Typical Booster Drawing
Typical Booster Drawing
Typical Booster Drawing
5'-2"
12
13
10 11
14
15
16
17
(8) MOUNTING HOLES
(4 EACH SIDE)
18
PIPE TO DRAIN
DISCHARGE END
4'-8"
STEEL BASE O.D.
5'-3"
2'-3 7/8"
SPLIT FRAME
2'-11 1/8"
SPLIT FRAME
5'-4"
HEIGHT
GAL. EXPANSION TANK
DIAMETER
CONNECT TANK TO DISCHARGE OF SYSTEM AS SHOWN
HYDROPNEUMATIC
TANK
DRAIN VALVE
(BY CONTRACTOR)
ISOLATION VALVE
(BY CONTRACTOR)
FLOW
THE PENTHOUSE
THE PUMP ROOM
FLOW
IF LOCATED IN THE PUMP ROOM
TANK TO BE LOCATED IN:
PRESSURE
RELIEF VALVE
PIPE TO
DRAIN
FROM PUMP
DISCHARGE
TO PRESSURE
GAUGE
AQUASTAT
SOLENOID VALVE
RECIRCULATION
TO PUMP CASE
PIPE TO
DRAIN
CLASS 125/150 DISCHARGE PIPING
CLASS 250/300 DISCHARGE PIPING
19
DETAIL A
SCALE 1:4
8
6
4
3
20
1/2" TAP PER PUMP
(SEE DETAIL A)
LIFTING POINT
S
P
L
IT
L
IN
E
2
4
5
6
7
1
SUCTION END
5
THIS DRAWING IS FOR SUBMITTAL PURPOSES ONLY, AND IS
TYPICAL IN NATURE. THE LAYOUT, DIMENSIONS, AND DETAILS
OF THE SYSTEM MAY CHANGE DURING THE FABRICATION-
DESIGN PROCESS. FINAL-FABRICATION DRAWINGS WILL BE
PROVIDED, FOLLOWING RECEIPT OF APPROVED SUBMITTALS.
NOTES:
1. MAXIMUM HP FOR 208/230 VOLT = 20HP.
MAXIMUM HP FOR 460 VOLT = 30HP.
2. CR PUMPS THAT CAN FIT ON STANDARD SYSTEM:
CR 10 = ALL STAGES
CR 15 = ALL STAGES
CR 20 = ALL STAGES
CR 32 = -1-1 THRU -8
CR 45 = -1-1 THRU -4
3. SYSTEM TO BE INSTALLED BY A QUALIFIED & EXPERIENCED CONTRACTOR.
4. SOME ITEMS NOT SHOWN FOR CLARITY.
5. CONTRACTOR/ENGINEER TO VERIFY SUCTION & DISCHARGE CONNECTION
ORIENTATION.
6. CONTRACTOR TO LIFT SYSTEM WITH ALL SUPPLIED LIFTING POINTS.
7. ENGINEER TO VERIFY SYSTEM PIPING MATERIAL & AND WORKING PRESSURE
WITH LIQUID BEING PUMPED AND SHUT-OFF HEAD OF THE PUMP PLUS SUCTION
PRESSURE.
ESTIMATED MAX. SYSTEM WEIGHT: 4,000LB.
ITEM NO. QTY. PART NUMBER DESCRIPTION
1 3 CR-XX (SEE NOTE) MULTI-STAGE PUMP
2 3 CR-XX-3x6-XX_SUCTION INTERMEDIATE STOCK
3 3 CR-XX-3x6-XX_DISCHARGE ELBOW STOCK
4 6 3" SILENT CHECK VALVE STOCK
5 6 CR-XX-3x6-XX_SPOOL STOCK
6 3 3" BUTTERFLY VALVE STOCK
7 1 CRT-XX-3x6-XX_SUCTION HEADER STOCK
8 1 CRT-XX-3x6-XX_DISCHARGE HEADER STOCK
9 1 CRT-XX-3x6_STEEL FRAME STOCK
10 1 ALARM PANEL
11 1 CONTROL ENCLOSURE
12 3 VFD
13 1 POWER DISTRIBUTION PANEL
14 3 PUMP PRESSURE GAUGE
15 1 SUCTION PRESSURE GAUGE
16 1 DISCHARGE PRESSURE GAUGE
17 1 LOWSUCTION CUT-OFF SWITCH
18 1 WIRING TROUGH
19 1 PRESSURE TRANSDUCER
20 1 TEMP & PRESSURE RELIEF DRAIN HEADER 2" N.P.T. BOTH ENDS (PIPE TO DRAIN)
DATE DATE BY REVISION TITLE: BY REVISION
DRN. BY:
DATE:
APP. BY:
CAC
11/01/07
SCALE: 1:8
METROPOLITAN INDUSTRIES, INC.
(815)886-9200 FAX (815)886-4573
PUMPS - CONTROLS - SYSTEMS
37 FORESTWOOD DR. ROMEOVILLE, ILLINOIS 60446
PREFABRICATED VARIABLE SPEED
TRIPLEX WATER BOOSTER SYSTEM
PROJECT:
TRIPLEX DOMESTIC WATER BOOSTER STATION
C
M
e
tro
p
o
lita
n
In
d
u
s
trie
s
, In
c
. 2
0
0
7
CRT-XX-3x6
SHEET 1 OF 1
DRN'G INDEX / JOB NO.
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF METROPOLITAN INDUSTRIES, INC.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF METROPOLITAN INDUSTRIES, INC. IS PROHIBITED.