Tecumseh Service Handbook
Tecumseh Service Handbook
Tecumseh Service Handbook
Service Handbook
Service Handbook
Hermetic Compressor
REV 3/11
1 2 2 2 4 4 4 5 6 7 7 8 9 10 11 12 13 15 16 17 19 21 24 26 26
Table of Contents
Servicing
Introduction to Servicing Think Safety... Before Servicing Servicing or Troubleshooting Water-utilizing Systems: Preventing Explosions Troubleshooting Chart Installation and Replacement Compressor Tube Connections Refrigerant Line Sizes Service Valves Processing the System System Cleanup and Compressor Replacement After Compressor Failure Replacing Compressors in Water-Utilizing Systems: Preventing Explosions 29 31 31 31 32 34 73 74 76 82 82 83 87 89 90 93 94 95 98 99 101 102 104 105 106 108 110
Operation
Control of Liquid Migration to the Compressor During Shutdown Crankcase Heaters Starting a System with Liquid Refrigerant in the Compressor Control of Liquid Refrigerant Floodback to the Compressor During Operation Accumulator Selection Internal Pressure Relief Valves
Appendix
The Basic Refrigeration Cycle Example of a Tecumseh Hermetic Compressor Reciprocating Compressor Capillary Tube Sizing Approved Hermetic Compressor Oils Notes
SERVICE HANDBOOK
Introduction
Tecumseh Products Company has prepared this handbook to assist service personnel in safely working with refrigeration and air conditioning equipment that uses Tecumseh Products Company hermetic compressors. It is not designed to replace the training required for professional service personnel. It is also not intended to replace other information available from refrigeration and air conditioning equipment manufacturers.
3
fault. Mark and red tag the compressor to indicate that there is a ground fault. Do not reconnect the power leads. Tape and insulate each power lead separately. Disconnect power before servicing. Always disconnect power before servicing unless it is required for a specific troubleshooting technique. In these situations, use extreme caution to avoid electric shock.
FIGURE 1-1: Compressor with (1) protective cover and (2) bale strap removed to show (3) hermetic terminal.
FIGURE 1-4: Compressor with (1) protective cover held in place by (2) metal bale strap.
FIGURE 1-2: Close up view of hermetic terminal showing individual terminal pins with power leads removed.
FIGURE 1-5: Compressor with (1) protective cover held in place by (2) nut.
SERVICE HANDBOOK
Compressor Removal
Failure to properly remove the compressor can result in serious injury or death from electrocution, fire, or sudden release of refrigerant and oil. Follow these precautions when removing a compressor from a system: Disconnect ALL electrical power. Disconnect all electrical power supplies to the system making sure that all power legs are open. (NOTE: the system may have more than one power supply.) Be sure refrigerant is recovered before removing compressor. Attempting to remove the compressor before removing all refrigerant from the system can cause a sudden release of refrigerant and oil. Among other things, this can: cause a variety of injuries including burns and frostbite. cause a fire if a torch is used to disconnect tubing. expose the service person to toxic gas. To avoid serious injury or death, be sure to remove and recover all refrigerant before removing the compressor. Use a tubing cutter, not a torch. Use a tubing cutter to remove the compressor. A torch can cause even trace amounts of refrigerant to decompose and release toxic fumes. In addition, using a torch to remove the compressor can cause a fire. If you ignore this recommendation and use a torch, be prepared to extinguish a fire.
5
Use a pressure regulating valve and pressure gauges. Commercial cylinders of nitrogen contain pressures in excess of 2000 psig at 70F. At pressures much lower than 2000 psig, compressors can explode and cause serious injury or death. To avoid over pressurizing the system, always use a pressure-regulating valve on the nitrogen cylinder discharge (see Figure 1-7). The pressure regulator must be able to reduce the pressure down to 1 or 2 psig and maintain this pressure. The regulating valve must be equipped with two pressure gauges: one gauge to measure cylinder pressure, and one gauge to measure discharge or downstream pressure. Use a pressure relief valve. In addition to a pressure regulating valve and gauges, always install a pressure relief valve. This can also be a frangible disc type pressure relief device. This device should have a discharge port of at least MPT size. The valve or frangible disc device must be set to release at 175 psig (see Figure 1-7). Do not pressurize the system beyond 150 psig field leak test pressure. When field testing a system for leaks, 150 psig is adequate test pressure. Disconnect nitrogen cylinder and evacuate the system before connecting the refrigerant container. Disconnect the nitrogen cylinder and evacuate the system according to the equipment manufacturer's recommendations prior to charging the system.
System Charging
Failure to properly charge the system can result in serious injury or death from explosion or fire. Follow these precautions when charging a system: Do not operate the compressor without charge in the system. Operating the compressor without a charge in the system can damage the hermetic terminal. As always, to avoid serious injury or death from terminal venting with ignition, never energize the compressor unless the protective terminal cover is securely fastened. Use proper refrigerant.
Gauges
To System
Use only the serial label refrigerant when charging the system. Using a different refrigerant can lead to excess system pressure and an explosion. Use of a refrigerant other than the serial label refrigerant will void the compressor warranty. Do not overcharge a refrigeration or air conditioning system.
Dry nitrogen cylinder with attached pressure gauges needed for pressure testing for leaks and purging.
FIGURE 1-7
Overcharging a refrigeration or air conditioning system can result in explosion. To avoid serious injury or death, never overcharge the system. Always use proper charging techniques. Limit charge amounts to those specified on the system equipment serial label or in the original equipment manufacturers service information. Overcharging the system immerses the compressor motor, piston, connecting rods, and cylinders in liquid refrigerant. This creates a hydraulic block preventing the compressor from starting. The hydraulic block is also known as locked rotor. Continued supply of electricity to the system causes heat to build in the compressor. This heat will eventually vaporize the refrigerant and rapidly increase system pressure. If, for any reason, the thermal protector fails to open the electrical circuit, system pressure can rise to high enough levels to cause a compressor housing explosion.
SERVICE HANDBOOK
Service Procedures
In light of the risk of explosion, be especially alert for signs of water leaking into the refrigerant side of the system. Whenever servicing or troubleshooting a water-utilizing system, always check to see if it has either a pressure relief valve or a high-pressure cutout as previously described. If the system does not have at least one of these, DISCONNECT ALL ELECTRICAL POWER and look for indications that water has leaked into the refrigerant side of the system. These indications may include: Observation or a report of a blown fuse or tripped circuit breaker. Signs that water has leaked to the outside of the system. Reports that the system has made gurgling or percolating noises. A history of loss of refrigerant charge without a leak being found in the system. NOTE: Common leak detection methods will not detect a water-to-refrigerant leak in the systems heat exchanger(s). Observation of or a report of the compressor giving off an unusual amount of heat. If ANY of these indications are present, do the following checks to determine if water has leaked into the refrigerant side: Step 1: Check for a Ground Fault (a Short to Ground) Use only a megohmmeter (megger) or a Hi-Potential Ground tester (Hi-Pot) to check for a ground fault. A conventional ohmmeter will not reliably detect a ground fault under certain circumstances. To check for a ground fault, use the procedure outlined on pages 40-41. If a ground fault does not exist, go to Step 2. If a ground fault does exist, keep the power off.
7
WARNING! To avoid electric shock, electrocution and terminal venting with ignition, do not energize a compressor that has a ground fault. Mark and red tag the compressor to indicate that there is a ground fault. Do not reconnect the power leads. Tape and insulate each power lead separately. Proceed to Step 2. Do not replace the compressor or energize the system before performing Step 2. Step 2: Check for Water in the System Once the compressor is cool to the touch, open the system process valve slightly to see if any water comes out of the system. WARNING! Opening the system process valve while the compressor is hot can cause severe burns from steam coming out of the valve. If ANY water comes out of the process valve, the entire system must be replaced. See "replacing a Single-wall Water-utilizing System below. If water does not come out of the process valve, there is still a possibility that some water has leaked into the refrigerant side of the system. To address this possibility, determine if the system has a history of losing refrigerant charge without a leak being found or repaired. If you find ANY indication of a history of losing refrigerant charge without detection of a leak, this is a sign that refrigerant has leaked in the water inside the heat exchanger. The entire system must be replaced. See Replacing a Single-wall Water-utilizing System on page 33. If you do not find any indication of a history of loss of charge without detection of a leak, you still need to install: a high-pressure cut-out which interrupts power to ALL leads to the compressor, or an external pressure relief valve. Also, if you found a ground fault in the compressor in Step 1, replace the compressor before applying power to the system.
System Evacuation
Never use a compressor to evacuate a system. Instead, use a high-vacuum pump specifically designed for that purpose. Never start the compressor while it is under deep vacuum. Always break a vacuum with a minimum 2 psig refrigerant charge before energizing the compressor. The compressor is cooled primarily by the flow of refrigerant. Running a system that is low on charge will reduce the life of the comperssor. Failure to follow these instructions can damage the hermetic terminal. As always, to avoid serious injury or death from terminal venting with ignition, never energize the compressor unless the protective terminal cover is securely fastened.
10
SERVICE HANDBOOK
A
Release Variant (Generation)
4
Application
4
Number of Digits in Rated BTU Capacity
40
First Two Digits of Rated BTU Capacity
Y
Refrigerant
XA
Voltage
XC
Condensing Units
AE AG AH AJ AK AN AV AW AZ HG RG RK RN SA SF TP TH TW VS
In this example (4) total digits, with the first two (40), or 4,000 BTU capacity
Primary Application Parameters Evap Rating Motor Starting Temperature Point Torque 1. Low -10F Normal 2. Low -10F High 3. High +45F Normal 4. High +45F High 5. Air Cond +45F Normal 6. Medium +20F Normal 7. Medium +20F High 8. Air Cond +49F Normal 9. Commercial +20F High 0. Commercial +20F Normal F. Low Vapor Inj -10F High G. Low Vapor Inj -10F High
Voltage Codes XA = 115-60-1; 100-50-1 XB = 230-60-1; 200-50-1 XC = 220-240-50-1 XD = 208-230-60-1; 200-50-1 XF = 208-230-60-3;200-240-50-3 XG = 460-60-3; 380-420-50-3 XH = 575-60-3; 480-520-50-3 XN = 208-230-60-1; 200-220-50-1 XP = 220-60-1; 200-50-1 XT = 200-230-60-3; 200-220-50-3 XU = 100-60-1; 100-50-1 XV = 265-60-1 AB = 115-60-1; 90-50-1 VA = 265-60-1; 220-240-50-1 NA = 208-230-60-1 AA = 115-60-1
Y = R134a Z = R404A/R507
NOTE: For explanation of compressor families and codes, contact Tecumseh Products Company.
11
AEA4440YXA XC
E and G = Evaporative Condensate Units S = Shaded Pole Fan Motor (Celseon) C = Electrically Commutated Fan Motor (Celseon) X = A holding character, reserved for future use H = Housed Unit Condensing Unit Features, see chart below Accumulator Interconnect Compressor Air Water Cooled BX Cable
Receiver Tank
A Standard Unit B Std. Unit W/Receiver Tank C Std. Unit W/Receiver Tank & BX Cable D Std. Unit W/BX Cable E,F,K Physical Design Variant (Conduit) G,H,J,L,P Physical Design Variant (Standard) M Advanced Commercial Design N Advanced Commercial Design S Customer Special T Interconnect Compressor U Water Cooled - Adv. Commercial Design V Electrical Special (Conduit Design) W Water Cooled Unit X Interconnect Unit Y Air Water Cooled Unit Z Electrical Special (Standard Unit) Evaporative Condensate Units Plastic Base EC Large Evaporative Condensate Units Black Plastic Base ED Large Evaporative Condensate Units Black Plastic Base EE Large Evaporative Condensate Units Black Plastic Base GC Small - Fan Guard, Power Cord, Receiver Tank, Service Valves GB Small - Fan Guard, Power Cord, Receiver Tank GK Small - Fan Guard, Power Cord GL Small - Fan Guard Outdoor Condensing Units HL Outdoor Condensing Unit with Options Celseon Air Cooled Units Std. Unit W/EC Fan Motor, Sweat Conns, Power Cord & CB Receiver Tank Std. Unit W/EC Fan Motor, Sweat Conns, Power Cord, CC Receiver Tank & Service Valves CK Std. Unit W/EC Fan Motor, Sweat Conns, Power Cord Std. Unit W/EC Fan Motor, Sweat Conns, Power Cord & CS Service Valves Std. Unit W/SP Fan Motor, Sweat Conns, Power Cord & SB Receiver Tank Std. Unit W/SP Fan Motor, Sweat Conns, Power Cord, SC Receiver Tank & Service Valves SK Std. Unit W/SP Fan Motor, Sweat Conns, Power Cord Std. Unit W/SP Fan Motor, Sweat Conns, Power Cord & SS Service Valves
See B/M
Fan Cooled
Water Cooled
12
SERVICE HANDBOOK
AH301FT - 077
SE1490C 281254 AH5540E
LRA103.0 USA P
COMPRESSOR MODEL NUMGER
FIGURE 2-3:
LETTER INDICATES MONTH (SEE TABLE 2-1), NEXT 2 DIGITS INDICATE DAY OF THE MONTH, FOLLOWING 2 DIGITS INDICATE YEAR
FIGURE 2-4:
MANUFACTURING CODE DATE MONTH=SEPTEMBER J2400 YEAR=2000 DAY = 24 THE LETTER REPRESENTS THE MONTH (SEE TABLE 2-1). THE NUMBERS REPRESENT THE YEAR.
