Horse Power (H.P.) Selection: Calculation of Discharge Rate of Bore Well, Water Level, Friction Loss in Pipes, Valves & Fittings, H.P. Selection For Submersible Pump Sets, Unit Conversion
Horse Power (H.P.) Selection: Calculation of Discharge Rate of Bore Well, Water Level, Friction Loss in Pipes, Valves & Fittings, H.P. Selection For Submersible Pump Sets, Unit Conversion
Horse Power (H.P.) Selection: Calculation of Discharge Rate of Bore Well, Water Level, Friction Loss in Pipes, Valves & Fittings, H.P. Selection For Submersible Pump Sets, Unit Conversion
Calculation of Discharge (Yield) of Bore-well, Water Level, Friction Loss in Pipes, Valves & Fittings,
Cable Selection for Submersible Pump Sets
The discharge during drilling or after completion of drilling is required, which is necessary for choosing
appropriate pump. Taking the values of discharge and total head, the HP of pump set will be selected.
The pump set should be selected which is efficient and consumes less power. Moreover the drawdown
is another factor for correctly choosing the pump.
Obviously deeper you install a pump, less water it pumps. Please note that higher the HP you use
does not mean that more water you get. Ideally, a pump should extract only that much water as
much as the yield rate of the aquifer permits so as to maintain a steady state in the pumping water
level.
Also a pump lifts water depending on the speed, diameter and stages of the impellers which again the
pump manufacturers decide. For a given discharge capacity, one needs more stages (counted by
the number of rings in the pump body) as one goes deeper.
Ideally a bore well should be tested for its optimal yield before selecting a pump. Such test is
known as Step Drawdown Test.
In this test a submersible pump is lowered at a suitable depth and the pump is run for a fixed time
(say 1 hr.) in steps. In each step the pump is made to lift water at very low, low, medium and high
discharge rates using a Glove Valve in the delivery pipe to maintain a constant discharge for the
particular step. The drawdown (fall in the pumping water level) is measured during and at the end
of each step (1 hr.). The discharge drawdown curve gives the optimum discharges of the well.
Lowering the pump at a suitable depth with sufficient submergence is important as the pumping water
level usually falls depending upon the discharge rate of the pump and aquifer yielding capacity
(permeability).
Ideally a pump should extract water at such a rate so that the water level in the well stabilizes
after some times and do not fall further. A pump running dry with lowering water level can burn
out easily. To prevent this, you are advised to install a 1.0-1.25 flexible PVC pipe in the bore well
till the pump depth so that you can monitor the pumping water level using an electrical water level
recorder at any time. The PVC guide pipe needs to the clamped at the top securely to prevent it
from falling in to the bore hole.
To decide about the correct size of submersible pump set, the details regarding Discharge (LPS) Total
Head i.e. pumped water level (Static water head + Drawdown) in metres to discharge point on ground
level required. Discharge data of winter season and pumped water level date of summer season is
necessary as these are the maximum values based on which we can calculate H.P of pump set.
Other option is, take the data of discharge and total head of your bore well to pump dealer. By using
pump curves, the dealer can suggest you the correct size of pump set. You have to select the pump set
which consumes less power.
As per V-Notch method (at 90 degrees) at 2" the discharge is about 1LPS and 45 degrees the yield is
still
less.
As
per
Drillers
assumption
2"
means
about
2
LPS.
As no pump set is installed in bore well, I suggest you collect the discharge and total head (winter
and summer respectively) data of your neighbouring bore wells having same depth and approach
the
pump
dealer
for
correct
size
of
submersible
pump
set.
However, correct details regarding discharge and pumped water level data can obtain by carrying out
step-draw-down test by trained professionals. In addition, the existing voltage conditions, variable
discharge and Totaleasons causes under loading and overloading of motor which leads to more
1 |12 P a g e
consumption of power and low power factor. In such conditions installation of L.T. Capacitor is
necessary to safe guard your pump set.
Capacity of the pump to be chosen depends on the depth at which the pump/foot valve is to be installed
and the desired discharge. Based on the total depth of the bore well, the depth at which the pump is to
be installed (usually 10-25 feet above total depth of pumps) is decided.
The total head is determined using the depth of pump, overhead tank level and friction loss expected in
the suction and delivery pipes.
In the absence of above, the discharge and total head data of neighbouring wells having same depth and
rock formations may be utilized for the selection of pump set. We should insist the pump dealer to suggest
the pump set based on discharge and total head and pump should have BIS standard. Well reputed
brands may be purchased having BIS standard.
