PDH Online Course M371

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

An Approved Continuing Education Provider

Shell and Tube Heat Exchangers



Basic Calculations



Instructor: Jurandir Primo, PE

2012







PDH Online | PDH Center

5272 Meadow Estates Drive
Fairfax, VA 22030-6658
Phone & Fax: 703-988-0088
www.PDHonline.org
www.PDHcenter.com
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 2 of 32







Imperial and Metric Units

Jurandir Primo, PE





www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 3 of 32























1.0 Introduction:

In intercoolers, boilers, pre-heaters and condensers inside power plants as well as other engineering
processes, heat exchangers are utilized for controlling heat energy. Heat exchangers are devices that
regulate efficient heat transfer from one fluid to another.

There are two main types of heat exchangers.

The first type of a heat exchanger is called the recuperative type, in which heat are exchanged
on either side of a dividing wall by fluids;

The second type is regenerative type, in which hot and cold fluids are in the same space which
contain a matrix of materials which work alternately as source for heat flow.

The optimum thermal design of a shell and tube heat exchanger involves the consideration of many
interacting design parameters which can be summarized as follows:

Process:

1. Process fluid assignments to shell side or tube side.
2. Selection of stream temperature specifications.
3. Setting shell side and tube side pressure drop design limits.
4. Setting shell side and tube side velocity limits.
5. Selection of heat transfer models and fouling coefficients for shell side and tube side.

Mechanical:

1. Selection of heat exchanger TEMA layout and number of passes.
2. Specification of tube parameters - size, layout, pitch and material.
3. Setting upper and lower design limits on tube length.
4. Specification of shell side parameters materials, baffles cut, baffle spacing and clearances.
5. Setting upper and lower design limits on shell diameter, baffle cut and baffle spacing.

To develop calculations there are several software design and rating packages available, including
Codeware, Compress, Aspen BJAC, HTFS and CC-THERM, which enable the designer to study the
effects of the many interacting design parameters and achieve an optimum thermal design.
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 4 of 32
These packages are supported by extensive component physical property databases and
thermodynamic models.

2.0 Concepts:

The biggest problem in thermodynamics is the student to learn and recognize heat, work, force,
energy, power and other technical terms. So to facilitate the basic comprehension of the terms used for
shell and tube heat exchangers calculations it is very important to remember some concepts below:

Cal - The Cal is the standard unit of measurement for heat. The gram calorie, small calorie or calorie
(cal) is the amount of energy required to raise the temperature of one gram of water from 19.5 C to
20.5 C under standard atmospheric pressure of 1.033 Kg/cm (14.7 psi).

Btu - British Thermal Unit: The Btu is the standard unit of measurement for heat. A Btu is defined as
the amount of energy needed to raise the temperature of one pound of water from 58.5F to 59.5F
under standard pressure of 30 inches of mercury (14.7 psi).

UNIT MULTIPLY TO OBTAIN
1 Btu 1055.0 J
1.0550 kJ
0.2521 kcal
107.7 Kgf.m
778.7 ft.lbf
1 cal 4.18 J
0.00396 Btu
0.00000116 kW.h
1 kcal 1000 cal
3.9604 Btu


Joule - energy exerted by the force of one Newton acting to move an object through a distance of 1 m.

UNIT MULTIPLY TO OBTAIN
1 J 0.001 kJ
0.238 cal
0.0002387 kcal
0.102 kgf.m
0.000947 Btu
0.7375 ft.lbf

Watt metrical unit for power.

UNIT MULTIPLY TO OBTAIN
1 W 0.001 kW
0.00134 hp
0.000102 hp (boiler)
0.0002387 kcal/s
0.102 kgf.m/s
0.7375 ft.lbf/s
44.2 ft.lbf/min
0.000948 Btu/s
0.000284 ton (refrig)


www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 5 of 32
2.1. Temperature:

Celsius (also known as centigrade) is a temperature scale that is named after the Swedish astronomer
Anders Celsius (17011744), who developed a similar temperature scale two years before his death.
Then nominally, 0 C was defined as the freezing point of water and 100 C was defined as the boiling
point of water, both at a pressure of one standard atmosphere (1.033 Kg/cm).

Fahrenheit is the temperature scale proposed in 1724 by, and named after, the physicist Daniel Gabriel
Fahrenheit (16861736). On the Fahrenheit scale, the freezing point of water was 32 degrees
Fahrenheit (F) and the boiling point 212 F at standard atmospheric pressure (14.7 psi).

Kelvin scale were named after the Scottish physicist William Thomson, 1st Baron Kelvin (18241907),
who wrote of the need for an "absolute thermometric scale". The Kelvin and the degree Celsius are often
used together, as they have the same interval, and 0 Kelvin is = 273.15 degrees Celsius.

C = 5 (F - 32)
9

F = 1.8 C(F+ 32)

C = K - 273

2.2. Pressure:

Pressure (symbol: P) is the force per unit area applied in a direction perpendicular to the surface of an
object. Gauge pressure is the pressure relative to the local atmospheric or ambient pressure.

Unit
Pascal
(Pa)
bar
(bar)
atmosphere
(atm)
Torr
(Torr)
pound-force per
square inch
(psi)
1 Pa 1 N/m 0.00001 0.000009867 0.0075006 0.000145
1 bar 100000 106 dyn/cm2 0.9867 750 14.5
1 at 98066 0.980665 0.968 735.5 14.223
1 atm 101325 1.01325 1 atm 760 14.7
1 torr 133.322 0.013332 0.0013158 1 mmHg 0.0193
1 psi 0.006894 0.068948 0.068046 51.72 1 lbf/in

Energy Unit Conversions:

UNIT MULTIPLY TO OBTAIN

1 Btu/s
0.3002 ton (refrig)
1.056 kW
1.435 hp
106.6 kgf.m/s
778.8 ft.lbf/s

1 joule/kilogram/K = J/(kg.K) =

1 joule/kilogram/C = J/(kg.C)





1.0 joule/kilogram/C = J/(kg.C)
0.001 joule/gram/C = J/(g.C)]
0.001 kilojoule/kilogram/C = kJ/(kg.C)
0.000239 calorie /gram/C = cal/(g.C)
0.000239 kilocalorie /kilogram/C = kcal/(kg.C)
0.000239 kilocalorie /kilogram/K = kcal/(kg.K)
0.102 kilogram-force meter/kilogram/K
0.000239 Btu/pound/F = Btu/(lb.F)
0.000423 Btu/pound/C = Btu/(lb.C)
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 6 of 32