FIGURE 2-5:
13
Table 2-1: Serial Label Month Identifiers A January B February C March D April E May F June G July H August J September K October L November M December
Evaporator Temperatures
The key specification is the evaporator temperature of the system. Compressors that are operating outside their design evaporator temperature range can be expected to have poor pumping efficiency and experience motor problems. Tecumseh hermetic compressors are designed for one of the following evaporator temperature ranges shown in Table 2-2.
Refrigerant
Use only the serial label refrigerant when charging the system. Using a different refrigerant can lead to excess system pressure, damage to the compressor and an explosion. For example, using R-404A in a compressor designed for R-134a can lead to higher operating pressures that can overload the bearings and overwork the motor. Use of a refrigerant other than the serial label refrigerant will void the compressor warranty.
Table 2-2: Evaporator Temperature Ranges Application Air conditioning Improved performance air conditioning Heat pump (approved models) High evaporator temperature Medium evaporator temperature Low evaporator temperature (normal torque motor) Low evaporator temperature (high torque motor) Commercial Low Evaporator Temperature - Vapor Injection (high torgue motor) Low Evaporator Temperature - Liquid Injection (high torque motor)
*Some exceptions exist, contact Tecumseh Products Company
Approved Evaporator Temperatures +32F to +55F +32F to +57F -15F to +55F +20F to +55F -10F to +30F -10F to +30F -40F to +10F 0F to +50F* -40F to +10F -40F to +10F
Line 1
Control
Compressor - specific requirements of starting Tecumseh hermetic compressors contain motors designed forUnit R torque and running efficiency. There are four general Ground of single-phase motors, each distypes y tinctly different from the others. Each type of motor may have two to four differentPTC Rela configurations depending on the compressor components.
Rela - Current y
S
S
R
PTC Relay
FIGURE 3-1:
FIGURE 3-2:
Ground Line 2 Compressor - Unit (115 Volt Ground Only - Neutral) Ground Ground Compressor - Unit Ground Compressor - Unit Ground
R R
R
PTC Rela y
Line 1
Control Control
Main Winding
(115 Line 2Volt Only - Neutral) Line 2 Conductor Identi ed (115 Volt Only - Neutral)
Line 2
Ground Ground Ground Compressor - Unit Compressor- Unit Ground Compressor - Unit Ground Ground
R R
PTC Relay
Thermal
External Thermal Protector Alt. 3/4" Thermal Protector External Thermal Control Protector C Control C Line 1 4 T M Ther mal Protector Line 1 Control Line 1 Relay - Current C Relay - Current S Line 2 (115 Volt Only - Neutral) Start Capacitor S Line 2 S
Main Winding
16
SERVICE HANDBOOK
Start Winding
17
potential relay removes the start capacitor from the circuit after the motor is up to speed. This motor may use either: an external thermal protector, or an internal thermal protector.
External or Internal Thermal Protector Start Winding Line 1 Line 2 Ground Compressor Unit Ground
S R
Start Winding
a wired-in Positive Temperature Coefficient (PTC) relay, or a module Positive Temperature Coefficient (PTC) relay. This motor may use either: an external thermal protector, or an internal thermal protector. PSC motors are basically air conditioning compressor motors and are very common up through 5 HP .
Line 2
(115 Volt Only - Neutral)
Ground
Start Winding
Line 2 FIGURE 3-5: PSC motor diagram (115 Volt Only - Neutral) Ground
Start Winding
Start Winding
C2 C1
(115 Volt Only - Neutral) Line 1
PTC Relay
Thermal Protector
Line 2
Line 2
(115 Volt Only - Neutral)
Ground
PTC Starting and ckage Compressor - Protector Pa Unit Ground External or Internal Thermal Protector
Start Winding
Control
Line 2
Relay Potential
inding
ding
Main Winding
C PSC motor diagram with start Relay assist kit-that includes a module Potential PTC relay
Main Winding
Ground Plug-In PTC Starting and Run Capacitor - Protector Pa ckage Compressor Unit Ground C2 PTC Relay C1
N C
R
C
Main Winding
Compressor R Thermal Protector Unit Ground Line 1 Run Capacitor C C Plug-In Run Capacitor
Main Winding
External or Internal Compressor R Thermal Protector Unit Ground Run Capacitor Control C Line 1
Main Winding
Here a run capacitor is in series with the start winding. Both run capacitor FIGURE 3-4: CSR motor diagram and start winding remain in the circuit during start and after motor is up to speed (see Figure 3-5). This normal starting torque motor is sufficient for capillary and other self-equalizing system. No start capacitor or relay is necessary. For additional starting External or Internal torque, a proper start assist kit may Thermal Protector be added (see Figure 3-6). Some Control start assist kits may include: C Line 1
Main Winding
18
SERVICE HANDBOOK
Minimum starting voltage for the compressor when it is attempting to start (locked rotor) is listed in Table 3-1. Unequalized system pressure: Head and suction pressures must be equal and not more than the pressures listed in Table 3-2. Refrigeration metering device (cap tube or TX valve) should equalize system pressure within 3 minutes. Unequal system pressure may be caused by excessive refrigerant charge, short cycling thermostat, or system restriction. Circuit breaker or fuse trips: Branch circuit fuses or circuit breakers sized too small will cause nuisance tripping (see Fuse and Circuit Breaker Sizing on page 27). If the fuse or circuit breaker trips, see Identifying Compressor Electrical Problems on pages 4041 for electrical troubleshooting techniques. Electrical components: A failed run capacitor will not allow the compressor to start, and it will trip the thermal protector. See Identifying Compressor Electrical Problems on pages 40-41 for electrical troubleshooting techniques.
Table 3-1: Minimum Starting Voltage Serial Label Voltage 115 208 230 208/230 265 Min. Voltage for Start 103 188 207 198 239
Table 3-2: Maximium Equalized Pressures Refrigerant R-410A R-22 R-407C R-134a Maximium Equalized Pressures 275 psig 170 psig 180 psig 104 psig
19
FIGURE 3-7: External thermal protector. (Models AE, TP TH, AK AJ, CAJ AZ, HG, , RK, RG, RN, TW and some CL)
FIGURE 3-9: AE refrigeration compressor showing (1) hermetic terminal, (2) thermal protector, (3) thermal protector clip, (4) push-on relay, (5) protective terminal cover, and (6) bale strap.
FIGURE 3-10: AE refrigeration compressor with the thermal protector and relay assembled.
20
SERVICE HANDBOOK
Table 3-3: Facts About Thermal Protectors External Line-Break Thermal Protectors Currently used on all AE, AK, AZ, TP , TH, TW, HG, RK, RG, RN, and AJ models. Sense motor current and housing temperature or combination thereof Break line current when tripped Generally do not protect against loss of charge When, by design, no air flow passes over housing, a special static thermal protector must be used Are designed for specific compressors and their intended application. Make no substitutions Will not protect motor if compressor is operated outside its evaporator temperature range Internal Line-Break Thermal Protectors Currently used on all AH, AB, AV, AG, AW, VS and most AN, SA and SF models Sense motor current and motor winding temperature or combination thereof Break line current when tripped Generally protect against loss of charge Will not protect motor if compressor if operated outside its evaporator temperature range Not repairable or replaceable Line Voltage-Electronic Protection Module (note - for more specific details consult an authorized wholesaler) Originally used on some AN and SF models Employs use of solid state temperature sensors in motor windings and compressor discharge muffler Sensor resistance values change with temperature variations Module will interrupt power to the contactor coil when resistance values of sensors exceed the specified range. This power interruption thus stops the compressor motor Module provides protection against Abnormal locked rotor conditions Loss of refrigerant High compressor discharge temperatures Excessive current conditions Time delays of 3 to 5 minutes occur on power interruption or sensor trip
21
22
SERVICE HANDBOOK
Table 3-4: Facts about Starting Relays Relay Type Current Relay Compressor Motor Type RSIR and CSIR Characteristics Sense starting current to main (run) windings Contacts normally open Contacts close and then release in less than 1 second as motor starts Must be installed vertically since contacts open by gravity PTC Relay RSIR and PSC Sense starting current to start winding Solid state device whose resistance increases with heat from current as motor starts Takes 3 to 10 minutes to cool down between operating cycles Potential Relay CSR Sense voltage generated by start winding Contacts normally closed Contacts open in less than 1 second as motor starts
Potential Type Relay Supplier Code Designations In recent years, Tecumseh has used an increasing number of potential relays with hermetic compressors. A large number of these have been used on air conditioning applications, but there are also many other applications. Since there are many variations with regard to these relays such as number of terminals, coil group, hot pick up, and mounting position, an explanation of the code numbers should be useful in the field. Tecumseh has two major suppliers of potential relays: the General Electric Company and the White Rodgers Company. An explanation of the code designation for relays manufactured by each of these companies is provided in Figures 3-14 and 3-15. NOTE: The G.E. and White Rodgers relay model numbers indicate the position the relay is to be mounted. Refer to Figures 3-14, 3-15 and 3-16. It is of utmost importance that the relays be mounted in the required position. Mounting in any other position can change the relays operating characteristics enough so that the compressor will not start properly. This can result in compressor motor failure.
23
Example: 3ARR3-A5C3 3ARR3POTENTIAL RELAY TYPE A NUMBER OF TERMINALS AND BRACKET 5 COIL GROUP (CONTINUOUS VOLTAGE) C CALIBRATION (HOT PICKUP) (VOLTS) A = 260-280 B = 280-300 C = 300-320 D = 320-340 E = 340-360 F = 350-370 G = 360-380 H = 365-395 J = 120-130 K = 130-140 L = 140-150 M = 150-160 N = 160-170 3 MOUNTING POSITION
A = 5 screw terminal "L" bracket B = 5 screw terminal flat bracket C = 3 screw terminal "L" bracket D = 3 screw terminal flat bracket U = 5 quick connect terminal "L" bracket
See note on page 22. 1 = Face down 2 = Face up 3 = Face out - numbers horizontal 4 = Face out - rotated 90 clockwise from number 3 position 5 = Face out - numbers upside down - horizontal 6 = Face out - rotated 90 counterclockwise from number 3 position
P = 170-180 R = 180-190 S = 190-200 T = 200-220 U = 220-240 V = 240-260 W = 210-230 BA=290-310 BB=110-120 TP=170-180 TV=240-260 TW=210-230
FIGURE 3-14: Explanation of GE Potential Relay Code. Example: 128-122-1335CA 128POTENTIAL RELAY TYPE 12 TYPE OF BRACKET 2CONTACT STRUCTURE 13 3 5 MOUNTING POSITION C CALIBRATION (HOT PICK UP) (VOLTS) A CUSTOMER'S PART NUMBER (TO BE STAMPED ON RELAY) L = 140-150 M = 150-160 N = 160-170 P = 170-180 R = 180-190 S = 190-200 T = 200-220 U = 220-240 V = 240-260 W = 210-230
2 = SPNC - less than 1 HP 6 = SPNC - 1 and larger 11 = 3 screw terminal 12 = 4 screw terminal (seldom used) 13 = 5 screw terminal 23 = 5 quick connect terminals
11 = Flat bracket remote (Tecumseh) 12 = "L" bracket (Tecumseh) 16 = "L" bracket for "FB" model compressors 20 = "L" bracket for Tecumseh Twins = 1 HP and larger 21 = "L" bracket for capacitor box mounting 29 = Flat bracket (Marion) was "14" (under cover)
A = 260-280 B = 280-300 C = 300-320 D = 320-340 E = 340-360 F = 350-370 G = 360-380 H = 365-395 J = 120-130 K = 130-140
NOTE: Room temperature calibration is 5 to 7% lower than these values. See note on page 22. 1 = Face down 2 = Face up 3 = Face out - numbers horizontal 4 = Face out - rotated 90 clockwise from number 3 position 5 = Face out - numbers upside down - horizontal 6 = Face out - rotated 90 counterclockwise from number 3 position
24
SERVICE HANDBOOK
Selecting Capacitors
Never use a capacitor with a lower voltage rating than that specified. A higher voltage rating than that specified is acceptable.