If the capacity of the pump set is more and pump setting is in low depth, after few minutes of pumping
the water level may go below the pump setting. If the pump setting is quite deep the discharge may be
very low. Hence correct details regarding discharge and total head are necessary to select the correct
size (HP) of pump set and pump setting in the bore well.
Then how to get the details of discharge and total head before actually installing pump set in a bore well.
To conduct the yield test or step draw-down test to arrive at correct discharge, total head and
specific capacity etc.
How to determine yield of a bore well while drilling?
Usually V-Notches (a metal plate/wooden board with V shaped slot on top) are used by bore well drillers
for determining yield of a bore well during the bore well drilling process. To measure the flow, water
coming out of the bore well during drilling process is allowed to flow through an earthen barrier created
around the site is fixed with a V-notch temporarily.
Drillers wont be inclined to do so as this is an additional task they have to do. Based on their experience,
they tell the rough yield which may not www.indiawaterportal.org be always correct. Yield of a bore well
is usually referred in inches (i.e. depth of water flowing over the notch).
How yield of an existing bore well can be determined?
Yield of a bore well can be determined by conducting a step drawdown test, in which water is pumped
at different rates (that is, so many litres per hour) by keeping the submersible pump at different depths to
know the actual quantum of water that could be safely pumped and the resulting lowering of water level
or drawdown. The test helps to know whether the bore well can meet the water requirements.
Usually, reputed pump dealers can conduct such tests at a fee before deciding to purchase a pump. Such
tests are necessary for large settlements like apartments to arrive at very suitable pumps which can
provide huge quantities of water needed.
Checking water resource capability of unused bore well
In a pumping test or step drawdown test, water is pumped at different rates (that is, so many litres
per hour) by keeping the submersible pump at different depths to know the actual quantum of
water that could be safely pumped and the resulting lowering of water level or drawdown. The
test helps to know whether the bore well can meet the water requirements of the land to be
irrigated and the types of crops that could be grown with the available water.
2 |12 P a g e
TABLE 8-X: Discharge Rate in Gallons per Minute (GPM) for Large Capacity Systems
Horiz.
Nominal Pipe Size (in Inches)
Dist.(X) 1 1.25 1.5 2 2.5 3
4
5
6
8
Inches
Discharge Rate in Gallons Per Minute (GPM)
4
5.7 9.8
13.3 22
31
48 83
5
7.1 12.2 16.6 27.5 39
61 104 163
6
8.5 14.7 20
33
47
73 125 195 285
7
10
17.1 23.2 38.5 55
85 146 228 334 380
8
11.3 19.6 26.5 44
62
97 166 260 380 665
9
12.8 22
29.8 49.5 70
110 187 293 430 750
10
14.2 24.5 33.2 55.5 78
122 208 326 476 830
11
15.6 27
36.5 60.5 86
134 229 360 525 915
12
17
29
40
66
94
146 250 390 570 1000
13
18.5 31.5 43
71.5 102 168 270 425 620 1080
14
20
34
46.5 77
100 170 292 456 670 1160
15
21.3 36.3 50
82.5 117 183 312 490 710 1250
16
22.7 39
63
88
125 196 334 520 760 1330
17
41.5 56.5 93
133 207 355 550 810 1410
18
60
99
144 220 375 590 860 1500
19
100 148 232 395 620 910 1580
20
156 244 415 650 950 1660
21
256 435 685 1000 1750
3 |12 P a g e
Calculating Low Capacity Outlets: A simple procedure for measuring low capacity outlets such as
small pump outlets, hose spigots, and faucets is to record the amount of time it takes to fill a container
of known size.
EXAMPLE: Select a container of known size such as a 5-gallon paint bucket. With a watch, measure, in
seconds, the amount of time it takes to fill the bucket. If it takes 30 seconds to fill a 5-gallon bucket,
Table 8-W indicates that the flow is 10.0 gallons per minute. To obtain gallons per hour (gph) multiply
10.0 x 60 to obtain 600 GPH. NOTE: Multiply gallons per minute (GPM) by 60 to obtain gallons per hour
(GPH).
TABLE 8-W: Discharge Rate in Gallons Per Minute (GPM) for Low Capacity Systems
Capacity of
Time (in seconds) to Fill Container
Container
10
15
20
30
45
60
90
120
(Gallons)
Discharge Rate in Gallons Per Minute (GPM)
1
6
4
3
2
1.3
1
0.7
0.5
3
18
12
9
6
4
3
2
1.5
5
30
20
15
10
6.7
5
3.3
2.5
10
60
40
30
20
13.3
10
6.7
5
How to measure depth of water and total depth of existing bore well?