1 Btu/pound/F = Btu/(lbF)
1.0 kilocalorie /kilogram/C = kcal/(kg.C)
1.8 Btu/pound/C = Btu/(lb.C)
4186.8 joule/kilogram/K = J/(kg.K)
4186.8 joule/kilogram/C = J/(kg.C)
4.1868 joule/gram/C = J/(g.C)
4.1868 kilojoule/kilogram/K = kJ/(kg.K)
4.1868 kilojoule/kilogram/C = kJ/(kg.C)
426.9 kilogram-force.meter/kilogram/K
778.2 pound-force.foot/pound/R

3. Basic Concept of Specific Heat:
7.3
Specific heat is defined as the amount of heat energy needed to raise 1 gram of a substance 1C in
temperature, or, the amount of energy needed to raise one pound of a substance 1F in temperature.

Q = m.Cp. (T
2
T
1
)

Where:

Q = heat energy (Joules) (Btu),
m = mass of the substance (kilograms) (pounds),
Cp = specific heat of the substance (J/kgC) (Btu/pound/F),
(T
2
T
1
) = is the change in temperature (C) (F)

The higher the specific heat, the more energy is required to cause a change in temperature. Substances
with higher specific heats require more of heat energy to lower temperature than do substances with a
low specific heat.

Example 1:

Using metric units and imperial units, how much energy is required to heat 350 grams (0.77 pounds) of
gold from 10C (50F) to 50C (122F)?

Mass = 350g = 0.35 Kg = 0.77 lb
Specific heat of gold = 0.129 J/(g.C) = 129 J/(Kg.C) x 0.000239 = 0.0308 Btu/(lb.F)

Q = m.Cp. (T
2
T
1
)

Metric Units:

Q = (0.35 Kg) (129 J/(Kg.C) (50C - 10C)

Q = 1806 J

Conversion:
1806 joules x 0.000947 = 1.71 Btu

Evaluation in Btu

Q = m.Cp. (T
2
T
1
)

Imperial Units:

Q = (0.77 lb) (0.0308 Btu/(lb.F) (122F - 50F) =

Q = 1.71 Btu
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 7 of 32
Consult www.unitconversion.org (to convert energy units):



Some samples of specific heat values are presented in the table below:

Product
Specific Heat Capacity - Cp
(J/ g C) (Btu/lb
o
F)
Alcohol, ethyl 32
o
F (ethanol) 2.3 0.55
Ammonia, 104
o
F 4.86 1.16
Castor Oil 1.8 0.43
Dowtherm 1.55 0.37
Freon R-12 saturated 0
o
F 0.91 0.217
Fuel Oil max. 2.09 0.5
Gasoline 2.22 0.53
Heptane 2.24 0.535
Kerosene 2.01 0.48
Gold 0.129 0.0308
Light Oil, 60
o
F 1.8 0.43
Light Oil, 300
o
F 2.3 0.54
Mercury 0.14 0.03
Octane 2.15 0.51
Oil, mineral 1.67 0.4
Olive oil 1.97 0.47
Petroleum 2.13 0.51
Propane, 32
o
F 2.4 0.576
Propylene Glycol 2.5 0.60
Sodium chloride 3.31 0.79
Soya bean oil 1.97 0.47
Toluene 1.72 0.41
Water, fresh 4.19 1
Water, sea 36
o
F 3.93 0.94

www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 8 of 32
4. Heat Exchangers Calculations:

The main basic Heat Exchanger equation is:

Q = U x A x T
m


The log mean temperature difference Tm is:

T
m
= (T
1
t
2
) (T
2
t
1
) = F


Where:

T
1 =
Inlet tube side fluid temperature
t
2 =
Outlet shell side fluid temperature
T
2 =
Outlet tube side fluid temperature
t
1 =
Inlet shell side fluid temperature
When used as a design equation to calculate the required heat transfer surface area, the equation can be
rearranged to become:

A = Q/ (U x T
m
)

Where:

A = Heat transfer area (m) (ft)
Q - Heat transfer rate (kJ/h) (Btu\h);
U - Overall heat transfer coefficient (kJ/h.m.C) (Btu/hr.F)
T
m
- Log mean temperature difference (C) (F)

And:

C
t =
Liquid specific heat, tube side (kJ/kg.K) (Btu/lb.F)
C
s =
Liquid specific heat, shell side (kJ/kg.K) (Btu/lb.F)

4.1. The Overall Design Process:

Design of a heat exchanger is an iterative (trial & error) process. Here is a set of steps for the process:

Calculate the required heat transfer rate, Q, in Btu/hr from specified information about fluid flow
rates and temperatures.
Make an initial estimate of the overall heat transfer coefficient, U, based on the fluids involved.
Calculate the log mean temperature difference, Tm, from the inlet and outlet temperatures of the
two fluids.
Calculate the estimated heat transfer area required, using: A = Q/(U Tm).
Select a preliminary heat exchanger configuration.
Make a more detailed estimate of the overall heat transfer coefficient, U, based on the preliminary
heat exchanger configuration.
Estimate the pressure drop across the heat exchanger. If it is too high, revise the heat exchanger
configuration until the pressure drop is acceptable.
If the new estimate of U is significantly different than the previous estimate, repeat steps 4
through 7 as many times as necessary until the two estimates are the same to the desired degree
of accuracy.
Input information needed. In order to start the heat exchanger design process, several items of
information are needed as follows:

The two fluids involved need to be identified.
ln (T
1
t
2
)
(T
2
t
1
)
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 9 of 32
The heat capacity of each fluid is needed.
The required initial and final temperatures for one of the fluids are needed.
The design value of the initial temperature for the other fluid is needed.
An initial estimate for the value of the Overall Heat Transfer Coefficient, U, is needed.

Knowing the first four items allows determination of the required heat transfer rate, Q, and the inlet and
outlet temperatures of both fluids, thus allowing calculation of the log mean temperature difference, T
m
.

