Ducab Cable
Ducab Cable
Ducab Cable
CONTENTS
Page
Introduction .................................................................................................................................... 1 Customer Service............................................................................................................................ 2-3 Product Range ................................................................................................................................ 4 Specification and Construction ...................................................................................................... 4 5 Salient Features of Ducab Cables Design .................................................................................... 6 Installation and Electrical Data ...................................................................................................... 6 19 XLPE Insulated Cables to BS 5467: Technical Data Tables ........................................................ 20-33
Single Core Cables................................................................................................................ 20-21 Two Core Cables................................................................................................................... 22-23 Three Core Cables................................................................................................................. 24-25 Four Core Cables .................................................................................................................. 26-27 Four Core Cables with Reduced Neutral Conductors........................................................... 28-29 Three and Four Core Armoured Cables................................................................................. 30
1900/3300V rated, Armoured Copper Conductors.................................................................. 31 XLPE insulated Lead Sheathed Armoured Cables to BS 5467............................................... 32-33
Advantages of XLPE Insulated Cables........................................................................................... 34 LSF Cables...................................................................................................................................... 34 XLPE Cable Voltage Drop Data for partial loads........................................................................... 35 Components Reference Chart......................................................................................................... 36-37
Ducab is listed in the following publication issued by the Department of Trade and Industry of the United Kingdom. THE DTI QA REGISTER - PRODUCTS AND SERVICES LIST Only those companies whose quality system is assessed and certified by U.K. accredited certification bodies appear in the above publication.
BICC
INTRODUCTION
Dubai Cable Company (Private) Limited Ducab is a joint venture between the Government of Dubai, the Government of Abu Dhabi. Ducab is located on a site of 54 hectares in Jebel Ali, Dubai, in the United Arab Emirates. A major factory expansion took place in 1991 with production capacity being more than doubled. In 1999, Ducab again increased production capacity for low voltage cables and commissioned a world class production and testing facilities for Ducab Powerplus Medium Voltage cables. In 2001, Ducab installed the second Medium Voltage CCV line. The current factory floor area is 16,000 m2. Ducab manufactures electric cables to the highest quality standards. This catalogue provides working information on Ducabs complete range of XLPE Power Cables rated up to 3.3 kV and also includes data on components. Separate catalogues are available for Ducabs range of Control and Auxiliary Cables, Wiring Cables, Ducab Smokemaster LSF Cables and Ducab Powerplus Medium Voltage Cables. Details of PVC Power Cables are available on request. Due to the wide range of cables in the catalogue, it is advisable, when ordering, to provide as much information as possible. Please use the following table as a guide:
ORDERING ADVICE
The following details will ensure that your enquiries and orders are dealt with quickly and efficiently: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Length of cables required and individual drum lengths.* Voltage designation. Relevant British or International Standard. Number of cores. Conductor size and, where applicable, size of reduced neutral conductor. Conductor material i.e. copper, aluminium. Type of insulation. Type of bedding. Type of armour. Type of outer sheath. Any other special requirement, e.g. circular conductors, special PVC sheath material, drum weight limitation, etc. * Cables are normally supplied in lengths of 300 metres, 500 metres and 1000 metres depending on conductor size. Other lengths can be supplied if required.
BICC
CUSTOMER SERVICE
Dubai Cable Company - Ducab - is the leading cable manufacturer in the United Arab Emirates and, since 1979, has been meeting the requirements of customers throughout the Middle and Far East. Ducabs cables are used by some of the most demanding utilities in the world, for the following reasons:
Product Quality
Ducab is committed to supplying its customers with the highest quality of product and of service. Ducabs Power cables have been type approved by Lloyds Register of the UK and have undergone rigorous type testing by the British Standards Institution (via BASEC) of the UK. They fully conform to BS 6346 and BS 5467 specifications for PVC and XLPE insulated cables respectively, for electricity supply, up to and including 600/1000 V ratings. In addition, Ducab was presented with the Dubai Quality Award 1994, for the best local industrial company of the year. Four years later, Ducab was presented with the Dubai Quality Award 98 Gold Category. The Gold Award rewards the most distinguished companies which are judged to be world class.
Reliability
Specifying the right cable for a particular application is the first step. The key to reliability however, is in the manufacturing process. The cable must be free from material and manufacturing defects, and weaknesses that will be revealed in service. Ducab constantly monitors its manufacturing processes and operates stringent quality assurance procedures to give long term reliability. This is of vital significance where cables are to be installed in locations where future access would be difficult and this is where Ducabs reputation and the resources give peace of mind.
Performance
Optimum cable performance can be provided only by a company such as Ducab, with access to the latest developments in conductor, insulation and protective materials technology. In addition, Ducabs knowledge of application requirements throughout the Middle and Far East is an assurance of high performance. Where required, Ducab can incorporate special features, for example to give the cable low smoke and fume (LSF) or reduced flame propagation characteristics, or to resist damage from chafing or impacts. Our experienced Technical staff can provide guidance on cable selection and installation and can ensure that you get the right cable for the job.
Safety
Ducab is able to maintain a close watch on world developments in cable technology and regulations and therefore ensure that its products are designed and constructed to be hazard-free under the prescribed conditions of use. Ducab uses only tried and tested materials and processes in full compliance with all relevant British and International Standards. Our cables are therefore manufactured for safe use without risk to health on the understanding that users will exercise the same degree of care in their selection and application.
Safety is an important issue for Ducab, and the strictest standards are adhered to throughout the company. Ducab is proud of its safety record and has been awarded RoSPA (Royal Society for the Prevention of Accidents) Gold Awards for safety from 1991 to 1999. In 2000, Ducab was awarded the prestigious Presidents Award for Health and Safety which is a recognition of Ducab winning 10 consecutive annual Gold awards and acknowledges Ducabs total commitment to health and safety. In 2002, Ducab was declared the joint winner of the Manufacturing Industry Sector Award from RoSPA. Ducab is the first organisation in the Middle East to receive accreditation to BS 8800 by the BASEC (British Approvals Service for Cables). Certification to BS 8800 provides a recognisable Occupational Health and Safety Management standard against which an organisations management systems can be assessed and certified. Based on the structure of ISO 14001, the standard requires continual improvement in health and safety related activities.
