Repair Manual 06-09-10
Repair Manual 06-09-10
Repair Manual 06-09-10
CONTENTS:
Section: Topic:
I.
II.
III.
Page:
2
14
25
SECTION I
ROOF INSPECTION & MAINTENANCE
All roofs require periodic inspection and maintenance in order to perform as designed and to
provide a long and effective service life. Periodic inspection and maintenance is also typically
required by roofing system manufacturers to keep roofing warranties in full force and effect.
Although all building owners should establish a periodic roof inspection program, inspection and
maintenance of any roof should be undertaken only by qualified persons who are familiar with safe
roofing practices, including all applicable occupational, health and safety regulations relating to the
roofing and construction industries.
Modern roofing systems contain a wide variety of components and installation techniques. All roof
inspections should be conducted by a licensed roofing contractor or similar roofing professional.
Typically, two inspections should be conducted each year, one in the spring and one in the late fall.
If the roof is warranted, at least one roof inspection each year should be conducted by the licensed
contractor who originally installed the roof.
Please note that the cost of periodic inspection is typically not included in the original cost of a
manufacturers warranty. Accordingly, the building owner should contact a licensed contractor to
obtain a proposal for ongoing inspection and maintenance services.
For additional information, including the most current details and specifications, please refer to the
Firestone Technical Database at www.firestonebpco.com.
Subject:
Roof Traffic
Contaminants
Drainage
Wind Storm Damage
Moisture Infiltration
Roof Membrane Seams
Base Attachments
Roof Inspection Checklist
Page:
3
5
6
7
9
10
11
13
REMEDIAL ACTIONS:
1. Remove Debris. Bag and remove from the roof.
2. Repair Drainage Components. Please refer to "Inspecting Roof Sealants and Sheet Metal."
PREVENTATIVE ACTIONS:
1. Add Roof Drains. Roof drains can be added to remove water from impacted areas.
2. Add Taper Systems. Water in impacted areas can be diverted by adding tapered "saddles"
and "crickets".
3. Redundant Membrane Layer. If it is not economically possible to re-work an impacted
drainage area, the potential for damage can be reduced by the application of redundant
layer of membrane and flashing, in order to reduce the possibility of cutting or puncture.
PREVENTATIVE ACTIONS:
1. Add Roof Ballast. If some areas of ballast stone are frequently displaced by winds, consider
adding a larger size of ballast stone or replacing ballast stone with concrete pavers.
Note: Ballast should not be added to a roof without a review of the roof load capacity by a
structural engineer.
2. Review Roof System Design. If damage consistently occurs in certain areas of the roof, the
roof system design should be reviewed by an engineer or roof consultant.
REMEDIAL ACTIONS:
1. Replace Wet Roof Insulation. A licensed roofing contractor should perform this work.
2. Re-Attach and Re-Caulk Metal Components. Maintenance of metal flashings and caulking
joints typically can be performed either by a roofing contractor or trained maintenance
personnel.
3. Repair Deteriorated Walls. Repair of walls can be performed by a variety of trades. Be sure
to select a recognized professional.
PREVENTATIVE ACTIONS:
1. Roof Moisture Survey. If a new roof will be installed over an existing roof, or whenever
moisture is suspected to be entrapped within a roof deck, a roof moisture survey should be
conducted by a recognized professional, and the findings of the survey should be used by
the roof designer to select the most appropriate roofing system.
2. Rooftop Equipment Maintenance Standards: A roof access log should be maintained in order
to review and monitor the maintenance of rooftop equipment.
REMEDIAL PROCEDURES:
1. Emergency Repair of Field Seams. Most single-ply field seams can be repaired temporarily
by covering the seam edge with duct tape, construction grade butyl caulk, or silicone. Clean
the membrane around the edge with a non-abrasive cleaner and apply a piece of duct tape
extending beyond the affected area at least one inch in all directions. Most seams in
modified bitumen membranes can be repaired temporarily by applying plastic roof cement
to the seam edge. Make arrangements for a permanent repair as soon as possible.
2. Permanent Restoration of Roof Seams. Restoration of aged roofing seams should be
performed by a licensed roofing contractor.
a. Single-Ply Seams. EPDM and TPO seams typically can be restored by "stripping in" the
seam with a new covering of membrane material. See Section II for specific repair
procedures.
b. Modified Bitumen Seams. Minor repairs to modified bitumen seams can be performed by
pulling open the affected seam area and re-sealing the seam using a roofing torch.