With values now available for Q, U, and T
m
, an initial estimate for the required heat transfer area can be
calculated from the equation:

A = Q / (U . T
m
)

Example 2:

1: Calculate a preliminary estimate of the heat exchanger area needed to cool 55,000 lb/hr of a light oil
(specific heat = 0.74 Btu/lb.F) from 190F to 140F using cooling water that is available at 50F. The
cooling water can be allowed to heat to 90F. An initial estimate of the Overall Heat Transfer
Coefficient is 120 Btu/hr.ft.F. Also estimate the required mass flow rate of cooling water.



Solution: First calculate the required heat transfer rate for the above indicated light oil:

Q = m.Cp. (T
2
T
1
)

Imperial Units:

Q = (55,000 lb/hr) (0.74 Btu/lb.F) (190 140) F = 2,035,000 Btu/hr.

Next calculate the log mean temperature difference:

T
1 =
Inlet tube side fluid temperature (light oil hot side = 190 F)
t
2 =
Outlet shell side fluid temperature (water cold side = 90 F)
T
2 =
Outlet tube side fluid temperature (light oil cold side = 140 F)
t
1 =
Inlet shell side fluid temperature (water cold side = 50 F)


Tm = (190 90) (140 50) = F


ln (190 90)
(140 50)
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 10 of 32
Tm = (100) (90) = F



Tm = 10 = 94.9 F
0.10536

The preliminary area estimate of the heat exchanger can now be calculated as:

A = Q / (U x Tm) =

A = 2, 035, 000 Btu/hr = 178.7 ft
(120Btu/h.ft.F).(94.9F)

The required mass flow rate of water can be calculated from Q = m.Cp.Tm.

Rearranging:

m = Q
Cp. Tm
m = (2,035,000 Btu/hr)

= 28,978 lb/hr
(0.74Btu/lb.F)(94.9F)

Example 3:

Taking the shell and tube heat exchanger described in Example 1, how many tubes of 3 inch diameter
and 10 ft length should be used?

Solution: The surface area per tube will be:

Sa = DL = (3/12) (10) ft = 7.854 ft - (D tube diameter in ft).

The number of tubes required would thus be:

n = 178.7 ft = 22.7 tubes (23 or 24 tubes).
7.854 ft

The next step would be to check on the pressure drop for this tube configuration and the specified flow. If
the pressure drop is acceptable, then the Overall Heat Transfer Coefficient (U) could be re-estimated
for this heat exchanger configuration.

4.2. Calculation Concepts:

It is frequently necessary to determine the performance of a particular heat exchanger under conditions
of other than that for which it was designed.

Input

1. Overall Heat Transfer Coefficient U (Btu/hr.ft.F). For the heat exchanger under design.

2. Area (ft). Heat transfer area of the heat exchanger under consideration.

3. Entering temperature hot (F). Entering fluid temperature on the hot side of the heat exchanger.

4. Entering temperature cold (F). Entering fluid temperature on the cold side of the heat exchanger.

ln (100)
(90)
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 11 of 32
Example 4:

Assume a redesign of a gasoline heat exchanger, area 8.9 ft, flow rate hot 8 gpm, operating on 135F
to another heat exchanger operating on 150F flow rate hot 10.30 gpm, using a Overall Heat Transfer
Coefficient, 800 Btu/hr.ft.F. What would be the impact in capacity only as a comparison?

Imperial Units:

Input using 135 F.

1. Gasoline = 0.53 Btu/lb.F
2. Overall U = 800 Btu/hr.ft.F
2. Area = 8.90 ft
3. Entering temp hot = 135.00 F
4. Entering temp cold = 110.00 F
5. Flow rate hot = 8.00 gpm = 2961.6 lb/h

Capacity:

Q = (2961.6 lb/h) (0.53 Btu/lb.F) (135 110) F = 39,241 Btu/hr.

The T
m
can be calculated, since the indicated heat exchanger area is, 8.90 ft:

A = Q / (U x T
m
) =

8.90 ft = 39,241 Btu/hr =
(800Btu/h.ft.F).( T
m
F)

T
m
= 5.5 F

Input using 150 F

1. Overall U 800 Btu/hr.ft.F
2. Area = 8.90 ft
3. Entering temp hot = 150.00 F
4. Entering temp cold = 110.00 F
5. Flow rate hot = 10.30 gpm = 3,813 lb/h

Capacity:

Q = (3,813 lb/h) (0.53 Btu/lb.F) (150 110) F = 80,835 Btu/hr.

A = Q / (U x T
m
) =

8.90 ft = 80,835 Btu/hr =
(800Btu/h.ft.F).( T
m
F)

T
m
= 11.3 F

4.3. Concept of Overall Heat Transfer Coefficient, U

For a given heat transfer service with known mass flow rates and inlet and outlet temperatures the
determination of Q is direct and Tm can be easily calculated if a flow arrangement is selected (e.g.
Logarithmic Mean Temperature difference for pure countercurrent or concurrent flow).

The literature has many tabulations of such typical coefficients for commercial heat transfer services.


www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 12 of 32
Following is a table with values for different applications and heat exchanger types:

Typical Overall Heat Transfer Coefficients in Heat Exchangers
Type Application and Conditions U U
W/(m.K) Btu/(hr.ft.F)
Tubular,
heating or
cooling





Gases at atmospheric pressure inside and outside
tubes
5 - 35 1 - 6
Gases at high pressure inside and outside tubes 150 - 500 25 - 90
Liquid outside (inside) and gas at atmospheric
pressure inside (outside) tubes
15 - 70 3 - 15
Gas at high pressure inside and liquid outside tubes 200 - 400 35 - 70
Liquids inside and outside tubes 150 - 1200 25 - 200
Steam outside and liquid inside tubes 300 - 1200 50 - 200
Tubular,
condensation

Steam outside and cooling water inside tubes 1500 - 4000 250 - 700
Organic vapors or ammonia outside and cooling
water inside tubes
300 - 1200 50 - 200
Tubular,
evaporation


Steam outside and high-viscous liquid inside tubes,
natural circulation
300 - 900 50 - 150
Steam outside and low-viscous liquid inside tubes,
natural circulation
600 - 1700 100 - 300
Steam outside and liquid inside tubes, forced
circulation
900 - 3000
150 500

