660 17 432 26 660 15 381 3
1200 20 508 29 737 20 508 29 737 18 457 4
1350 20 508 29 737 20 508 29 737 18 457 4
1600 20 508 29 737 20 508 29 737 18 457 5
2000 26 660 29 737 26 660 29 737 18 457 6
2500 – – – – 26 660 29 737 18 457 8
2500 26 660 29 737 – – – – 18 457 8
3000 33 838 34 864 33 838 34 864 23 584 9
2
4000 33 838 34 864 33 838 34 864 23 584 12
5000 – – – – 39 991 34 864 23 584 15
¬ Mechanical type (CU-AL wire) lugs standard; crimp type optional. One ground lug standard through 3000-Amp CU.
Two ground lugs standard for 4000-Amp AL, 5000-Amp CU. Optional one ground lug per phase lug.
Box size may change when using some compression type lugs. Check with factory.
inches
millimeters
H
AØ BØ CØ N
"Ø SIDE" C
24®
33⁄4 LUG DIRECTION
95
610
10
254
Note: Smaller special purpose end cable tap boxes are available.
Contact the factory for details.
® 24 dimension changes to 28 for 5000-Amp or if optional one ground lug per phase lug is required.
610 711
www.geelectrical.com 17
Spectra Series™ Busway
Dimensions, Cable Bending Space and Lug Data “C” Cable Number
Number Aluminum Copper Bend of #2-600
L L
of Bars Amp W W Space MCM Lugs
Per Phase¬
Per Phase Inches MM Inches MM Inches MM Inches MM Inches MM
225 17 432 26 610 17 432 26 660 15 381 1
400 17 432 26 610 17 432 26 660 15 381 2
600 17 432 26 610 17 432 26 660 15 381 2
800 17 432 26 610 17 432 26 660 15 381 3
1 1000 17 432 26 610 17 432 26 660 15 381 3
1200 20 508 29 737 20 508 29 737 18 457 4
1350 20 508 29 737 20 508 29 737 18 457 4
1600 20 508 29 737 20 508 29 737 18 457 5
2000 26 660 29 737 26 660 29 737 18 457 6
2500 – – – – 26 660 29 737 18 457 8
2500 26 660 29 737 – – – – 18 457 8
3000 33 838 34 864 33 838 34 864 23 584 9
2
4000 33 838 34 864 33 838 34 864 23 584 12
5000 – – – – 39 991 34 864 23 584 15
¬ Mechanical type (CU-AL wire) lugs standard; crimp type optional. One ground lug standard through 3000-Amp CU.
Two ground lugs standard for 4000-Amp AL, 5000-Amp CU. Optional one ground lug per phase lug.
Box size may change when using some compression type lugs. Check with factory.
Fig. 18.1
Alternate End Tap Box: Feeder or Plug-In
inches
millimeters W
24 ®
610
BOX & BUSWAY
L
33/4
95 LUG DIRECTION Note: Smaller special purpose end cable tap boxes are available.
(See Below) Contact the factory for details.
10
254
® 24 dimension changes to 28 for 5000-Amp
JOINT
610 711
END AND BOTH
SIDES ARE or if optional one ground lug per phase lug
REMOVABLE is required.