25
Run Capacitors
Since January 1979, capacitors provided by Tecumseh have contained non-PCB oils or have been constructed using non-PCB impregnated metallized paper electrodes and polypropylene dielectric. These capacitors are protected against case rupture by a device within the capacitor can if failure occurs. The operation of this safety device could cause the terminal end to bulge outward . Suitable head space and/or rubber caps should be provided when installing such capacitors. In some instances, for reasons of both space and economics, it is advantageous to use two capacitors whose MFD values add up to the total amount specified. In these cases, the capacitors should be connected in parallel. Rated voltage for each should not be less than that specified. The tolerance on a run capacitor is 10%, and therefore only one rating figure is given. You should not go below this figure on any application. You may exceed this figure by a small amount, and the limits are shown in Table 3-5:
FIGURE 3-18: 15000 OHMS 2 WATT 20% bleeder resistor wired across capacitor terminals.
Remember the voltage rating of all capacitors must be the same or greater than the original rating. If the voltage rating is not known, use 370 volt capacitors on 115 volt units and 440 volt capacitors on 230 volt units. Table 3-6 lists useful information regarding capacitors. Table 3-5: Limits for Run Capacitor Ratings Specific Rating 10 to 20 MFD 20 to 50 MFD Over 50 MFD Table 3-6: Facts about Capacitors Capacitor Type Start Capacitor Compressor Motor Type CSIR and CSR Characteristics Designed to operate for only a few seconds during start Taken out of start winding circuit by relay Excessive start capacitor MFD increases start winding current, increases start winding temperature, and may reduce start torque Capacitors in CSR motors should have 15,000 ohm, 2 watt bleed resistor across terminals Capacitor rated voltage must be equal to or more than that specified Capacitor MFD should not be more than that specified Table 3-5: Facts about Capacitors continued on next page Maximum Addition + 2 MFD + 5 MFD + 10 MFD
26
SERVICE HANDBOOK
Table 3-6: Facts about Capacitors Capacitor Type Run Capacitor Compressor Motor Type CSR and PSC Characteristics Permanently connected in series with start winding Excessive MFD increases running current and motor temperature Fused capacitors not recommended for CSR and not required for PSC motors Capacitor rated voltage must be equal to more than that specified Capacitor MFD should not exceed limits shown in Table 3-5 on page 25
Star t
Common
P R, AP & AR Models (1953 to phaseout) , Common T & AT Models AZ & AE (Refrigeration Models) TH, TP TW , Common Star t Star t Run Common Common Common Startt Star Run Star t Run Run Run t Star
AU & AR26 Air Conditioning Models Common AE Air Conditioning Models AW, AB, AJ, RK, RG and HG Star t Common Common Common Run Run t Start Star t Star AV Models Run
Run
Run
Start Run
27
Maximum Size
The maximum size of the fuse or circuit breaker used to protect against short circuit and/ or ground fault of a unit utilizing a hermetic compressor shall be no more than the sum of 225% of the compressor Rated Load Amps (RLA) as marked on the system serial label, plus the RLA values of each of the other motors which use the same branch circuit.
Minimum Size
The minimum value of the fuse or circuit breaker shall be no less than 175% of the RLA of the compressor. The interpretations and directions given above apply only to single branch power supplies and do NOT pertain to any plug-in type of appliances. Also, see PSC Motor Starting on pages 17-18.
Servicing
Chapter 4
30
SERVICE HANDBOOK
31
Servicing
Introduction to Servicing
This chapter provides information to assist service personnel in identifying and correcting compressor problems. It provides a general troubleshooting chart that relates complaints or problems to possible causes and solutions. This chapter also provides greater detail about specific compressor problems. For your safety, read and follow the General Service Safety Precautions on pages 2-7.
Think Safety...
Before Servicing
Be alert for sounds of arcing (sizzling, sputtering or popping), inside the compressor. IMMEDIATELY GET AWAY if you hear these sounds. Disconnect ALL electrical power before removing the protective terminal cover. Never energize the system unless: the protective terminal cover is securely fastened, and the compressor is properly connected to ground. Never reset a breaker or replace a fuse without first checking for a ground fault (also known as a short circuit to ground.)
32
SERVICE HANDBOOK
Service Procedures
In light of the risk of explosion, be especially alert for signs of water leaking into the refrigerant side of the system. Whenever servicing or troubleshooting a water-utilizing system, always check to see if it has either a pressure relief valve or a high pressure cut-out as previously described. If the system does not have at least one of these, DISCONNECT ALL ELECTRICAL POWER and look for indications that water has leaked into the refrigerant side of the system. These indications may include: Observation of or a report of a blown fuse or tripped circuit breaker. Signs that water has leaked to the outside of the system. Reports that the system has made gurgling or percolating noises. A history of loss of refrigerant charge without a leak being found in the system. NOTE: common leak detection methods will not detect a water-to-refrigerant leak in the systems heat exchanger(s). Observation of or a report of the compressor giving off an unusual amount of heat. If ANY of these indications are present, do the following checks to determine if water has leaked into the refrigerant side:
33
Step 1: Check for a Ground Fault (a Short to Ground) Check the compressor for a ground fault (also known as a short circuit to ground) using the procedure outlined in Identifying Compressor Electrical Problems on pages 40-41. If a ground fault does not exist, go to Step 2. If a ground fault does exist, keep the power off. WARNING! To avoid electric shock, electrocution or terminal venting with ignition, do not energize a compressor that has a ground fault. Mark and red tag the compressor to indicate that there is a ground fault. Do not reconnect the power leads. Tape and insulate each power lead separately. Proceed to Step 2. Do not replace the compressor or energize the system before performing Step 2. Step 2: Check for Water in the System Once the compressor is cool to the touch, open the system process valve slightly to see if any water comes out of the system. WARNING! Opening the system process valve while the compressor is hot can cause severe burns from steam coming out of the valve. If water does come out of the process valve, the entire system must be replaced. See Replacing a Single-wall Water-utilizing System below. If water does not come out of the process valve, there is still a possibility that some water has leaked into the refrigerant side of the system. To address this possibility, determine if the system has a history of losing refrigerant charge without a leak being found or repaired. If you find ANY indication of a history of losing refrigerant charge without detection of a leak, this is a sign that refrigerant has leaked in the water inside the heat exchanger. The entire system must be replaced. See Replacing a Single-wall Water-utilizing System below. If you do not find any indication of a history of loss of charge without detection of a leak, you still need to install: a high-pressure cut-out which interrupts power to ALL leads to the compressor, or an external pressure relief valve. Also, if you found a ground fault in the compressor in Step 1, replace the compressor before applying power to the system.
34
SERVICE HANDBOOK
Troubleshooting Chart
For your safety, review the General Service Safety Precautions (on pages 2-7) before using the troubleshooting chart below. The General Service Safety Precautions section provides information on the following topics: Trained Personnel Only Terminal Venting and Electrocution Refrigerants and Other Chemicals Compressor Removal System Flushing, Purging, and Pressure Testing for Leaks System Charging Prevention of Water-Utilizing System Explosions Start Capacitor Overheating System Evacuation This Troubleshooting Chart (Table 4-1) is not designed to replace the training required for a professional air conditioning/refrigeration service person, nor is it comprehensive. If you have any questions about returns under warranty, see Is Your Compressor Eligible for Return Under Warranty on page 70.
Table 4-1: Troubleshooting Chart Complaint Compressor will not start - no hum Possible Causes System component not functioning properly: 1. Control/ contactor stuck in Refer to the original equipopen position ment manufacturer (OEM) 2. Control off due to cold lo- service information cation 3. Thermostat not functioning properly Line disconnect switch open Close the start switch or the disconnect switch Response
Circuit breaker tripped or fuse Before resetting breaker or reopen or removed placing fuse, see "Identifying Compressor Electrical Problems" on pages 40-41 Thermal protector not working See "Identifying Compressor properly Electrical Problems" on pages 40-41 Wiring improper or loose Check against wiring diagram and wire properly
Compressor motor has a See "Identifying Compressor ground fault (also known as a Electrical Problems" on pages short circuit to ground) 40-41
35
Table 4-1: Troubleshooting Chart Complaint Possible Causes Response Check against wiring diagram and wire properly Turn off system until proper voltage is restored Compressor will not start - Improperly wired hums but trips on thermal protector Low voltage to compressor
System component, such as Refer to the OEM service thermostat or control/ contac- information tor, not functioning properly
Compressor electrical problems: 1. Compressor motor has a See "Identifying Compressor winding open or shorted Electrical Problems" on pages 2. Start capacitor not work- 40-41 ing properly 3. Relay does not close
Liquid refrigerant in compres- Add crankcase heater and a sor suction line accumulator. It is difficult to determine how liquid refrigerant got into the compressor. A crankcase heater along with a suctionline accumulator will prevent liquid refrigerant from getting into the compressor
Internal mechanical trouble in See "Checking for Adequate compressor. Compressor Pumping" on page 70
Compressor starts, but does Improperly wired not switch off of start winding Low voltage to compressor Compressor electrical problems:
Check against wiring diagram and wire properly Turn off system until proper voltage is restored
1. Compressor motor has a See "Identifying Compressor winding open or shorted Electrical Problems" on pages 2. Relay failing to open 40-41 3. Run capacitor not working properly
36
SERVICE HANDBOOK
Table 4-1: Troubleshooting Chart Complaint Possible Causes Response If this is a water-utilizing system, see "Servicing or Troubleshooting WaterUtilizing Systems: Preventing Explosions" on pages 32-33 Also refer to the OEM service information Compressor starts, but does Discharge pressure too high not switch off of start winding (continued)
Internal mechanical trouble in See "Checking for Adequate compressor Compressor Pumping" on page 70 Compressor starts and runs, Too much current passing but short cycles on thermal through thermal protector: protector 1. Extra sources of current 1. Check wiring diagram. draw Check for extra sources 2. Compressor motor has of current passing through thermal protector (such as winding shorted fan motors, pumps.) Refer to the OEM service information 2. See "Identifying Compressor Electrical Problems" on pages 40-41
Low voltage to compressor Turn off system until proper (single phase) or unbalanced voltage is restored voltage (three-phase) Compressor electrical prob- See "Identifying Compressor lems, such as thermal protec- Electrical Problems" on pages tor or run capacitor not work- 40-41 ing properly Discharge pressure too high If this is a water-utilizing system, see "Servicing or Troubleshooting Water-Utilizing Systems: Preventing Explosions" on pages 32-33. Also, refer to the OEM service information
If this is a water-utilizing system, see "Servicing or Troubleshooting Water-Utilizing Systems: Preventing Explosions" on pages 32-33. Also, refer to the OEM service information
37
Table 4-1: Troubleshooting Chart Complaint Possible Causes Response If this is a water-utilizing system, see "Servicing or Troubleshooting Water-Utilizing Systems: Preventing Explosions" on pages 32-33. Also, refer to the OEM service information Compressor starts and runs, Return gas too warm but short cycles on thermal protector (continued)
Unit runs OK, but run cycle is System components, such as Refer to the OEM service inforshorter than normal (due to thermostat, control or contac- mation component(s) other than ther- tor, not functioning properly mal protector) High pressure cut-out due to: 1. Insufficient air or water 1. - 3. Refer to the OEM service information supply 2. Overcharge of refrigerant 3. Air in system 4. Water leak into refrigerant side of a water-utilizing system 4. See "Servicing or Troubleshooting WaterUtilizing Systems: Preventing Explosions" on pages 32-33. Also, refer to the OEM service information
Low pressure cut-out due to: 1. Liquid line solenoid leak- 1. Repair or replace solenoid ing valve 2. Undercharge of refrigerant 2. Refer to the OEM service information 3. Restriction in expansion device Unit operates long or continu- Undercharge of refrigerant ously 3. Repair or replace expansion device If this is a water-utilizing system, see "Servicing or Troubleshooting Water-Utilizing Systems: Preventing Explosions" on pages 32-33. Also, refer to the OEM service information
System components, such as Refer to the OEM service inforthermostat or contactor not mation functioning properly or control contacts stuck or frozen closed
38
SERVICE HANDBOOK
Table 4-1: Troubleshooting Chart Complaint Possible Causes Response Unit operates long or continu- Refrigerated or air conditioned Refer to the OEM service inforously (continued) space has excessive load or mation poor insulation, or system inadequate to handle load
Restriction in refrigeration sys- Refer to the OEM service infortem mation Dirty condenser Filter dirty Space or cabinet temperature System problems, such as: too high 1. Control setting too high 2. Expansion device restricted or too small 3. Cooling coils too small 4. Inadequate air circulation Refer to the OEM service information Refer to the OEM service information
Water leaked into refrigerant See "Servicing or Troubleside of a water-utilizing system shooting Water-Utilizing Systems: Preventing Explosions" on pages 32-33. Also, refer to the OEM service information
Suction line frosted or sweat- First measure superheat to ing determine if line frosting or Refer to the OEM service inforsweating is due to floodback. mation If floodback is confirmed, possible problems are: 1. Expansion valve passing excess refrigerant or is oversized 2. Expansion valve is stuck open 3. Evaporator fan not running 4. Overcharge of refrigerant
39
Complaint
Possible Causes
Response
Liquid line frosted or sweating System problems such as, re- Refer to the OEM service inforstriction in filter-drier or strain- mation er or liquid shut-off (king valve) partially closed Water leak into refrigerant side of a water-utilizing system
System rattles or vibrates dur- Loose parts or mountings, tub- Refer to the OEM service inforing operation ing rattle, bent fan blade caus- mation ing vibration, fan motor bearings worn, etc
40
SERVICE HANDBOOK
! WARN ING
Oil and refrigerant can spray out of the compressor if one of terminal pins is ejected from the hermetic terminal. This can occur as a result of a ground fault in the compressor. The oil and refrigerant spray can be ignited by electricity and produce flames that can lead to serious burns or death. If this spray is ignited, it is called terminal venting with ignition. To reduce the risk of electrocution, serious burns or death from terminal venting with ignition: Be alert for sounds of arcing (sputtering or popping) inside the compressor. IMMEDIATELY GET AWAY if you hear these sounds. Disconnect ALL electrical power before removing the protective terminal cover. Never energize the system unless: the protective terminal cover is securely fastened, and the compressor is properly connected to ground. Never reset a breaker or replace a fuse without first checking for a ground fault. An open fuse or tripped circuit breaker is a strong indication of a ground fault.