When seam deficiencies are widespread, the only effective long-term repair is the
installation of a new layer of modified bitumen membrane over the affected roof surface
area.
INTRODUCTION:
Modern perimeter attachments are designed to provide many years of secure performance, but
these attachments are subjected to stresses which over time may produce distortion of the base
attachments. Typically, base attachments do not need to be inspected during the normal ten to
fifteen warranty period unless observations of distortion have been observed. After the normal
warranty period, it may be advisable to completely renovate the base attachments by installing
new base attachments.
WHERE TO LOOK:
1. Parapet Walls And Equipment Curbs.
2. Sheet metal Roof Edges.
WHAT TO LOOK FOR:
1. "Bridging". "Bridging" refers to an inherent loss of dimensional stability in excess of the
design criteria. Minor bridging, extending beyond the angle change less than one inch, can
typically be expected from any roofing membrane after a reasonable period of service.
Bridging greater than one inch may be caused by a failure of the substrate, and can indicate
that the base attachment itself is beginning to experience stress. This stress may lead to
water entry through roof seams which run through the angle change of the base
attachment.
2. Loose Fasteners. The observation of loose or "tented" fasteners beneath the membrane at
the base attachment may indicate a significant wind event or a substrate failure detrimental
to the systems ability to accommodate long-term stress on the base attachment.
REMEDIAL PROCEDURES:
1. Emergency Repair. If bridging or distortion at a base attachment is causing active leakage,
try to seal the leak with duct tape, construction-grade butyl caulking, or silicone.
2. Permanent Restoration of Roof Seams. Restoration of aged base attachments should be
performed by a licensed roofing contractor. ( See Section II for specific base attachment
repair procedures. )
Building Address:
Original Contractor:
Inspected By:
ITEM:
Roof Traffic
Contaminants
Drainage
Moisture Infiltration
WHERE TO LOOK:
Roof Access Points
Walkways
Mechanical Units
Mechanical Units
Kitchen Exhausts
Mid-Span Of Beams & Joists
Large Rooftop Units
Roof Drains
Wall Scuppers
Gutters & Downspouts
Roof Perimeter
Roof Membrane Surface
SECTION II
ROOF REPAIR & RENOVATION
Even with periodic inspection and maintenance, roofing systems will require repair from time to
time. Although roof repair is typically conducted as a response to some type of damage to the roof,
a pro-active approach to roof repair and renovation can improve the performance and extend the
service life of most modern roofing systems. The procedures and specifications contained in this
section provide valuable general information about the efficient and effective repair of different
roofing systems, including EPDM and modified bitumen roofs.
These procedures and specifications are offered as a complementary service only, and Firestone
disclaims any liability, under any theory of law, arising out of the use of these procedures.
Topic:
Page:
15
16
17
18
19
20
21
22
23
3" Min.
Note: The application of new EPDM membrane to existing in-service EPDM membrane requires
special cleaning and priming procedures. Refer to Section F - Cleaning and Priming of In-Service
Membrane.
1. Typical Repair of TPO Membrane:
3" Min.
Note: The application of new TPO membrane to existing in-service TPO membrane requires special
cleaning and priming procedures. Refer to Section F - Cleaning and Priming of In-Service
Membrane.
FIRESTONE BUILDING PRODUCTS COMPANY
Roof Inspection, Maintenance & Repair Guide
Interim Updates at www.firestonebpco.com
Revision No. 2 06/09/10
15
4" Min.
Note: Prepare existing surface by heating with a roofing torch and embed any exposed roofing
granules and or lightly remove (without distorting the membrane compound) any applied coating
with a heated trowel. After preparing the receiving surface and allowing to cool, apply primer to all
surfaces receiving the new membrane patch.
Note: The application of new EPDM membrane to existing in-service EPDM membrane requires
special cleaning and priming procedures. Refer to Section F - Cleaning and Priming of In-Service
Membrane.
FIRESTONE BUILDING PRODUCTS COMPANY
Roof Inspection, Maintenance & Repair Guide
Interim Updates at www.firestonebpco.com
Revision No. 2 06/09/10
16
3" ( T yp )
3" ( T yp )
B utt Jo int ( T yp )
La p S e a la nt
6" Q uick Se a m Co v e r Strip
Note: The application of QuickSeam Tape and FormFlash to existing in-service EPDM membrane
requires special cleaning and priming procedures. Refer to Section F - " Cleaning and Priming of InService Membrane.