LUG
N N
DIRECTION LUG
CØ CØ DIRECTION
BØ BØ
AØ AØ
"Ø SIDE"
C C
L L
"Ø SIDE"
www.geelectrical.com 18
Spectra Series™ Busway
Physical Data
Center Cable Tap Boxes
Table 19.1
Dimensions, Cable Bending Space and Lug Data Cable Number
Number Aluminum Copper Bend of #2-600
W W
of Bars Amp E L E L Space MCM Lugs
Per Phase¬
Per Phase Inches MM Inches MM Inches MM Inches MM Inches MM Inches MM Inches MM
225 24 610 4 3⁄8 111 20 508 24 610 4 3⁄8 111 20 508 15 381 1
400 24 610 4 3⁄8 111 20 508 24 610 4 3⁄8 111 20 508 15 381 2
600 24 610 4 3⁄8 111 20 508 24 610 4 3⁄8 111 20 508 15 381 2
800 24 610 4 3⁄8 111 20 508 24 610 4 3⁄8 111 20 508 15 381 3
1 1000 24 610 4 3⁄8 111 20 508 24 610 4 3⁄8 111 20 508 15 381 3
1200 30 762 6 152 28 711 30 762 6 152 28 711 18 457 4
1350 30 762 6 152 28 711 30 762 6 152 28 711 18 457 4
1600 30 762 6 152 28 711 30 762 6 152 28 711 18 457 5
2000 36 914 9 229 28 711 36 914 9 229 28 711 18 457 6
2500 — — — — — — 36 914 9 229 32 813 18 457 8
2500 36 914 9 229 32 813 — — — — — — 18 457 8
3000 48 1219 12 3⁄4 324 39 991 48 1219 12 3⁄4 324 39 991 23 584 9
2 4000 48 1219 12 3⁄4 324 39 991 48 1219 12 3⁄4 324 39 991 23 584 12
5000 — — — — — — 48 1219 12 3⁄4 324 46 1168 23 584 15
2000 Amp (Max) Center Branch Tap Boxes
1 2500 — — — — — — 36 914 9 229 28 711 18 457 6
2500 36 914 9 229 28 711 — — — — — — 18 457 6
3000 43 1092 12 3⁄4 324 28 711 43 1092 12 3⁄4 324 28 711 18 457 6
2 4000 43 1092 12 3⁄4 324 28 711 43 1092 12 3⁄4 324 28 711 18 457 6
5000 — — — — — — 43 1092 12 3⁄4 324 28 711 18 457 6
¬ Mechanical type (CU-AL wire) lugs standard; crimp type optional. One ground lug standard through 3000-Amp CU. Two ground lugs standard for
4000-Amp AL, 5000-Amp CU. Optional one ground lug per phase lug.
Box size may change when using some compression type lugs. Check with factory.
24 ®
610
33⁄4
95 Fig. 19.3
10 Standard Box Down Position, Side View
254
® 24 dimension changes to 28 for 5000-Amp or if optional one ground lug per phase lug is required.
610 711
www.geelectrical.com 19
Spectra Series™ Busway
Transformer Taps
Table 20.1 Fig. 20.1
Dimensions for Three Phase End Tap Three-Phase End Tap
¬ Mechanical type (CU-AL wire) lugs standard; crimp type optional. One ground lug à 24 dimension changes to 28 for 5000-Amp
standard through 3000-Amp CU. Two ground lugs standard for 4000-Amp AL, 610 711
5000-Amp CU. Optional one ground lug per phase lug. or if optional one ground lug per phase lug
is required.
Table 20.2
Dimensions for Single Phase End Tap Fig. 20.2
Single-Phase Transformer Taps
Dimensions and Lug Data Number
Number 171⁄2 TYP
Aluminum Copper of #2-600
W W
of 445
Amp MCM Lugs
Per Phase®
Stacks Inches MM Inches MM
1000 16 406 – – 2 1021⁄2 min
26031⁄2 371⁄2 min
1200 16 406 16 406 3
9521⁄2
1350 20 508 16 406 3 22
1 559
1600 20 508 16 406 3
2000 20 508 20 508 4 10 min.
2500 – – 20 508 5 254 6
152
2500 24 610 – – 5
3000 32 813 24 609 6 63⁄8 53⁄4
2 162
4000 32 813 32 813 8 146
5000 – – 32 813 10
Box size may change when using some compression type lugs. Check with factory.
® Mechanical type (CU-AL wire) lugs standard; crimp type optional. One ground lug
standard through 3000-Amp CU. Two ground lugs standard for 4000-Amp AL,
5000-Amp CU. Optional one ground lug per phase lug.
Fig. 20.3
Standard Lug Position
15
381
43⁄8 43⁄8
111 111
www.geelectrical.com 20
Spectra Series™ Busway
Physical Data
Flanged end stub
Provides a universal stub for field connections (customer connection only).
