Relay Setting Guide GE
Relay Setting Guide GE
Relay Setting Guide GE
MUL TILIN
GET-8048A
GE Power Management
WWW.ELCENEMAN.MIHANBLOG.COM
Table of Contents
INTRODUCTION
Page
WWW.ELCENEMAN.MIHANBLOG.COM
INTRODUCTION
Power distribution systems serving industrial or commercial facilities represent a variety of costs to the owner. Obviously, the capital cost of the equipment is a concern, as is the cost of the energy which that power system delivers to the loads which convert electrical energy to a saleable product or service. There are some less obvious costs - the cost or reliability, measured in products or services which cannot be sold because power is unavailable, or an even more illusive concept, the cost of quality, which relates to customer satisfaction. Ultimately, as the designer of the system struggles with devising a system arrangement and choosing equipment, he must face the reality that no matter how clever he is, no matter how much redundancy he builds into the system, and no matter how much he pays for premium quality components, he simply cannot build a system which will never fail. This is where system protection, and protective relays become important. If component failure is inevitable, then it is necessary to provide a means of detecting these failures. Better and faster protection afford a number of desirable attributes, all of which ultimately result in saving the owner of the system money through cost avoidance. When component distress is detected and corrected earlier, the damage associated with the failure is minimized, which results in lower repair costs (or even the ability to repair versus the need to replace). At the same time, faster and more sensitive detection of problems means that the cause of the problem can be corrected while it is still a minor problem, and before it escalates into a major catastrophe. Protection is applied on a component basis. Relays are associated with each major component of the power distribution system to detect various forms of distress associated with those components. If one of those relays operates (which means that an output contact closes because the relay detects a level of distress in excess of its calibration or setting), it initiates tripping of circuit breakers or other protective devices which then isolates the defective system components. It may be convenient to think of the circuit breaker as the muscle that does the work of isolating the component, while the relay is the brain which decides that isolation is required. Because protection is associated with components, it has become customary to talk about relays which protect the component with which they are paired. While it is true that faster and more sensitive protection does reduce the amount of damage at the point of the actual fault or distress, and in this sense, relays which detect and de-energize defective equipment do protect their associated components, the value of relay protection on system continuity is even greater. In the limit, a failed motor may have to be replaced, but good relaying on the motor will isolate the motor from the remainder of the power distribution system, allowing it to continue to function and permitting the facility to continue in-service. Ultimately, therefore, it is system protection and service continuity that are the justification for good relay protection.
WWW.ELCENEMAN.MIHANBLOG.COM
1
BASIC CONCEPTS
Zones of Protection One of the most powerful conceptual
tools available to the protection engineer is the notion of zones" as shown in Figure 1 Rather than thinking of the power distribution system as unbounded, successful protection relies on visualizing the system as a collection of discrete zones which can be individually protected using equipment designed to detect the unique forms of abnormalities associated with each component.
Figure 1 Zones include any circuit breakers associated with protected equipment
Association with a significant component (in this case, a line). Terminates at and includes a circuit breaker (or other interrupter) which can respond to trip signals from relays associated with the zone. Represents a minimum amount of system which must be de-energized to correct a problem anywhere in the zone.
Other zones could be defined to comprise buses, generators, motors, cables, etc. Figure 2 shows one final requirement about these zones - they must overlap. Because protection is applied in association with these defined zones, it is absolutely essential that every portion of the system must fall within a zone in order to assure that there are no areas which are unprotected.
WWW.ELCENEMAN.MIHANBLOG.COM
2
TYPES OF DISTRESS
Overcurrent Overcurrent is the term employed in the National Electrical
Code to mean short-circuit. On a healthy system, the flow of current is a function of the magnitude of elecrical load. A short-circuit is a breakdown in insulation which results in an abnormal flow of current limited only by the impedance of the electrical distribution system. The distress associated with a short-circuit comes about because of the flash and arcing at the fault point, the depression in system voltage associated with the fault, and the thermal stress imposed on the conductors which must carry fault current. Short-circuits are the focus of greatest attention in protection of medium and high voltage systems. The change in state from load current to short-circuit current occurs rapidly. From fundamental physics, it is known that the magnitude of current in an inductor cannot change instantaneously. This conflict can be resolved by considering the short-circuit current to consist of two components, a symmetrical ac current having the higher magnitude of the short-circuit current, and an offsetting dc transient which has an initial magnitude equal to the initial value of the ac current and which decays rapidly. The initial magnitude of the dc transient is directly controlled by the point on the voltage wave at which the short-circuit Asymmetrical fault current with decaying dc component occurs; if the short-circuit occurs at the natural zero crossing of the driving voltage sinusoid, the transient is maximized where as it is a minimum if the fault occurs at the crest of the voltage sinusoid. At any subsequent point in time, the magnitude of the dc transient is determined by the time constant of the decay of the dc which is controlled by the ratio of reactance to resistance in the impedance limiting the fault. For the protection engineer, the worst case initial current is that which includes the full dc transient. The voltage which drives a short-circuit includes sources such as remote generators with voltage regulators that will maintain their value regardless of the presence of a shortcircuit on the system, as well as nearby sources whose voltage will decay when the short-circuit is present. The amount of decay is determined by the nature of the source. Nearby generators and synchronous motors which have active excitation systems will sustain some voltage, but since the short-circuit will cause their terminal voltage to drop, the current they produce will gradually be reduced as the fault is allowed to persist. At the same time, induction motors will initially participate as short-circuit current sources, but their voltages will decay rapidly as the trapped flux is rapidly drained.
