The document contains settings for various protection functions of electrical relays including phase fault protection, earth fault protection, and directional earth fault protection. It lists settings for parameters like start current, operating time, time multiplier, measurement mode, and operating characteristics. The settings are provided for different panels and relay types.
The document contains settings for various protection functions of electrical relays including phase fault protection, earth fault protection, and directional earth fault protection. It lists settings for parameters like start current, operating time, time multiplier, measurement mode, and operating characteristics. The settings are provided for different panels and relay types.
The document contains settings for various protection functions of electrical relays including phase fault protection, earth fault protection, and directional earth fault protection. It lists settings for parameters like start current, operating time, time multiplier, measurement mode, and operating characteristics. The settings are provided for different panels and relay types.
The document contains settings for various protection functions of electrical relays including phase fault protection, earth fault protection, and directional earth fault protection. It lists settings for parameters like start current, operating time, time multiplier, measurement mode, and operating characteristics. The settings are provided for different panels and relay types.
Download as XLS, PDF, TXT or read online from Scribd
Download as xls, pdf, or txt
You are on page 1of 6
PANEL NO CT ratio Relay type ADOPTED SETTING
start current .1-----5.0*In 0
PHASE FAULT TIME MULTIPLIER SETTING(TMS) .05------1 0.15 Not in use extremely inverse Normal inverse very inverse, MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency Start current .1-----40.0*In operate time .05 ----30 sec .01 sec Not in use Definite time Instanataneous MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current 1-------500%o f In 0 TIME MULTIPLIER SETTING(TMS) .05------1 sec 0.15 Not in use extremely inverse Normal inverse very inverse, MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current .1-----12.0*In 0 operate time .05------300 sec 0.15 Not in use Definite time Instanataneous MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current .05-----40.0*In 0 operate time .05------300 sec 0.15 Not in use extremely inverse Normal inverse very inverse, TIME MULTIPLIER SETTING(TMS) .05------1 Basic angle 0 to 90 degree Forward Reverse Disabled, enabled Mode1 (Phase-to-phase voltages/Peak-to-peak currents) Mode2 (Phase-to-phase voltages/Fund. freq. Currents) Mode3 (Phase-to-earth voltages/Peak-to-peak currents) Mode4 (Phase-to-earth voltages/Fund. freq. Currents) Directional PHASE FAULT (67-1) 3I>--> MEASUREMENT MODE K01 600/1 REX521 OPERATING MODE Operation Direction Non directional EARTH FAULT (50N-1) 3I0> Non directional EARTH FAULT (50N-2) 3I0>> OPERATING MODE Not in use Earth fault protection disabled SETTING RANGE OPERATING MODE Not in use OPERATING MODE Not in use OPERATING MODE Not in use Non directional PHASE FAULT (50-1) 3I> Non Directional PHASE FAULT (50-2) 3I>> and 31>>> Not in use PANEL NO CT ratio Relay type ADOPTED SETTING ` start current .05-----40.0*In 0 operate time .05------300 sec 0.15 OPERATING MODE Not in use ,DT ,Inst etc TIME MULTIPLIER SETTING(TMS) .05------1 Basic angle 0 to 90 degree Forward Reverse Disabled ,enabled Enabled, disabled Mode1 (Phase-to-phase voltages/Peak-to-peak currents) Mode2 (Phase-to-phase voltages/Fund. freq. Currents) Mode3 (Phase-to-earth voltages/Peak-to-peak currents) Mode4 (Phase-to-earth voltages/Fund. freq. Currents) start current 1-------500%o f In 0 Start voltgae 2.0----200% Un operate time in DT mode .1------300 sec 0.15 TIME MULTIPLIER SETTING(TMS) in IDMT mode .05------1 Not in use extremely inverse Normal inverse very inverse, Basic angle & Uo IoSin/Cos,& Uo