41
electrocution, always follow the manufacturers procedures and safety rules when using these devices. Connect one lead of either the megger or Hi-Pot to the copper suction line. Connect the other lead to one of the terminal pins. Repeat this procedure for the two remaining terminal pins. If the instrument indicates any resistance less than 2 megohms between any pin and the housing (copper suction line), a ground fault exists. WARNING! To avoid electric shock, electrocution, and terminal venting with ignition do not energize a compressor that has a ground fault. If a ground fault exists, keep the power off and replace the compressor. See System Cleanup and Compressor Replacement After Compressor Failure on pages 83-86. If the compressor is not replaced immediately, mark and red tag the compressor to indicate there is a ground fault. Do not reconnect the power leads. Tape and insulate each power lead separately. If a ground fault does not exist, leave the power off and all external components disconnected from the terminal pins. Check for continuity and proper resistance using the procedure on page 42.
FIGURE 4-1: Top: Amprobe megohmmeter (commonly referred to as a "megger"). (Photo courtesy of Amprobe.) Bottom: A Slaughter Hi-Potential Ground Tester (commonly referred to as a "Hi-Pot"). (Photo courtesy of Slaughter.)
42
SERVICE HANDBOOK
3-Phase Compressors
When servicing 3-phase compressors with internal thermal protectors, be sure to allow time for the thermal protector to reset prior to starting these electrical wiring checks. For some compressors, the internal thermal protector may take as long as an hour to reset Check the windings by measuring between each pair of terminal pins: Leg1 - Leg2, Leg2 - Leg3, and Leg1 - Leg3. If there is no continuity, replace the compressor. See "System Cleanup and Compressor Replacement After Compressor Failure" on pages 83-86.
Step Two
Check Continuity
43
Checking for Other Electrical Problems in Single-phase Motors
This section provides procedures for checking the components such as the thermal protector, relay and capacitor in a single-phase compressor. Table 4-3 (below) can be used to locate the appropriate procedure for the compressor you are servicing. Examine the compressor and determine presence and/or the type of: Thermal protector (internal or external) Relay (current, potential or PTC) Capacitor(s) (start or run) With that information, use Table 4-3 to determine the location of the procedure for the compressor you are servicing. For more information on: Compressor motor types, see Single-phase Compressor Motor Types on pages 1617. Thermal protectors, see Hermetic Compressor Thermal Protectors on page 19. Starting relays, see Compressor Motor Starting Relays on pages 21-24. Capacitors, see Selecting Capacitors on pages 24-26.
Table 4-3: Locating Service Procedures by Component Types If your compressor has: Compressor Motor Type Resistance Start Induction Run (RSIR) (Split-Phase) Capacitor Start Induction Run (CSIR) Capacitor Start and Run (CSR) Thermal Protector Type Internal External Permanent Split Capacitor (PSC)
WIRED MODULE
Page
46 48
50 53 56 59 62 64 66 68
44
SERVICE HANDBOOK
This RSIR (Split-Phase) compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC Capacitor Type Run Start
The electrical system on this type of motor is shown in FIGURE 4-2. The actual position of terminals on the relay may be different than shown in FIGURE 4-2. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Control
C Star t Winding
S R
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-2: RSIR compressor motor with external thermal protector and current type relay mounted on hermetic terminal.
Main Winding
45
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked with windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 4: Check Current Relay Keep the relay upright. Check the relay by measuring continuity between: Relay terminals 1 (or L) and S. If there is continuity, then the contacts are closed when they should be open. Replace the current relay. Relay terminals 1 (or L) and M. If there is no continuity, replace the current relay.
Step 5: Replace Current Relay If all above tests prove satisfactory, there is no capillary restriction, and the unit still fails to operate properly, replace the relay. The new relay will eliminate any electrical problems which cannot be determine with the above tests.
Step 6: Continue Troubleshooting If the new relay does not correct the problem, check for adequate compressor pumping as outlined in the procedure on page 70.
46
SERVICE HANDBOOK
This RSIR (Split-Phase) compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC
WIRED
The electrical system on this type of motor is shown in FIGURE 4-3. The actual position of terminals on the relay may be different than shown in FIGURE 4-3. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Ground
R PTC Relay
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-3: RSIR compressor motor with external thermal protector and wired-in PTC relay.
Main Winding
Fan Motor*
47
Step 1: Before Continuing Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check Wired-in PTC Relay Check the relay by measuring continuity between the pin holes where the R and S pins on the compressor are inserted. If there is no continuity, the relay may be open. Wait 3 minutes, then check continuity again. If there is still no continuity, replace the relay.
Step 4: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 5: Continue Troubleshooting If all above tests prove satisfactory and unit still fails to operate properly check for adequate compressor pumping as outlined in the procedure on page 70.
48
SERVICE HANDBOOK
This RSIR (Split-Phase) compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC
MODULE
The electrical system on this type of motor is shown in FIGURE 4-4. The actual position of terminals on the relay may be different than shown in FIGURE 4-4. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Line 1
Control L
Thermal Protector
Fa n Motor* C1
PTC Relay
Line 2 Ground
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-4: RSIR compressor motor type with external PTC starting and protector package.
Main Winding
C2
Star t Winding
49
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector. For GE modules, replace the entire starting and protector package. For TI (Sensata) modules, replace the thermal protector.
Step 4: Check Module PTC Relay Check the relay be measuring continuity between the starting and protector package pin holes where the R and S pins on the compressor are inserted. If there is no continuity, the relay may be open. Wait 3 minutes, then check continuity again. If there is still no continuity, replace the protector package.
Step 5: Continue Troubleshooting If all above tests prove satisfactory and unit still fails to operate properly, check for adequate compressor pumping as outlined in the procedure on page 70.
50
SERVICE HANDBOOK
This CSIR compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC Capacitor Type Run Start
The electrical system on this type of motor is shown in FIGURE 4-5. The actual position of terminals on the relay may be different than shown in FIGURE 4-5. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Fan* 1 S
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-5: CSIR compressor motor type with external protector, current type relay mounted on hermetic terminal and start capacitor.
Main Winding
Relay - Current
51
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 4: Check Current Relay Keep the relay upright. Check the relay by measuring continuity between: Relay terminals 1 and S. If there is continuity, then the relay contacts are closed when they should be open. Replace the current relay. Relay terminals 2 and M. If there is no continuity, replace the current relay.
Step 5: Check Start Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the start capacitor from the system. Use a capacitance meter to measure the capacitance. The capacitance value should be the rated value minus 0% to plus 20%. If it is outside of this range, then the start capacitor needs to be replaced. As an alternative, check the start capacitor by measuring continuity across capacitor terminals: Rx1 scale: If there is continuity, then the start capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the start capacitor is open and needs to be replaced. Possible reasons that a start capacitor is not working properly include: Use of incorrect start capacitor. Replace with proper start capacitor. The relay contacts are not working properly. Replace the relay. Prolonged operation on start cycle due to low voltage. Determine if the line voltage is too low (less than 90% of rated voltage). Prolonged operation on start cycle due to incorrect relay. Replace with correct relay.
52
SERVICE HANDBOOK
Prolonged operation on start cycle due to starting load too high. Refer to the OEM service information to use pump down arrangement, if necessary. Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For more information on troubleshooting the system components, refer to the OEM service information.
Step 6: Replace Current Relay If all above tests prove satisfactory, there is no capillary restriction, and the unit still fails to operate properly, replace the relay. The new relay will eliminate any electrical problems which cannot be determined with above tests.
Step 7: Continue Troubleshooting If the new relay does not correct the problem, check for adequate compressor pumping as outlined in the procedure on page 70.
53
This CSIR compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC Capacitor Type Run Start
The electrical system on this type of motor is shown in FIGURE 4-6. The actual position of terminals on the relay may be different than shown in FIGURE 4-6. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Line 1 Line 2
Fan*
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-6: CSIR compressor motor type with external thermal protector, potential relay mounted remote and start capacitor.
Main Winding
Relay - Potential
54
SERVICE HANDBOOK
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 4: Check Protector Wiring Confirm that there is continuity between: The power input terminal on the thermal protector and 5 on relay. The protector common lead wire and C.
Step 5: Check Potential Relay Before checking the relay, be sure it is mounted at the proper position (see pages 28-32). Check the potential relay by measuring continuity between: Relay terminals 5 and 2. If there is no continuity, replace the relay. Relay terminals 2 and 1. If there is no continuity, then the contact are open. Replace the relay. Possible reasons that a relay is not working properly include: Use of incorrect relay. Replace with correct relay. Line voltage is too high or low (greater than 100% or less than 90% of rated voltage). Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For more information on troubleshooting the thermal protector, see Step 3. For troubleshooting the system components, refer to the OEM service information. Vibration due to loose relay mounting. Tighten relay mounting. Use of incorrect run capacitor. Replace with proper run capacitor.
55
Step 6: Check Start Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the start capacitor from the system. Remove the bleed resistor. Use a capacitance meter to measure the capacitance. The capacitance value should be the rated value minus 0% to plus 20%. If it is outside of this range, then the start capacitor needs to be replaced. As an alternative, check the start capacitor by measuring continuity across the capacitor terminals. Using the Rx1 ohm scale: If there is continuity the start capacitor is shorted and needs to be replaced. Using the Rx100,000 ohm scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the start capacitor is open and needs to be replaced. Possible reasons that a start capacitor is not working properly include: Use of incorrect start capacitor. Replace with proper start capacitor. The relay contacts are not working properly. Replace the relay. Prolonged operation on start cycle due to low voltage. Determine if the line voltage is too low (less than 90% of rated voltage). Prolonged operation on start cycle due to incorrect relay. Replace with correct relay. Prolonged operation on start cycle due to starting load too high. Refer to the OEM service information to use pump down arrangement if necessary. Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For more information on troubleshooting the thermal protector, see Step 3. For troubleshooting the system components, refer to the OEM service information.
Step 7: Check Protector Wiring Confirm that there is continuity between 2 and S and between 4 and R, then reconnect unit.