Figure 3
illustrates how the various elements of asymmetry combine to create the most realistic case of the decaying symmetrical ac current combined with the decaying dc transient. From this figure, it is possible to describe a generalized short-circuit current in the following terms: High initial magnitude dc transient component of current which decays fairly rapidly with time. High initial magnitude symmetrical ac current which diminishes gradually with time. Symmetrical ac current lags driving voltage by a significant angle, approaching 90.
Figure 3
WWW.ELCENEMAN.MIHANBLOG.COM
3
Open Circuit The power distribution system can tolerate open circuits
continuously without harm. Where open circuits are a concern is on rotating machines - motors and generators where they translate into abnormal rotor heating for which these equipments have little tolerance. Hence, open circuit protection is frequently applied on motors and generators, and seldom on the passive portions of the distribution system.
DETECTION MODES
Circuit - Current or Impedance Based on the desire to array protection in logical zones, the most common mode of protection is one which can not only detect that an abnormality (such as a short circuit) exists, but which can also determine its location. The parameter which most simply locates faults is current short-circuits result in abnormal flow of current, and a relay system which looks for high current will be able to selectively detect faults. Current is the parameter which is used in the vast majority of all protection schemes, and is used almost exclusively from 35kV down through 120V residential distribution. System - Voltage or Frequency V oltage
measurements can be used to detect that something unusual is happening on the system, but generally voltage will not give any indication of the location of the problem. Hence, measurement of voltage is usually reserved for overall system protection functions. Likewise, frequency is an overall system issue. Closely related to current detection is measurement of apparent impedance. Apparent impedance is the ratio of voltage to current measured at a relay location and is a direct measure of the electrical separation between the relay location and a point on the system where the voltage is depressed to zero by a short-circuit. Impedance measurement is more complicated than current measurement, and hence its use is reserved for more critical applications at the higher voltages, typically above 69 kV.
WWW.ELCENEMAN.MIHANBLOG.COM
4
PROTECTION CHARACTERISTICS
Time Overcurrent Time overcurrent protection is the predominant form of
protective relaying in medium voltage industrial and commercial power systems. This form of protection employs relays with inverse time-current characteristics; that is, operating time of these relays becomes less as the current magnitude increases. The basic operating characteristics trace their heritage to the natural operating characteristics of the induction disk overcurrent relay, and as a result static analog and digital relays are designed to emulated this basic characteristic, but there is also a noble rationale for the inverse-time relationship. Relays are intended to detect and initiate tripping of high-magnitude fault currents quickly enough to avoid thermal damage to conductors, and the natural heating characteristic is also an inverse-time relationship. Traditionally, the characteristics of time overcurrent relays has been published in the form of graphical curves showing the dependent variable (operating time) on the vertical axis and the independent variable (operating current) on the horizontal axis. It is also a tradition that these curves are plotted on a special log-log paper. These traditions trace their origin to the manual practices involved in determining settings for relays. There are a number of characteristics in common use, which are shown in Figure 4. Each of these exists to address specific application needs. Following is a list of the most common characteristics together with their usual applications and also the code number which GE uses to identify each curve shape: Inverse medium time (51) - best suited for applications where the variations in the magnitude of fault current are related primarily to switching of sources on the system, such as in paper mill systems with a number of small hydroelectric generators which are switched on and off depending on water conditions. Very inverse medium time (53) - best suited for general applications where the variations in the magnitude of fault current are primarily determined by system impedance and fault location. This relay characteristic is the best choice for most industrial and commercial applications. Inverse medium-long time (57) - best suited for applications as backup ground fault protection on complex low-resistance grounded medium voltage systems. Inverse long time (66) - best suited for overload and locked rotor protection of motors.