Air-cooled
heat
exchangers






Cooling of water 600 - 750 100 - 130
Cooling of liquid light hydrocarbons 400 - 550 70 - 95
Cooling of tar 30 - 60 5 - 10
Cooling of air or flue gas 60 - 180 10 - 30
Cooling of hydrocarbon gas 200 - 450 35 - 80
Condensation of low pressure steam 700 - 850 125 - 150
Condensation of organic vapors 350 - 500 65 - 90
Plate heat
exchanger
Liquid to liquid 1000 - 4000 150 - 700
Spiral heat
exchanger

Liquid to liquid 700 - 2500 125 - 500
Condensing vapor to liquid 900 - 3500 150 - 700

1 Btu/(hr.ft
2
.F) = 5.6785 W/(m
2
.K). Coefficients are based on outside bare tube surface
4.4. Heating up With Steam:

The amount of heat required to raise the temperature of a substance can be expressed as:

Q = m.cp.dT

Where:

www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 13 of 32
Q = quantity of energy or heat (kJ) (Btu)
m = mass of the substance (kg) (lb)
cp = specific heat capacity of the substance (kJ/kg
o
C ) (Btu/(lb.F)
dT = temperature rise of the substance (
o
C) (F)
4.5. Non-flow or Batch Heating:
In a non-flow type applications the process fluid is kept as a single batch within a tank or vessel. A steam
coil or a steam jacket heats the fluid from a low to a high temperature. The mean rate of heat transfer for
such applications can be expressed as:
q = m.cp.dT / t

Where:

q = mean heat transfer rate (kW) (kJ/s) (HP) (Btu/s)
m = mass of the product (kg) (lb)
cp = specific heat capacity of the product (kJ/kg.
o
C) (Btu/(lb.F)
dT = Change in temperature of the fluid (
o
C) (F)
t = total time over which the heating process occurs (seconds)

4.6. Flow or Continuous Heating Processes:

In heat exchangers the product or fluid flow is continuously heated. The mean heat transfer can be
expressed as

q = cp.dT. m / t

Where:

q = mean heat transfer rate (kW) (kJ/s) (HP) (Btu/s)
m / t = mass flow rate of the product (kg/s) (lb/s)
cp = specific heat capacity of the product (kJ/kg.
o
C) (Btu/(lb.F)
dT = change in temperature of the fluid (
o
C) (F)

4.7. Calculating the Amount of Steam:

If we know the heat transfer rate - the amount of steam can be calculated:

m = q / h
e

Where:
m = mass of steam (kg/s) (lb/s)
q = calculated heat transfer (kW) (kJ/s) (HP) (Btu/s)
h
e
= evaporation energy (latent heat) of the steam (kJ/kg) (Btu/lb) (see steam tables)
Example 4:
A quantity of water is heated with steam of 5 bar (72.5 psi) from a temperature of 35
o
C (95F) to 100
o
C
(212F) over a period of 1200 s. The mass of water is 50 kg (110 lb) and the Specific Heat capacity of
water is 4.19 kJ/kg.
o
C (1.0 Btu/(lb.F) .
The heat transfer rate is:
Metric Units:
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 14 of 32
q = (50 kg) (4.19 kJ/kg
o
C) (100
o
C - 35
o
C) / (1200 s) =

q = 11.35 kJ/s = 11.35 kW
Imperial Units:
q = (110 lb) (1.0 Btu/(lb.F) (212F - 95F) / (1200 s) =

q = 10.72 Btu/s = 15.4 HP
Amount of steam:
At 5 bar g (72.5 psi) considering absolute 6 bar, saturation temperature (T
s
) is 158.9C (318 F), and the
Latent Heat (or Specific Enthalpy) h
e
= 2085 kJ/kg = 896.4 Btu/lb (from steam tables).
Metric Units:
m = (11.35 kJ/s)
(2085 kJ/kg)
m = 0.0055 kg/s = (19.8 kg/h)
Imperial Units:
Converting h
e
= 2085 kJ/kg = 896.4 Btu/lb, we find:

m = (10.72 Btu/s)
(896.4 Btu/lb)
m = 0.012 lb/s = (43.0 lb/h)
Example 5:

Water flowing at a constant rate of 3.0 l/s (0.79 gal/s) is heated from 10
o
C (50F) to 60
o
C (140F) with
steam flow at 8 bar. At 8 bar g (absolute 9 bar), saturation temperature (T
s
) is 175C, and h
e
= 2029
kJ/kg (from steam tables). It is assumed that 1 litre of water has a mass of 1 kg.

Mass flowrate = 3.0 l/s (0.79 gal/s) x 1 kg/l = 3.0 kg/s (6.60 lb/s)
h
e
= 2029 kJ/kg is equal to 872.3 Btu/lb.
cp (water) = 4.19 kJ/kg.
o
C is equal to 1.0 Btu/(lb.F
Metric Units:
q = (4.19 kJ/kg.
o
C) (60
o
C - 10
o
C) (3 l/s) (1 kg/l) =

q = 628.5 kJ/s = 628.5 kW
Imperial Units:
q = (1.0 Btu/(lb.F) (140
o
F - 50
o
F) (6.60 lb/s) =

q = 594 Btu/s = 840 HP
The steam flow rate can be expressed as:
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 15 of 32
Metric Units:
m = (628.5 kJ/s)
(2029 kJ/kg)
m = 0.31 kg/s (1,115 kg/h)
Imperial Units:
m = (595.7 Btu/s)
(872.3 Btu/lb)
m = 0.683 lb/s = (2,459 lb/h)
5.0. Temperature Controlled Applications:

The term heat exchanger is used to describe all types of equipment where heat transfer is promoted from
one fluid to another. For convenience, this broad definition will be applied to the term heat exchanger.

In a temperature control application, the inlet temperature of the secondary fluid to the heat exchanger
may change with time. This can be achieved by using a control valve on the inlet to the primary side of
the heat exchanger, as shown in figure below:



5.1. Typical Temperature Control of a Steam/Water Shell and Tube Heat Exchanger:

A control valve is used to vary the flow rate and pressure of the steam so that the heat input to the heat
exchanger can be controlled. Modulating the position of the control valve then controls the outlet
temperature of the secondary fluid.

A sensor on the secondary fluid outlet monitors its temperature and provides a signal for the controller to
compare the actual temperature with the set temperature and, as a result, signals the actuator to adjust
the position of the control valve.