TPO GP Sealant
TPO GP Sealant
Note: The application of new TPO membrane to existing in-service TPO membrane requires special
cleaning and priming procedures. Refer to Section F - Cleaning and Priming of In-Service
Membrane.
FIRESTONE BUILDING PRODUCTS COMPANY
Roof Inspection, Maintenance & Repair Guide
Interim Updates at www.firestonebpco.com
Revision No. 2 06/09/10
17
STEP 2:
A p p ro x. 1/2" B itum e n Flo w
Re -S e a l Se a m Wi th A R o o fing To rc h
Insulation
Roof Deck
STEP 2:
Splice to Exisitng Wall Flashing With Spilce Adhesive or
in-seam tape
New EPDM Membrane
Adhered to Wall with Bonding Adhesive or Splice Adhesive
2 Seam Plates & Firestone Fasteners 12 o.c.
6 QuickSeam Reinforced Perimeter Fastening Strip (RPF)
Splice to Exisitng Field Membrane with Splice Adhesive or
In-seam tape.
Insulation
Roof Deck
Note: The application of new EPDM membrane to existing in-service EPDM membrane requires
special cleaning and priming procedures. Refer to Section F - Cleaning and Priming of In-Service
Membrane.
FIRESTONE BUILDING PRODUCTS COMPANY
Roof Inspection, Maintenance & Repair Guide
Interim Updates at www.firestonebpco.com
Revision No. 2 06/09/10
19
2.
Allow the receiving surface to thoroughly dry. If necessary, dry the washed surface
with clean towel or rags. Make sure that no moisture can be trapped.
3.
It is also acceptable to broom clean the membrane in the repair area and apply
Firestone Membrane Pre-Wash using a garden sprayer at the rate of 300 t0 500 square
feet per gallon. (See TIS Sheet for exact procedure) After Pre-Wash has dried for
approximately ten minutes, use a pressure washer providing 4 gallons (15.1 L) per
minute at 3000 PSI (20.6 MPa) to remove the Pre-Wash and accumulated dirt and
debris. A 40 fan spray nozzle for pressure washer is suggested.
NOTE: If utilizing Firestone Membrane Pre-Wash is the contractors preferred
method of cleaning the existing membrane, identify this preference clearly
within your labor price submittal and include the necessary amount of PreWash so we may adjust our material provision accordingly.
4.
Wash the existing EPDM twice with Firestone Clear Splice Wash and clean, white,
cotton rags, allowing the surface to evaporate and dry between washings. Change
cleaning rags often.
5.
Wash the mating side of the repair piece once with Firestone Clear Splice Wash and
clean, white, cotton rags, allowing the surface to dry before the application with Splice
Adhesive. Change cleaning rags often. No cleaning of QuickSeam Tape products is
necessary. If QuickSeam Tape becomes dirty, it must not be used.
6.
Ensure that the existing area to which new Thermoplastic membrane is to be mated
is clean, smooth, and free of all contaminants.
2.
Thoroughly clean this area with detergent and water. It is recommended that a
water-soluble granular cleaner be used such as T-M-T brand, which is manufactured
by the U.S. Borax Company. Liquid cleaners tend to leave a film residue that can
interfere with heat-weld quality.
3.
4.
It is imperative that the area be thoroughly rinsed several times to remove all
detergent and contaminants before heat welding. Further, the area must be allowed
to dry completely before continuing. If blisters form upon heat welding, the area has
not been allowed to dry sufficiently and heat welding should discontinue.
5.
After allowing to dry sufficiently, the heat-welding areas on the existing membrane
shall be cleaned a second time with Denatured Alcohol and clean cotton rags to
remove all surface impediments and eliminate any surface curing which may have
occurred.
AGAIN: THOROUGH CLEANING WITH DENATURED ALCOHOL SOLVENT IS THE MOST
CRITICAL PROCEDURE TO ENSURE THE PERFORMANCE OF THE NEW TO EXISTING
MEMBRANE HEAT-WELD.
6.
All heat welding shall be in accordance with Firestone Thermoplastic details and
specifications as published. Keep in mind that the existing sheet is aged, which may
call for more allowance. Care should be taken not to overheat and scorch either
membrane.
7.