Figure 4
Extremely inverse medium time (77) - best suited for application on utility residential distribution circuits where selectivity with distribution fuse cutouts and reclosers is a requirement, and where cold load pickup is a consideration. Inverse short time (95) - best suited for backup ground fault protection applications on solidly grounded low voltage systems where the feeders have instantaneous ground fault protection.
The principle of time overcurrent protection is that relays are applied appropriately at the terminals of zones, and each relay is then given both a current pickup and a time delay setting. The current pickup establishes the sensitivity of the relay; a variety of rules dictate what this sensitivity must be. Some of these rules are mandatory and must be followed; the National Electrical Code contains a number of requirements on the current setting of overcurrent relays. Other rules are embodied in application standards, and while these are not absolutely mandatory, they do represent a consensus of the industry from which most engineers would not want to deviate. Finally, there are several rules of thumb, or conventional practices which, through experience, have been recognized as good things to do.
WWW.ELCENEMAN.MIHANBLOG.COM
5
T he
time setting is used to achieve selective backup protection. How this happens is best illustrated with characteristic curves as in Figure 5. For a fault on a feeder, the current magnitude determines the operating time of all relays. Relays which are closest to the fault have time settings which result in faster operation than those which are further away. Therefore, the primary relays which are closest to the fault want to trip first while the more remote backup relays wait, but if the primary relays (or their associated circuit breakers) fail, then the backup relays time out and trip. The time margin between the settings of these relays must take into account three factors:
Figure 5
Selective coordination of time overcurrent relays assumes that the backup relay will always be slower than the primary relay
WWW.ELCENEMAN.MIHANBLOG.COM
6
Figure 6
A directional relay on Phase A uses the B-C voltage as its polarizing reference, and together they establish a directional phasor which leads the B-C reference voltage by an angle which is fixed in the design of the relay. Operation can occur if the current angle falls within 90 of the angle of the directional phasor. In most instances, directionality is a function which is added to other relay characteristics. That is, overcurrent relays are made directional by incorporating a directionality function to the design of the relay such that an overcurrent measurement can only be made if the directionality is satisfactory. With induction relays, one induction unit is required for the overcurrent measurement, while a separate unit is used to determine the direction of the current. Digital relays are less complex; the directional function may be a few more lines of code.
Directional phasor
I s V
Non-operating region
Figure 7
Operating region
WWW.ELCENEMAN.MIHANBLOG.COM
7
WWW.ELCENEMAN.MIHANBLOG.COM
8
PROTECTION PACKAGES
The following protection packages are organized according to the types of equipment generally encountered in medium voltage systems. Generators, Motors, Feeders, Transformers, Buses, and Incoming Lines will be addressed. Packages are based on commonly used power system configurations. Other considerations may be needed if unique power system arrangements are used.
WWW.ELCENEMAN.MIHANBLOG.COM
9
GEN G E N E R A T O R
Protective Zone (GEN1)
Minimum protection for a small machine with low resistance grounding:
BUS
CONTROL PACKAGE
3*
GEN
64B 50GS
27 32 40 46 49R 50GS
46
51V 2 (or 3)
32
40
87G
49R
86G
27
81L/H
59
Undervoltage Power Direction Loss of Excitation Current Unbalance Overload (RTD) Instantaneous Overcurrent Ground 51GN Time Overcurrent Ground 51V Time Overcurrent (V Restraint) 59 Overvoltage 64B Bus Ground Detection 81L/H Frequency 86G Lockout Auxiliary 87G Differential
Qty.
Device No.
GE Model No.
3 1
51V 51GN
Options
1 1 1 1 1 1 3 1 1 27 32 40 46 49R 50GS 51VC 59 64B Undervoltage Relay Reverse Power Relay (detects losses over 5%) or Reverse Power Relay (detects losses below 5%) Loss-of-excitation Relay Negative Sequence Relay Stator Overtemperature Relay (RTD input) Ground Sensor Overcurrent Relay (in place of 51GN where system ground is not generator neutral) Voltage-controlled Overcurrent Relay (in place of 51V) Overvoltage Relay Generator Ground Overvoltage Relay (in place of 51GN where generator is ungrounded) Under/Overfrequency Relay Lockout Auxiliary Relay Self-balancing Current Differential Relay (for connections see MTR1A figure) or Percentage Current Differential Relay TOV5 or IAV54 ICW51A or GGP53C CEH51A SGC21C IRT51E DIFC or HFC21 IFCS51AD TOV5 or IFV71AD TOV5 or IFV51DD SFF202B HEA61 MDP or CFD22A
1 1 1
WWW.ELCENEMAN.MIHANBLOG.COM
10
GEN
1
GENERATO R
CONTROL PACKAGE
3*
50GS
40
46/49C
51
51VC
32
2 (or 3) 87G
51GN
27
81L/H
GEN 86G
49R RTD
59
3 1
LOW RES
Qty.