BICC
BASEC Certification
Ducab is also proud to hold a Product Marketing Licence issued by BASEC (British Approvals Service for Cables) for several cables in its product range.
Customer Satisfaction
Ducabs customer satisfaction programme, The Value Edge is designed to ensure that customers receive a consistently high level of service from Ducabs dedicated staff.
BICC
PRODUCT RANGE
Voltage range: 0.6/1kV and 1.9/3.3 kV Cable Types: 1) Armoured/unarmoured XLPE insulated cables 2) Lead sheathed cables 3) Copper or Aluminium PE tape (with drain wire) shielded Cable sizes: Single core up to and including 1000 mm2 2 core up to and including 300 mm2 3 core up to and including 400 mm2 4 core up to and including 500 mm2 Specification: BS 5467..........................for XLPE insulated armoured cables BS 7889..........................for XLPE insulated single core unarmoured cables IEC 60502 (Part 1) ........for XLPE insulated single/multicore armoured/unarmoured cables Any other International Specification as per VDE/DIN,GOST and as per customers specifications.
INSULATION
The rated voltage level of the cable depends on the dielectric strength and thickness of the insulation. Material: Cross-linked polyethylene (XLPE) Type GP8 as per BS 7655:Section 1.3. Colour Masterbatch: Ultra-violet (UV) resistant polyethylene masterbatch is used for colouring of insulation. This protects the insulation from deterioration when exposed to continuous sunlight.
CORE IDENTIFICATION
Core identification is by colour as follows (unless otherwise agreed): No. of cores Core Colours 1 Red or Black 2 Red and Black 3 Red, Yellow and Blue 4 Red, Yellow, Blue and Black 5 Red, Yellow, Blue, Black and Green/Yellow
FILLERS
For providing circular shape to the cable non-hygroscopic compatible fillers (wherever necessary) are included between laid up cores. METALLIC SCREEN: If required by the customer screening may be provided for electrical shielding. Material: Copper tape Aluminium PE tape along with tinned copper drain wire (for providing screen continuity).
BICC
BARRIER TAPE: Material: Polypropylene/PETP tape is used as a barrier tape over the laid up cores. Functions: Holds the cores together and prevents them from opening out. Works as a separator between different polymers used in a cable. LEAD SHEATH Material: Extruded Lead Alloy E Sheath. Thickness of applied lead sheath is as per EEMUA - 133 (Engineering Equipment and Material Users Association). Function: Protects insulation from corrosion by petroleum products in oil and gas industries.
BEDDING
Extruded bedding serves as a bedding for the armour and as a protection for the laid-up cores. Material: Extruded PVC Type 9 Compound as per BS 7655. Reduced propagation flame retardant (RPLHCL)/RP PVC Compound for reduced flame propagation characteristics. Smokemaster Low smoke and fume for installations where fire hazards exist.
ARMOUR
Armour provides mechanical protection to the cable. It also serves as an Earth Continuity Conductor (ECC). One layer of round wire is applied helically over the bedding. Material: Galvanised round steel wire (GSW). Galvanised round steel wire (GSW) along with tinned copper wires (TCW) for maintaining specified conductivity of armour (if required by the customer). Aluminium round wire armour (AWA) is generally used for single core ac circuits as aluminium is a non-magnetic material and this will reduce losses due to armour. Note: Aluminium glands should be used in conjunction with cables having aluminium wire armour.
OVERSHEATH - FINISH
Following types of materials may be specified for oversheathing. General Purpose: Extruded PVC Type 9 Compound as per BS 7655. Medium Density Polythylene (MDPE): Offers higher protection from water ingress and mechanical abrasion. Anti Termite: Termite resistance can be built in both types described above by compounding with proper additives. Reduced Propagation (RP): Retards propagation of flame in fire situation. (Oxygen Index 30) Reduced Propagation and Low Acid Fumes (RPLHCL): Retards propagation of flames and gives low emission of hydrochloric acid fumes. (OI 30 & acid gas emission is less than 18 %) Smokemaster Low Smoke & Fume (LSF): Smokemaster cables are ideal for installations where the dense black smoke generated by PVC cables in a fire are a danger to people. Smokemaster is characterised by the features as Oxygen Index greater than 35, acid-gas liberation almost nil (<0.5%) and smoke density within controllable limit of 40% smoke density. Smokemaster cables are offered to BS 6724.
BICC
INSTALLATION
Whichever form of conductor is used, XLPE insulated cables are simple to handle, install and joint. All the cables described in this publication can be used indoors or outdoors, but some reservations are necessary concerning cables for direct burial in the ground or for use in sustained wet conditions as follows: (i) Unarmoured cables are not generally recommended for laying directly in the ground.
(ii) Cables laid directly in the ground, particularly in sustained wet conditions, should have extruded bedding and preferably MDPE - Medium Density Polyethylene - as the outersheath material. Other important factors to be taken into account are:
Sheath Damage
Care should be taken to ensure that the oversheath is not damaged during installation. This is especially important where aluminium wire armour is used, as ingress of moisture could lead to corrosion or ultimate loss of earth continuity.
BICC
Table 1
Type of Cable Circular copper conductors armoured or unarmoured Shaped copper or aluminium conductors, armoured or unarmoured For lead sheathed cables Overall Diameter (D) Any Any Any Minimum internal radius of bend 6D 8D 12D
Connectors
The use of compression type connectors is recommended for XLPEinsulated cables since the use of soldered connectors would limit the maximum short circuit temperature of the cable to 160C (and consequently reduce the final short circuit current by approximately 30 per cent).
Overhead terminations
Ultra violet resistant sleeving or taping should be provided on XLPE insulated cores to avoid degradation due to exposure to solar rays.