Basic angle Non-directional Io IoSin/Cos Non-directional Uo Forward Reverse Basic angle -90 to 60 degree IoSin() IoCos() Intrmittent earth fault Active Not active MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current 1-------500%o f In 0 Start voltgae 2.0----200% Un operate time .1------300 sec 0.15 TIME MULTIPLIER SETTING(TMS) in IDMT mode .05------1 Not in use Definite time Instanataneous Basic angle & Uo IoSin/Cos,& Uo Basic angle Non-directional Io IoSin/Cos Non-directional Uo Forward Reverse Basic angle -90 to 60 degree IoSin() IoCos() Intrmittent earth fault Active Not active MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency K01 600/1 REX521 SETTING RANGE operational characteristics Operation Direction MEASUREMENT MODE Directional PHASE FAULT (67-2) 3I>>--> OPERATING MODE Not in use Nonm Direc Earth fault protection disabled Directional Earth FAULT (67N-1) 3I0>--> Operating direction Operating criteria Operating direction operational characteristics Operating criteria Not in use OPERATING MODE Directional Earth FAULT (67N-2) 3I0>-->> PANEL NO CT ratio Relay type ADOPTED SETTING start current .1-----5.0*In 0 PHASE FAULT TIME MULTIPLIER SETTING(TMS) .05------1 0.15 Not in use extremely inverse Normal inverse very inverse, MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency Start current .1-----40.0*In operate time .05 ----30 sec .01 sec Not in use Definite time Instanataneous MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current 1-------500%o f In 0 TIME MULTIPLIER SETTING(TMS) .05------1 sec 0.15 Not in use extremely inverse Normal inverse very inverse, MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current .1-----12.0*In 0 operate time .05------300 sec 0.15 Not in use Definite time Instanataneous MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current .05-----40.0*In 0 operate time .05------300 sec 0.15 Not in use extremely inverse Normal inverse very inverse, TIME MULTIPLIER SETTING(TMS) .05------1 Basic angle 0 to 90 degree Forward Reverse Disabled, enabled Mode1 (Phase-to-phase voltages/Peak-to-peak currents) Mode2 (Phase-to-phase voltages/Fund. freq. Currents) Mode3 (Phase-to-earth voltages/Peak-to-peak currents) Mode4 (Phase-to-earth voltages/Fund. freq. Currents) Not in use Non Directional PHASE FAULT (50-2) 3I>> and 31>>> OPERATING MODE Not in use Non directional EARTH FAULT (50N-1) 3I0> OPERATING MODE Not in use Non directional EARTH FAULT (50N-2) 3I0>> SETTING RANGE K02,K03,K04, K05 100/1 REX521 Non directional PHASE FAULT (50-1) 3I> OPERATING MODE Operation Direction Earth fault protection disabled OPERATING MODE Not in use Directional PHASE FAULT (67-1) 3I>--> OPERATING MODE Not in use MEASUREMENT MODE PANEL NO CT ratio Relay type ADOPTED SETTING ` start current .05-----40.0*In 0 operate time .05------300 sec 0.15 OPERATING MODE Not in use ,DT ,Inst etc TIME MULTIPLIER SETTING(TMS) .05------1 Basic angle 0 to 90 degree Forward Reverse Disabled ,enabled Enabled, disabled Mode1 (Phase-to-phase voltages/Peak-to-peak currents) Mode2 (Phase-to-phase voltages/Fund. freq. Currents) Mode3 (Phase-to-earth voltages/Peak-to-peak currents) Mode4 (Phase-to-earth voltages/Fund. freq. Currents) start current 1-------500%o f In 0 Start voltgae 2.0----200% Un operate time in DT mode .1------300 sec 0.15 TIME MULTIPLIER SETTING(TMS) in IDMT mode .05------1 Not in use extremely inverse Normal inverse very inverse, Basic angle & Uo IoSin/Cos,& Uo Basic angle Non-directional Io IoSin/Cos Non-directional Uo Forward Reverse Basic angle -90 to 60 degree IoSin() IoCos() Intrmittent earth fault Active Not active MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current 1-------500%o f In 0 Start voltgae 2.0----200% Un operate time .1------300 sec 0.15 TIME MULTIPLIER SETTING(TMS) in IDMT mode .05------1 Not in use Definite time Instanataneous Basic angle & Uo IoSin/Cos,& Uo Basic angle Non-directional Io IoSin/Cos Non-directional Uo Forward Reverse Basic angle -90 to 60 degree