Device No.
GE Model No.
Multifunction analog relay system containing the following modules: Multifunction Module with functions: Negative Sequence Thermal Image Definite Time Overcurrent Neutral Ground Overcurrent Voltage-controlled Overcurrent Modules
MID100 MGC
MIC7/TOV4
Options
1 1 1 27 32 81L/H Undervoltage Module (into MID100 system) Reverse Power Module (into MID100 system) Under/Overfrequency Module (into MID100 system) TOV5 TCW MFF
WWW.ELCENEMAN.MIHANBLOG.COM
11
GEN G E N E R A T O R
Protective Zone (GEN2)
Recommended protection for a small machine with low/high resistance grounding:
BUS 52 2 (or 3) 27 47 32 59 40Q RTD PROBE RTD 38 50/27 GEN 12 49 81U 51V 24 60FL 46 49 6 Output relays Output relays
s
81O
Qty.
1
Device No.
86G
WWW.ELCENEMAN.MIHANBLOG.COM
12
1
3
86G
50/51GN
59GN 27TN
GE Model No.
SR489
Options
Lockout Relay HEA61
GEN G E N E R A T O R
Protective Zone (GEN3)
Minimum protection for a large machine with high resistance grounding:
21GX
3**
52
BUS
81L/H
60V
3 (or 2)
27 21G 78 24
40
32
1 41 64F
3 (or 2)
FIELD
46
GEN 3**
86G
RES
64G1
27TN
If no external fault source exists, exchange connections of protection from line side CT's to neutral side CT's and vice versa.
Qty.
1
Device No.
GE Model No.
DGP--BA 0005
1 1 1 1 1 1
Options
System Backup Distance Relay (in place of 51V) Stator Overtemperature Relay (RTD) Voltage Balance Relay Field Ground Relay Out-of-step Relay (For additional options see GEN1 Options) 13
WWW.ELCENEMAN.MIHANBLOG.COM
GEN G E N E R A T O R
Protective Zone (GEN4)
Recommended protection for a more important large machine with high resistance grounding:
21GX
3**
52
BUS
81L/H
60V
3 (or 2)
59 21G 78 24
40
32
1 41 64F
3 (or 2)
FIELD
GEN 3**
86G
Distance Aux to 21G Overexcitation Undervoltage Undervoltage (Third Harmonic) Power Direction Loss of Excitation Current Unbalance Overload (RTD) Time Overcurrent (Ground) Time Overcurrent (V Restraint) Overvoltage Voltage Balance Ground (field) Ground (stator) Out-of-step Frequency Lockout Auxiliary Differential
RES
64G1
If no external fault source exists, exchange connections of protection from line side CT's to neutral side CT's and vice versa.
Qty.
1
Device No.
GE Model No.
DGP--CA
86G
HEA61
WWW.ELCENEMAN.MIHANBLOG.COM
14
MTR M O T O R
Protective Zone (MTR1)
Minimum protection for a small induction motor (below 1500HP):
BUS
48
CONTROL PACKAGE
62
60V
27 47 3
49R M
50/51
49/50
49S/50
50GS
RTD or Thermistor
Qty.
1 1 1 3 1 1 1
Device No.
27 50/51/50GS 27 50/51 50GS 27 46 49 49R 50GS 66
GE Model No.
IAV54E or TOV5 MDP0 or 735 IAV54E or TOV5 IFC66B or DIFC HFC21 or DIFC IAV54E or TOV5 P4A
Options
1 1 1 1 1 1 1 38 47 48 49R 49S/50 60V 62 Bearing Overtemperature Relay (RTD) Three-phase Undervoltage and Reverse Phase Sequence Relay (in place of 27) (Requires open-delta or wye-wye voltage transformers) Adjustable Time Delay Relay or Timer Winding Overtemperature Relay Stalled Rotor Relay Voltage Unbalance Relay (use with 62 and may require harmonic filter) Timing Auxiliary Relay IRT51E ICR
WWW.ELCENEMAN.MIHANBLOG.COM
15
MTR M O T O R
Protective Zone (MTR1A)
Recommended protection for a more important small inductions motor (below 1500 HP):
BUS
48
CONTROL PACKAGE
47 27 62
s
60V
49/ 49S/50
37
46
66
50GS
49R
86
38
TRIP
86M
87M
Qty.