BICC
CURRENT RATINGS
Current ratings for XLPE insulated cables for groundand ductinstallation are derived from the latest issue of ERA Report 69-30 Part 5 which is based upon IEC Publication 287. The ratings for In Airinstallation are taken from IEE Wiring Regulations, 16th Edition. All the ratings given are for single circuits installed thermally independent of other circuits or any other heat source and on the basis of the standard conditions of installation given in relevant Tables between 18 to 34. For other ambient or ground temperatures, depth of laying, soil thermal resistivity, the rating must be multiplied by relevant rating factors in Tables 2 to 6 and 8 to 12. It should be noted that if XLPE insulated cables, are subjected to operating temperatures appreciably higher than the 90C permissible for continuous operation, the insulation will undergo premature ageing thus affecting the normal life of the cable. However, limiting maximum conductor temperature to 105C during overloads with duration not exceeding 4 hours on any one occasion, or a maximum of 100 hours in any 12 consecutive months, or a total of 500 hours in the cables lifetime, would be tenable.
Protection against overload current: (Clause 433-01-01 of the 16th Edition of the IEE Wiring Regulations)
This states the requirements which effectively determine the sustained current ratios of the cable viz: (i) The current rating of the cable should not be less than the nominal current or current setting of the device providing protection against overload, which in turn should be not less than the circuit current. (ii) The overload protection should operate at not more than 1.45 times the current rating of the cable. The second requirement (ii) is met if the first (i) is met when the protective device is any of the standard fuses or MCBs mentioned in the regulations,except rewirable types of fuse to BS 3036. With fuses to BS 3036 the current ratings of the cable should not be less than 1.38 times the fuse rating to satisfy (ii).
Protection against short circuit: (Clause 434 of the 16th Edition of the IEE Wiring Regulations)
The cable has to have adequate short-circuit capacity for the current let through by the device providing short circuit protection for the time it will flow. The formula in Section 434-03-03 is effectively that used by cable makers to give the short-circuit ratings in their publications. If the device providing protection against short circuit is the same as that providing protection against overload and, therefore, has a rating not higher than the rating of the cables, the short circuit capacity of the cable will automatically be adequate, there is no need to check.
BICC
Protection against indirect contact by interruption of supply: (Clause 412 of the 16th Edition of IEE Wiring Regulations)
Protection against shock due to contact with exposed conductive parts of equipment during a fault to earth is deemed to be provided if disconnection due to flow of the fault current through the protective device will occur, either within 0.4 seconds for final circuits supplying socket outlets. (Table 41A of the 16th Edition of the IEE Wiring Regulations) or within 5 seconds for final circuits supplying fixed equipment. (Clause 413-02-12 of the 16th Edition of the IEE Wiring Regulations) Regulation 413 gives values of earth fault loop impedances which satisfy these conditions when the standard types of protective devices are used. Cables make the major contribution to earth fault loop impedance, but the impedance of the supply external to the installation has to be taken into account. It is not possible to say what maximum length of standard cables may be used in the installation without exceeding the requirements for earth fault loop impedance in the absence of information on the external impedance for the particular installation. Table 16 gives estimated values of the contribution to earth loop impedance by XLPE insulated copper conductor, steel wire armoured cables to BS 5467.
Cross sectional areas of protective conductors: (Clause 543 of the 16th Edition of IEE Wiring Regulations)
Regulation 543 explains how the cross sectional area of the circuit protective conductor should be calculated to avoid it over-heating during a fault to earth. Again the area required depends on the characteristics of the device providing protection against short circuit. The steel wire armour of standard cables to BS 5467 (XLPE) and BS 6346 (PVC) provides the required area, or more, when the protective device is one of the standard fuses or MCBs with a rating not higher than the current rating of the cable (assuming disconnection within 5 seconds). For the most of the cables the armour is still adequate when the fuse rating is one or two steps, or e ven more, above the current rating of the cable, the margins being greater for the small sizes and 4 core cables than for the larger sizes and two core cables.
BICC
VOLTAGE DROP
Voltage drop is normally only of importance for cables of voltage rating 600/1000V or below. If the installation is to be incompliance with Regulation 525 of the 16th Edition of the IEE Wiring Regulations, it is stipulated that the voltage drop within the installation does not exceed a value appropriate to the safe functioning of the associated equipment in normal service. The requirement is deemed to be satisfied if the drop in voltage from the origin of the installation (usually supply terminals) and the fixed current using equipment does not exceed 4 per cent of the nominal voltage of the supply, disregarding starting conditions. (Note: Diversity can be taken into account when calculating voltage drop). Since the actual power factor of the load is often not known, the most practical approach to the question of voltage drop is to assume the worst conditions i.e. where the phase angle of the load is equal to that of the cable. The voltage drop values in the tables have been based on this assumption. For conductor sizes up to and including 120 mm2 the figures provided apply with sufficient accuracy where the power factor lies between 0.6 lagging and 1.0, and for large cables where the power factor of the load does not exceed 0.8 lagging. Where the phase angles of the loads fall outside this range, the voltage drop deduced from the tables may be unduly conservative and more exact methods of calculation should be employed. The values of voltage drop for 600/1000 V rated cables are given in the current rating tables. In those cases where the actual current differs greatly from the tabulated current rating, the results obtained from the tables are only approximate; for a more accurate assessment, allowance should be made for the change in conductor resistance with operating temperature. Refer to page 35 and Table 32 for details. It should also be ensured that the cable size ultimately selected is capable of carrying the required current under the site conditions of installation. Values of voltage drop are tabulated for a current of one ampere for a 1 metre run, i.e. for a distance of 1 metre along the route taken by the cables, and represent the effect of the voltage drop in all the circuit conductors. For balanced three phase ac circuits, the values relate to the line voltage. For any given run the values need to be multiplied by the length of the run (in metres) and by the current (in amperes) that the cables are to carry. Examples: Consider a route of 200 metres of 4 Core armoured cable to be installed in air and to carry 100 amperes load per phase, with the supply voltage being 415 volts, three phase 50 Hz and the cable to be Copper XLPE/SWA/PVC. Using the tables: Let Vd be the voltage drop in volts. Vd = mV x I x L or mV = Vd x 1000 1000 IxL where I = Current in amperes L = Route length in metres mV = Approximate volt drop/ampere/metre Assume maximum permissible volt drop = 4 per cent of 415 volts = 16.6 volts Substitute for current, route length and maximum permissible volt drop then mV = 16.6 x 1000 = 0.83 200 x 100 Select a cable from the relevant Current Rating Table 27 such that the mV value from the voltage drop column is equal to or less than the 0.83 mV calculated, ensuring that it will carry the current. It will be seen that this value is 0.6 giving a cable size of 70mm2. However, 100 Amp load could be less than 80% current carrying capacity of 50mm2 cable, in which case of 50 mm 2 cable will suffice. Note: Please refer to pages 30 and 35 for additional information on voltage drop.