On partially closing the control valve, the steam pressure and the temperature difference fall. Conversely,
if the control valve is opened so that the steam mass flow and hence pressure in the heat exchanger rise,
the mean temperature difference between the two fluids increases.

Altering the steam pressure will also slightly affect the amount of heat energy available in the condensing
steam as the enthalpy of evaporation actually falls with increasing pressure.
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 16 of 32
Example 6:

A manufacturer is to design a heat exchanger in which the specification takes some steam at 4 bar g (58
psi g) to heat secondary water from 10C (50F) to 60C (140F).

It is assumed that 1 litre of water has a mass of 1 kg.

Mass flow rate = 1.5 l/s (24 gpm) x 1 kg/l = 1.5 kg/s (3.30 lb/s).

The manufacturer uses a Heat Transfer Coefficient 'U' for the heat exchanger of 2500 W/m2C (440
Btu/hr.ft.F). Take the Specific Heat of water (cp) as 4.19 kJ/kgC = 4190 J/ kgC (1.0 Btu/lb.F).

Determine:

(A) The design heat load.
(B) The corresponding steam flow rate.
(C) The minimum heating area required.

When the minimum heat load occurs when the inlet water temperature rises to 30C (86F), determine:

(D) The minimum heat load.
(E) The corresponding steam pressure in the heat exchanger.
(F) The corresponding steam flow rate.

Calculations:

(A) Find the design heat load using the heat transfer flow rate equation:

Q = m.cp. T
m


Where:

Q = Heat transfer flow rate (kJ/s) (kW) (Btu/s) (HP)
m = mass of steam (kg/s) (lb/s)
cp = Specific heat capacity of the secondary fluid (kJ/kgC) (Btu/lb.F)
T
m
= Temperature rise of the secondary fluid (K or C) -

Metric Units:

Q = 1.5 kg/s x 4.19 kJ/kgC (60 10)C =

Q = 314.25 kJ/s = 314.25 kW

Imperial Units:

Q = 3.30 lb/s x 1.0 Btu/lb.F x (140F - 50F) =

Q = 297 Btu/s = 420 HP

(B) Find the corresponding steam flow rate:

At 4 bar g, (39F) the saturation temperature (T
s
) is 152C (305F), and h
e
= 2108.1 kJ/kg = 2,108,100
J/kg = 906 Btu/lb (from steam tables).

Calculate the required steam flow at the design condition using equation below:

Metric Units:
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 17 of 32
Steam flowrate (m) = kW x 3600 (kg/h)
h
e


Steam flowrate (m) = 314.25 x 3600 (kg/h)
2108.1

Steam flowrate (m) = 536.6 kg/h

Imperial Units:

Steam flowrate (m) = 297 x 3600 (lb/h)
906 Btu/lb

Steam flowrate (m) = 1180 lb/h

(C) Find the minimum heating area to meet the requirement.

Use the LMTD (T
m
) to calculate the minimum amount of heating area to satisfy the design rating:

T
m
= (T
2
T
1
)

In (T
s
T
1
)

(T
s
T
2
)

T
m =
Logarithmic Mean Temperature Difference (LMTD)
T
s
= Steam temperature = (152 C) (305F)

T
1
= Secondary fluid in temperature = (10 C) (50F)

T
2
= Secondary fluid out temperature = (60C) (140F)
In = The mathematical function known as 'natural logarithm'

Metric Units:

T
m
= (60 10)

In (152 -10)

(152 - 60)

T
m
= 50
In (142)
(92)
T
m
=

50
0.434

T
m
= 115C


Imperial Units:

T
m
= (140 50)

In (305 - 50)

(305 - 140)


www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 18 of 32

T
m
= 90
In (255)
(165)
T
m
=

90
0.435

T
m
= 206F

By re-arranging the general heat transfer equation (Q = U x A x T
m
):

A = Q
U .Tm

Where:

A

= Heating area (m

)
Q = Mean heat transfer rate (W)
U = Heat transfer coefficient (W/m

C)
T
M
= Mean Temperature Difference.

Obs:
T
M
may be either T
LM
(LMTD) or T
AM
(AMTD).

Metric Units:

A = 314,250 W
2500 W/m.C x 115.2C

A = 1.09 m

Imperial Units:

A = 1,072,800 Btu/h
440 Btu/hr.ft.Fx 239F

A = 10.2 ft

(D) Find the minimum heat load, when the inlet water temperature is 30C:

Q = m.cp. T
Metric Units:
Q = (1.5 kg/s).(4.19 kJ/kg.
o
C) (60
o
C - 30
o
C) =

Q = 188.5 kJ/s = 188.5 kW
Imperial Units:
Q = 3.30 lb/s x 1.0 Btu/lb.F x (140F - 86F) =

Q = 178.2 Btu/s = 252 HP
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 19 of 32
5.2. TDC Method - Temperature Design Constant:

When the data sets are not available and the heat exchanger is already installed in service, TDC can
be calculated by observing the steam pressure (and finding the steam temperature from steam tables)
and the corresponding secondary inlet and outlet temperatures at any load.

Once the exchanger size is fixed and the design temperatures are known, it easier to predict operating
temperatures using what could be termed a heat exchanger Temperature Design Constant (TDC).

The TDC method does not require logarithmic calculations.

TDC = T
s
- T
1

T
s
- T
2


Where:

TDC = Temperature Design Constant
T
s
= Steam temperature,
T
1
= Secondary fluid inlet temperature,
T
2
= Secondary fluid outlet temperature,

Example 7:

Consider the following design conditions:

Steam Pressure = 4 bar g (58 psi g)
Inlet water temperature (T
1
) = 10C (50F)
Outlet water temperature (T
2
) = 60C (140F)
Steam temperature at 4 bar g (T
s
) = 152C (305.6F)

Metric Units:

TDC = T
s
- T
1

T
s
- T
2


TDC = 152 - 10
152 - 60

TDC = 142
92

TDC = 1.543 for this particular Heat Exchanger

Imperial Units:

TDC = 305.6 - 50
305.6 - 140

TDC = 255.6
165.6

TDC = 1.543 for this particular Heat Exchanger
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 20 of 32
The TDC equation can be transposed to find any one variable as long as the other three variables
are known. The following equations are derived from the TDC equation.

a) To find the steam temperature at any load:

T
s
= (T
2
x TDC) - T
1

TDC -1

b) To find the secondary fluid inlet temperature at any load:

T
1
= T
s
- [TDC (T
s
- T
2
)]

c) To find the secondary fluid outlet temperature at any load:

T
2
= T
s
- (T
s
- T
1
)
TDC

OBS.: For any heat exchanger with a constant secondary flow rate, the operating steam temperature can
be calculated for any combination of inlet temperature and outlet temperature.