1
Device No.
1 1
86M 87M
WWW.ELCENEMAN.MIHANBLOG.COM
16
GE Model No.
239 or MMC
TOV5
Options
Lockout Auxiliary Relay HEA61 Self-balance Differential Relay HFC23 (Add if required and if possible to mount three 50/5A current transformers at the motor.) or Percentage Differential Relay CFD22A or DTP1 (Add if required. See MTR2 figure for one-line representation) (For additional options see MTR1)
MTR M O T O R
Protective Zone (MTR2)
Minimum protection for a large induction motor (1500 HP and above):
BUS
1
3 87M M
86M
Qty.
1
Device No.
1 1
WWW.ELCENEMAN.MIHANBLOG.COM
17
27/59
47
50/51
TRIP
Under and overvoltage Undercurrent Bearing Overtemperature (RTD) Current unbalance Undervoltage/reverse phase sequence 48 Incomplete sequence 49 Overload 49R Winding overtemperature (RTD) 49S Locked rotor protection 50/51 Instantaneous & time overcurrent 50GS/ Instantaneous & time overcurrent 51GS ground sensor 66 Successive starts 86,86M Lockout Auxiliary 87M Differential
Options
(See options for MTR1 and MTR1A)
GE Model No.
269 Plus
MTR M O T O R
Protective Zone (MTR2A)
Recommended protection for a more important large induction motor (1500 HP and above):
BUS
27/59 47
1
3 87M Motor
86M
Qty.
1
Device No.
87M
WWW.ELCENEMAN.MIHANBLOG.COM
18
81L/H
50/51
37
46 38
49R 10 RTD
26
GE Model No.
469
HEA61
Options
Differential Relay CFD22A or DTP1
MTR M O T O R
Protective Zone (MTR3)
Recommended protection for a synchronous motor in addition to that provided in preceding zones MTR1 through MTR2A:
BUS
48
CONTROL PACKAGE
26F 27DC 37 48 50 55 95
Winding Overtemperature Undervoltage Undercurrent Incomplete sequence Instantaneous overcurrent Power factor Reluctance Torque Sync/Re-Sync
50
55
27DC Vdc
95
MOTOR
Idc
26F
37
FIELD
Qty.
1
Device No.
GE Model No.
SPM
26F 27DC 37 50 55 95 96
WWW.ELCENEMAN.MIHANBLOG.COM
19
FDR F E E D E R
Protective Zone (FDR1)
Standard Non-directional circuit, residually connected ground relay:
BUS
50/51
50/51 51N
51N 50N
Phase overcurrent and short circuit Time delay ground fault Instantaneous ground fault
50N LOAD
Qty.
1
Device No.
50/51/ 51N or 50N
GE Model No.
MDP or SR735
Options
1 79 Recloser Relay SLR12
WWW.ELCENEMAN.MIHANBLOG.COM
20
FDR F E E D E R
Protective Zone (FDR2)
Standard Non-directional circuit, with ground sensor relay:
BUS
52 3
50GS 51GS
Phase overcurrent and short circuit Instantaneous ground fault Time delay ground fault
LOAD
Qty.
1
Device No.
50/51/ 51GS or 50GS
GE Model No.
MDP / SR735
Options
1 79 Recloser Relay SLR12
WWW.ELCENEMAN.MIHANBLOG.COM
21
FDR F E E D E R
Protective Zone (FDR3)
Standard Directional circuit:
BUS
67
67 67N
TRIP DIRECTION
67N
Directional overcurrent and short circuit Directional time delay and instantaneous ground fault
LINE/LOAD
Qty.
1
Device No.
67/67N
GE Model No.
DFP100 or SR750 / SR760
Options
1 79 Recloser Relay SLR12
WWW.ELCENEMAN.MIHANBLOG.COM
22
FDR F E E D E R
Protective Zone (FDR4)
Long lines and critical short length lines:
52
87L
s
87L 86L
PILOT WIRE
LINE BKR 52
86L
s
87L
Qty.
2 2
Device No.
87L 86L
GE Model No.