Step 8: Replace Potential Relay If all above tests prove satisfactory, there is no capillary restriction, and the unit still fails to operate properly, replace the relay. The new relay will eliminate any electrical problems which cannot be determined with above tests.
Step 9: Continue Troubleshooting If the new relay does not correct the problem, check for adequate compressor pumping as outlined in the procedure on page 70.
56
SERVICE HANDBOOK
This CSR compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC Capacitor Type Run Start
The electrical system on this type of motor is shown in FIGURE 4-7. The actual position of terminals on the relay may be different than shown in FIGURE 4-7. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
S 5 6 4 1 R 2
Run Capacitor Start Capacitor Bleeder Resistor Note: #4 and #6 on relay are dummy terminals
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-7: CSR compressor motor type with external thermal protector, potential relay mounted remote and run and start capacitors.
Main Winding
Ground
Rela y - Potential
57
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Check Potential Relay Before checking the relay, be sure it is mounted at the proper position (see pages 21-23). Check the potential relay by measuring continuity between: Relay terminals 5 and 2. If there is no continuity, replace the relay. Relay terminals 2 and 1. If there is no continuity, then the contacts are open. Replace the relay. Possible reasons that a relay is not working properly include: Use of incorrect relay. Replace with correct relay. Line voltage is too high or low (greater than 110% or less than 90% of rated voltage). Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For more information on troubleshooting the thermal protector, see Step 5. For troubleshooting the system components, refer to the OEM service information. Vibration due to loose relay mounting. Tighten relay mounting. Use of incorrect run capacitor. Replace with proper run capacitor.
Step 3: Check Run Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should be 10% of the marked capacitor value. As an alternative, check the run capacitor by measuring continuity across the capacitor terminals: Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the run capacitor is open and needs to be replaced. Possible reasons that a run capacitor is not working properly include: Use of incorrect run capacitor. Replace with proper run capacitor. Line voltage is too high (greater than 100% of rated voltage).
Step 4: Check Start Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock.
58
SERVICE HANDBOOK
Disconnect the start capacitor from the system. Remove the bleed resistor. Use a capacitance meter to measure the capacitance. The capacitance value should be the rated value minus 0% to plus 20%. If it is outside of this range, then the start capacitor needs to be replaced. As an alternative, check the start capacitor by measuring continuity across the capacitor terminals. Using the Rx1 ohm scale: If there is continuity the start capacitor is shorted and needs to be replaced. Using the Rx100,000 ohm scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the start capacitor is open and needs to be replaced. Possible reasons that a start capacitor is not working properly include: Use of incorrect start capacitor. Replace with proper start capacitor. The relay contacts are not working properly. Replace the relay. Prolonged operation on start cycle due to low voltage. Determine if the line voltage is too low (less than 90% of rated voltage). Prolonged operation on start cycle due to incorrect relay. Replace with correct relay. Prolonged operation on start cycle due to starting load too high. Refer to the OEM service information to use pump down arrangement if necessary. Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For troubleshooting the system components, refer to the OEM service information.
Step 5: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 6: Check Wiring Confirm that there is continuity between 5 and C, 2 and S, and 4 and R. Reconnect wiring.
Step 7: Replace Potential Relay If all above tests prove satisfactory, there is no capillary restriction, and the unit still fails to operate properly, replace the relay. The new relay will eliminate any electrical problems which cannot be determined with above tests.
Step 8: Continue Troubleshooting If the new relay does not correct the problem, check for adequate compressor pumping as outlined in the procedure on page 70.
59
This CSR compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC Capacitor Type Run Start
The electrical system on this type of motor is shown in FIGURE 4-8 and 4-9. The actual position of terminals on the relay may be different than shown in FIGURE 4-8 and 4-9. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Internal Thermal Protector Start Winding Run Capacitor Bleeder Resistor Note: #4 and #6 on relay are dummy terminals Start Winding Line 1 Line 2 Relay - Potential Ground
5 2 6 4 1
Start Capacitor
FIGURE 4-8: CSR compressor motor type with internal thermal protector without start winding protection, potential relay and run and start capacitors.
Internal Thermal Protector Line 1 Line 2 Relay - Potential Ground 5 Compressor - Unit Ground 4 Start Capacitor 6 1 R Run Capacitor Bleeder Resistor Note: #4 and #6 on relay are dummy terminals 2 S C
FIGURE 4-9: CSR compressor motor type with internal thermal protector with start winding protection, potential relay and run and start capacitors.
Main Winding
Main Winding
60
SERVICE HANDBOOK
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly. NOTE: the compressor housing MUST be at 130F or less for the following checks. This temperature can be read by Tempstik or is that temperature which will allow the hand to remain in contact with the compressor housing without discomfort.
Step 2: Check Internal Thermal Protector If there is continuity between all terminals the thermal protector should be good. If R to S has continuity and R to C and S to C do not, the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the compressor.
Step 3: Check Run Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should be 10% of the marked capacitor value. As an alternative, check the run capacitor by measuring continuity across the capacitor terminals: Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the run capacitor is open and needs to be replaced. Possible reasons that a run capacitor is not working properly include: Use of incorrect run capacitor. Replace with proper run capacitor. Line voltage is too high (greater than 100% of rated voltage).
Step 4: Check Potential Relay Before checking the relay, be sure it is mounted at the proper position (see pages 28-32). Check the potential relay by measuring continuity between: Relay terminals 5 and 2. If there is no continuity, replace the relay. Relay terminals 2 and 1. If there is no continuity, then the contacts are open. Replace the relay. Possible reasons that a relay is not working properly include: Use of incorrect relay. Replace with correct relay. Line voltage is too high or low (greater than 110% or less than 90% of rated voltage). Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For more information on troubleshooting the thermal protector, see Step 2. For troubleshooting the system components, refer
61
to the OEM service information. Vibration due to loose relay mounting. Tighten relay mounting. Use of incorrect run capacitor. Replace with proper run capacitor.
Step 5: Check Start Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the start capacitor from the system. Remove the bleed resistor. Use a capacitance meter to measure the capacitance. The capacitance value should be the rated value minus 0% to plus 20%. If it is outside of this range, then the start capacitor needs to be replaced. As an alternative, check the start capacitor by measuring continuity across the capacitor terminals. Using the Rx1 ohm scale: If there is continuity the start capacitor is shorted and needs to be replaced. Using the Rx100,000 ohm scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the start capacitor is open and needs to be replaced. Possible reasons that a start capacitor is not working properly include: Use of incorrect start capacitor. Replace with proper start capacitor. The relay contacts are not working properly. Replace the relay. Prolonged operation on start cycle due to low voltage. Determine if the line voltage is too low (less than 90% of rated voltage). Prolonged operation on start cycle due to incorrect relay. Replace with correct relay. Prolonged operation on start cycle due to starting load too high. Refer to the OEM service information to use pump down arrangement if necessary. Excessive short cycling. Short cycling can be caused by problems with the compressors thermal protector or system components such as the thermostat, control, contactor, or high or low pressure cut-out. For more information on troubleshooting the thermal protector, see Step 2. For troubleshooting the system components, refer to the OEM service information.
Step 6: Replace Potential Relay If all above tests prove satisfactory, there is no capillary restriction, and the unit still fails to operate properly, replace the relay. The new relay will eliminate any electrical problems which cannot be determined with above tests.
Step 7: Continue Troubleshooting If the new relay does not correct the problem, check for adequate compressor pumping as outlined in the procedure on page 70.
62
SERVICE HANDBOOK
This PSC compressor has the following components: Thermal Protector Type Internal External The electrical system on this type of motor is shown in FIGURE 4-10. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427. Current Relay Type Potential PTC Capacitor Type Run Start
Line 1 Line 2
R Run Capacitor
FIGURE 4-10: PSC compressor motor with external thermal protector and run capacitor.
FIGURE 4-11: PSC compressor motor with external thermal protector and a start assist kit that in cludes a potential relay.
Main Winding
63
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Check Wiring Confirm that there is continuity between C and the protector common lead wire.
Step 3: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 4: Check Run Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should be 10% of the marked capacitor value. As an alternative, check the run capacitor by measuring continuity across the capacitor terminals: Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the run capacitor is open and needs to be replaced. Possible reasons that a run capacitor is not working properly include: Use of incorrect run capacitor. Replace with proper run capacitor. Line voltage is too high (greater than 100% of rated voltage).
Step 5: Reconnect Run Capacitor Reconnect the run capacitor into circuit at terminals S and R. (Marked terminal should go to R.)
Step 6: Add Start Assist Kit If the compressor checks out satisfactorily on all the above PSC tests but still doesnt operate, add proper start assist kit to provide additional starting torque. See Figure 4-11 for proper wiring.
Step 7: Continue Troubleshooting If all above tests prove satisfactory and unit still fails to operate properly, check for adequate compressor pumping as outlined in the procedure on page 70.
64
SERVICE HANDBOOK
This PSC compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC Capacitor Type Run Start
The electrical system on this type of motor is shown in FIGURE 4-12 and 4-13. The actual position of terminals on the relay may be different than shown in FIGURE 4-12 and 4-13. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Internal Thermal Protector Control C Start Winding Run Capacitor FIGURE 4-12: PSC compressor motor type with internal protector without start winding protection and run capacitor. C Star t Winding Run Capacitor FIGURE 4-13: PSC compressor motor type with internal thermal protector with start winding protection and run capacitor. S Ground Compressor - Unit Ground R
Line 1 Line 2
Line 1 Line 2
Main Winding
Main Winding
65
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42, made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly. NOTE: the compressor housing MUST be at 130F or less for the following checks. This temperature can be read by Tempstik or is that temperature which will allow the hand to remain in contact with the compressor housing without discomfort.
Step 2: Check Internal Thermal Protector If there is continuity between all terminals the thermal protector should be good. If R to S has continuity and R to C and S to C do not, the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the compressor.
Step 3: Check Run Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should be 10% of the marked capacitor value. As an alternative, check the run capacitor by measuring continuity across the capacitor terminals: Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the run capacitor is open and needs to be replaced. Possible reasons that a run capacitor is not working properly include: Use of incorrect run capacitor. Replace with proper run capacitor. Line voltage is too high (greater than 100% of rated voltage).
Step 4: Reconnect Run Capacitor Reconnect the run capacitor into circuit at terminals S and R. (Marked terminal should go to R.)
Step 5: Continue Troubleshooting If all above tests prove satisfactory and unit still fails to operate properly, check for adequate compressor pumping as outlined in the procedure on page 70.
66
SERVICE HANDBOOK
This PSC compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC
WIRED
The electrical system on this type of motor is shown in FIGURE 4-14. The actual position of terminals on the relay may be different than shown in FIGURE 4-14. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
4TM Thermal Protector Line 1 Control C Line 2 Identi ed Conductor (115 Volt Only) Ground Fa n Motor* S Star t Winding
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-14: PSC compressor motor type with external thermal protector, wired-in PTC relay and run capacitor
Main Winding
67
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check Run Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should be 10% of the marked capacitor value. As an alternative, check the run capacitor by measuring continuity across the capacitor terminals: Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the run capacitor is open and needs to be replaced. Possible reasons that a run capacitor is not working properly include: Use of incorrect run capacitor. Replace with proper run capacitor. Line voltage is too high (greater than 100% of rated voltage).
Step 4: Check Wired-in PTC Relay Check the relay by measuring continuity between the pin holes where the R and S pins on the compressor are inserted. If there is no continuity, the relay may be open. Wait 3 minutes, then check continuity again. If there is still no continuity, replace the relay.
Step 5: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector.
Step 6: Continue Troubleshooting If all above tests prove satisfactory and unit still fails to operate properly, check for adequate compressor pumping as outlined in the procedure on page 70.
68
SERVICE HANDBOOK
This PSC compressor has the following components: Thermal Protector Type Internal External Current Relay Type Potential PTC
WIRED
Start
The electrical system on this type of motor is shown in FIGURE 4-15. The actual position of terminals on the relay may be different than shown in FIGURE 4-15. Use the letters and/ or numbers on the actual relay to locate the terminals. If replacement parts are needed, refer to the Tecumseh Electrical Service Parts Guide Book for information on proper replacement parts, or call Tecumseh Products Company at 1-800-211-3427.
Line 1
Thermal Protector
Star t Winding
S PTC Relay
Line 2 Ground
*Other auxiliary devices may be attached. Disconnect any auxilliary devices in Step 2.
FIGURE 4-15: PSC compressor motor type with an external PTC starting and protector package and plug-in run capacitor.