Example 8:

The secondary water outlet temperature remains at 60C, and minimum load occurs when the inlet
temperature is 30C. What will be the steam temperature at minimum load?

Inlet temperature = 30C

Outlet temperature = 60C

T
s
= (T
2
x TDC) - T
1

TDC -1

T
s
= (60 x 1.543) - 30
1.543 - 1

T
s
= 62.58
0.543

T
s =
115.2C = 239.3F

Imperial Units:

(E) Find the corresponding heat exchanger steam pressure and enthalpy at minimum load:

1) A steam temperature of 115.2C (239.3F) corresponds a steam pressure of 0.7 bar g.

2) The Specific Enthalpy of evaporation at 0.7 bar g (h
e
) = 2 215 kJ/kg (see steam tables).

(F) Find the steam flow rate at minimum load:

From (D) the minimum heat load is 188.5 kW = 252 HP

From (E) the h
e
is 2 215 kJ/kg = 952 Btu/lb


www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 21 of 32
Steam flowrate (m) = kW x 3600 kg/h
h
e


Steam flowrate (m) = 188.5 kW x 3600 kg/h
2 215 kJ/kg

Steam flowrate (m) = 306.4 kg/h at minimum load

Imperial Units:

Steam flowrate (m) = 178 Btu/s x 3600 lb/h
952 Btu/lb

Steam flowrate (m) = 673 lb/h - at minimum load.

6.0. Baffle Design Definitions:

Baffles are used to support tubes, enable a desirable velocity to be maintained for the shell side fluid,
and prevent failure of tubes due to flow-induced vibration.

There are two types of baffles: plate and rod.

Plate baffles may be single-segmental, double-segmental, or triple-segmental:



Rod Baffles:



Shell side cross flow area a
s
is given by:

a
s
= D.C.B
P
T


www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 22 of 32
Where:

a
s =
Shell side cross flow area
D = Shell Inside diameter
C = Clearance between tubes
B = Baffle spacing
PT = Tube pitch

Minimum spacing (pitch) of baffles normally should not be closer than 1/5 of shell diameter (ID) or 2
inches whichever is greater.

Maximum spacing (pitch) spacing does not normally exceed the shell diameter. Tube support plate
spacing determined by mechanical considerations, e.g. strength and vibration.

Maximum spacing is given by:



Most failures occur when unsupported tube length is greater than 80% due the designer is trying to limit
the shell side pressure drop.

Baffle cuts. Can vary between 15% and 45% and are expressed as ratio of segment opening height to
shell inside diameter. The upper limit ensures every pair of baffles will support each tube. Kern shell
side pressure drop correlations are based on 25% cut which is standard for liquid on shell side.

Baffle clearances. The outer tube limit (OTL) is the diameter created by encircling the outermost tubes
in a tube layout. The actual OTL is usually 1.5 times the design pressure. It is used during a
hydrostatic test that detects leaks at any joint on the heat exchanger.

For example fixed tube-sheet clearances are shown below:

Shell inside diameter mm (in) Clearance shell I.D and OTL mm (in)
254 (10) to 610 (24) 11 (7/16)
635 (25) 13 (1/2)

6.2. Tube-sheets:

Tube sheets are usually made from a round flat piece of metal with holes drilled for the tube ends in a
precise location and pattern relative to one another. Tubes are attached to the tube sheet by pneumatic
or hydraulic pressure or by roller expansion.

Tube holes are drilled and reamed and can be machined with one or more grooves. This greatly
increases the strength of the tube joint.




www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 23 of 32
6.3. Heat Exchanger Bundles:

Tube bundles are also known as tube stacks are designed for applications according to customer
requirements, including direct replacements for existing units.

There are two types of tube bundles:

a) Fixed Tube Sheet. A fixed-tube sheet heat exchanger has straight tubes that are secured at both
ends by tube sheets welded to the shell.

b) U-Tube. As the name implies, the tubes of a U-tube heat exchanger are bent in the shape of a U and
there is only one tube sheet in a U-tube heat exchanger.




a) Fixed-tube Sheet Heat Exchanger. b) U-Tube Heat Exchanger.

Bundle diameter Db can be estimated using constants shown:

D
b
= d
o
(N
t
/ K
1
)n

Where:

d
o
= Tube Outside Diameter.
N
t
= Number of tubes

K
1
- n = see table below:



6.4. Tube Diameters:

The most common sizes used are 3/4" and 1". Use the smallest diameter for greater heat transfer
area with a minimum of 3/4" tube due to cleaning considerations and vibration.

For shorter tube lengths say < 4ft can be used 1/2" tubes.

6.5. Tube Quantity and Length:

www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 24 of 32
Select the quantity of tubes per side pass to give optimum velocity. For liquids 3-5 ft/s (0.9-1.52 m/s)
can be used. Gas velocities are commonly used 50-100 ft/s (15-30 m/s).

If the velocity cannot be achieved in a single pass consider increasing the number of passes. The
tube length is determined by heat transfer required to process and pressure drop constraints.

To meet the design pressure drop constraints may require an increase in the number of tubes and/or a
reduction in tube length. Long tube lengths with few tubes may carry shell side distribution problems.

6.6. Tube Arrangement:

Triangular pattern provides a more robust tube sheet construction.

Square pattern simplifies cleaning and has a lower shell side pressure drop.

Tube pitch is defined as:

P
T
=

d
o
+ C

P
T
= tube pitch
d
o
= tube outside diameter

C = clearance










Typical dimensional arrangements are shown below, all dimensions in inches.

Tube Diameter Square Pitch Triangular Pitch
5/8 (16 mm) 7/8 (22 mm) (Note = 1) 25/32 (20 mm)
(19 mm) 1 (25 mm) 15/16 or 1 (24 or 25 mm)
1 (25 mm) 1 (32 mm) 1 (32 mm)
1 (32 mm) 1 9/16 (39 mm) 1 9/16 (39 mm)
1 (38 mm) 1 7/8 (47 mm) 1 7/8 (47 mm)

Note:

For shell = 12 square pitch = 0.8125 in.