inches
A
millimeters B D
C TYP
Fig. 21.2
Flanged End without Lugs,
41/2
1 Bar per Phase 5 114 TYP
127 Flanged end stub
41/2
5 114 TYP
127
GRDGRD
GRDGRD 41/2 41/2
114 114 12
305 1
A ØA BØ ØB ØC Ø C Ø N N 25
2 2
51 51 11/2 11/2 OPENING
38 38 CUTOUT
Side View 3 3
76 76 E
F
TYP TYP G
H
J
www.geelectrical.com 21
Spectra Series™ Busway
7 1/2 9 7 1/2 9
191 8 229 191
203 8 229
3 3/8 3 3/4 203
95 TYP TYP
86 TYP TYP
1
1 25
25
CUTOUT AND
DRILLING
CUTOUT AND
DRILLING E
F
E G
H FLANGE
F FLANGE J
G
H K
L
Table 22.1
Flanged End with Lugs
Amps Figure A B C D E F G H J K L
Aluminum 225-600 14 7 61/2 6 41/2 81/2 13
22.1
Copper 225-1000 356 178 165 152 114 216 330
Aluminum 800-1000 151/8 7 9/16 7 1/16 6 9/16 411/16 97/16 141/8
22.1
Copper 1200-1350 384 192 179 167 119 240 359
NA
Aluminum 1200 161/4 81/8 7 5/8 7 1/8 51/8 101/8 151/4
22.1
Copper 1600 413 206 194 181 130 257 387
NA
Aluminum 1350-1600 181/4 91/8 8 5/8 81/8 5 3/4 111/2 171/4
22.1
Copper 2000 464 232 244 206 146 292 438
NA NA
Aluminum 2000 20 10 91/2 9 43/4 91/2 141/2 19
22.1
Copper 2500 508 254 241 229 121 241 362 483
251/2 12 3/4 121/4 113/4 47/8 93/4 4 3/4 195/8 241/2
Aluminum 2500 22.2
648 324 311 298 200 248 375 498 622
24 12 111/2 11 65/8 131/4 193/4 211/2
Copper 3000 22.2 NA
610 305 292 279 108 337 502 546
27 131/2 13 121/2 51/4 101/2 151/2 203/4 26
Aluminum 3000 22.2
686 343 330 318 133 267 394 527 660
311/2 15 3/4 151/4 143/4 4 3/8 8 3/4 131/8 173/8 213/4 261/8 301/2
Copper 4000 22.2
800 400 387 375 111 222 333 441 552 664 775
32 16 151/2 15 41/2 9 131/2 171/2 22 261/2 31
Aluminum 4000 22.2
813 406 394 381 114 229 419 445 559 673 787
37 181/2 18 171/2 6 12 18 24 30 36
Copper 5000 22.2 NA
940 470 457 445 152 304 457 608 762 914
Note: For quantity and size of lugs, refer to Cable Tap Box, page 17, Table 17.1.
www.geelectrical.com 22
Spectra Series™ Busway
Physical Data
Switchboard/switchgear stub
Spectra Series offers full factory coordination to other GE equipment as shown. Other entrance combinations are available.
Refer to company. Straight and elbow stubs ar available with flange to joint or elbow dimensions per Table 23.1.
Table 23.1
Stubs, Switchboard Ends
Fig. 23.1
"A"
"A" "A"
6Á
152 GE
PowerBreak GE Type AKD-8/10
GE AV-Line®
12 Class 1, 2, 5 Switchboards Switchgear and the
305 FRONT 6 FRONT Class 3 all new Entellisys
Switchboards FRONT
911/2 90 152 92 92
2324 90 2337 2337
2286 FRONT
2286
Á Standard dimension 6” from rear may vary and must be coordinated with switchboard factory.
www.geelectrical.com 23
Spectra Series™ Busway
The compact size and flexibility resulting from the modular design allow takeoffs to be mounted at any joint,
whether feeder or plug-in. See Fig. 24.1.
Table 24.1
Flex-A-Tap Device
Table 24.2 Ø
Power Takeoff and Device Dimensions
www.geelectrical.com 24
Spectra Series™ Busway
Physical Data
Power takeoffs (PTO) (cont.)
Table 25.1.A
Meter Mod™ III bused. Main module.
Dimensions
Catalog Number/Frame W H D
IN MM IN MM IN MM
Bused Main Breakers
TMP3BR4/TJK4 19 483 18 457 5.94 151
TMP3BL6/TJK6 19 483 18 457 5.94 151
TMP3BR6/TJK6 19 483 18 457 5.94 151
TMP3BL8/TKM8 20 508 18 457 7.88 200
TMP3BR8/TKM8 20 508 18 457 7.88 200
TMP3BL10/TKM10 20 508 18 457 7.88 200
TMP3BR10/TKM10 20 508 18 457 7.88 200
TMP3BL12/TKM12 20 508 18 457 7.88 200
TMP3BR12/TKM12 20 508 18 457 7.88 200
Bused Main Switches
TMP3FL4/TFUSE400 19 483 18 457 5.94 151
TMP3FR4/TFUSE400 19 483 18 457 5.94 151
TMP3FL6/TFUSE600 19 483 18 457 5.94 151
TMP3FR6/TFUSE600 19 483 18 457 5.94 151
Table 25.1.B
Bar Width “A”
Amps Bar Per Ø
IN MM IN MM
1.625 41
2.225 57
225-1600 Al 2.875 73 16.75 425
225-2000 Cu 3.375 86
1 4.250 108
4.500 114
5.750 146
2000 Al 6.500 165 20.00 508
2500 Cu 8.250 210
2500 Al 4.250 108 25.00 635
3000 Cu 4.000 102
3000 Al 2
4000 Cu 5.750 146 28.75 730
4000 Al
5000 Cu 8.250 210 32.00 813
www.geelectrical.com 25
Spectra Series™ Busway
Note: Floor or wall opening should be 1” (25 mm) larger than applied busway.