We can find the water level in a bore well from the ground by time calculating the time taken for a very
small stone (0.5 inch) to strike the water surface. All you need is a watch and a very small stone. Drop
the stone and note the time taken for it to strike the water surface. Multiplying with 9.8 (i.e. an object free
falling near the earth surface would travel 9m/sec due to gravity) to the time taken for the stone to strike
the water surface measured in seconds, we can get the water level depth in meters (Ex: for a 10 seconds
time, depth to water is 9.8 x 10 = 98 meters) . Repeat the exercise few times to get the correct depth.
A thin nylon rope longer than the depth of bore well firmly attached to a small sized stone (2 inches) or
metal ring (a small automobile bearing is ideal for this purpose) in one end is used for finding both the
water level and total depth of the bore well. While leaving the stone/metal block attached to the rope into
the bore well, when reduction in the weight of the stone is felt due to buoyancy of water after it strikes
water surface, mark the point on the rope and remove the entire portion of rope let inside the bore well
to measure for the water level from the ground.
Similarly, when you feel that the rope is not freely moving downwards from your hand once the stone
strikes bottom of the bore well, mark the point and measure for the total depth of the bore well after
removing the rope.
Calculating Distance to Water Level
Install 18" or 14" pipe or tubing into the well so that the end of the tubing extends 10 to 20 feet below the
lowest possible pumping water level. Be sure that all joints in the tubing are airtight. As the tubing is
lowered into the well measure its length. Record the measurement.
Once the tubing is fixed in a stationary position at the top of the well, connect an air-line and pressure
gauge. With a tire pump or other air supply, pump air into the line until the pressure gauge reaches a
point where it doesn't read any higher. Record the pressure gauge reading at this point.
4 |12 P a g e
Figure 8-Y illustrates a typical method for measuring distance to water level:
X = Distance to water level (in feet). This figure to be determined.
Y = Total length of air line (in feet).
Z = Length of submerged air-line. This value is obtained from the pressure gauge reading which reads
in pounds per square inch (psi). Multiply the pressure gauge reading by 2.31 to obtain the length of the
submerged air-line in feet.
Distance to water level (X) = (Y) - (Z) = The total length of the air line (Y) minus the length of the
submerged portion of the air line (Z).
Example: Assume that the air line is 100 feet long and the pressure gauge reads 8 psi. Calculate the
distance to water level (X). 8 psi x 2.31 = 18.5 feet
(X) = 100 feet (Y) - 18.5 feet (Z) = 81.5 feet = distance to water level
Figure 8-Y: Calculating the distance to water level.
1
1
1
2
2
2
3
4
5
6
7
8
9
10
12
14
16
20
25
30
35
40
ID
0.622"
4.8
10
17.1
25.8
36.5
48.7
62.7
78.3
95.9
5 |12 P a g e
ID
0.824"
2.5
4.2
6.3
8.9
11.8
15
18.8
23
32.6
43.5
56.3
86.1
ID
1.049"
ID
1.380"
ID
1.610"
ID
2.067"
ID
2.469"
1.9
2.7
3.6
4.5
5.7
6.9
9.6
12.8
16.5
25.1
38.7
54.6
73.3
95
1.8
2.5
3.3
4.2
6.3
9.6
13.6
18.2
23.5
1.2
1.5
2
2.9
4.5
6.3
8.4
10.8
1.3
1.8
2.4
3.1
1.3
ID
3.068"
ID
4.026"
45
50
60
70
80
90
100
120
140
160
200
260
300
29.4
36
51
68.8
89.2
13.5
16.4
23.2
31.3
40.5
51
62.5
3.9
4.7
6.6
8.9
11.4
14.2
17.4
24.7
33.2
43
66.3
1.6
1.9
2.7
3.6
4.6
5.8
7.1
10.1
13.5
17.5
27
45
59.6
1.2
1.6
2
2.4
3.4
4.5
5.8
8.9
14.8
19.5
1.2
1.5
2.3
3.7
4.9
1
1
1
2
2
EQUIVALENT LENGTH OF PIPE (IN FEET)
Insert Coupling
Plastic
3
3
3
3
3
3
3
Threaded Adapter
Plastic
3
3
3
3
3
3
3
(Plastic to Thread)
900 Standard Elbow
Steel
2
2
3
4
4
5
6
Plastic
2
2
3
4
4
5
6
Standard Tee
Steel
1
2
2
3
3
4
4
(Flow Through Run)
Plastic
1
2
2
3
3
4
4
Standard Tee
Steel
4
5
6
7
8
11
13
(Flow Through Side)
Plastic
4
5
6
7
8
11
13
Gate Valve1
Steel
1
1
1
1
2
2
2
Swing Check Valve1
Steel
5
7
9
12
13
17
21
NOTES: Based on schedule 40 steel and plastic fittings.