10
BICC
RATING FACTORS
Where the conditions of installation differ from those defined in the current rating tables, the following rating factors may be used for cables size selection.
Table 2
45C
0.76
Table 3
Soil thermal resistivity in C m/W 0.8 1.16 1.17 1.17 0.9 1.12 1.12 1.12 1.0 1.07 1.07 1.07 1.5 0.91 0.91 0.91 2.0 0.81 0.80 0.80 2.5 0.73 0.73 0.73 3.0 0.66 0.66 0.66
Single core cables Up to 150 From 185 to 300 From 400 to 1000 Multicore cables Up to 16 From 25 to 150 From 185 to 500
In ERA Report 69-30 Part III, the types of load are classified under three headings, viz: Type A Cables carrying a constant load throughout the year. Type B Cables carrying varying loads, maximum in summer period. Type C Cables carrying varying loads, maximum in winter period. With knowledge of the type of load to be imposed on the cable it is then possible to determine the soil thermal resistivity along the cable route in accordance with recommendations in ERA Report 69-30.
BICC
11
Rating factors for depth of laying (to centre of cable or trefoil group of cables)
Depth of laying m
0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00 or more
Table 4
1900/3300 Volt
Up to 300mm 2 Above 300mm2
1.00 0.99 0.97 0.95 0.94 0.93 0.92 0.91 0.90 0.89
1.00 0.97 0.94 0.92 0.89 0.87 0.86 0.85 0.84 0.82
Group rating factors for circuits of three single core cables in trefoil or laid flat touching, in horizontal formation
Table 5
SPACING
SPACING
Number of Circuits Touching + Trefoil 2 3 4 5 6 2 3 4 5 6 0.78 0.66 0.61 0.56 0.53 0.78 0.66 0.59 0.55 0.52 Laid flat 0.81 0.70 0.64 0.60 0.57 0.80 0.68 0.62 0.58 0.55
Spacing of Circuits
0.15 m* 0.83 0.73 0.68 0.64 0.61 0.82 0.71 0.65 0.61 0.58
0.30 m 0.88 0.79 0.73 0.73 0.71 0.86 0.77 0.72 0.68 0.66
0.545 m 0.91 0.84 0.81 0.79 0.78 0.89 0.80 0.77 0.74 0.72
0.60 m 0.93 0.87 0.85 0.85 0.82 0.91 0.83 0.80 0.78 0.76
* +
This spacing will not be possible for some of the larger diameter cables. For high current carrying cables (i.e. large size) it is advisable to allow spacing between circuits. Alternatively the most appropriate group rating factor must be applied when determining the cable size and required number of cables in parallel.
12
BICC
Table 6
SPACING
Number of Cables in Group Spacing Touching+ 2 3 4 5 6 2 3 4 5 6 0.81 0.70 0.63 0.59 0.55 0.80 0.68 0.62 0.57 0.54 0.15 m 0.87 0.78 0.74 0.70 0.68 0.85 0.76 0.71 0.66 0.64 0.30 m 0.91 0.84 0.81 0.78 0.77 0.89 0.81 0.77 0.73 0.71 0.45 m 0.93 0.88 0.86 0.84 0.83 0.91 0.84 0.81 0.78 0.77 0.60 m 0.95 0.90 0.89 0.87 0.87 0.93 0.87 0.84 0.82 0.81
For high current carrying cables (i.e. large size) it is advisable to allow spacing between circuits. Alternatively the most appropriate group rating factor must be applied when determining the cable size and required number of cables in parallel.
Table 7
Ratings for cables installed in single way ducts, underground, have been based on values of soil temperature and soil thermal resistivity which are generally representative of conditions in the United Kingdom. Rating factors to take account of variations in ground temperatures are given in Table 3. Where conditions of operation can be fairly accurately estimated, and knowledge of the soil along the route is available, it is possible to determine the ratings more precisely by the use of estimated maximum ground temperature, the soil thermal resistivity factors, grouping factors, and factors for the depths of laying given in Tables 8 to 11.
BICC
13
Table 8
Rating factors of depth of laying (to centre of duct or trefoil group of ducts)
Depth in laying m 0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00 or more Single Core 1.00 0.98 0.95 0.93 0.91 0.89 0.88 0.87 0.86 0.85 600/1000 Volt Multicore 1.00 0.99 0.98 0.96 0.95 0.94 0.94 0.93 0.92 0.91 1900/3300 Volt Single Core 1.00 0.98 0.95 0.93 0.92 0.90 0.89 0.88
Table 9
Group rating factors for single core cables in trefoil single way ducts, horizontal formation (average values)
Number of Circuits
SPACING
Table 10
Spacing Touching + 2 3 4 5 6 2 3 4 5 6 0.87 0.78 0.74 0.70 0.69 0.85 0.75 0.70 0.67 0.64 0.45 m 0.91 0.84 0.81 0.79 0.78 0.88 0.80 0.77 0.74 0.72 0.60 m 0.93 0.87 0.85 0.83 0.82 0.90 0.83 0.80 0.78 0.76
For high current carrying cables (i.e. large size) it is advisable to allow spacing between circuits. Alternatively the most appropriate group rating factor must be applied when determining the cable size and required number of cables in parallel.