SPD11 HEA61
Options
1 1 85LM 85LM Pilot Wire Monitor Relay (sending end) Pilot Wire Monitor Relay (receiving end) SPA11 SPA12
Alternate Package
2 2 87L 86L Current Differential Relay Lockout Auxiliary Relay DLS3 HEA61
WWW.ELCENEMAN.MIHANBLOG.COM
23
TR T R A N S F O R M E R
Protective Zone (TR1)
Protection for transformers 2500KVA and below, medium and low voltage windings:
52 3
50/51 50GS
50GS
L.V. 52
Qty.
1
Device No.
50/51/50GS
Description Basic Package
Overcurrent, Short Circuit and Ground Fault Relay MDP or SR735
M.V.
GE Model No.
WWW.ELCENEMAN.MIHANBLOG.COM
24
TR T R A N S F O R M E R
Protective Zone (TR2)
Protection for transformers 750kVa and above, medium voltage windings:
3
87T
s
3 1 86T M.V.
M.V.
Qty.
Device No.
1 X 1
Differential Relay Fault Pressure Auxiliary Relay Lockout Auxiliary Relay (quantity as required) Overcurrent, Short Circuit and Ground Fault Relay
WWW.ELCENEMAN.MIHANBLOG.COM
25
52 52
50/51
50GS
*
63 63X
*INTEGRAL TO TRANSFORMER
GE Model No.
TR T R A N S F O R M E R
Additional Transformer Ground Protection
52
52
Qty.
1 1
Device No.
51G 87N
WWW.ELCENEMAN.MIHANBLOG.COM
26
51G
1 Aux. CT
87N
(other devices)
GE Model No.
DIFC or IFC53A IFD51D
BUS B U S
Protective Zone (BUS1)
Single source, radial configuration:
SOURCE 3
52
51 51N
BUS
52
52
Qty.
1
Device No.
51/51N
GE Model No.
MDP or SR735
Options
1 64 Ground Fault Relay (ungrounded systems) TCCV
WWW.ELCENEMAN.MIHANBLOG.COM
27
BUS B U S
Protective Zone (BUS2)
Multiple sources with bus tie breaker:
SOURCE 3 SOURCE
51
51
52 51N 51N
52
52
52
Qty.
1
Device No.
51/51N
Options
1 64 Ground Fault Relay (ungrounded systems) TCCV
WWW.ELCENEMAN.MIHANBLOG.COM
28
BUS
GE Model No.
MDP or SR735
BUS B U S
Protective Zone (BUS3)
Single or multiple sources, with or without bus tie breakers:
3
52
52
87B
Differential
BUS 52 3
Qty.
3
Device No.
87B
GE Model No.
PVD21 or SBD11
WWW.ELCENEMAN.MIHANBLOG.COM
29
BUS B U S
Protective Zone (BUS4)
Multiple sources, bus tie breakers, multi-ratio CT's:
3
52 3 3
52
87B
Differential
BUS
52
52
52 3
Qty.
1
Device No.
87B
GE Model No.
BUS1000
WWW.ELCENEMAN.MIHANBLOG.COM
30
I L INCOMING LINE
Protective Zone (IL1)
Single source incoming line (no internal generation):
TO UTILITY SOURCE
s
3
TO 87B 51N 51
27 52
59
81L/H
Qty.
1
Device No.
51/51N
GE Model No.
MDP
WWW.ELCENEMAN.MIHANBLOG.COM
31
I L INCOMING LINE
Protective Zone (IL2)
Single source incoming line via utility transformer (no internal generation):
TO UTILITY SOURCE TRANSFORMER s TO TRANSFORMER 3 s NEUTRAL CT
TO 87B
51G1 3
51G2
51
60V 52 3
62
TO 87T
2 (or 3)
Qty.
1 1
Device No.
51/51G 51/51G/ 74LM
GE Model No.
MDP DFM3
WWW.ELCENEMAN.MIHANBLOG.COM
32
I L INCOMING LINE
Protective Zone (IL3)
Single source incoming line with internal generation:
TO UTILITY SOURCE
s
3
52
TO 87B
51 51N
67 67N
AUX PT
s
87L
86L
85 LM/TT
Qty.
1 1 1 1
Device No.
