Symmetrical Components & Faults Calculations
Symmetrical Components & Faults Calculations
Symmetrical Components & Faults Calculations
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 Symmetrical Components & Faults Calculations
3.0 Introduction
Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the symmetrical components of the original phasors. The method of symmetrical components is a general one, applicable to any polyphase system. Usually, we apply symmetrical component method to symmetrical and unbalanced 3- circuits. The term 'symmetrical' in power systems is used for a poly phase N/W if and only if all the phases are having same impedance (i.e., in magnitude as well as phase angle). A N/W is said to be balanced if and only if all the phases containing voltages / currents in same magnitude but should be displaced by same phase angle. According to Fortescue's theorem, three unbalanced phasors of a three phase system can be resolved into three balanced systems of phasors. The balanced sets of components are : 1. Positive sequence components consisting of three phasors equal in magnitude, displaced from each other by 120 in phase, and having the same phase sequence as the original phasors. 2. Negative sequence components consisting of three phasors equal in magnitude, displaced from each other by 120 in phase, and having the phase sequence opposite to that of the original phasors 3. Zero sequence components consisting of three phasors equal in magnitude and with zero phase displacement from each other. * Three sets of balanced phasors which are the symmetrical components of three unbalanced phasors. Shown in below figures.
Page : 1
Symmetrical Components & Faults Calculations Negative Sequence Components Zero Sequence
Fig. 3.1
* For the positive sequence components, Stator and rotor field directions are same. Considering leads by 120 electrical, and the vector the negative sequence components, the vector lags behind by 120 electrical. * Since these three are also equal in magnitude
Page : 2
Power System
* For the negative sequence components, Stator and rotor field directions are reverse. For zero sequence components, we have and can be resolved into three sets of balanced Since the three un balanced vectors of phase a, the vectors, the vector is equal to the sum of the positive sequence component of phase a.and zero negative sequence component of phase a, and zero sequence component of phase a. sequence component
* Since all power systems considered to be linear, so superposition principle holds good. Similarly
resolved into a total of 9 vectors, i.e, and 3 unbalanced vectors and . Out of these, only 3 are unknown. So, only three components are we can find out linearly independent. (i.e. from the knowledge of the three vectors all the remaining vectors)
OPERATORS: An operator 'a' is introduced, which when operates upon a phasor rotates it by
+120 without changing the magnitude of the phasor upon which it operates. It is represented as
* Assuming phases a as the reference, the relationship between the symmetrical components of phases 'b' and 'c' in terms of symmetrical component of phase 'a' can be written. (phase sequence is abc)
Page : 3
Power System
Where, T = symmetrical transformation matrix V a0 = (1/3) [V a + V b + V c] V a1 = (1/3) [V a +a Vb +a2 V c ] V a2 = (1/3) [V a +a2 V b +a V c ] or in matrix form = = (1/3) [T-1]
(1/3) [T]
where, T-1 = inverse symmetrical transformation matrix Average 3 phase power in Terms of Symmetrical Components: + |V a1 | I a1 | +|V a2 |I a2 | ] P = 3 [|V a0 |I a0 |
Impedance:
= [Zabc] [T] = [Zabc] [T] = [T-1] [Zabc] [T] = [T-1] [Zabc] [T] (since Z012 = [Zabc] = & [Z012] = are self & mutual impedances / )
Z a0 = 1/3 (Z a + Z b + Z c ) zero sequence Z a1 = 1/3 (Z a +aZ b +a2 Z c ) positive sequence Z a2 = 1/3 (Z a +a2Z b +aZ c ) negative sequence
Page : 5
Power System
Eb1 + Z1
Ib1
IC1 Fig. 3.2 The three phase system can be replaced by a single phase network as shown in the below: Ia1 Z1 Va1 V for the Terminal voltage.
+ Ea1 ~
Page : 6
Power System
Z2 N
Z2
Z2 Ic2 Ib2
Fig. 3.4 The three phase network can be replaced by a single phase network as shown in the below figure.