14
BICC
Group rating factors for multicore cables in single way ducts, horizontal formation (average values)
Table 11
Number of Ducts in Ground Touching + 2 3 4 5 6 2 3 4 5 6 0.90 0.83 0.79 0.75 0.73 0.88 0.80 0.76 0.72 0.69 0.30 m 0.93 0.88 0.85 0.83 0.82 0.91 0.85 0.81 0.78 0.76
SPACING
Spacing 0.45 m 0.95 0.91 0.89 0.88 0.87 0.93 0.88 0.85 0.83 0.81 0.60 m 0.96 0.93 0.92 0.91 0.90 0.94 0.90 0.88 0.86 0.85
For high current carrying cables (i.e. large size) it is advisable to allow spacing between circuits. Alternatively the most appropriate group rating factor must be applied when determining the cable size and required number of cables in parallel.
Table 12
55C 0.76
BICC
15
Copper Conductors
0.5
0.1
The values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 90C) and a final conductor temperature of 250 C. It should be ensured that the accessories associated with the cables are also capable of operation at these values of fault current and temperature.
Aluminium Conductors
Note: With XLPE cables the use of soldered type connectors (instead of the compression type) is not recommended since their use in the system would limit the final conductor temperature to 160 C (and consequently reduce the fault current rating by approximately 30 per cent).
16
BICC
Table 14
1900/3300 V Three Core amp XLPE 3700 4200 4700 5600 6200 6900 9400 10100 10800 11900 13000 -
Based on wire diameters larger than those specified in BS 5467. Refer to Table 17, 33 and 35 for single core cable armour wire diameter 1. The ratings given in the Table above are based on a fault duration of one second and an armour temperature rise from 80C at commencement of the fault to a final temperature of 200C. The asymmetrical fault rating of the smaller sizes may be decided by the short circuit capability of the conductor rather than the armour rating. It is therefore necessary to compare the two ratings.
Notes:
2.
BICC
17
18
BICC
600/1000 V
Contribution by cable to earth fault loop impedance milli ohms/metre 2 core 6.67 5.87 4.02 3.55 2.98 2.11 3 core 6.42 4.35 3.77 3.17 2.73 1.98 1.79 1.23 1.10 0.97 0.89 4 core 5.91 4.10 3.39 2.92 1.98 1.73 1.25 1.10 0.98 0.86 0.78 0.60
Table 16
Note: For information on maximum length of cable that meets the earth fault loop impedance requirement for 5 second disconnection, refer to Ducabs Technical Department.
BICC
19
600/1000 V
Nominal area of conductor mm2 50 70 95 120 150 185 240 300 400 500 630 800 1000
Table 17
Cable weight Copper kg/km 800 990 1280 1550 1900 2320 2930 3580 4600 5680 7160 9315 11490
Thickness of insulation mm 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8
Single core unarmoured cables are as per BS 7889. * Wire diameters are larger than those specified in BS 5467. Aluminium wire armour for AC system.
20
BICC
CURRENT RATINGS (AC) STRANDED COPPER & ALUMINIUM CONDUCTORS SINGLE CORE CABLES
600/1000 V
Table 18
Approximate voltage drop per ampere per metre
3D
mm
Direct in ground amps 235 290 345 390 435 490 560 630 700 770 840 888 942
In single way ducts amps 235 280 330 370 405 440 500 550 580 620 670 692 735
Installed in air amps 222 285 346 402 463 529 625 720 815 918 1027 1119 1214
Ground mV 0.87 0.62 0.47 0.39 0.33 0.28 0.24 0.21 0.20 0.18 0.17 0.17 0.16
Duct mV 0.93 0.70 0.56 0.48 0.43 0.39 0.35 0.32 0.30 0.28 0.26 0.25 0.24
Air mV 0.87 0.62 0.47 0.39 0.33 0.28 0.24 0.21 0.20 0.18 0.17 0.17 0.16
Direct in ground amps 175 220 260 295 330 375 435 490 540 580 630
In single way ducts amps 180 220 260 295 330 365 410 455 480 510 540
Ground mV 1.40 0.98 0.72 0.58 0.48 0.39 0.31 0.27 0.35 0.31 0.28
Duct mV 1.60 1.00 0.79 0.66 0.57 0.49 0.42 0.38 0.38 0.35 0.32
Air mV 1.40 0.98 0.74 0.60 0.49 0.41 0.34 0.29 0.25 0.22 0.20
50 70 95 120 150 185 240 300 400 500 630 800 1000
Installed in air amps 162 207 252 292 337 391 465 540 625 714 801
600/1000 V
Table 19
Approximate voltage drop per ampere per metre Ground mV 1.40 0.98 0.71 0.57 0.47 0.39 0.31 0.26 0.36 0.33 0.28 Duct mV 1.50 1.10 0.79 0.66 0.57 0.49 0.42 0.38 0.38 0.35 0.32 Air mV 1.45 0.98 0.73 0.59 0.47 0.39 0.32 0.27 0.23 0.20 0.19
Aluminium Conductors
Current Ratings
mm2
50 70 95 120 150 185 240 300 400 500 630 800 1000
Direct in ground amps 230 285 335 385 435 490 570 650 740 840 960 1120 1300
In single way ducts amps 240 295 345 395 445 500 580 650 750 850 960 1130 1320
Ground mV 0.85 0.61 0.45 0.36 0.31 0.26 0.22 0.19 0.17 0.16 0.15 0.15 0.14
Duct mV 0.93 0.70 0.56 0.48 0.43 0.39 0.35 0.32 0.30 0.28 0.26 0.25 0.24
Air mV 0.87 0.61 0.45 0.37 0.31 0.26 0.22 0.20 0.18 0.16 0.15 0.15 0.14
Installed in air amps 209 270 330 385 445 511 606 701 820 936 1069 1214 1349
Direct in ground amps 175 215 255 295 325 370 430 490 550 620 690
In single way ducts amps 180 220 260 300 335 375 440 510 570 640 730
3D
Installed in air amps 159 206 253 296 343 395 471 544 638 743 849
Direct in ground Trefoil touching Single way ducts - ducts touching Spacing in air - As shown above (D = Cable diameter)
Installation conditions for above ratings: Ambient air temperature:30C Ground temperature: 15C Depth of laying:0.5 m Soil thermal resistivity: 1.2C m/W Maximum conductor operating temperature at rated current is 90C For rating factors see Tables 2 to 6 and 8 to 12
BICC
21
600/1000 V
Nominal area of conductor mm2 16* 25* 35* 50 70 95 120 150 185 240 300 Thickness of insulation mm 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8
Table 20
Cable weight Copper kg/km 900 1240 1710 1800 2320 3150 3880 4820 5920 7300 8770
415 480 497 690 850 1170 1450 1810 2280 2760
915 1255 1430 1780 1950 2440 3050 3690 4380 5100