87L 86L 67/67N 51/51N
Alternates
1 3 1 4 87L/85LM/ 85TT 67 67N 51, 51N Line Differential & Channel Monitor & Transfer Trip Auxiliary Relay Directional Phase Overcurrent Relay (Single Phase Units) Directional Ground Overcurrent Relay (Single Phase Units) Phase/Ground Overcurrent Relays (Single Phase Units) DLS3* IBC53 or JBC53 IBCG53 or JBCG53 DIFC or IFC53A
Options
1 1 1 85LM 85LM/TT 87B Pilot Wire Monitor [different device at send and receive ends] Relay Pilot Wire Monitor and Transfer Trip Auxiliary Relay [different device at send and receive ends] Differential Relay (See Bus Protective Zones for Details) (For additional alternates and options see IL1 and IL2) SPA11A or 12A* SPA11B or 12B*
Notes:
*Must be selected in accordance with companion relay at opposite end of the line. Pilot wire protective auxiliaries may be required.
WWW.ELCENEMAN.MIHANBLOG.COM
33
2 (or 3)
GE Model No.
SPD11* HEA61 MOR3 MDP
I L INCOMING LINE
Protective Zone (IL4)
Dual source incoming line (dual line with internal generation & via utility transformer):
sTO L-N VT ON XFMR 'T1' s TO UTILITY SOURCE
3 HIGH SIDE
52
(XFMR T1)
TO 87B1
s
50L 51B 51BN
27L
59L
27L 32 47
MAIN 1
51G
67N
67
32
62 TO MAIN BKR 2 s
52 TIE
Qty.
1 1 1
Device No.
67/67N 51B/51BN 51G
2 (or 3)
Undervoltage Power direction Phase undervoltage and reverse phase sequence 50L Instantaneous overcurrent 51B Phase time overcurrent 51BN Residual time overcurrent 51G Ground overcurrent 59B Overvoltage 59L Overvoltage 62 Timer 67 Directional phase overcurrent 67N Directional ground overcurrent 81L/H Frequency
TO 87T1
47
59B
81L/H
87B1s
Options
GE Model No.
MOR3 MDP DIFC
1 1
27L 59L
1 1
32 62
1 1 1 1 1
Line Undervoltage (transformer highside) Relay Line Overvoltage (transformer highside) Relay (Add 27L & 59L as a means of detecting Delta-Wye transformer highside ground fault after utility separation.) Power Directional Relay (detects transf. magnetizing current) Auxiliary Timing Relay (add 32 & 62 in lieu of 27L and 59L as alternate means of detecting system ground faults) Phase Undervoltage and Reverse Phase Sequence Relay (add if required for motor bus monitoring or intertie) Bus Overvoltage Relay (add if required for intertie) Over and Underfrequency Relay (add for intertie or load shedding requirements) Instantaneous Overcurrent Relay (add if highside disconnect is not rated for fault interruption) Differential Relay (See Bus and Transformer Protective Zones for Details) (For additional alternates and options see IL1 and IL2)
CCP13E SAM201
34 WWW.ELCENEMAN.MIHANBLOG.COM
RELAY INDEX
MODEL
239 269 PLUS 469 489 735/737 745 750/760 ALPS BDD BUS1000 CAP CCP CEB CEH CEX57 CEY CEY-IAC CEYG CFD CFV CFVB CHC CJCG CLPG DAR DBF DBT DDS DFF DFM DFP100 DFP200 DGP DIAC DIFC DLP DLS DSFC DTP GCX GCY GGP GSY GXS HAA HEA HFA HFC HGA HGA18 HMA HSA IAC IAV IBC IBCG ICR ICW IFC IFCS IFCV
DESCRIPTION
Small HP MV motor management relay Medium HP MV motor management relay Large HP MV motor management relay with metering Small/medium size generator relay 3 phase + ground feeder relay Transformer management relay Multifunction feeder relay High speed distance relay Transformer differential, harmonic restraint Bus protection relay Power directional Power directional Phase offset MHO distance Loss of excitation Angle impedance Phase MHO distance Phase distance overcurrent Ground MHO distance Machine differential Instantaneous overvoltage Voltage balance Instantaneous overcurrent Ground directional overcurrent Carrier ground Reclosing Breaker failure relay Breaker coil/tripping circuit supervision relay Digital distribution system Frequency relay Feeder monitor + hi impedance ground Multifunction feeder relay with reclose Multifunction feeder + hi impedance ground Generator protection Time overcurrent relay Time overcurrent relay Distance relay Current differential line protection Time overcurrent relay Transformer protection relay Phase reactance distance Phase MHO distance Sensitive power directional Generator out-of-step Auto sync/sync check Annunciator auxiliary Auxiliary lockout Multicontact auxiliary Instantaneous overcurrent Contact auxiliary Reclosing Contact auxiliary Auxiliary lockout Time overcurrent Time over/under voltage Phase directional overcurrent Ground directional overcurrent Undervoltage and phase sequence Time over/underpower Time overcurrent Time overcurrent with voltage control Time overcurrent with voltage restraint
DEVICE NO.