Z2
Ia2 Va2
Page : 7
Power System
Z0
Ia0 Va0
Fig. 3.6 The equivalent circuit for the zero sequence network is different from the positive and negative sequence networks the impedance offered to zero sequence currents depends on grounding of the star point. If the star point is not grounded, then the zero sequence impedance is infinity. If the star point is grounded through some impedance Zn, then the equivalent zero sequence impedance is equal to the sum of the zero sequence phase impedance and is equal to 3Z n . Balanced three phase system consists of positive sequence components only; the negative and zero sequence components being zero. The presence of negative or zero sequence currents in a three phase system introduces asymmetry and is indication of an abnormal condition of the circuit in which these components are found. The vector sum of the positive and negative sequence currents of an unbalanced three phase system is zero. The resultant solely consists of three zero sequence currents i.e., Vector sum of all sequence currents in three phase unbalanced system = + +
In a three phase, 4 wire unbalanced system, the magnitude of zero sequence component is one third of the current in the neutral wire. In a three phase unbalanced system, the magnitude of negative sequence component cannot exceed that of the positive sequence component. If the negative sequence component are greater, the phase sequence of the resultant system would be reversed. The current of a single phase load drawn from a three phase system comprises equal positive, negative and zero sequence component
Example:
The line to ground voltage on the high voltage side of a step up Transformer are 100 kV, 33 kV, 38 kV on phases a, b, & c respectively. The voltage of phase leads That of phase by 100 & lags That of phase by 176.5. Determine analytically The symmetrical component of voltage , ,
Page : 8
Power System
Solution:
Shunt faults are characterized by increase in current and decrease in voltage, frequency and power factor. Series faults are characterized by decrease in current and increase in voltage, frequency and power factor. 2. Two open conductors fault
The series faults are classified as 1. One open conductor fault 1. 2. 3. 4. The shunt type of fault are classified as: Single line to ground fault Line to Line fault Double line to Ground fault Three phase fault The first three faults are the unsymmetrical faults. The three phase fault is symmetrical faults. Severity & occurrence of Faults:
Page : 9
Power System
Fig. 3.7 Fault 1) 2) 3) 4) 3- (LLL,LLLG) Phase to phase ground (LLG) Phase to phase fault (LL) Single line to ground Faults (LG) Severity Severe Severe Less Severe Very less Occurrence 5% 10% 15% 70%
Overvoltage caused by lightning or switching surge. Insulation contamination salt spray, pollution. Mechanical causes overheating, abrasion. Most common lines are exposed to elements of nature 60 70% lightning stroke over voltage causes insulation to flash over Line to ground short circuit or line to line s.c. High winds topple tower, tree falls on line. Winds an ice loading mechanical failure of insulation. For, salt spray, dirty insulation conduction path insulation failure.
S. C. other elements.
Cabels (10 15%), C.B. (10 12%) generator, motor, X-mer (10 15%) much less common over loading for extended periods deterioration of insulation
Page : 10
Power System
Page : 11
Power System
Ia Z ~ ~ Ec Eb + Z Ib + Ea
~
+ Z
Ic Fig. 3.8 The sequence network equations are V a0 = - I a0 Z 0 V a2 = I a2 Z 2 Since ..(4) ....(6) I a1 = (1/3) [I a + a I b + a2 I c ] I a2 = (1/3) [I a + a2 I b + a I c ] I a0 = (1/3) [I a + I b + I c] Substituting the values of I b and I c from equations (2), (3)in above three equations I a1 = I a2 = I a0 = I a/3 V a = 0 = V a1 + V a2 + V a0 Now substituting the values of V a0 , V a1 and V a2 from the sequence network equation, E a - I a1 Z 1 I a2 Z 2 I a0 Z 0 = 0 Since I a1 = I a2 = I a0 Equation (8) becomes
Page : 12
V a1 =E a- I a1 Z 1 (5) The solution of these six equations will give six unknowns V a0 , V a1 , V a2 and I a0 , I a1 , and I a2
.(7)
(8)
Power System
E a I a1 Z 1 I a1 Z 2 - I a1 Z 0 =0 I a1 = I f = I a = I a1 + I a2 + I a0 ; connected in series. If = single Line of Ground fault with Z f : I a1 = Ia1 Va1 and +ve, ve and zero sequence networks are
Z1 ~
Z2
Ia2 Va2
Z0
Ia0
Va0
Fig. 3.9
Conclusion:
1. The three sequence networks are connected in series. 2. If the neutral of the generator is not grounded, the Zero network is open circuited.