Main Winding
69
Step 1: Before Continuing with Troubleshooting WARNING! All electric power should be disconnected and you should have already made sure that the compressor does not have a ground fault (see Checking for a Ground Fault on pages 40-41). You should have also checked the windings for continuity and proper resistance (see Checking for Continuity and Proper Resistance on page 42), made sure the system is getting proper voltage, and that the control, thermostat, and contactor are working properly.
Step 2: Disconnect Fan Motor or Any Other Devices If there is a fan motor or any other auxiliary device, open the circuit for the fan motor or any other device.
Step 3: Check Plug-in Run Capacitor CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from the system to avoid damage to measuring devices and risk of electric shock. Disconnect the run capacitor from the system. Use a capacitance meter to check capacitor. Capacitance should be 10% of the marked capacitor value. As an alternative, check the run capacitor by measuring continuity across the capacitor terminals: Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be replaced. Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter indicates infinite resistance, then the run capacitor is open and needs to be replaced. Possible reasons that a run capacitor is not working properly include: Use of incorrect run capacitor. Replace with proper run capacitor. Line voltage is too high (greater than 100% of rated voltage).
Step 4: Check External Thermal Protector Check for continuity across the thermal protector (line 1 and compressor terminal connection). If there is no continuity then the thermal protector may be tripped. Wait for the protector to cool off and close. This may take more than an hour. Check continuity gain. If there is no continuity, replace the protector. For GE modules, replace the entire starting and protector package. For TI (Sensata) modules, replace the thermal protector. Step 5: Check Module PTC Relay Check the relay by measuring continuity between the starting and protector package pin holes where the R and S pins on the compressor are inserted. If there is no continuity, the relay may be open. Wait 3 minutes, then check continuity again. If there is still no continuity, replace the protector package.
Step 6: Continue Troubleshooting If all above tests prove satisfactory and unit still fails to operate properly, check for adequate compressor pumping as outlined in the procedure on page 70.
70
SERVICE HANDBOOK
71
74
SERVICE HANDBOOK
On some AE refrigeration models, the terminal cover faces the other way.
75
Discharge Tube
Discharge Tube
AK AJ AN
Discharge Tube
Discharge Tube
AH
AB AG
Discharge Tube
Discharge Tube
RK, RG
AZ
AV
76
SERVICE HANDBOOK
Table 5-1: R-22 Refrigerant Line Sizes, 45F Evap Temp, 65F Suction Vapor Temp, 105F Condensing and Liquid Temp
Line Size, Type L Copper OD (in) Velocity = 1500 fpm* 10 3/16 3/16 3/16 3/16 3/16 1/4 1/4 1/4 1/4 5/16 5/16 5/16 3/8 3/8 1/2 1/2 5/8 1/2 1/2 1/2 1/2 5/8 5/8 5/8 3/8 1/2 1/2 3/8 1/2 1/2 3/8 3/8 1/2 3/8 1/2 1/2 5/8 5/8 3/4 5/16 3/8 3/8 3/8 5/16 5/16 3/8 5/16 1/4 5/16 5/16 5/16 3/8 3/8 3/8 1/2 1/2 1/2 5/8 5/8 5/8 1/4 5/16 5/16 1/4 5/16 1/4 1/4 5/16 1/4 5/16 1/4 1/4 1/4 3/16 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 5/8 3/4 3/4 3/16 1/4 1/4 3/16 1/4 1/4 3/16 3/16 1/4 ~ 1/4 1/4 1/4 5/16 5/16 3/8 1/2 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 7/8 3/16 3/16 3/16 ~ 3/16 3/16 1/4 25 50 100 3/16 1/4 5/16 5/16 3/8 3/8 1/2 1/2 5/8 3/4 3/4 7/8 7/8 1 1/8 1 1/8 1/4 5/16 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 7/8 1-1/8 LIQUID LINE SIZE OD (in) Line Length, Equivalent Feet Velocity = 100 fpm* DISCHARGE LINE SIZE OD (in) Velocity Line Length, Equivalent Feet = 1500 fpm* 10 25 50 100 ~ 3/16 3/16 1/4 5/16 5/16 3/8 3/8 3/8 1/2 5/8 5/8 3/4 3/4 7/8
Cond. Unit CAPACITY SUCTION LINE SIZE OD (in) Line Length, Equivalent Feet (Btu/h) 10 25 50 100 5/16 3/8 1/2 1/2 1/2 5/8 5/8 5/8 3/4 7/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8
1,000 3/8 3/8 1/2 1/2 1/2 5/8 5/8 3/4 7/8 7/8
1/4
1/4
5/16
2,000
1/4
5/16
5/16
3,000
5/16
5/16
4,000
5/16
3/8
6,000
3/8
3/8
8,000
3/8
1/2
10,000
1/2
1/2
12,000
1/2
1/2
18,000
1/2
5/8
24,000
5/8
5/8
30,000
5/8
3/4
36,000
5/8
3/4
48,000
3/4
7/8
1 1/8
60,000
3/4
7/8
1 1/8
72,000
7/8
7/8
1 1/8
* Largest line size that will maintain the stated refrigerant velocity. Please consult industry references such as the ASHRAE Refrigeration Handbook for additional information regarding how to properly size suction and discharge line risers and condenser to receiver condensate lines.
77
78
Table 5-2: R-22 Refrigerant Line Sizes, 20F Evap Temp, 40F Suction Vapor Temp, 105F Condensing and Liquid Temp
Line Size, Type L Copper OD (in) Velocity = 1500 fpm* 10 3/16 3/16 3/16 3/16 3/16 1/4 1/4 1/4 5/16 5/16 5/16 3/8 1/2 1/2 5/8 3/8 1/2 1/2 1/2 5/8 3/8 3/8 1/2 3/8 5/16 3/8 3/8 3/8 5/16 5/16 3/8 5/16 1/4 5/16 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 1/4 5/16 5/16 1/4 5/16 1/4 1/4 5/16 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 3/16 1/4 1/4 3/16 1/4 5/16 3/16 3/16 1/4 3/16 1/4 1/4 3/16 3/16 1/4 ~ 1/4 1/4 1/4 5/16 5/16 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 3/16 3/16 3/16 ~ 3/16 3/16 1/4 25 50 100 1/4 5/16 3/8 3/8 1/2 1/2 5/8 5/8 3/4 7/8 1 1/8 1 1/8 1/4 5/16 3/8 3/8 1/2 1/2 1/2 1/2 5/8 3/4 3/4 7/8 LIQUID LINE SIZE OD (in) Line Length, Equivalent Feet Velocity = 100 fpm* DISCHARGE LINE SIZE OD (in) Velocity Line Length, Equivalent Feet = 1500 fpm* 10 25 50 100 3/16 1/4 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 5/8 3/4
SERVICE HANDBOOK
Cond. Unit CAPACITY SUCTION LINE SIZE OD (in) Line Length, Equivalent Feet (Btu/h) 10 25 50 100 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 1 1/8 1 1/8 1 3/8 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8
1,000
1/4
5/16
5/16
2,000
5/16
5/16
3,000
5/16
3/8
4,000
3/8
1/2
6,000
3/8
1/2
8,000
1/2
1/2
10,000
1/2
5/8
12,000
1/2
5/8
18,000
5/8
3/4
24,000
5/8
3/4
36,000
3/4
7/8
1 1/8
48,000
7/8
1 1/8
1 1/8
Table 5-3: R-134a Refrigerant Line Sizes, 45F Evap Temp, 65F Suction Vapor Temp, 105F Condensing and Liquid Temp 3/8 1/2 1/2 5/8 5/8 3/4 3/4 3/4 7/8 3/4 5/8 5/8 1/4 1/4 5/16 1/2 1/4 1/2 1/4 3/8 3/16 1/4 1/4 1/4 5/16 5/16 3/8 5/16 3/16 1/4 5/16 3/16 3/16 1/4 1/4 1/4 5/16 5/16 5/16 5/16 3/8 1/4 3/16 3/16 3/16 3/16 1/4 1/4 5/16 5/16 5/16 3/8 3/8 1/2 ~ ~ 3/16 3/16 1/4 1/4 5/16 5/16 3/8 3/16 3/16 3/16 1/4 1/4 5/16 5/16 3/8 3/8 3/16 1/4 1/4 5/16 5/16 3/8 1/2 1/2 1/2 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 5/8 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 3/16 3/16 1/4 1/4 5/16 3/8 3/8 3/8 1/2 3/8 1/2 1/2 5/8 5/8 5/8 3/4 7/8
1,000
1/4
5/16
5/16
2,000
5/16
5/16
3,000
5/16
3/8
4,000
3/8
1/2
6,000
1/2
1/2
8,000
1/2
1/2
10,000
1/2
5/8
12,000
1/2
5/8
18,000
5/8
3/4
* Largest line size that will maintain the stated refrigerant velocity. Please consult industry references such as the ASHRAE Refrigeration Handbook for additional information regarding how to properly size suction and discharge line risers and condenser to receiver condensate lines.
Table 5-4: R-134a Refrigerant Line Sizes, 20F Evap Temp, 40F Suction Vapor Temp, 105F Condensing and Liquid Temp
Line Size, Type L Copper OD (in) Velocity = 1500 fpm* 10 3/16 3/16 3/16 3/16 1/4 1/4 1/4 1/4 5/16 3/8 3/8 1/2 3/8 5/16 3/8 3/8 5/16 3/8 3/8 5/16 5/16 3/8 5/16 5/16 1/4 5/16 3/8 1/4 5/16 3/8 1/2 1/2 1/2 1/4 5/16 5/16 1/4 1/4 5/16 1/4 1/4 5/16 3/16 1/4 5/16 1/4 1/4 1/4 3/16 3/16 1/4 5/16 5/16 3/8 3/8 1/2 1/2 5/8 3/16 1/4 1/4 ~ 3/16 1/4 1/4 3/16 3/16 3/16 ~ 3/16 3/16 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 25 50 100 1/4 3/8 3/8 1/2 5/8 5/8 3/4 7/8 7/8 LIQUID LINE SIZE OD (in) Line Length, Equivalent Feet Velocity = 100 fpm* DISCHARGE LINE SIZE OD (in) Velocity Line Length, Equivalent Feet = 1500 fpm* 10 25 50 100 3/16 3/16 1/4 1/4 5/16 3/8 3/8 3/8 1/2
Cond. Unit CAPACITY SUCTION LINE SIZE OD (in) Line Length, Equivalent Feet (Btu/h) 10 25 50 100 3/8 1/2 1/2 5/8 5/8 3/4 3/4 7/8 1 1/8 1 1/8 7/8 7/8 3/4 5/8 5/8 1/2 1/2
1,000
5/16
5/16
2,000
3/8
3/8
3,000
3/8
1/2
4,000
1/2
1/2
6,000
1/2
5/8
8,000
1/2
5/8
10,000
5/8
3/4
12,000
5/8
3/4
18,000
3/4
7/8
1 1/8
Table 5-5: R134a Refrigerant Line Sizes, -10F Evap Temp, 40F Suction Vapor Temp, 105F Condensing and Liquid Temp 1/2 5/8 3/4 3/4 7/8 1 1/8 7/8 1/4 1/4 5/16 7/8 3/4 3/16 1/4 1/4 3/4 5/8 3/16 1/4 1/4 5/8 1/2 3/16 3/16 1/4 1/4 1/4 5/16 5/16 1/2 3/8 3/16 3/16 3/16 3/16 ~ 3/16 3/16 3/16 1/4 3/16 3/16 1/4 1/4 5/16 3/16 1/4 5/16 5/16 3/8 1/4 5/16 5/16 3/8 3/8 1/4 5/16 3/8 3/8 3/8 3/16 1/4 1/4 5/16 1/2
1,000
3/8
1/2
2,000
3/8
1/2
3,000
1/2
5/8
4,000
1/2
5/8
6,000
5/8
3/4
* Largest line size that will maintain the stated refrigerant velocity. Please consult industry references such as the ASHRAE Refrigeration Handbook for additional information regarding how to properly size suction and discharge line risers and condenser to receiver condensate lines.