The table above uses minimum pitch 1.25 times tube diameter i.e. clearance of 0.25 times tube
diameter, the smallest pitch in triangular 30 layout for turbulent or laminar flow in clean service. For
90 or 45 layout allow 6.4 mm clearance for tube for ease of cleaning.

6.7. Corrosion Fouling:

Fouling is deposit formation, encrustation, deposition, scaling, scale formation, or sludge formation
inside heat exchanger tubes.

However if economics determine that some corrosion is acceptable and no data is available from past
experience an allowance of 1/16 in (1.59 mm) is commonly applied.

6.8. Fouling Considerations:

www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 25 of 32
Typical fouling coefficients are shown below. It can be shown that the design margin achieved by
applying the combined fouling film coefficient is given by:



OBS.: Clean OHTC (Overall Heat Transfer Coefficient).

6.9. Typical Fouling Resistances Coefficients:


Cooling Water Fouling Resistances Coefficients
(ft h F/Btu)

Hot Fluid Temperature Up to 240 F 240 F to 400 F

Water

Temperature Up to 125 F Over 125 F
Velocity Up to 3 ft/s Over 3 ft/s Up to 3 ft/s Over 3 ft/s
Boiler Blowdown 0.002 0.002 0.002 0.002
Boiler Feed (Treated) 0.001 0.005 0.001 0.001
City Water 0.001 0.001 0.003 0.002
Condensate 0.0005 0.0005 0.0005 0.0005
Cooling Tower
Treated Make-
up

0.001

0.001

0.002

0.002
Untreated
Make-up
0.003 0.003 0.005 0.004
Distilled Water 0.0005 0.0005 0.0005 0.0005
Muddy Water 0.0003 0.0002 0.0004 0.0003
River Water
Minimum 0.002 0.001 0.003 0.002
Average 0.003 0.002 0.004 0.003
Sea Water 0.0005 0.0005 0.0001 0.0001


Chemical Processing Fouling Coefficients - (ft h F/Btu)
Gases and Vapors
Acid Gases 0.025
Stable Overhead Products 0.001
Solvent Vapors 0.001



Liquids






Caustic Solutions 0.002
DEG and TEG Solutions 0.002
MEA and DEA Solutions 0.002
Vegetable Oils 0.003
Ammonia 0.001
Chlorine 0.002
CO2 0.001

Ethanol Solutions 0.002
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 26 of 32


Liquids

Ethylene Glycol Solutions 0.002
Hydraulic Fluid 0.001
Methanol Solutions 0.002
Refrigerant Liquids 0.001
Sodium Chloride Solutions 0.003
Oils
Engine Lube Oil 0.001
Fuel Oil # 2 0.002
Transformer Oil 0.001
6.10. Fouling Factors [m
2
K/W]:
Process Fluid Fouling Factors
Gas and Vapour
Hydrogen 0.00176
Steam 0.00009
Organic solvent vapours 0.00018
Compressed air 0.00035
Natural gas 0.00018
Liquids
Cooling Fluid 0.00018
Organic heat transfer fluids 0.00018
Salts 0.00009
LPG, LNG 0.00018
Caustics 0.00035
Vegetable Oils 0.00053
Products
Gasoline 0.00018
Naphtha and Light Distillates 0.00018
Kerosene 0.00018
Light gas oil 0.00035
Heavy gas oil 0.00053
Heavy fuel oils 0.00088
Cracking and Coking Units
Overhead vapors 0.00035
Light cycle oil 0.00035
Heavy cycle oil 0.00053
Light coker gas oil 0.00053
Heavy coker gas oil 0.00070

Processing Streams
Overhead vapors and gases 0.00018
Liquid products 0.00018
Absorption oils 0.00035
Reboiler streams 0.00053
Lube oil processing streams 0.00053
Solvent 0.00018

7.0. Basic physical properties for water, steam, air and organic liquids:

www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 27 of 32
Property Units Water
Organic
Liquids Steam Air
Organic
Vapors
Heat
Capacity
KJ/kg C 4.2 1.0 - 2.5 2.0 1.0 2.0 - 4.0
Btu/lb F 1.0 0.239 - 0.598 0.479 0.239 0.479 - 0.958
Density
kg/m 1000 700 - 1500
1.29@STP
(1.0 bar, 0C)

lb/ft 62.29 43.6 - 94.4


0.08@STP
(14.7 psia,
60F)

Latent Heat
kJ/kg 1200 - 2100 200 - 1000
Btu/lb 516 - 903 86 - 430
Thermal
Conductivity
W/m C 0.55 - 0.70 0.10 - 0.20 0.025 - 0.070 0.025 - 0.05 0.02 - 0.06
Btu/h ft F 0.32 - 0.40 0.057 - 0.116 0.0144 - 0.040 0.014 - 0.029 0.116 - 0.35
Viscosity cP
1.8 @ 0 C
**
0.01 - 0.03 0.02 - 0.05 0.01 - 0.03
0.57 @ 50 C
0.28 @ 100 C
0.14 @ 200 C
Prandtl Nbr

1 -15 10 - 1000 1.0 0.7 0.7 0.8


** Viscosities of organic liquids vary widely with temperature.

8.0. Pressure Drop Estimate:

The following preliminary conservative estimates are given for pressure drops due to friction. It can
be noticed that an additional pressure change occurs if the exchanger is placed vertically.


9.0. Experienced-Based Rules

Experience is typically what turns a good engineer into a great engineer. It means someone who
can at least estimate the size of a vessel without doing too many calculations.

The rules below are for estimation and are not necessary to replace rigorous calculations when
such calculations should be performed.

Anyway, these rules can save you hours and hours of stages of analysis and design.

The rules to be considered are:

1. For the heat exchanger equation, Q = U.A.F (LMTD), use F = 0.9 when charts for the LMTD
correction factor are not available.
2. Most commonly used tubes are 3/4 in. (1.9 cm) in outer diameter on a 1 in triangular spacing at 16
ft (4.9 m) long.
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 28 of 32

3. Typical velocities in the tubes should be 3 - 10 ft/s (1 - 3 m/s) for liquids and 30 - 100 ft/s (9 - 30
m/s) for gases.