* Circular conductor, all others are sector shaped Note: Unarmoured cables are as per IEC 60502 (Part 1)
22
BICC
CURRENT RATINGS (AC) STRANDED COPPER & ALUMINIUM CONDUCTORS TWO CORE CABLES
600/1000 V
Table 21
Approximate voltage drop per ampere per metre
Aluminium Conductors
Current Ratings In single way ducts amps 110 130 155 195 237 Installed in air amps 112 138 166 211 254
Nominal area of conductor mm2 16* 25* 35* 50 70 95 120 150 185 240 300
Direct in ground amps 140 180 215 255 315 381 410 472 539 636 732
In single way ducts amps 115 145 175 210 260 313 344 384 432 504 560
Installed in air amps 115 152 188 228 291 354 430 480 540 630 700
600/1000 V
Table 22
Approximate voltage drop per ampere per metre
Aluminium Conductors
Current Ratings In single way ducts amps 105 130 150 195 235 Installed in air amps 108 135 164 211 257
Nominal area of conductor mm2 16* 25* 35* 50 70 95 120 150 185 240 300
Direct in ground amps 140 180 215 255 315 380 410 473 542 641 741
In single way ducts amps 115 140 170 205 255 311 344 384 432 504 560
Installed in air amps 115 149 185 225 289 352 430 480 540 630 700
Direct in ground Cables touching Single way ducts - ducts touching * Circular conductors, all others are sector shaped Note: (1) 50 mm2 and above are with D-shaped conductor (2) Unarmoured cables are as per IEC:60502 (part 1)
Installation conditions for above ratings: Ambient air temperature:30C Ground temperature: 15C Depth of laying:0.5 m Soil thermal resistivity: 1.2C m/W Maximum conductor operating temperature at rated current is 90C For rating factors see Tables 2 to 6 and 8 to 12
BICC
23
600/1000 V
Nominal area of conductor mm2 16* 25* 35* 50 70 95 120 150 185 240 300 400 Thickness of insulation mm 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
Table 23
Cable weight Copper kg/km 1130 1710 2100 2450 3120 4310 5160 7160 8600 10755 13080 15810
* Circular conductors, all others are sector shaped. Note: Unarmoured cables are as per IEC 60502 (Part 1)
24
BICC
CURRENT RATINGS (AC) STRANDED COPPER & ALUMINIUM CONDUCTORS THREE CORE CABLES
600/1000 V
Table 24
Approximate voltage drop per ampere per metre
Nominal area of conductor mm2 16 25 35 50 70 95 120 150 185 240 300 400
Direct in ground amps 115 150 180 215 265 315 360 405 460 530 590 667
In single way ducts amps 94 125 150 175 215 260 300 335 380 440 495 570
Installed in air amps 99 131 162 197 251 304 353 406 463 546 628 728
Ground mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2
Duct mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2
Air mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2
600/1000 V
Table 25
Approximate voltage drop per ampere per metre Ground mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 Duct mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 Air mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2
Nominal area of conductor mm2 16 25 35 50 70 95 120 150 185 240 300 400
Direct in ground amps 120 145 180 215 265 315 365 405 465 540 600 675
In single way ducts amps 93 125 145 175 215 255 300 330 380 440 500 575
Direct in ground Cables touching Single way ducts - ducts touching Note: Unarmoured cables are as per IEC 60502 (Part 1)
Installation conditions for above ratings: Ambient air temperature:30C Ground temperature: 15C Depth of laying:0.5 m Soil thermal resistivity: 1.2C m/W Maximum conductor operating temperature at rated current is 90C For rating factors see Tables 2 to 6 and 8 to 12
BICC
25
600/1000 V
Nominal area of conductor mm2 16* 25 35 50 70 95 120 150 185 240 300 400 500# Thickness of insulation mm 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2
Table 26
Cable weight Copper kg/km 1320 1840 2310 2970 4240 5400 7000 8350 10130 12840 15530 19950 24360
* Circular conductors, all others are sector shaped. # Cable as per IEC 60502 (Part 1) Note: Unarmoured cables are as per IEC 60502 (Part 1)
26
BICC
CURRENT RATINGS (AC) STRANDED COPPER & ALUMINIUM CONDUCTORS FOUR CORE CABLES
600/1000 V
Table 27
Approximate voltage drop per ampere per metre
Nominal area of conductor mm2 16 25 35 50 70 95 120 150 185 240 300 400 500
Direct in ground amps 115 150 180 215 265 315 360 405 460 530 590 667 720
In single way ducts amps 94 125 150 175 215 260 300 335 380 440 495 570 605
Installed in air amps 99 131 162 197 251 304 353 406 463 546 628 728 800
Ground mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
Duct mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
Air mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
600/1000 V
Table 28
Approximate voltage drop per ampere per metre
Aluminium Conductors
Current Ratings In single way ducts amps 72 92 110 135 165 195 225 255 290 340 385 443 470 Installed in air amps 74 97 120 146 187 227 263 304 347 409 471 570 626
Nominal area of conductor mm2 16 25 35 50 70 95 120 150 185 240 300 400 500
Direct in ground amps 120 145 180 215 265 315 365 405 465 540 600 675 730
In single way ducts amps 93 125 145 175 215 255 300 330 380 440 500 575 610
Ground mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
Duct mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
Air mV 4.2 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
Direct in ground Cables touching Single way ducts - ducts touching Note: Unarmoured cables are as per IEC 60502 (Part 1)
Installation conditions for above ratings: Ambient air temperature: 30C Ground temperature: 15C Depth of laying: 0.5 m Soil thermal resistivity: 1.2C m/W Maximum conductor operating temperature at rated current is 90C For rating factors see Tables 2 to 6 and 8 to 12
BICC
27
STRANDED COPPER & ALUMINIUM CONDUCTORS FOUR CORE CABLES WITH REDUCED NEUTRAL CONDUCTOR