79
80
SERVICE HANDBOOK
Table 5-6: R-404A Refrigerant Line Sizes, 45F Evap Temp, 65F Suction Vapor Temp, 105F Condensing and Liquid Temp
Line Size, Type L Copper OD (in) Velocity = 1500 fpm* 10 3/16 3/16 3/16 3/16 1/4 1/4 1/4 1/4 5/16 5/16 3/8 3/8 3/8 1/2 1/2 1/2 1/2 1/2 1/2 3/8 1/2 3/8 3/8 1/2 1/2 1/2 5/8 5/8 5/16 3/8 3/8 5/16 5/16 3/8 5/16 5/16 3/8 5/16 3/8 3/8 1/2 1/2 5/8 5/8 3/4 1/4 5/16 5/16 5/16 1/4 1/4 5/16 1/4 1/4 1/4 1/4 3/16 1/4 1/4 5/16 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 3/16 1/4 1/4 3/16 1/4 3/16 3/16 3/16 ~ 3/16 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 5/8 25 50 100 3/16 1/4 5/16 5/16 3/8 3/8 1/2 1/2 5/8 3/4 3/4 7/8 7/8 3/16 LIQUID LINE SIZE OD (in) Line Length, Equivalent Feet Velocity = 100 fpm* DISCHARGE LINE SIZE OD (in) Velocity Line Length, Equivalent Feet = 1500 fpm* 10 25 50 100 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8 5/8 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 ~ 3/16 3/16 1/4 5/16 5/16 3/8 3/8 3/8 1/2 1/2 5/8 5/8
Cond. Unit CAPACITY SUCTION LINE SIZES OD (in) Line Length, Equivalent Feet (Btu/h) 10 25 50 100 5/16 3/8 1/2 1/2 5/8 5/8 5/8 3/4 3/4 7/8 1 1/8 1 1/8 1 1/8
1,000 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 7/8
1/4
1/4
5/16
2,000
1/4
5/16
5/16
3,000
5/16
3/8
4,000
5/16
3/8
6,000
3/8
1/2
8,000
3/8
1/2
10,000
1/2
1/2
12,000
1/2
1/2
18,000
1/2
5/8
24,000
5/8
3/4
30,000
5/8
3/4
36,000
5/8
3/4
42,000
3/4
7/8
1 1/8
* Largest line size that will maintain the stated refrigerant velocity. Please consult industry references such as the ASHRAE Refrigeration Handbook for additional information regarding how to properly size suction and discharge line risers and condenser to receiver condensate lines.
Table 5-7: R-404A Refrigerant Line Sizes, 20F Evap Temp, 40F Suction Vapor Temp, 105F Condensing and Liquid Temp
Line Size, Type L Copper OD (in) Cond. Unit Velocity CAPACITY SUCTION LINE SIZE OD (in) Line Length, Equivalent Feet = 1500 (Btu/h) fpm* 10 25 50 100 LIQUID LINE SIZE OD (in) Line Length, Equivalent Feet 10 3/16 3/16 3/16 3/16 1/4 1/4 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8 1/2 1/2 5/8 5/8 3/4 7/8 1/2 1/2 1/2 5/8 3/8 1/2 1/2 1/2 3/8 3/8 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/16 3/8 3/8 3/8 3/8 5/16 5/16 3/8 3/8 3/8 5/16 5/16 3/8 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 1/4 5/16 5/16 5/16 5/16 5/16 1/4 1/4 5/16 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 1/4 1/4 1/4 1/4 1/4 1/4 5/16 3/16 1/4 1/4 3/16 1/4 1/4 1/4 3/16 3/16 3/16 ~ 3/16 3/16 1/4 1/4 5/16 5/16 3/8 1/2 1/2 1/2 1/2 5/8 5/8 3/4 3/4 7/8 1 1/8 25 50 100 Velocity = 100 fpm* DISCHARGE LINE SIZE OD (in) Velocity Line Length, Equivalent Feet = 1500 fpm* 10 25 50 100 ~ 3/16 3/16 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 5/8 3/4 7/8 3/8 1/2 1/2 5/8 5/8 3/4 3/4 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 7/8 7/8 3/4 5/8 5/8 1/2 1/2 3/8 3/8 5/16 1/4 3/8 1/2 1/2 5/8 5/8 3/4 3/4 7/8 7/8
1,000
1/4
5/16
5/16
2,000
5/16
3/8
3,000
3/8
3/8
4,000
3/8
1/2
6,000
1/2
1/2
8,000
1/2
5/8
10,000
1/2
5/8
12,000
1/2
5/8
18,000
5/8
3/4
24,000
3/4
7/8
30,000
3/4
7/8
1 1/8
36,000
3/4
7/8
1 1/8
48,000
7/8
1 1/8
1 1/8
60,000
1 1/8
1 1/8
1 3/8
Table 5-8: R-404A Refrigerant Line Sizes, -10F Evap Temp, 40F Suction Vapor Temp, 105F Condensing and Liquid Temp 3/8 1/2 5/8 5/8 3/4 3/4 7/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 7/8 7/8 3/4 1/4 1/4 5/16 5/16 7/8 5/8 1/4 3/4 1/2 1/4 5/8 1/2 3/16 1/4 1/4 1/4 5/16 5/16 5/16 3/8 5/8 3/8 3/16 3/16 1/2 5/16 3/16 3/16 3/16 1/4 1/4 1/4 5/16 5/16 3/8 3/8 1/2 3/16 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 ~ 3/16 1/4 1/4 5/16 3/8 3/8 3/8 1/2 3/16 1/4 1/4 5/16 5/16 3/8 3/8 3/8 1/2 1/4 1/4 5/16 5/16 3/8 3/8 1/2 1/2 1/2 1/4 1/4 5/16 5/16 3/8 1/2 1/2 1/2 5/8 1/4 5/16 5/16 3/8 1/2 1/2 1/2 5/8 5/8 ~ 3/16 1/4 1/4 5/16 3/8 3/8 3/8 1/2
1,000
5/16
3/8
2,000
3/8
1/2
3,000
1/2
1/2
4,000
1/2
5/8
6,000
1/2
5/8
8,000
5/8
3/4
10,000
5/8
3/4
12,000
3/4
7/8
18,000
3/4
7/8
1 1/8
* Largest line size that will maintain the stated refrigerant velocity. Please consult industry references such as the ASHRAE Refrigeration Handbook for additional information regarding how to properly size suction and discharge line risers and condenser to receiver condensate lines.
81
82
SERVICE HANDBOOK
Service Valves
As shipped with the compressors, the rotolock service valves have a small plastic dust plug inside the threaded end. Be sure to remove this plug before installing. Service valves on Tecumseh systems are front seated by turning the valve stem clockwise. This closes the valve and opens the gauge port. Turning the stem counter-clockwise back seats the valve and thus opens the system and closes the gauge port. If present, the valve port to the system control (high pressure cutout, low pressure control, fan control, etc.) is always open regardless of the position of the valve stem. If the system is to be operated with the service gauge functioning, it is necessary to crack the valve from its back seated position for the gauges to perform. Before removing the gauges, close the gauge port by returning the valves to their fully open position (back seated). Remember to check the packing gland nut (if present) on the stem for snugness before leaving the job. Install the cover nut over the valve stem as a secondary safeguard against leaks at the stem.
83
7. If a suction line accumulator is present, charge into the accumulator to prevent liquid refrigerant from reaching the compressor. If this is not possible, then break the vacuum by allowing refrigerant vapor to enter the low side at the suction service valve. When the system pressure reaches 60 psig for R-22 (70 psig for R-502 & R-404A, 35 psig for R-12 & R-134a), start the compressor and continue charging at rate not more than 5 pounds per minutes for the larger systems and somewhat less for smaller systems. Follow the safety precautions outlined in System Charging on page 5. 8. Check fans and blowers for correct direction of rotation, belt tension, and proper air flow (CFM). 9. With the protective terminal cover securely fastened, run the compressor and allow the system pressures and temperatures to stabilize. Systems vary in their operating characteristics, but generally these approximations will apply:
Table 5-6: Pressure and Temperature Stabilization Pressure Saturated head pressure Water cooled Air conditioning Medium temperature Low temperature Temperature Ambient temperature F + 20F for air cooled condenser Discharge water F + 10F Saturated evaporator pressure Discharge air F -20F Product temperature -10F to -12F Product temperature -6F to -8F
10. Before leaving the job, run the system for a while. Listen for abnormal noises. Feel the bottom crankcase housing and determine that it is warm. Is the compressor upper housing sweating indicating that liquid refrigerant is reaching the compressor? Is the return gas temperature at the compressor within proper limits for the application (i.e. not too low to cause flooding or not too high to produce high discharge and motor temperatures)? Recheck pressures, amps, fan motors, belts, CFM, etc.
If a compressor motor failure has occurred, refrigerant or mixtures of refrigerant and oil in the system can be acidic and can cause chemical burns. As always, to avoid injury, wear appropriate protective eye wear, gloves and clothing when servicing an air conditioning or refrigeration system. If refrigerant or mixtures of refrigerant and oil come in contact with skin or eyes, flush the exposed area with water and get medical attention immediately. The following outlines a process for compressor replacement and system clean-up for a system equipped with a Tecumseh compressor. You should refer to the original equipment manufacturers (OEM) service information.
84
SERVICE HANDBOOK
85
WARNING! Never use a compressor to evacuate a system. Instead, use a high vacuum pump specifically designed for that purpose. Never start the compressor while it is under deep vacuum. Always break a vacuum with refrigerant charge before energizing the compressor. Failure to follow these instructions can damage the hermetic terminal and may result in terminal venting. As always, to reduce the risk of serious injury or death from fire due to terminal venting, never energize the compressor unless the protective terminal cover is securely fastened.
Table 5-7: Suggested Maximum Pressure Drop (psi) for Permanent Suction Filter-Drier Installation Application Evaporator Range, F R-12, R-134a R-22, R-404A, R407C, R-502, R-507 Air Cond +55 to +32 2 High +55 to +20 2 Medium +30 to -10 1 1/2 Low +10 to -20 1/2 -20 to -40 1/2
1/2
86
SERVICE HANDBOOK
Table 5-8: Suggested Maximum Pressure Drop (psi) for Temporary Suction Filter-Drier Installation During Cleanup Application Evaporator Range, F R-12, R-134a R-22, R404A, R407C, R-502, R-507 Air Cond +55 to +32 6 High +55 to +20 6 Medium +30 to -10 3 Low +10 to -20 2 -20 to -40 3/4
1 1/2
At Least 6 Diameters
Suction Line
1/2" Shut O
Valve
FIGURE 5-12:
Method of obtaining oil sample on hermetic system. After satisfactory oil test, Schrader valve may be capped and the oil sample taken to the next job.
87
Operation
FIGURE 6-1:
Liquid refrigerant migration to compressor
Chapter 6
90
SERVICE HANDBOOK
High Pressure Gas High Pressure Liquid Low Pressure Liquid Low Pressure Gas Filter Fan Fan
Evaporator
Condenser
Expansion Device
Compressor
FIGURE 6-1: Liquid refrigerant migration to compressor
91
FIGURE 6-2:
Refrigerant and oil mixture fill sight glass after weekend shutdown
FIGURE 6-3:
Five seconds after start-up, violent foaming action fill sight glass as refrigerant boils away taking oil charge with it
FIGURE 6-4:
More than 60 seconds after start-up, oil level is well below normal operating levels - a condition that is an important factor in compressor bearing wear.
92
SERVICE HANDBOOK
This sequence (see Figures 6-6 and 6-7) shows the effects of an electric strap-on crankcase heater applied to the compressor (also see Figure 6-5). The system was again shutdown for a weekend under identical conditions with the exception that the heater was energized throughout the shutdown period. By raising the temperature of the oil, we have reduced its ability to attract and hold refrigerant.
Operation
Note that liquid refrigerant accumulation in the compressor can also be caused by liquid floodback under certain conditions while operating. This condition can be controlled by the application of a suction line accumulator. Crankcase heat does nothing to prevent liquid floodback and an accumulator does nothing to prevent refrigerant migration. Each without the other is half a job. Both together provide balanced compressor protection.
FIGURE 6-5:
When applied to a compressor with a low pressure housing, an electric strap-on crankcase heater prevents liquid migration.
FIGURE 6-6:
View through sight glass shows that the crankcase heater effectively prevents migration of liquid refrigerant to the compressor.
FIGURE 6-7:
Normal run with heat. Oil level is maintained thereby assuring effective lubrication for compressor bearings.