3. Allow the adhesive to set-up on each surface until tacky so as not to stick or string to
the touch of a dry finger. Adhesive film should also be pushed with the index finger
to assure it is dry within the film. (The Touch-Push Test)
4. Mate the repair piece onto the receiving surface, centering it over the area in need of
repair. Do not stretch or wrinkle the cover strip while mating it. A minimum 3
EPDM to EPDM lap splice must be achieved.
5. With 2 3 silicon rollers, roll the newly spliced piece twice; first across (or
perpendicular to) the mated surface, and then second along the length of the spliced
edge.
6. After the splice has been allowed to cure no more than four hours, clean any
contaminants from the base membrane a minimum of one inch on each side of the
lap edge with a damp, clean, cotton rag of Clear Splice Wash. This step is only
necessary if the seam edge has become dirty or contaminated. Do not soak the lap
edge with Clear Splice Wash.
7. Immediately after cleaning, apply a 2 wide thin coat of Splice Adhesive to the seam
step-off.
8. After the Splice Adhesive has dried a minimum of four hours, apply a 3/8 bead of
lap sealant and trowel the sealant so as to leave a mound over the lap edge.
Coverage should be about 20 LF per caulking tube.
STANDARD COVERAGE RATES
Splice Adhesive
Seam/Coverstrip width
3------------4------------6------------8------------10-----------12------------
Coverage Rate
160 LF/GAL
120 LF/GAL
80 LF/GAL
60 LF/GAL
50 LF/GAL
40 LF/GAL
40 SF per GAL
Seam/Coverstrip width
15------------18------------24------------QUICKSEAM width
5------------6------------9-------------
Coverage Rate
32 LF/GAL
27 LF/GAL
20 LF/GAL
Coverage Rate
200 LF/GAL
160 LF/GAL
110 LF/GAL
I. WALKWAY SYSTEMS
The Firestone Roofing System is designed to be a waterproofing component not a traffic bearing
component of the building envelop. Effective roof walkway systems must be designed to
accommodate two different forces:
1. Puncture forces, which can cut the roofing membrane. Puncture forces can be exerted on the
roof membrane by dropped tools, broken glass, nails, metal scraps, etc., especially when
such sharp objects are stepped on by foot traffic.
2. Compressive forces, which can crush the underlying roof insulation. Although little formal
research has been conducted regarding the forces exerted by foot traffic on the roof, it is
generally acknowledged that an individual will exert a foot force anywhere from 10 psi to 30
psi, depending on body mass, shoe profile and momentum. This wide range of variability
is very important since many common types of roof insulation, such as expanded
polystyrene and polyisocyanurate foam, have relatively low compressive strengths.
While rubber walkway pads will provide effective membrane protection against cutting and
puncture, these pads are relatively thin and they cannot distribute large compressive forces. If
frequent or heavy roof traffic loads are anticipated over a roof system which uses a low
compressive strength insulation, one or more of the following products should be considered:
1. Smooth Concrete Pavers. Concrete pavers have very high compressive strengths and can
significantly distribute the force of foot traffic. Because the edges of the pavers can be
sharp, and because concrete over time may crack or spall, it is advisable to install a
protective fabric mat or a redundant layer of roofing membrane beneath concrete pavers.
Before an extensive concrete paver walkway is installed, the live load capacity of the roof
deck and building structure should be evaluated to verify that the structure can
accommodate the added weight of the pavers.
2. High-Density Roof Boards. Compressive forces can also be distributed by installing a
high-density roofing board directly over the roof insulation prior to installing the roofing
membrane. Examples of common roofing boards are:
CoverDeck. This product is a high performance mineral fiber coverboard that combines
high wind and water resistance with excellent lightweight/high strength characteristics.
Typical thicknesses are 3/8 and 5/8.
If a high-density roof board is selected, it will still be necessary to install rubber walkway
pads over the membrane to protect against cutting and puncture.
3. Protected Membrane Systems. Protected membrane systems utilize a layer of high density
extruded polystyrene board loosely laid directly above the roofing membrane and covered
with a fabric mat and concrete pavers.
FIRESTONE BUILDING PRODUCTS COMPANY
Roof Inspection, Maintenance & Repair Guide
Interim Updates at www.firestonebpco.com
Revision No. 2 06/09/10
23
NOTE: As with any concrete paver system, ballast rock, or garden system, the load capacity of the
roof should be evaluated before installing this type of system. Although this type of system can
provide very excellent protection against both crushing and puncture, it is very difficult to service if
a leak does occur. Because of this, the roofing warranty coverage available for protected
membrane systems may be less than the warranty coverage available with other roofing systems.