600/1000 V
Nominal area of conductor mm2 25 35 50 70 95 120 150 185 240 300 400 500#
Table 29
Cable weight Copper kg/km 1750 2130 2770 3870 4910 6060 7610 9150 11620 13980 18250 22000
Nominal Thickness of area of insulation neutral (phase) conductor mm mm2 16* 16* 25* 35 50 70 70* 95 120* 150* 185* 240* 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2
* Circular stranded conductors, all others are sector shaped. # Cable as per IEC 60502 (Part 1) Note: Unarmoured cables are as per IEC 60502 (Part 1)
28
BICC
CURRENT RATINGS (AC) STRANDED COPPER & ALUMINIUM CONDUCTORS FOUR CORE CABLES WITH REDUCED NEUTRAL CONDUCTOR
600/1000 V
Nominal Nominal area of area of conductor neutral conductor
Table 30
Approximate voltage drop per ampere per metre
Ground
Duct
Air
mV 1.7 1.2 0.9 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.2 0.2
mV 1.7 1.2 0.9 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.2 0.2
mV 1.7 1.2 0.9 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.2 0.2
mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
600/1000 V
Table 31
Approximate voltage drop per ampere per metre Ground Duct Air
Nominal Nominal area of area of Current Ratings conductor neutral conductor Direct in In single Installed ground way ducts in air mm2 25 35 50 70 95 120 150 185 240 300 400 500 mm2 16* 16* 25* 35 50 70 70* 95 120* 150* 185* 240* amps 145 180 215 265 315 365 405 465 540 600 675 730 amps 125 145 175 215 255 300 330 380 440 500 575 610 amps 127 158 192 246 298 346 399 456 538 621 741 814
mV 1.7 1.2 0.9 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.2 0.2
mV 1.7 1.2 0.9 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.2 0.2
mV 1.7 1.2 0.9 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.2 0.2
mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
mV 2.7 1.9 1.4 1.0 0.7 0.6 0.5 0.4 0.3 0.3 0.2 0.2
Direct in ground Cables touching Single way ducts - ducts touching * Circular conductors, all others are sector shaped Note: Unarmoured cables are as per IEC 60502 (Part 1)
Installation conditions for above ratings: Ambient air temperature:30C Ground temperature: 15C Depth of laying:0.5 m Soil thermal resistivity: 1.2C m/W Maximum conductor operating temperature at rated current is 90C For rating factors see Tables 2 to 6 and 8 to 12
BICC
29
STRANDED COPPER CONDUCTORS Three and four core armoured, PVC sheathed cables
Conductor Current Voltage Current size in air drop in ground mm2 A mV/A/m A 251 240 230 220 210 195 185 170 150 0.607 0.599 0.589 0.580 0.572 0.562 0.554 0.545 0.536 265 260 250 245 235 225 215 205 195
Table 32
Conductor Current Voltage Current in air drop in ground size mm2 A mV/A/m A 99 97 93 89 84 80 74 68 62 2.50 2.50 2.47 2.43 2.39 2.35 2.31 2.27 2.23 115 112 110 105 100 97 94 89 84
Conductor Current Voltage Current size in air drop in ground mm2 A mV/A/m A 463 450 430 415 395 370 345 320 290 0.255 0.252 0.249 0.246 0.243 0.240 0.237 0.235 0.232 460 450 435 420 405 390 375 355 335
16
70
185
25
95
240
35
162 155 150 145 135 130 120 110 100 197 190 180 175 165 155 145 135 120
120
300
50
150
400
Installation conditions for above ratings: Ambient temperature:30C Ground Temperature: 15C 30
BICC
Table 33
Nominal Thickness area of of conductor insulation 2 mm mm 50 70 95 120 150 185 240 300 400 500 630 800 1000 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.2 2.4 2.6 2.8
Diameter under armour mm 15.0 16.6 18.4 19.8 21.2 23.0 25.5 27.7 31.0 36.0 40.0 45.8 50.8
Armour^ wire diameter mm 1.6* 1.6* 1.6* 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5
Cable diameter overall mm 29.3 32.2 34.8 34.7 38.0 41.4 45.7 48.5 51.9 56.9 61.2 -
Cable weight copper kg/km 1600 2060 2400 3200 3800 4730 6070 7010 8270 10310 12300 -
CURRENT RATINGS
1900/3300 V
Nominal area of conductor mm2 50 70 95 120 150 185 240 300 400 500 630 800 1000 Direct in ground amps 222 271 324 366 409 460 528 589 651 720 789 831 880
Table 34
Installed in air amps 106 142 168 202 255 312 361 410 471 554 634 -
Direct in ground Trefoil touching Single way ducts - ducts touching Spacing in air - As shown above (D=Cable diameter) *Wire diameters are larger than those specified in BS 5467 ^Aluminium wire armour for AC system
Installation conditions for above ratings: Ambient air temperature: 30C Ground temperature: 15C Depth of laying: 0.5 m Soil thermal resistivity: 1.2C m/W Maximum conductor operating temperature at rated current is 90C For rating factors see Tables 2 to 6 and 8 to 12
BICC
31
Table 35
Approximate diameter Nominal lead sheath thickness mm
1.1 1.1 1.1 1.2 1.2 1.3 1.4 1.4 1.6 1.7 1.8 2.0 2.1 1.1 1.2 1.3 1.2 1.3 1.4 1.4 1.5 1.6 1.8 1.9 1.1 1.2 1.3 1.3 1.4 1.5 1.6 1.7 1.9 2.0 2.2 2.3 1.2 1.2 1.3 1.4 1.5 1.6 1.7 1.9 2.0 2.2 2.3 2.5
Over lead mm
13.0 15.0 16.8 18.5 20.5 22.8 25.5 28.1 32.3 37.0 40.8 47.5 52.5 15.5 18.9 21.3 19.0 22.2 24.8 27.2 30.3 33.7 38.9 42.9 16.5 20.5 23.0 24.0 26.5 30.5 33.5 37.8 42.8 48.2 52.2 57.8 18.8 20.5 23.2 26.2 30.5 34.8 37.8 43.2 47.8 53.8 58.5 65.9
Armour Wire mm
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2..0 2.0 2.5 2.5 1.25 1.25 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 1.25 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.15
Overall cable mm
20.8 22.6 24.5 26.2 28.5 30.8 33.5 36.4 41.8 46.6 50.8 59.2 64.2 21.8 25.5 29.4 27.2 30.5 34.5 37.8 41.1 46.3 51.7 56.3 23.0 28.6 31.2 32.0 35.0 40.5 43.5 49.4 54.5 60.2 65.2 71.8 25.5 28.5 31.3 34.6 40.5 44.8 49.8 55.0 60.0 66.5 72.5 82.6
* Cable with 1.6mm wire armour, a deviation from BS 5467. Tolerance on the above dimensions are -0.3mm and +0.5mm. Cable sizes marked + and higher have sector shaped conductors.