Figures given are friction losses in terms of Equivalent Lengths of straight pipe.
(1) Friction loss figures are for screwed valves and are based on equivalent lengths of steel pipe.
Head and Pressure
Head and pressure are related in a very simple and direct manner. Since water has known weight, we
know that a 231 foot long, one inch square pipe holds 100 pounds of water. At the bottom of the oneinch square pipe we refer to the pressure as 100 pounds per square inch (psi). For any diameter pipe
231 feet high, the pressure will always be 100 psi at the bottom.
Head is usually expressed in feet and refers to the height, or elevation, of the column of water. In a
column of water 231 feet high creates a pressure reading of 100 psi. That same column of water is
referred to as having 231 feet of head. Thus, for water, 231 feet of head is equivalent to 100 psi. Or,
2.31 feet of head equals 1 psi.
6 |12 P a g e
It should be noted that head and pressure readings for non-flowing water depend on the elevation of
the water and not on the volume of water nor the size or length of piping.
7 |12 P a g e
(a) 1/2 drop pipe (or rising pipe) friction head for 2 LPS is 2.2 feet per 100 feet.
200 feet of new 1 1/2 drop pipe has a total loss of. = 2.2 x 2.0 = 4.4 Feet
(b) Friction head loss in one 1 1/2 check valve =.....................................= 2.2 Feet
(Where total head exceeds 200, the use of a drop pipe check valve is recommended. Check valve
should be located approximately 20 above the bowl assembly. For settings over 600, the use of two
check valves are recommended, with the first valve approximately 100 above bowl unit and the
second located approximately 60% of the distance between the first valve and the surface plate.)
(2) Impeller Selection: Since no speed was specified, use 3450 RPM. The S9XHC shows 76%
efficiency, full diameter.
(i) Number of stages required = TDH/ (Head/Stage) = 311/125 = 2.48, USE 3 stages, 75.5%.
(ii) Total Pump Thrust = TDH x Impeller Thrust Factor x Specific Gravity + (Rotor Weight per Stage x
Number of Stages)
= (311 x 4.9 x 1) + (10.6 x 3) = 1554.80
(iii) Water Horse Power (WHP) = GPM x TDH x Sp. Gr. = 158.5 x 311 x 1 = 12.45
3960
3960
(iii) Bowl Horsepower (Break Horse Power) = GPM x TDH x Sp. Gr. = 158.5 x 311 x 1 = 16.48 BHP
3960x Bowl (Pump) Efficiency 3960 x 75.5%
(iv) Pump Efficiency = GPM x TDH x Sp. Gr. = 158.5 x 311 x 1 = = 75.53%
3960 x Bowl H.P.
3960 x 16.48
9 |12 P a g e
11 |12 P a g e
Where K = Meter constant = watts per revolution of revolving disc (value of K is marked on the meter
nameplate or on the revolving disc). Where current transformers are used, multiply meter constant by
current transformer ratio.
R = Number of disc revolutions counted.
t = Time in seconds for R revolutions.
CALCULATING OPERATING COSTS OF PUMPS:
Costs in Cents per 1,000 Gallons:
Cost () = kw Input x r x 1,000/ GPH
Cost in Cents per Acre-Inch
Cost () = kw Input x r x 452.6/ GPM
Where: r = cost of power in cents per kw-hr.
UNITS OF VOLUME AND WEIGHT: Weight equivalent basis water at 60F.
1 U.S. GALLON = 3.785 LITERS = 0.003785 m3 = 8.34 POUNDS = 0.833 IMPERIAL GALLON
UNITS OF FLOW: Discharge Rate
1 U.S. GALLON PER MINUTE (GPM) = 0.2271 m3/hr. = 0.0631 LITERS/SECOND (LPS)
UNITS OF PRESSURE AND HEAD:
NOTES: (1) Equivalent units are based on density of fresh water at 68F.
(2) Equivalent units are based on density of mercury at 32F.
(3) Each 1,000 feet of ascent decreases pressure about 12 pound per square inch.
1 LBS. PER SQUARE INCH = 2.31 x FEET OF WATER
12 |12 P a g e