SECTION III
FIRESTONE WARRANTY SERVICE
Firestone's Warranty Services Department is responsible for assuring a timely and effective response
to all customer service requests for warranted Firestone roofs. In addition, Warranty Services is
charged with maintaining effective channels of communication between the owners of Firestone
roofs and the licensed contractors who install these roofs so that all parties are involved in assuring
the long-term performance of Firestone roofing systems.
Firestone Warranty Services can be contacted Monday through Sunday by calling 1800-830-5612. Requests for service can also be faxed directly to
1-317-575-7210 or by email at [email protected].
Warranty Services is staffed with knowledgeable warranty administrators and experienced roofing
professionals who can respond to customer calls by issuing emergency repair orders, arranging for
field investigations and resolving questions concerning Firestone's warranty programs and policies.
Typically, Firestone's response begins with an immediate notification to the roofing contractor who
originally installed the roof, so that the Firestone contractor is involved in all communications and
actions regarding the performance of the roof. Because of this, the success of our warranty service
program is a joint effort between Firestone and the independent Firestone licensed contractors who
serve as the first and most important contact with owners of Firestone Roofing Systems.
Topic:
Reporting Leaks To Firestone
Warranty Response Procedures
Non-Warranted Repairs
Fax Leak Notification Form
Post Warranty Alteration Form
Warranty Transfer Form
Page:
26
27
28
29
30
31
Building Identification.
Building Address.
Building Owner Name.
Building Owner Key Contact Person and Telephone Number.
FBPCO ( Roof Drawing ) Number.
Warranty Number.
Date Leak Observed.
Notifier Name with Telephone and Fax Number.
Accurate Description Of Leak.
Purchase Order Number for any Non-Warranted Repairs
A FAX number for the notifier is very important, since Firestone will send an acknowledgemnt to
confirm our issuance of a work order to a responsive repair contractor.
Firestone encourages both building owners and roofing contractors to use the above mentioned
methods to communicate a roof leak to Firestone. A special Fax Leak Notification form has been
prepared by Firestone and is included in this manual. ( See Section D. )
C. NON-WARRANTED REPAIRS
Because many of the leaks that occur on Firestone warranted roofs are caused by conditions relating
to building maintenance and are not covered by the terms of the Firestone warranty, Firestone has
adopted a pro-active policy to inform and educate building owners about the importance of roof
inspection and maintenance.
This pro-active policy starts with the distribution of extensive inspection and maintenance
information. Comprehensive roofing inspection and maintenance guidelines can be obtained from
any Firestone sales or technical representative.
In addition, Firestone always advises building owners that non-warranted repairs associated with
requests for emergency warranty service will be invoiced in accordance with item 2 (c) of Firestone's
current Red Shield Warranty:
Should the investigation reveal that the leak is excluded under the Terms, Conditions and
Limitations, the Owner is responsible for payment of the investigation costs.
If non-warranted repairs are made by the Firestone contractor who is responding to an emergency
repair work order, and if the contractor is unable to arrange for appropriate reimbursement directly
with the building owner, Firestone will pay the contractor for any reasonable repairs that are
necessary to protect the serviceability of the roof system. In turn, Firestone will issue an invoice to
the building owner for these repairs. Firestone's invoice will cover only those costs clearly
associated with non-warranted repairs. All invoices issued by Firestone will also include a detailed
description of the specific non-warranted repairs performed and a customer contact to obtain
additional information concerning the invoice and the repairs performed.
Examples of typical non-warranted emergency repairs include:
1. Repair of membrane cuts and punctures.
2. Caulking or re-sealing of non-Firestone building components, such as:
Thank you for providing us with this important information. Upon receipt of this form, Firestone's
Warranty Service Department will issue an emergency work order via fax to an authorized Firestone
repair contractor. In addition, we will fax an acknowledgment directly to you to advise you the name
and telephone number of the authorized contractor who will be responding to your service request.
If you have any questions concerning your Firestone roof or your roofing warranty, please do not
hesitate to call us at 1-800-428-4442.
In order to transfer an existing Firestone Warranty, building owners and their authorized agents
must complete the following form. This form can be submitted electronically at
www.firestonebpco.com.