Lead sheath thicknesses are nominal values based on EEMUA 133. For 2 core cables, 50 mm2 and above have D-shaped conductors.
32
BICC
Table 36 Lead Sheathed Armoured Power Cables to BS 5467 and EEMUA 133
Nominal area of conductor mm2 16 25 35 50+ 70 95 120 150 185 240 300 Approximate diameter Nominal lead sheath thickness mm 1.3 1.4 1.5 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.2 Over lead mm 22.9 26.1 28.6 29.8 31.1 32.7 38.0 39.8 43.8 48.9 53.3 Armour Wire mm 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 Overall cable mm 31.8 34.9 37.6 40.2 41.7 43.5 50.4 52.7 56.6 62.3 66.9 Approx. weight kg/km 2750 3412 4045 4822 5560 6582 8440 9540 11272 13819 16456
Table 37 Lead Sheathed Armoured Power Cables to BS 5467 and EEMUA 133
Maximum Resistance (ohms) per 1000 metres of cable at 20C 600/1000 V Single core Lead Armour 8.14 6.63 6.01 5.24 4.56 4.07 3.30 3.03 2.48 2.03 1.86 1.41 1.16 0.98 0.76 0.65 0.62 0.54 0.50 0.47 0.42 0.39 0.35 0.32 0.29 0.26 0.24 0.17 0.15 0.13 0.09 0.08 Two core Lead Armour 8.98 7.56 6.37 5.85 4.91 4.29 3.21 2.60 3.19 2.52 2.10 1.89 1.58 1.33 1.02 0.87 6.21 5.51 4.88 4.59 4.01 3.10 2.64 1.69 1.88 1.64 1.14 1.04 0.95 0.69 0.61 0.55 Three core Lead Armour 8.54 7.09 6.27 5.40 4.71 4.11 2.96 2.41 2.37 1.95 1.60 1.32 1.13 0.89 0.76 0.62 0.53 5.96 5.26 4.81 4.31 2.93 2.64 1.58 1.42 1.40 1.27 0.87 0.78 0.58 0.52 0.47 0.42 0.39 Four core Lead Armour 7.72 6.29 5.41 4.91 4.10 3.31 2.93 2.38 1.96 1.59 1.30 1.11 0.88 0.75 0.61 0.53 0.43 5.59 4.84 4.31 3.02 2.63 2.36 1.57 1.41 1.27 0.87 0.77 0.57 0.51 0.47 0.42 0.38 0.26 1900/3300 V Three core Lead Armour 2.42 1.97 1.68 1.61 1.54 1.37 1.10 1.00 0.86 0.73 0.61 0.53 1.37 1.22 1.13 0.84 0.81 0.77 0.54 0.52 0.48 0.43 0.40 0.37 -
Nominal area of conductor mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
Note: Single core cables with Aluminium Wire Armour and Multicore cables with Steel Wire Armour
BICC
33
LSF CABLES
Ducab can manufacture a dedicated cable called LSF (Low Smoke and Fume) for installations where fire and its associated problems - the emission of smoke and toxic fumes - offer a serious potential threat. LSF compound is free from halogens (fluorine, chlorine and bromine) and when tested to BS 6425 Part 1 and IEC 754 Part 1 the acidic gas evolved during combustion is less than 0.5% by weight of material. Furthermore, when tested in accordance with BS 2782 Method 141D, the oxygen index of both bedding and sheath will not be less than 30. These cables comply with BS 6724 and also meet the requirements of IEC 332 Part 3. LSF Cable:
is slow to ignite,burns slowly and gives off reduced smoke and fumes which can kill people does not produce corrosive halogen acid gases which destroy sensitive electronic equipment helps people to escape from a fire - helps them to see and to breathe for longer wins time for people to escape and for emergency services to help is essential in public buildings, transport or confined areas where larger numbers of people - many of them strangers to the surroundings or infirm - regularly congregate Some of the key benefits of LSF cables are as follows:
... to the Public much improved safety margins to help them survive a fire situation in enclosed areas or high population, high-tech commercial offices in which they might work or visit ... to the Specifier enhanced fire damage protection for both structure and sensitive electronic equipment demonstrates proper concern for public and environmental safety ... to the Contractor
no loss of versatility can be installed wherever conventional cables would be used and are compatible with standard accessories
34
BICC
BICC
35
36
BICC
BICC
37