49/50/51(+) 87(+) 87(+) 87(+) 50/51 87(+) 50/51(+) 21(+) 87 87 32 32 21, 68 40 78 21 21/50/51 21N 87 59 60 50 67 67 79 50BF 74 50/51(+) 81 51/51G/74 50/51(+) 50/51/74(+) 87(+) 51, 50/51 51, 50/51 21(+) 87(+) 51, 50/51 87 21 21 32 78 25 30, 74 86 86, 94 50 27, 74, 94 79 27, 74, 94 86 51, 50/51 27, 59, 64 67 67N 47 32, 37 51, 50/51 51 51V
MODEL
IFD IFV IJC IJD IJF IJS IRT JBC JBCG JBCV LPS MCP MDP MFF MGC MIC MLJ MLP MMC MOR MRC MRS NAA NBT NBV NGA NGV NLR NSR OST PJC PJG PJV PLS PVD SAM SBA SBC SBD SCA SFF SGC SLJ SLR SLV SLY SLYG SPA SPD SPM STD STV TCC TCCV TCW TLS TOC TOV TRS TTS TYS
DESCRIPTION
Transformer differential Time overvoltage Current balance Machine differential Over/under frequency Synchronism check Temperature Phase directional overcurrent Ground directional overcurrent Directional overcurrent, voltage restraint Distance relay Capacitor bank protection 3 phase + ground feeder relay Over/under frequency Small generator protection Overcurrent Synchrocheck Three pole tripping distance relay Small motor protection Directional overcurrent with reclosing Thermal image Transmission line reclosing Pilot/distance auxiliary Breaker trip supervisor Voltage balance Contact auxiliary Instantaneous under/over voltage Multi-shot reclosing Single-shot reclosing Out-of-step protection Instantaneous overcurrent Machine field ground Over/under voltage Polyphase transmission line protection system Bus differential Time delay Breaker auxiliary Breaker backup Bus differential Directional comparison, blocking auxiliary Over/underfrequency Negative sequence overcurrent Synchronism check Multi-shot reclosing Over/under voltage Phase distance Ground distance Pilot wire monitor AC pilot wire Synchronous motor controller Transformer differential Overexcitation (V/Hz) Directional overcurrent Ground fault Directional power Phase/zone transmission line protection system Overcurrent Over/under voltage Transmission line reclosing Transformer differential Phase/zone transmission line protection system
DEVICE NO.
87 59, 64 46 87 81 25 38, 49 67 67N 67 21(+) 50/51(+) 50/51 81 46, 49, 51 50/51 25 21 49/50(+) 50/51/79 49, 50/51 79 78, 85 74 47, 60 94 27, 59 79 79 78 37, 50, 76 64 27, 59 21(+) 67 2 94 50BF 87 85 81 46 25 79 27, 59 21, 68 21N, 68 85 87 50/55/27(+) 87 24 67 64 32 21(+) 50/51 27, 59 79 87 21(+)
35 WWW.ELCENEMAN.MIHANBLOG.COM
REFERENCES
U.S. Standards ANSI
1. 2. 3. Y14.15-1996 (R1988) 4. 5. 6. 7.
ANSI/IEEE
100-1992 375-1975 (R1989)
Title
Standard Dictionary of Electrical and Electronic Terms Graphic Symbols for Electrical and Electronic Diagrams Electrical and Electronics Diagrams
Electrical Power System Device Function Relays and Relay Systems Associated with Electric Power Apparatus Guide for Protective Relaying of Utility-Consumer Interconnections Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems
Codes 9. 1993 National Electrical Code NFPA Publication 1993 Books 10. Industrial Power Systems Handbook D.L. Beeman, Editor, McGraw-Hill Book Co., 1955
Standards may be purchased from: American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036 Institute of Electrical and Electronics Engineers, Inc. Service Center 445 Hoes Lane Piscataway, NJ 08855 National Fire Protection Association 1 Batterymarch Park Quincy, MA 02269
Note: IEC Standards may be purchased from the American National Standards Institute.
WWW.ELCENEMAN.MIHANBLOG.COM
36
WWW.ELCENEMAN.MIHANBLOG.COM
TILIN MUL
GE Power Management
INDUSTRIAL GE Multilin EUROPE GEPCE
215 Anderson Avenue Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222
http://www.ge.com/edc/pm GET-8048A
WWW.ELCENEMAN.MIHANBLOG.COM
TCC/MPI - 01.98 - 1000