Fig. 26.2
End Boxes End Box 6 1/8
End boxes are used to terminate busway runs. No joint is required. End surface 152 A+ 3
of box adds 6” (152 mm) to length of drip-proof, splash-proof and outdoor runs.
See Table 27.1 for “A” dimension. Box is secured via joint cap bolts. 45/8
117
JOINT
Floor/Wall Flanges
Note: Floor or wall opening should provide 1/2” clearance all around the
busway. Fig. 26.3
Table 26.2 Floor/Wall Flange Cutout and Drilling Detail
Floor/Wall Flange Dimensions (inches)
.750
www.geelectrical.com 26
Spectra Series™ Busway
Physical Data
No fuse reducers
Table 27.1
“A” Dimensions
Aluminum Copper
No. of Stacks Amp
IN MM IN MM
225 4.38 111 4.38 111
400 4.38 111 4.38 111
600 4.38 111 4.38 111 No fuse reducer
800 5.63 143 4.38 111
1 1000 6.13 156 5.00 127
1200 7.00 178 5.63 143
1350 8.50 216 6.13 156
1600 9.25 235 7.00 178 inches
2000 11.00 279 8.50 216 millimeters
2500 — — 10.50 260
2500 15.50 394 — — Fig. 27.1
2 3000 18.00 457 14.50 368 Reducer
45/8
4000 23.00 584 18.00 457 117
5000 — — 21.50 546
A
NOTE: Per NEC 368.17 (B), a no-fuse reduced busway shall not exceed 50 feet in length and have a current
rating at least 1/3 the rating of the upstream overcurrent protective device.
JOINT
36
A 914
JOINT
www.geelectrical.com 27
Spectra Series™ Busway
www.geelectrical.com 28
Spectra Series™ Busway
Physical Data
Transposition lengths
A transposition length is available in any dimension from three feet through
10 feet (3M). Standard lengths are 36” and 42”. “A” dimension varies with
ampere rating. See Table 27.1 for “A” dimension.
inches
millimeters
Phase transposition
A G Fig. 29.1
B N Transposition Length
TOTAL C C
N B
G A
A C
B B
PHASE C A JOINT
ONLY N N 36
G G
917
A G ( 42 FOR 2000 and 4000 Al,
NEUTRAL/ B N
GROUND C A 914 2500 and 5000 Cu)
ONLY
N B A
G C
Fig. 29.2
Measuring Spectra busway for a field check.
www.geelectrical.com 29
Spectra Series™ Busway
Hangers
Cat. No. (SBR “X”) where “X” = Quantity of springs (1 or 2) on each side of Standard clevis hanger
Floor opening size refer to Table 11.1 for “A” dimension. Fig. 30.1
Cat. No. SBR “X”
A+ 1
25 inches
51⁄2
millimeters
FLOOR OPENING 140 (
161⁄4 171⁄2
)
413 445 for 5000 Amp
8
203
Horizontal mounting – 1 stack clevis hangers
(1 furnished every 10 feet. Requires (1) .50 inch diameter
drop rods. Drop rods by others.)
2
81⁄2
+2 51 216
One Stack Flatwise Hangers 51 3
⁄4
Aluminum Copper 1
A+ 5 ⁄2 19
Catalog Number Ampere Range Catalog Number Ampere Range 140
Minimum Clearance
SBF16 225-600 SBF16 225-800
SBF28 800 SBF22 1000
SBF33 1000 SBF28 1200 Fig. 30.2 Fig. 30.3
SBF42 1200 SBF33 1350 One Stack (Standard) Flatwise One Stack Edgewise
SBF57 1350 SBF42 1600 Cat. No. SBF “XX” Cat. No. SBE45
(See table at left) (Up to 2000 Amp Max)
SBF65 1600
SBF82 2000
www.geelectrical.com 30
Spectra Series™ Busway
Plugs
Switch-operated fusible plugs are equipped with type QMR quick-make,
quick-break mechanisms, in ratings from 30 to 600 amps, 240 and 600 volts.
Positive pressure NEC fuse clips are furnished standard. They are also available
with class “J” or “R” fuse clips.