93
Crankcase Heaters
When most air conditioning and commercial systems are started up for the first time each season, a large part of the system refrigerant charge is in the compressor. On startup, the refrigerant boils off taking the oil charge with it, and the compressor is forced to run for as long as 3 or 4 minutes until the oil charge circulates through the system and returns to the crankcase. Obviously, this is not good for the compressor and definitely shortens its service life. The initial solution is to charge the system so that little or no refrigerant collects in the crankcase and to operate the crankcase heater at least 12 hours before startup or after a prolonged shutdown. Three types of crankcase heaters are in common use on Tecumseh compressors: wrap-around resistance heater (belly band), immersion type integral heater, and the run capacitance off-cycle heat. The wrap-around heater should be strapped to the housing below the oil level and in close contact with the housing. A good heater will maintain the oil at least 10F above the temperature of any other system component and (when the compressor is stopped) desirably at or above a minimum temperature of 80F. The immersion type heater is factory assembled and is presently used with AB, AW, AG, AV, and AN compressors. It is self-regulating and energy efficient. In the run capacitance off-cycle heat method used by some OEM, single-phase compressors are stopped by opening only one leg (L2) and thus the other power supply leg (L1) to the run capacitor remains hot. A trickle current through the start windings results thereby warming the motor windings and thus the oil on the off-cycle. WARNING! Before servicing systems with off-cycle run capacitor type heaters, be sure to disconnect ALL power supplies. Make sure that all power legs are open. Failure to do so can result in serious injury or death from electric shock. Capacitance crankcase heat systems can be recognized by one or more of the following: Contactor or thermostat breaks only one leg to the compressor (and condenser fan). Equipment should carry a notice indicating power is on compressor when it is not running and that main breaker should be opened before servicing. Run capacitor is sometimes split (3 terminals) so that only part of the capacitance is used for off-cycle heating. NOTE: use exact replacement when changing such dual purpose run capacitors. Capacitor must be fused and carry a bleeder resistor across the terminals. See Figure 6-8 for the basic wiring diagram for a PSC compressor with run capacitance off-cycle heat.
94
SERVICE HANDBOOK
External Thermal Protector Line 1 C L1 Rela y - Potential Line 2 Ground Compressor Unit Ground Start Capacitor Bleeder Resistor L2 T2 Single Pole Contactor or On - O Switch Hi Side Fan 5 2 1 Bleeder Resistor Star t Winding
C S
A B
Run Capacitor Single Can (Split Capacitor Optional) R Temperature Control (Room Air Conditioner) Single Phase - PSC Type Single Phase - CSR Type Potential Rela y
FIGURE 6-8: Wiring diagram for PSC compressor with run capacitance off-cycle heat.
Main Winding
Motor
95
High Pressure Gas High Pressure Liquid Low Pressure Liquid Low Pressure Gas Filter Fan Fan
Evaporator
Condenser
96
SERVICE HANDBOOK
FIGURE 6-10:
Liquid refrigerant enters compressor and settles to the bottom, below the oil.
FIGURE 6-11:
Five seconds after start-up, violent foaming action fills sight glass as refrigerant boils away taking the oil charge with it.
FIGURE 6-12:
More than 60 seconds after start-up, oil level is well below normal operating levels - a condition that is an important factor in compressor bearing wear.
97
Liquid floodback can be prevented by the application of a properly designed and sized suction line accumulator (see Figures 6-13 and 6-14 below and Accumulator Selection on page 98). When properly selected based upon system charge, a suction line accumulator will improve compressor reliability and endurance by preventing damaging liquid refrigerant floodback. Note that liquid refrigerant accumulation in the compressor can also be caused by liquid migration to the compressor during periods of shutdown. This condition can be controlled by the application of a crankcase heater. A suction line accumulator does nothing to prevent liquid migration and a crankcase heater does nothing to prevent liquid floodback. Each without the other is half a job. Both together provide balanced compressor protection.
High Pressure Gas High Pressure Liquid Low Pressure Liquid Low Pressure Gas Filter Fan Fan
Evaporator Accumulator
Condenser
FIGURE 6-13: Application of a properly designed and sized suction line accumulation.
FIGURE 6-14: A suction line accumulator prevents damaging liquid refrigerant floodback.
98
SERVICE HANDBOOK
Accumulator Selection
Selecting the proper size is of primary importance. Only one factor need be considered in order to assure the correct accumulator for a particular system -- the total refrigerant charge in that system. It is not necessary to know the holding capacity of the accumulator or system variants such as evaporator temperature and capacity in tons of refrigeration. These factors were considered in the design and testing of the accumulator. On older systems, if the system refrigerant charge is not known, consider the rule of thumb provided in Table 6-1 when selecting the correct size of suction accumulator:
Table 6-1: Selecting Correct Suction Accumulator Application Air conditioning and heat pump and high evaporator temperature Medium evaporator temperature Low evaporator temperature System Charge (lb/HP) 3 5 7
99
Table 6-2: Compressors with IPR valves AG Models AV Models AW Models AHA4520E AHA4522E AHA4524E AHA4531E AHA4540E AHA7513Z AHA7515J AHA7521Z AHA7524J AJC5519E AJD8520E SFA5554E SFA5558E SFA5560E SFA5572E SFA5581E SFAA530Z SFAA536Z SFAA540Z
Appendix
102
SERVICE HANDBOOK
Condenser Fan Liquid Line Valve Condenser Hermetic Compressor Discharge HI LO Accumulator Crankcase Heater Suction
Receiver Tank
Heat Exchanger
Pressure Cutout
TEV Sensin Bulb Thermostatic Expansion Valve or Capillary Tube Filter-Drier Evaporator Evaporator Fan
103
104
SERVICE HANDBOOK
105
Reciprocating Compressor
106
SERVICE HANDBOOK
Table A-1: Capillary tube selections assume a 115F liquid temperature and 3 ft of heat exchange length
Capillary Tube, Length - OD Evaporator Temperature, F Refrigerant Btu/h per circuit 500 750 1,000 1,250 1,500 22 2,000 3,000 4,000 6,000 8,000 10,000 12,000 500 750 1,000 1,250 1,500 134a 2,000 3,000 4,000 6,000 8,000 10,000 12,000 -10 19 ft - 0.026" 12 ft - 0.028" 11 ft - 0.031" 16 ft - 0.036" 11 ft - 0.036" 14 ft - 0.042" 19 ft - 0.052" 10 ft - 0.052" 14 ft - 0.064" 10 ft - 0.052" (2) 13 ft - 0.059" (2) 14 ft - 0.064" (2) 14 ft - 0.028" 10 ft - 0.031" 12 ft - 0.036" 18 ft - 0.042" 12 ft - 0.042" 22 ft - 0.052" 9 ft - 0.052" 10 ft - 0.059" 9 ft - 0.052" (2) 10 ft - 0.059" (2) 10 ft - 0.064" (2) 10 ft - 0.059" (3) 20 18 ft - 0.026" 11 ft - 0.028" 10 ft - 0.031" 15 ft - 0.036" 10 ft - 0.036" 13 ft - 0.042" 18 ft - 0.052" 10 ft - 0.052" 13 ft - 0.064" 10 ft - 0.052" (2) 12 ft - 0.059" (2) 13 ft - 0.064" (2) 14 ft - 0.028" 10 ft - 0.031" 12 ft - 0.036" 18 ft - 0.042" 12 ft - 0.042" 22 ft - 0.052" 9 ft - 0.052" 10 ft - 0.059" 9 ft - 0.052" (2) 10 ft - 0.059" (2) 10 ft - 0.064" (2) 10 ft - 0.059" (3) 45 17 ft - 0.026" 10 ft - 0.028" 10 ft - 0.031" 15 ft - 0.036" 10 ft - 0.036" 13 ft - 0.042" 18 ft - 0.052" 9 ft - 0.052" 13 ft - 0.064" 9 ft - 0.052" (2) 12 ft - 0.059" (2) 13 ft - 0.064" (2) 14 ft - 0.028" 10 ft - 0.031" 12 ft - 0.036" 18 ft - 0.042" 12 ft - 0.042" 22 ft - 0.052" 9 ft - 0.052" 10 ft - 0.059" 9 ft - 0.052" (2) 10 ft - 0.059" (2) 10 ft - 0.064" (2) 10 ft - 0.059" (3)
107
Table A-1: continued
Capillary Tube, Length - OD Evaporator Temperature, F Refrigerant Btu/h per circuit -10 20 45
404A/507
500 750 1,000 1,250 1,500 2,000 3,000 4,000 6,000 8,000
10,000 12,000
Table A-2: Capillary tube correction factors assume a 115F liquid temperature and 3 ft of heat exchange length
(1) Capillary Tube Size from Table A-1 Tube ID (in) 0.026 0.028 (2) Desired Capillary Tube Size 0.031 0.036 0.040 0.042 0.044 0.049 0.050 0.052 0.054 0.055 0.059 0.064 0.070 0.075 0.026 1.00 1.52 2.71 0.028 0.66 1.00 1.78 0.56 1.00 2.34 0.24 0.43 1.00 1.82 2.40 0.42 0.76 1.00 1.30 2.40 0.30 0.39 0.71 0.80 1.00 1.24 1.38 2.05 0.35 0.39 0.49 0.60 0.67 1.00 1.59 2.64 0.31 0.38 0.42 0.63 1.00 1.66 2.46 0.031 0.036 0.042 0.052 0.059 0.064
Example No. 1 To convert 16 ft of 0.031" capillary to 0.028", multiply length by 0.56, i.e., 16 ft * 0.56 = 9 ft. As a result, 9 ft of 0.028" capillary has aprroximately the same capacity as 16 ft of 0.031" capillary
108
SERVICE HANDBOOK
Legend
Table A-4: Most Common Oil Types to be Used in Compressor Families 1. AE manufactured in Brazil. Ak, AV and AW manufactured in India 2. (LBP and CBP using R22, R502) for AE, AJ,AH, AK, AV, and AW. For compressor manufactued in Brazil only, AE, AZ, THB, AK, and TW. (R-12 and R-22) 3. AG, AK,AV,and AW. EXCEPTION: Not to be used in AWA & AWF families. NOTE: These oils must be used with SYN-O-AD 8478LW. 4. AE and AZ families 5. HG, RG, RK & RK split systems, and AG CBP using R-22 or R-502. NOTE: These oils must be used with SYN-O-AD 8478LW. 6. Tecumseh Brazil built AE (R-12 models) HBP and CBP only. For Tecumseh Brazil Market Only 7. AZ, AE, AK, AJ, AH, AV, AW using R-134a, R-404A, and R-507 refrigerant. NOTE: These oils must be used with SYN-O-AD 8478LW. 8. AW-F family only. NOTE: These oils must be used with SYN-O-AD 8478LW. 9. THA,THB, TP TS, TW using R-134a. , 10. VS and HS using R-404A and R-410A 11. RG, HG, RK, RN using R-134a, R-404A, R-410A, and R-407C refrigerant.
109
Table A-4: Most Common Oil Types to be Used in Compressor Families Compressor Families Source
Naphthenic Witco Suniso 3 GS Witco Suniso 1 GS Lubrax CP-32-RF Synthetic Alkylate (Alkylbenzene) Zerol 150TD Venoco DL-008AS Zerol 150T Venoco DL-008A Zerol 300 SUS Soltex SA56 Lubrax BR-069C-EX Lubrax ALP-415-LCR Naphthenic / Paraffinic Sonneborn (Witco) LP 200 Penreco-Sontex 200LT, (A) LT Paraffinic Total Oil Company 68CST Petrobas CP-68-RAD Polyol Ester ProEco 32M CP-2932-E ProEco RF32 Hatcol 3680 Emkarate RL15H Emkarate RL10H ProEco 3844 ProEco 10S CP-2910-E ProEco 22S CP-2922-E Freol Alpha 10W Freol Alpha 22E Hatcol 3681 Polyvinyl Ether Apollo America Corp FVC68D 11 11 11 11 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 10 6 6 3 3 3 3 3 3 3 3 4 4 4 4 2 2 4 4 1,2 2 4 4 5 5 5 5 5 5 5 5 1,2 2 2 2 2 2 1,2 2 1,2 2 2 2 2 2 1 1 1 1 8 1 1 1 1 AZ AE AK AJ AH AW AV AG RK RG THA THB TP TS TW HG RN VS
110
SERVICE HANDBOOK
Notes
Think Safety!
Be alert for sounds of arcing (sizzling, sputtering or popping) inside the compressor. IMMEDIATELY GET AWAY if you hear these sounds. Disconnect ALL electrical power before removing the protective thermal cover. Never energize the system unless the protective terminal cover is securely fastened and the compressor is properly connected to ground Never reset a breaker or replace a fuse without first checking for a ground fault (also known as a short circuit to ground).
Tecumseh Products Company 1136 Oak Valley Drive Ann Arbor, MI 48108 800.211.3427 | 734.585.9500 www.tecumseh.com
2011 Tecumseh Products Company. All rights reserved. Publication No. TR - 103