Page : 13
Power System a Ea
EC C
Z Z
Eb
b Ib Ic
Fig. 3.10 The sequence network equations are V a0 = -I a0 Z 0 V a1 = E a = I a1 Z 1 V a2 = - I a2 Z 2 .. (4) (5) (6)
The solution of these six equations will give six unknowns V a0 , V a1 , V a2 , and I ao , I a1 and I a2 Since I a1 = (1/3) [I a + a I b + a2 I c ] I a = (1/3) [I a + a2 I b + a I c] I a1 = (1/3) [I a + I b + I c] Substituting the values of I a , I b and I c from equations in above three equations I a1 = (1/3) [0 +a I b - a2 I b ] = (1/3) [a- a2] I b I a2 = (1/3) [0 +a2 I b - a I b ] = (1/3) [ a2 - a] I b I a0 = (1/3) [0 + I b - I b ] I a0 = 0 Which means for a line to line fault the zero sequence component of current is absent and positive sequence component of current is equal in magnitude but opposite in phase to negative sequence component of current, i.e.,
Page : 14
Power System
Z1 Ia1
Ea
Fig. 3.11 I a1 = -I a2 Since V b = a V a1 + aVa2 + V a0 V C = aV a1 + a2V a2 + V a0 a2V a1 + aV a2 + V a0 = aV a1 + a2V a2 V a0 V a1 = V a2 (10) i.e., positive sequence component of voltage equals the negative sequence component of voltage. This also means that the two sequence networks are connected in opposition. Now making use of the sequence network equation and the equation (10) V a1 = V a2. E a - I a1 Z 1 = -I a2 Z 2 = I a1 Z 2 I a1 = I f = I b = - I c = a2I a1 + aI a2 + I a0 (I a2 = - I a1 , I a0 =0) = = I a1
2
Conclusion:
1. The connection of sequence currents are connected in parallel. 2. The phase difference between I a1 and I a2 for line to line fault should be 180 (I a1 = I a2 ). Line to Line fault with Z f I a1 =
Double Line to Ground Fault: Here sequence networks are connected in parallel.
Page : 15
Power System
Double line to ground fault takes place on phases b and c The boundary conditions are I a = 0 .(1) V b = 0 .(2) V c = 0 .(3) The sequence network equations are V a0 = -I a0 Z 0 V a2 = -I a2 Z 2 .(4) .(5)
Ia
V a1 = E a I a1 Z 1
..........(6)
Z +
Ea
Ec Z C
Eb Z b Ic Ib
Fig. 3.12 The solution of these six equations will give six unknowns V a0 , V a1, V a2 and I a0 , I a1 and I a2 . Since V a0 = (1/3) [V a + V b + V c] V a1 = (1/3) [V a + aVb + a2 V c ] V a2 = (1/3) [V a + a2V b + a Vc ] Using above three equations and substituting for V a , V b and V c from the equation (2) and (3) V a0 = (1/3) [V a + 0 + 0 ] = V a/3 V a1 = (1/3) [V a +a. 0 +a2. 0 ] = V a/3
Page : 16
Power System
V a2 = (1/3) [V a +a2. 0 + a.0 ] = V a/3 V a0 = V a1 = V a2 .(7) Using this relation of voltages and substituting in the sequence network equations V a0 = V a1 I a0 Z 0 = E a I a1 Z 1 I a0 = Similarly V a2 = V a1 I a2 Z 2 = E a I a1 Z 1 I a2 = Now from equation (1) I a = I a1 + I a2 +I a0 =0 Ea + Z1 Va1 + Ia1 Fig. 3.13 Substituting values of I a2 and I a0 from the equation(9) and (8) I a1 = Therefore I a1 = I f =I b + I c = 3 I a0 I a0 = -I a1 I f = -3 I a1
Page : 17
..(8)
.(9)
Z2 Va2
Z0
+ Ia2 Ia0
=0
Power System
Conclusion:
Zero sequence and negative sequence networks are parallel and this is in series to the positive sequence.