Circuit breaker plugs are available with molded case circuit breakers, in ratings
from 15 to 800 amps, 240 to 600 volts.
Both fusible and circuit breaker Spectra Series busway plugs have:
• Plug assist mechanism standard on plugs rated above 100 amps.
• A cover interlock that prevents opening the cover when the switching device
is in the “ON” position. The interlock can be defeated by operating the
release mechanism through the door. However, by bending down a tab
inside the cover, the interlock becomes non-defeatable.
• A device interlock that prevents the switching device from being accidentally
operated when the cover is open.
• A provision to padlock the plug in the “OFF” position when the cover is closed
(suitable for single padlock with a 5⁄16-inch shank).
• A handle that can be mounted either on the side or end of the plug. In addition,
the handle may be mounted in one of two positions at each location.
• A handle that can be operated by a hook stick.
• A safety interlock that prevents insertion or removal of the plug when in the
“ON” position.
• Positive locator pin for exact, safe positioning.
• Both drip-proof (IP45) and splash-proof (IP54) plugs are available.
www.geelectrical.com 31
Spectra Series™ Busway
www.geelectrical.com 32
Spectra Series™ Busway
Plugs
Table 33.1
Spectra Bus Plugs with Tranquell TVSS Protection with Ground Fault
Max. Cont.
Nominal Voltage
Configuration 65kA 80kA 100kA Overvoltage
(Volts, RMS)
Capability (MCOV%)
1 Phase, 3 Wire
120/240 TPME120S06WC TPME120S08WC TPME120S10WC 125%
+ Ground
3 Phase, 4 Wire
120Y/208 TPME120Y06WC TPME120Y08WC TPME120Y10WC 125%
+ Ground
3 Phase, 4 Wire
240 Delta TPME240D06WC TPME240D08WC TPME240D10WC 115%
+ Ground
3 Phase, 4 Wire Vertical riser bus with plug installed
120/240 Delta HL TPME240H06WC TPME240H08WC TPME240H10WC 115%
+ Ground
3 Phase, 4 Wire
240Y/415 TPME240Y06WC TPME240Y08WC TPME240Y10WC 130%
+ Ground
3 Phase, 4 Wire
277Y/480 TPME277Y06WC TPME277Y08WC TPME277Y10WC 115% Fig. 33.1
+ Ground
3 Phase, 4 Wire Typical vertical application
220Y/380 TPME220Y06WC TPME220Y08WC TPME220Y10WC 145% with Spectra Series riser busway
+ Ground
3 Phase, 4 Wire
480 Delta TPME480D06WC TPME480D08WC TPME480D10WC 170% inches
+ Ground
3 Phase, 4 Wire millimeters
347Y/600 TPME347Y06WC TPME347Y08WC TPME347Y10WC 115%
+ Ground
3 Phase, 3 Wire D W
600 Delta
+ Ground
TME600D065WC TME600D080WC TME600D100WC 170% 12
305
Table 33.2 4
24 L 102
Spectra RMS™ Circuit Breaker Bus Plugs (Outer Dimensions)
Dimensions Handle
610 NC BA
Weight Plug-in
Tier Frame W L D Height¬ Figure NORMAL
Inches MM Inches MM Inches MM Inches MM
(lbs.) Outlets 120
3048 PLUG-IN SIDE
Lowest SED 11.00 279 13.00 330 8.00 203 9.12 232 25 1 33.2
SEH 11.00 279 13.00 330 8.00 203 9.12 232 25 1 33.2 ELEVATION
SFH 11.00 279 21.25 540 9.00 229 9.50 241 41 1 33.2
12 VIEW
Low
SGH 16.75 425 26.50 673 12.00 305 9.5 241 91 2 33.3
305
SKH 16.75 425 36.50 927 12.00 305 18 457 160 2 33.3
SEL 11.00 279 13.00 330 8.00 203 9.12 237 25 1 33.2
SFL 11.00 279 21.25 540 9.00 229 9.5 241 41 1 33.2
Mid
SGL 16.75 425 26.50 673 12.00 305 18 457 91 1 33.3
SKL 16.75 425 36.50 927 12.00 305 18 457 160 2 33.3
SEP 11.00 279 13.00 330 8.00 203 9.12 232 25 1 33.2 Fig. 33.2
SFP 11.00 279 21.25 540 9.00 229 9.5 241 41 1 33.2 Door hinges at left end.
Peak
SGP 16.75 425 26.50 673 12.00 305 18 457 91 1 33.3 All dimensions are shown over largest part of plug.