IoSin() IoCos() Intrmittent earth fault Active Not active MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency K01 600/1 REX521 Directional PHASE FAULT (67-2) 3I>>--> Operation Direction Nonm Direc Earth fault protection disabled MEASUREMENT MODE Directional Earth FAULT (67N-1) 3I0>--> SETTING RANGE Operating direction operational characteristics OPERATING MODE Not in use Operating criteria Operating direction operational characteristics Directional Earth FAULT (67N-2) 3I0>-->> OPERATING MODE Not in use Operating criteria PANEL NO CT ratio Relay type ADOPTED SETTING start current .1-----5.0*In 0 PHASE FAULT TIME MULTIPLIER SETTING(TMS) .05------1 0.15 Not in use extremely inverse Normal inverse very inverse, MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency Start current .1-----40.0*In operate time .05 ----30 sec .01 sec Not in use Definite time Instanataneous MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current 1-------500%o f In 0 TIME MULTIPLIER SETTING(TMS) .05------1 sec 0.15 Not in use extremely inverse Normal inverse very inverse, MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current .1-----12.0*In 0 operate time .05------300 sec 0.15 Not in use Definite time Instanataneous MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current .05-----40.0*In 0 operate time .05------300 sec 0.15 Not in use extremely inverse Normal inverse very inverse, TIME MULTIPLIER SETTING(TMS) .05------1 Basic angle 0 to 90 degree Forward Reverse Disabled, enabled Mode1 (Phase-to-phase voltages/Peak-to-peak currents) Mode2 (Phase-to-phase voltages/Fund. freq. Currents) Mode3 (Phase-to-earth voltages/Peak-to-peak currents) Mode4 (Phase-to-earth voltages/Fund. freq. Currents) Not in use Non Directional PHASE FAULT (50-2) 3I>> and 31>>> OPERATING MODE Not in use Non directional EARTH FAULT (50N-1) 3I0> OPERATING MODE Not in use Non directional EARTH FAULT (50N-2) 3I0>> SETTING RANGE K01,K09 600/1 REX521 Non directional PHASE FAULT (50-1) 3I> OPERATING MODE Operation Direction Earth fault protection disabled OPERATING MODE Not in use Directional PHASE FAULT (67-1) 3I>--> OPERATING MODE Not in use MEASUREMENT MODE PANEL NO CT ratio Relay type ADOPTED SETTING ` start current .05-----40.0*In 0 operate time .05------300 sec 0.15 OPERATING MODE Not in use ,DT ,Inst etc TIME MULTIPLIER SETTING(TMS) .05------1 Basic angle 0 to 90 degree Forward Reverse Disabled ,enabled Enabled, disabled Mode1 (Phase-to-phase voltages/Peak-to-peak currents) Mode2 (Phase-to-phase voltages/Fund. freq. Currents) Mode3 (Phase-to-earth voltages/Peak-to-peak currents) Mode4 (Phase-to-earth voltages/Fund. freq. Currents) start current 1-------500%o f In 0 Start voltgae 2.0----200% Un operate time in DT mode .1------300 sec 0.15 TIME MULTIPLIER SETTING(TMS) in IDMT mode .05------1 Not in use extremely inverse Normal inverse very inverse, Basic angle & Uo IoSin/Cos,& Uo Basic angle Non-directional Io IoSin/Cos Non-directional Uo Forward Reverse Basic angle -90 to 60 degree IoSin() IoCos() Intrmittent earth fault Active Not active MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency start current 1-------500%o f In 0 Start voltgae 2.0----200% Un operate time .1------300 sec 0.15 TIME MULTIPLIER SETTING(TMS) in IDMT mode .05------1 Not in use Definite time Instanataneous Basic angle & Uo IoSin/Cos,& Uo Basic angle Non-directional Io IoSin/Cos Non-directional Uo Forward Reverse Basic angle -90 to 60 degree IoSin() IoCos() Intrmittent earth fault Active Not active MEASUREMENT MODE Fundamental frequency, peak to peak Fundamnetal frequency K01,K09 600/1 REX521 Directional PHASE FAULT (67-2) 3I>>--> Operation Direction Nonm Direc Earth fault protection disabled MEASUREMENT MODE Directional Earth FAULT (67N-1) 3I0>--> SETTING RANGE Operating direction operational characteristics OPERATING MODE Not in use Operating criteria Operating direction operational characteristics Directional Earth FAULT (67N-2) 3I0>-->> OPERATING MODE Not in use Operating criteria