Ea
Z ECZ
Eb
b C Ic
Ib
Fig. 3.14 I a1 =1/3 (I a + a I b + a . I c ) and substituting the values of I b and I c I a1 = 1/3 (I a + a. a2 I a + a2 a I a ) Ia 1 = Ia I a2 = 1/3 (I a + a2 I b + a I c ) = 1/3 (I a + a4 I b + a2 I c ) = 1/3 (I a + a I a + a2 I c )
2
Page : 18
Power System = =0 I a0 = 1/3 (I a + I b +I c ) =0 V a1 = 1/3 (V a + a Vb + a2 V c ) = 1/3 (V a + a Va + a2 V a ) = V a (1 + a + a2) = 0 V a1 = 1/3 (V a + a2 V b + a.Vc ) =0 Since V a1 = 0 = E a I a1 Z 1 , I a1 = E a / Z 1 (1 + a + a2)
The frequent fault in transformer line is single line to ground fault. The most severe fault is 3-phase fault. The most severe fault nearer to generator is single line to ground fault.
From the analysis of the various faults, the following observations are made: 1. Positive sequence currents are present in all types of faults. 2. Negative sequence currents are present in all unsymmetrical faults. 3. Zero sequence currents are present when the neutral of the system is grounded and the fault also involves the ground, and magnitude of the neutral current is equal to 3 I a0. When currents are entering a delta connected winding, positive sequence components of line currents lead the corresponding positive sequence components of phase currents (winding current) in delta winding by 90. Positive sequence components of line currents on the star side of a star delta transformer, lead the corresponding positive sequence line currents on the delta side by 90. Positive sequence components of line and phase voltages on the star side of a star delta transformer lead the corresponding positive sequence line and equivalent phase voltages respectively on the delta side by 90.
Proof:
Balanced three phase system consists of positive sequence components only; the negative and zero sequence components being zero. Balanced system, Voltages must be in the form of V b = a2V a V c = aV a From Inverse symmetrical transformation,
Page : 19
= (1/3)
= (1/3)
Va 1 + a + a2 = 0
= 1/3
Va
Load Flow
* Load cannot be same for all time in the system. The power flow idea is to find out the voltage at different bus bar, sub - station, node point & the flow of power on these lines, with given constraints and specifications.
Types of Buses:
1. Load bus: In this type of bus, and The unknowns are | | and are known. . and
2. Slack Bus Reference Bus Swing Bus:This bus is a special type of bus. Here real and reactive powers are not specified only are known. 3. Generator Voltage control PV Bus:In this type of bus and are known. and are not known.
Page : 20
Power System
generator
~
bus burs
~
Fig. 3.15 L Load G Generator [Those bus who has self generator are called generated bus bar.] [Whos dont have generator called load bus bar.]
to bus s to bus m to bus
gen Load
Fig. 3.16
Page : 21
Power System
Where injected power (real) in to bus. injected (reactive) power into bus. & For load bus So we can write (i) (ii) On the behalf of equation (i) and (ii) load bus are drawing the power.
Example:
to bus J to bus m
to bus i Bus K
Fig. 3.17
Static analysis of Power Network. Mathematical model of the Network T.L. nominal model. Bus power injection . .
Page : 22
Power System
Shunt admittance
Fig. 3.19
Page : 23
Power System
self admittance. (Driving point admittance) transfer admittance or mutual adce. 1. 2. formatting is so easy & & Z matrix comp. is symmetric matrix
matrix is sparse matrix. (Sparse means most of the elements of Because there are 90% elements are zero. 3. Dimension of is (N N) N = No. of bus
. , k, n = 1, 2, - - - - - N.
Page : 24
Power System
There are two methods to solve these non linear equations: 1. Newton Raphson method 2. Gauss Seidal method Newton Raphson (N.R.) method has got quadratic convergence and is fast as compared to Gauss Seidal and always converge. But N.R. method requires more time per iteration. Gauss Seidal has got linear convergence, convergence is affected by choice of slack bus and the presence of sense capacitor.
Characteristics of power flow equation Power flow equation are algebraic static system _____________________nonlinear Iterative solution Relate P, Q in terms of V, & elements
Example:
Assume a three phase system with a sustained supply voltage of 2,300 volts from line to neutral and with line impedance and . Compute the magnitude of fault current for a single line to ground fault at the end of the line.
Solution:
Supply voltage = 2300 V line/neutral For a single line to ground fault at a in Figure below.
a
Page : 25
Power System
then
where
is prefault voltage
Also
Page : 26