SKP 16.75 425 36.50 927 12.00 305 18 457 160 2 33.3
¬ Maximum distance from enclosure bottom to handle tip. TOP EDGE OF
For ground fault option, increase width by 2.125 inches and length by 6.00 inches. BUSWAY 3
/4
19
GENERAL
Table 33.3
Molded Case Circuit Breakers W
ELECTRIC
Dimensions
Type Frame W L D Figure HINGE
Inches MM Inches MM Inches MM
OFF
ON
Standard TEB, TED, THED 11.00 279 13.00 330 8.00 203 33.2 L D
TFJ, TFK, THFK 11.00 279 18.50 470 9.50 241 33.2
and
TJJ, TJK4, TJK6, THJK4, THJK6 16.75 425 24.50 622 12.00 305 33.3
Hi-Break®
TKM8, THKM8, THK 16.75 425 36.50 927 12.00 305 33.3
Fused TB1 11.00 279 18.50 470 8.00 203 33.2
Current TB4 30.50 775
16.75 425 12.00 305 33.3 Fig. 33.3
Limiting TB6, TB8 45.25 1149
Door hinges at top.
Table 33.4 All dimensions are shown over largest part of plug.
Fusible Switches
Dimensions HINGE 3/4
30 24 18.63 473
60 25 240, 380, 11.25 286 13.00 330
NA NA 8.75 222 33.2
QMR 100 28 415, 480,
OFF
18.75 476
ON
www.geelectrical.com 33
Spectra Series™ Busway
Cataloging
Busway plugs
Fusible bus plug catalog numbering system.
Table 34.1
Code Description SB 3 6 2 R G R P I
SB Spectra Bus (Industrial)
Type CSB* Spectra Bus (Commercial)
AC Armor Clad
FVK FVK Bus
3 3Ø 3W
Service
4 3Ø 4W
2 240 V
Volts
6 380, 415, 480 V
1 30
2 60
3 100
Amps
4 200
5 400
6 600
R QMR
Switch
W QMW
Notes:
All plugs provided with 2-600MCM/(2) 1/0 - 250MCM mechanical lug as standard.
Compression lugs available as an option.
* Plug assist option is available for 200 amp and greater only
www.geelectrical.com 34
Spectra Series™ Busway
Cataloging
Plugs
A plug assist is furnished as standard on all plugs greater than 100 amps
listed on this page. If plug assist is required on other plugs, add Suffix “P” to
Catalog Number.
All fusible plugs are furnished with Type “NEC” fuse clips as standard.
Optional fuse clips are available.
Table 35.1
Switch-operated Fusible Plug with QMR Interrupter
Table 35.4
Combination motor starter plugs-fusible and circuit breaker¬
(3-pole, full-voltage, non-reversing, single-speed)
Includes 3 overload relays with manual reset
www.geelectrical.com 35
Spectra Series™ Busway
Busway plugs
Plug assist is furnished as standard on all circuit breaker plugs except in the 100-amp frame sizes.
If plug assist is required on the 100-amp frame sizes, add Suffix “P” to Catalog Number.
Table 36.1
Circuit Breaker Plugs
Type Frame Trip Amps 3Ø-3W Cat. No. 3Ø-4W Cat. No. Type Frame Trip Amps 3Ø-3W Cat. No. 3Ø-4W Cat. No.