4. Pressure drops are about 1.5 psi (0.1 bar) for vaporization and 3-10 psi (0.2 - 0.68 bar) for other
services.

5. The minimum approach temperature for shell and tube exchangers is about 20 F (10 C) for
fluids and 10 F (5 C) for refrigerants.

6. Double pipe heat exchangers may be a good choice for areas from 100 to 200 ft (9.3-18.6 m).

7. Spiral heat exchangers are often used to slurry interchangers and other services containing solids.

8. Plate heat exchanger with gaskets can be used up to 320 F (160 C) and are often used for
interchanging duties due to their high efficiencies and ability to "cross" temperatures.

NOTES:

a) A 1 ft (30 cm) shell contains approximately 100 ft (9.3 m).

b) A 2 ft (60 cm) shell contains approximately 400 ft (37.2 m).

c) A 3 ft (90 cm) shell contains approximately 1,100 ft (102 m).
10.0. Sizing Heat Exchangers Online:
Visit www.engineeringpage.com
1) CALCULATION INPUT (PRACTICAL EXAMPLE)
Duty
Required Heat Transfer Duty

cal/h
Btu/h
2,000,000
7,931

Overall Heat Transfer Coefficient, U
W/m
2
C
Btu/h ft F
1,000
176


Fluids
Hot Fluid Cold Fluid
Medium Steam

Water
Volumetric Flowrate m
3
/h 95 4.75
Density kg/m
3
0.7 995
Inlet Temperature C 105 38
Specific Heat Cp kJ/kg K 2.0476 4160

Exchanger Data
Number of Shells in Series 1
Shell and Tube Side
Shell Side Tube Side
Fluid Cold Fluid Hot Fluid
Number of Passes 1 1
2) CALCULATION RESULTS
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 29 of 32
Shell Side Tube Side
Fluid Cold Fluid Hot Fluid
Medium Water Steam
Flowrate 4.75 m
3
/h 2.796 ft
3
/min 95 m
3
/h 55.915 ft
3
/min
Density 995 kg/m
3
62.116 lb/ft
3
0.7 kg/m
3
0.044 lb/ft
3

Mass Flowrate 1.313 kg/s 2.894 lb/s 0.018 kg/s 0.041 lb/s
Specific Heat (Cp) 4160 kJ/kg K 993.599 Btu/lb F 2.048 kJ/kg K 0.489 Btu/lb F
Fouling Factor 0 m
2
K/W 0 h ft
2
F/Btu 0 m
2
K/W 0 h ft
2
F/Btu
Inlet Temperature 38 C 100.4 F 105 C 221 F
Outlet
Temperature
38 C 100.401 F 43.504 C 110.308 F

LMTD and Heat Exchange Surface

Log Mean Temperature Difference 24.61 C 76.29 F
Correction factor F

1.0 1.0

Corrected Mean Temperature
Difference
24.61 C 76.2 F
Total Heat Exchanger Surface 0.09 m
2



1.02 ft
2


11.0. Types of Shell Constructions:

The TEMA-E - is the most common shell type, as it is most suitable for most industrial process
cooling applications.

The TEMA-F - shell design provides for a longitudinal flow plate to be installed inside the tube bundle
assembly. This plate causes the shell fluid to travel down one half of the tube bundle, then down the
other half, in effect producing a counter-current flow pattern which is best for heat transfer.

The TEMA-G and H - shell designs are most suitable for phase change applications where the
bypass around the longitudinal plate and counter-current flow is less important than even flow
distribution.

The TEMA-J - shells are typically specified for phase change duties where significantly reduced
shell side pressure drops are required. They are commonly used in stacked sets with the single
nozzles used as the inlet and outlet. A special type of J-shell is used for flooded evaporation of shell
side fluids.

The TEMA-K - shell, also termed as kettle reboiler, is specified when the shell side stream will
undergo vaporization. The liquid level of a K shell design should just cover the tube bundle, which
fills the smaller diameter end of the shell. This liquid level is controlled by the liquid flowing over a wier
at the far end of the entrance nozzle.

The TEMA-X - shell, or cross flow shell is most commonly used in vapor condensing
applications, though it can also be used effectively in low pressure gas cooling or heating. It
produces a very low shell side pressure drop, and is therefore most suitable for vacuum service
condensing.

See the main types of Shell Constructions in the table below:




www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 30 of 32
Shell Constructions

www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 31 of 32
12.0. Examples of the TEMA designation for Heat Exchangers:

BEM Bonnet (Intergral Cover), One Pass Shell, Fixed Tubesheet Bonnet
Fixed tubesheet heat exchanger. This is a very popular version as the heads can be removed to
clean the inside of the tubes. The front head piping must be unbolted to allow the removal of the front
head, if this is undesired this can be avoided by applying a type A front head.

In that case only the cover needs to be removed. It is not possible to clean the outside surface of the
tubes as these are inside the fixed part. Chemical cleaning can be used.

Shown above is a version with one shell pass and two tube passes.

BEM This is the same type of heat exchanger as above, but with one tube pass.

AEM Channel with Removable Cover, One Pass Shell, Fixed Tubesheet Bonnet
This is almost the same type of heat exchanger as the first BEM, the removable cover allows the inside
of the tubes to be inspected and cleaned without unbolting the piping.

AES Channel and Removable Cover, One Pass Shell, Floating Head with Backing Device
Floating Head Heat Exchanger. A floating head is excellent for applications where the difference in
temperature between the hot and cold fluid causes unacceptable stresses in the axial direction of the
shell and tubes.

Notice that the bundle can not be pulled from the front end. For maintenance both the front and rear
end head, including the backing device, must be disassembled.

If pulling from the front head is required, a type AET should be selected.
www.PDHcenter.com PDHonline Course M371 www.PDHonline.org
2010 Jurandir Primo Page 32 of 32
13.0. Shell Tube Sheet and Tube Hole Count Data:


Related Links:

1. ASHRAE: at: www.ashrae.org.
2. The Tubular Exchanger Manufacturers Association at: www.tema.org.
3. OSHA Technical Manual at: www.osha.gov.
4. Cooling Tower Thermal Design Manual at: www.daeilaqua.com.
5. Tower Design Free Online eBook Collection at: www.pdftop.com/ebook/tower+design.

You might also like