Standard Circuit Breakers¬ 70 SB37FKG SB47FKG
15 SB31EBG SB41EBG 80 SB38FKG SB48FKG
20 SB32EBG SB42EBG 90 SB39FKG SB49FKG
25 SB32.5EBG SB42.5EBG 100 SB310FKG SB410FKG
30 SB33EBG SB43EBG TFK 600 Volts 110 SB311FKG SB411FKG
35 SB33.5EBG SB43.5EBG 125 SB312FKG SB412FKG
40 SB34EBG SB44EBG 150 SB315FKG SB415FKG
TEB 240 Volts 45 SB34.5EBG SB44.5EBG 175 SB317FKG SB417FKG
50 SB35EBG SB45EBG 200 SB320FKG SB420FKG
60 SB36EBG SB46EBG 225 SB322FKG SB422FKG
70 SB37EBG SB47EBG 125 SB312JJG SB412JJG
80 SB38EBG SB48EBG 150 SB315JJG SB415JJG
90 SB39EBG SB49EBG 175 SB317JJG SB417JJG
100 SB310EBG SB410EBG 200 SB320JJG SB420JJG
15 SB31ED4G SB41ED4G TJJ 600 Volts 225 SB322JJG SB422JJG
20 SB32ED4G SB42ED4G 250 SB325JJG SB425JJG
25 SB32.5ED4G SB42.5ED4G 300 SB330JJG SB430JJG
30 SB33ED4G SB43ED4G 350 SB335JJG SB435JJG
35 SB33.5ED4G SB43.5ED4G 400 SB340JJG SB440JJG
40 SB34ED4G SB44ED4G 125 SB312JK4G SB412JK4G
TED4 480 Volts 45 SB34.5ED4G SB44.5ED4G 150 SB315JK4G SB415JK4G
50 SB35ED4G SB45ED4G 175 SB317JK4G SB417JK4G
60 SB36ED4G SB46ED4G 200 SB320JK4G SB420JK4G
70 SB37ED4G SB47ED4G TJK4 600 Volts 225 SB322JK4G SB422JK4G
80 SB38ED4G SB48ED4G 250 SB325JK4G SB425JK4G
90 SB39ED4G SB49ED4G 300 SB330JK4G SB430JK4G
100 SB310ED4G SB410ED4G 350 SB335JK4G SB435JK4G
15 SB31ED6G SB41ED6G 400 SB340JK4G SB440JK4G
20 SB32ED6G SB42ED6G 250 SB325JK6G SB425JK6G
25 SB32.5ED6G SB42.5ED6G 300 SB330JK6G SB430JK6G
30 SB33ED6G SB43ED6G 350 SB335JK6G SB435JK6G
35 SB33.5ED6G SB43.5ED6G TJK6 600 Volts 400 SB340JK6G SB440JK6G
40 SB34ED6G SB4ED6G 450 SB345JK6G SB445JK6G
45 SB34.5ED6G SB44.5ED6G 500 SB350JK6G SB450JK6G
50 SB35ED6G SB45ED6G 600 SB360JK6G SB460JK6G
TED6 600 Volts 60 SB36ED6G SB46ED6G 300 SB330KMG SB430KMG
70 SB37ED6G SB47ED6G 350 SB335KMG SB435KMG
80 SB38ED6G SB48ED6G 400 SB340KMG SB440KMG
90 SB39ED6G SB49ED6G TKM8 600 Volts 450 SB345KMG SB445KMG
100 SB310ED6G SB410ED6G 500 SB350KMG SB450KMG
110 SB311ED6G SB411ED6G 600 SB360KMG SB460KMG
125 SB312.5ED6G SB412.5ED6G 700 SB370KMG SB470KMG
150 SB315ED6G SB415ED6G 800 SB380KMG SB480KMG
70 SB37FJG SB47FJG ¬ TEB, TED4, THED, TFJ and TJJ are fixed trip circuit breakers.
80 SB38FJG SB48FJG
90 SB39FJG SB49FJG
100 SB310FJG SB410FJG
110 SB311FJG SB411FJG
TFJ 600 Volts 125 SB312FJG SB412FJG
150 SB315FJG SB415FJG
175 SB317FJG SB417FJG
200 SB320FJG SB420FJG
225 SB322FJG SB422FJG
www.geelectrical.com 36
Spectra Series™ Busway
Cataloging
Table 37.1
Circuit Breaker Plugs (continued)
Type Frame Trip Amps 3Ø-3W Cat. No. 3Ø-4W Cat. No. Type Frame Trip Amps 3Ø-3W Cat. No. 3Ø-4W Cat. No.
Tri-Break® Circuit Breakers (Includes Limiters) Hi-Break® Circuit Breakers (Includes Limiters)
15 SB31B1E05 SB41B1E05 15 SB31HED SB31HED
20 SB32B1E05 SB42B1E05 20 SB32HED SB32HED
25 SB32.5B1E05 SB42.5B1E05 25 SB32.5HED SB32.5HED
30 SB33B1E05 SB43B1E05 30 SB33HED SB33HED
35 SB33.5B1E05 SB43.5B1E05 35 SB33.5HED SB33.5HED
40 SB34B1E05 SB44B1E05 40 SB34HED SB34HED
45 SB34.5B1E05 SB44.5B1E05 45 SB34.5HED SB34.5HED
TB1 600 Volts 50 SB35SB1E09 SB45B1E09 THED 600 Volts 50 SB35HED SB35HED
60 SB36SB1E09 SB46B1E09 60 SB36HED SB336HED
70 SB37SB1E09 SB47B1E09 70 SB37HED SB37HED
80 SB38SB1E09 SB48B1E09 80 SB38HED SB38HED
90 SB39SB1E09 SB49B1E09 90 SB39HED SB39HED
100 SB310SB1E09 SB410B1E09 100 SB310HED SB310HED
110 SB311B1E10 SB411B1E10 110 SB311HED SB311HED
125 SB312.5B1E10 SB412.5B1E10 125 SB312.5HED SB312.5HED
150 SB315B1E10 SB415B1E10 150 SB315HED SB315HED
125 SB312B4F14 SB412B4F14 70 SB37HFK SB37HFK
150 SB315B4F14 SB415B4F14 80 SB38HFK SB38HFK
175 SB317B4F14 SB417B4F14 90 SB39HFK SB39HFK
200 SB320B4F14 SB420B4F14 100 SB310HFK SB310HFK
TB4 600 Volts 225 SB322B4F14 SB422B4F14 THFK 600 Volts 110 SB311HFK SB311HFK
250 SB325B4F14 SB425B4F14 125 SB312HFK SB312HFK
300 SB330B4F14 SB430B4F14 150 SB315HFK SB315HFK
350 SB335B4F14 SB435B4F14 175 SB317HFK SB317HFK
400 SB340B4F14 SB440B4F14 200 SB320HFK SB320HFK
300 SB330B6J14 SB430B6J14 225 SB322HFK SB322HFK
350 SB335B6J14 SB435B6J14 125 SB312HJK4 SB312HJK4
TB6 600 Volts 400 SB340B6J14 SB440B6J14 150 SB315HJK4 SB315HJK4
450 SB345B6J14 SB445B6J14 175 SB317HJK4 SB317HJK4
500 SB350B6J14 SB450B6J14 200 SB320HJK4 SB320HJK4
600 SB360B6J14 SB460B6J14 THJK4 600 Volts 225 SB322HJK4 SB322HJK4
250 SB325HJK4 SB325HJK4
TB8Â 600 Volts
600 SB360B8K20 SB360B8K20
700 SB370B8K20 SB370B8K20 300 SB330HJK4 SB330HJK4
800 SB380B8K20 SB380B8K20 350 SB335HJK4 SB335HJK4
400 SB340HJK4 SB340HJK4
300 SB330HKM SB330HKM
350 SB335HKM SB335HKM
400 SB340HKM SB340HKM
THKM8 600 Volts 450 SB345HKM SB345HKM
500 SB350HKM SB350HKM
600 SB360HKM SB360HKM
700 SB370HKM SB370HKM
800 SB380HKM SB380HKM
¬ TEB, TED4, THED, TFJ and TJJ are fixed trip circuit breakers.
TBI is a fixed trip circuit breaker.
 Not UL listed.
www.geelectrical.com 37
Spectra Series™ Busway
Table 38.1
Code Description F 3 H A 02 SL I 02
F Feeder
Type P Plug-In
R Riser
3 3PH, 3W
Service
4 4PH, 4W Indoor
H Integrated Housing
Ground
G Internal Bus
Conductor C Copper
A Aluminum
Code Amps
02 225
04 400
06 600
08 800
10 1000
12 1200
13 1350
16 1600
20 2000
25 2500
30 3000
40 4000
50 5000
Code Configurations
SL Straight Length
EL Elbow Left
ER Elbow Right
EU Elbow Up
ED Elbow Down
CT Center Cable Tap Box-Up
CB Center Cable Tap Box-Down
TT End Cable Tap Box-Up
TB End Cable Tap Box-Down
EB End Box
FE Flanged End
FL Flanged End with Lugs
www.geelectrical.com 38
Spectra Series™ Busway
www.geelectrical.com 39
Spectra Series™ Busway
Plugs
Where shown on plans, furnish and install busway plugs
of the types and ratings indicated. When applicable,
plugs shall be UL labeled.
www.geelectrical.com 40
Spectra Series™ Busway
Notes
www.geelectrical.com 41
Spectra Series™ Busway
www.geelectrical.com 42
Spectra Series™ Busway
Joint Guard™
Positive torque indication. Time after time.
GE’s exclusive Joint-Guard™ protection system shows you, with color,
whether a busway joint is loose or tight. The center spot is bright red when
a joint is loose and turns dark when proper torque is applied. It does this not
just once — as with double-headed break-off bolts — but even after the
repeated tightening and loosening so often required during installation. And it
will keep on working that way for 30 years*.
How it works
Joint-Guard technology was developed for the nuclear and aerospace industries.
It measures the elongation of the busway joint bolt, and is more accurate
that a torque wrench, which is subject to substantial variations in static and
dynamic friction, depending on thread wear and lubrication.
*assumes busway operates 14 hours per day, six days per week,
at 81% load in 25°C ambient